CP Rankin, Inc.
4359 County Line Road
Chalfont, PA 18914
SCANNED
BY
St. Lucie Count
RE: ENGINEERING MEASUREMENTS
Advanced Auto Parts # 9232
7075 Indrio Road; Fort Pierce, FL
Dear Sir or Madam:
ENGINEERING & TESTING, INC.
Phone: (866) 781-6889 -Fax: (866) 784-8550
wn c.floridnengineeringandtesting.com
250 S.W.13`" Avenue
Pompano Beach, FL 33069
Job Order No.: 16-284
Per your request, Florida Engineering & Testing Inc. has measured the existing metal roof deck thickness
and the spacing of the structural roof supports on January 21, 2016 to verify that the existing roof deck
meets the requirements specified on page 52 of 89, Deck Type 7I, in the Notice of Acceptance #13-
1212.04 which specifies "Min. 22 ga. steel deck with supports spaced maximum 6 ft. o.c."
Measurements:
FE&T measured the metal roof deck thickness with calibrated calipers and determined that the deck
thickness is 20 gauge. Additionally, the steel bar joist roof supports were measured to be spaced at a
maximum of 5 ft. o.c.
Conclusions:
We were able to determine that the existing steel roof deck is in general accordance with the
product approval requirements of a minimum 22 ga. steel deck with supports spaced at a maximum
of 6 ft. o.c.
Florida Engineering & Testing, Inc. appreciates the opportunity to be of service to you at this phase of
your project. Should you have questions or comments, please feel free to contact us at your earliest
convenience.
Sincerely, .
Mark A. Mesiano, P.E.
Florida Engineering & Testing, Inc.
Florida Rog. No. 48202
Certificate of. Authorization No. 6923
49% �`%
Q It
Qnalify �A�11.9sseawnce
m 00) pis,
1-1
January 21, 2016
CP Rankin, Inc.
4359 County Line Road
Chalfont, PA 18914
SC BY ED
St, Lucie COunty
RE: ENGINEERING MEASUREMENTS
Advanced Auto Parts # 9232
7075 Indrio Road; Fort Pierce, FL
Dear Sir or Madam:
ENGINEERING & TESTING, INC.
Phone: (866) 781-6889 *Fax: (866) 784-8550
www.floridaengineeringandtesting.com
250 S.W. UP Avenue
Pompano Beach, FL 33069
Job Order No.: 16-284
FEB - 1 2016
Public Works
St. Lucie County, FL
Per your request, Florida Engineering & Testing Inc. has measured the existing metal roof deck thickness
and the spacing of the structural roof supports on January 21, 2016 to verify that the existing roof deck
meets the requirements specified on page 52 of 89, Deck Type 71, in the Notice of Acceptance #13-
1212.04 which specifies "Min. 22 ga. steel deck with supports spaced maximum 6 ft. o.c."
Measurements:
FE&T measured the metal roof deck thickness with calibrated calipers and determined that the deck
thickness is 20 gauge. Additionally, the steel bar joist roof supports were measured to be spaced at a
maximum of 5 ft. o.c.
Conclusions:
We were able to determine that the existing steel roof deck is in general accordance with the
product approval requirements of a minimum 22 ga. steel deck with supports spaced at a maximum
of 6 ft. o.c.
Florida Engineering & Testing, Inc. appreciates the opportunity to be of service to you at this phase of
your project. Should you have questions or comments, please feel free to contact us at your earliest
convenience.
Sincerely,
Mark -A. Mesiano, RE-,
Florida Engineering &'Testing, Inc.
Florida Reg. No. 48202 '
Certificate of Authorization No. 6923
Ai
Quality A I1Y ✓lssurance
13 GL
January 21, 2016
CP Rankin, Inc.
4359 County Line Road
Chalfont, PA 18914
RE: ENGINEERING MEASUREMENTS
Advanced Auto Parts # 9232
7075 Indrio Road; Fort Pierce, FL
Dear Sir or Madam:
ENGINEERING & TESTING, INC.
Phone: (866) 781-6889 •Fax: (866) 784-8550
www.floridaenginceringandtesting.com
250 S.W.13th Avenue
Pompano Beach, FL 33069
Job Order No.: 16-284
Per your request, Florida Engineering & Testing Inc. has measured the existing metal roof deck thickness
and the spacing of the structural roof supports on January 21, 2016 to verify that the existing roof deck
meets the requirements specified on page 52 of 89, Deck Type 7I, in the Notice of Acceptance #13-
1212.04 which specifies "Mn. 22 ga. steel deck with supports spaced maximum 6 ft. o.c."
Measurements:
FE&T measured the metal roof deck thickness with calibrated calipers and determined that the deck
thickness is 20 gauge. Additionally, the steel bar joist roof supports were measured to be spaced at a
maximum of 5 ft. o.c.
Conclusions:
We were able to determine that the existing steel roof deck is in general accordance with the
product approval requirements of a'minimum 22 ga. steel deck with supports spaced at a maximum
of 6 ft. o.c.
Florida Engineering & Testing, Inc. appreciates the opportunity to be of service to you at this phase of
your project. Should you have questions or comments, please feel free to contact us at your earliest
convenience.
Sinceralq;
Mark A,- Mesia6o, P:E:
Florida Engineering &,Testing, Inc.
Floridateg. No. 48202
Certificate -of Authorization No. 6923