In regards to the planning comments for the above referenced project, I am writing to clarify
the issues raised in the responses received on March 10, 2016. Responses are listed in bold
1610 Trade Center Way below.
Suite #5
Naples, FL 34109
T. 239.631.2332
F: 239.300.6402 PLANS EXAMINER REVIEW COMMENTS (2)
1. Comment: Vestibules are by definition in several dictionaries, lobbies and therefore
have an occupancy. Please show correct occupant load for all vestibules.
Architecture
Response: See revised occupant load schedule.
Planning 2. Comment.- Please remove references in occupancy load section of sheet LS-101 to
classrooms, shops and vocational rooms in none exist, as stated in your response
summary.
Interior Design Response: Reference removed from occupancy load section
Programming
3. Comment: Please show correct occupant load for Barbor shop,1056.
Response: See revised occupant load schedule.
Graphic Design 4. Comment: Please show correct occupant load for Mechanical room,1077.
Response: See revised occupant load schedule.
Project Delivery
5. Comment: Please show correct occupant load for Mechanical mezzanine 2001.
Response: See revised occupant load schedule.
6. Comment: Please show correct occupant load for Janitor closet,1012.
Member A 1 A Response: See revised occupant load schedule.
ww w. il e a c ocka n d l e wi s. com ,
St. Lucie County Building Responses for Harbour Ridge 03.23.16
Page 2 - Marcn 23, 2016
Harbour Ridge Country Club
Specification Comments for Permit No.1511-0404
Peacock + Lewis Proposal No. 14-015
7. Comment: Please show compliance with threshold building requirements referenced
above.
Response: Based on revised occupant load building falls below requirement for
threshold building.
Sincerely,
Peacock + Lewis Architects and Planners, LLC
Sean Sukhu
Architect
St. Lucie County Building Responses for Harbour Ridge 03.23.16
PEACOCK + LEMS
Architects and Planners, LLC
Lic. # AAC 000020
19, 2016
St. Lucie County
Planning & Development Services
Building & Code Regulation Division
2300 Virginia Avenue
Fort Pierce, FL 34982
RE: Harbour Ridge County Club
134 Gilson Rd, Palm City, FL 34990
1295 US Highway one Specification Comments for Permit NAM - 0W
North Palm Beach, FL 33408 Peacock + Lewis Project No.14-015
T. '561'626.9704 Dear Plan Reviewers,
R 561.626.9719
SCANNED
BY
St. Lucie Countti
R�
MAR -2 2016
In regards to the planning comments for the above referenced project, I am writing to clarify
the issues raised in the responses received on February 2, 2016. Responses are listed in bold
1610 Trade Center Way below.
Suite #5
Naples, FL34109 DOCUMENTS MISSING
T: 239.631.2332 1. Comment: Needs subs for all trades HVAC, plumbing, electrical & roofing
F: 239.300.6402
Response: By General Contractor
2. Comment: Needs sub summary
Architecture Response: By General Contractor
3. Comment: Veg permit in drawer under (H) for Harbor Ridge Yacht & Country Club
Planning - A Humphrey
Response: By General Contractor
Interior Design
PLANS EXAMINER PLUMBING
Programming 1. Comment: Page LS-101 has the wrong code referenced; we are now using the 2014
codes. Please correct on plans.
Graphic Design Response: Updated Life Safety plans to show Th edition 2014 code references.
2. Comment: Please indicate what type of sewage disposal system this building will be
Project Delivery on. For example, on -site sewage treatment or county or city sewage treatment. You will
need to have grease interceptor approved by Health Dept if it is on -site (section 1003
FL Plumbing Code 2010) or utility company if city or county utility.
an on5t-he -- fea+Meth ��Cillfiy.
Response: The sewage system will be connected to .An
under counter grease interceptor is called for at the snack area. A note on sheet
p-212 has been expanded to include health department approval.
Member AIA
mww.peacockandlewis.com
St. Lucie County Building Responses for Harbour Ridge 02.15.16
Page 2 2 ruary 19, 2016
Harbour Ridge Country Club
Specification Comments for Permit No. 1511-0404
Peacock + Lewis Proposal No.14-015
3. Comment: Please show sq. footage of roof and rainfall rate for each roof drain per
Chapter 11 of the Florida Plumbing Code 2014.
Response: Square footage and rainfall rates for each roof drain/ drainage area are
labeled on sheet P-602. Two roof drainage areas were revised for this revision and
leaders increased.
4. Comment: Please show on plans what is draining into the floor sink located by the
door! Room number 1007. You list this room as storage.
Response: Floor sinks in room 1007 is now labeled to collect drainage from ice
machine and under counter refrigeration (clear -water waste). And the 4" floor sink
has been reduced to 3". The extra floor sink in room 1037 has also been labeled to
collect drainage from under counter bar cooler (clear -water waste).
5. Comment: Please show trap primers on emergency floor drains per section 1002.4 of
the Florida Plumbing Code 2014.
Response: Sanitary keynote #1 on sheets P-211 & P-212 specifies that floor drain
trap seals shall be primed by a trap primer (General note #29 on sheet P-001 also
states that floor drains shall be primed). Trap priming valve model &
manufacturer are specified by detail #2 on sheet P-901.
PLANS EXAMINER REVIEW
1. Comment: Please note this review is not complete but is being sent at the request of
Mike O'Neal. Other comments associated with this review will follow shortly.
Response: Provide final comments for review.
2. Comment: Please include all current code editions in design criteria block(s).
Response: Updated Life Safety plan to show current code references.
3. Comment: Please submit letter from threshold inspector and structural inspection
plan complying with FBC CH.110.8.
Response: The Florida Statute defines a threshold building as the following,
"Threshold building" means any building which is greater than three stories or 50
feet in height, or which has an assembly occupancy classification as defined in the
Florida Building Code which exceeds 5,000 square feet in area and an occupant
content of greater than 500 persons.
The building as designed is an assembly occupancy greater than 5,000 sf, however
the building has an occupant load of less than 500 persons. We believe this falls
below the criteria for a threshold building.
4. Comment: Please submit list of all persons performing inspections with special
inspector, including license numbers, complying with FBC CH 110.8.6.
Response: See plans examiner review comment #3 response.
St. Lucie County Building Responses for Harbour Ridge 02.19.16
Page 3 ruary 19, 2016
Harbour Ridge Country Club
Specification Comments for Permit No. 1511-0404
Peacock + Lewis Proposal No.14-015
5. Comment: Please show all required protection of building elements, complying with
FBC CH.6 and Table 601, associated with Type III A construction.
Response: Building type has been revised to Type III B construction. Life Safety
sheet has been revised to include all required protection of building elements.
6. Comment: Please locate on plans, and show occupant loads, for
classrooms/vocational rooms noted on Sheet LS 101.
Response: Occupancy load schedule is listed on Sheet LS-101 with occupant loads
and occupants for each space. The total occupants are listed at the bottom of the
schedule. Schedule has been updated to include all rooms. There are no
classrooms/vocational areas in the facility.
7. Comment: Please show rated assembly separation at mechanical room 1078.
Response: Will comply.
8. Comment: Please note areas 1080 and 1085 in occupancy load schedule.
Response: Occupancy load schedule is updated to include rooms 1080 through
1085 and mechanical mezzanine 2001.
9. Comment: Please include occupant loads for vestibules, lobbies, etc. in occupancy
load schedule.
Response: The building does not include lobbies. Reception areas are shown and
listed in the occupant load table for each separate space. Vestibules and galleries
through the building are intended as circulation and non -occupied space.
10. Comment Please show detail of referenced mezzanine ceiling assembly, noted on
sheets A403 and A404.
Response: Ceiling assembly shall be eliminated. Construction type is revised to
type III B.
11. Comment: Referenced sheet A904 appears to be missing.
Response: Sheet A-904 shall be eliminated.
12. Comment: Please include shop drawings for ship ladder to mezzanine.
Response: BY General contractor.
13. Comment: Please include product approval affidavit, or product approvals, for all
components used in the structural envelope of project.
Response: By General Contractor.
St. Lucie County Building Responses for Harbour Ridge 02.19.16
y
Page 4 ruary 19, 2016
Harbour Ridge Country Club
Specification Comments for Permit No.1511-0404
Peacock + Lewis Proposal No. 14-015
14. Comment: Please include 2 sets of truss shop drawings from truss manufacturer.
Response: By General Contractor.
15. Comment: Please submit 2 truss manufacturers' layout sheets, reviewed and
approved by design professional.
Response: By General Contractor.
Sincerely,
Peacock + Lewis Architects and P1 exs, LLC
Sean Sukhu
Architect
St. Lucie County Building Responses for Harbour Ridge 02.19.16
Debra Zampetti S( AAIAIGn
From: Amy Griffin St. Lucie County
Sent: Monday, January 11 2016 10:14 AM
To: Debra Zampetti; Monica Graziani
Cc: Jennifer McGee; Dana Caron; Benjamin Balcer
Subject: RE: Harbor Ridge Lifestyle Center - Release Vegetation Permit - Special Request
Good Morning Debra,
Please consider this email confirmation that ERD is allowing the release of the vegetation permit for Harbor Ridge
Lifestyle Center prior to the release of the Building Permit.
I made the determination to release the vegetation removal permit based on the following considerations:
• This expansion is part of an existing, approved and established, project;
• The vegetation avoidance, minimization and mitigation plan has been reviewed and approved by ERD and
efforts were made by the applicant to preserve and relocate mature trees and native habitat;
• The Plans Examiner confirmed that the building plans are substantially compliant with no alterations to the
presented footprint expected; and
• This request was made by Administration via the Business Navigator as a means to assist a desirable project.
Please let me know if you have any questions or concerns.
Amy Griffin
Division Director
Environmental Resources Department 12300 Virginia Ave I Ft Pierce, FL 34982
Office: 772.462.25311 Fax:772.462.1684 1Cell:772.579.11721 ERD Website
From: Dana Caron
Sent: Monday, January 11, 2016 9:18 AM,
To: Amy Griffin <griffina@stlucieco.org>
Cc: Jennifer McGee <McGeeJ@stlucieco.org>; Monica Graziani <GrazianiM@stlucieco.org>; Debra Zampetti
<Zam pettiD@stlucieco.org>
Subject: Harbor Ridge Lifestyle Center - Release Vegetation Permit - Special Request
Amy,
I called and notified Monica Graziani on 1/8/2016, per your request, to release the vegetation permit portion for Harbor
Ridge Lifestyle Center. All vegetation fees need to be paid at the time of pickup.
Debra Zampetti is requesting confirmation via email for their records. Please confirm and forward to Debra Zampetti.
Sincerely,
0
a
RFI Response
To: Sean Sukhu
Peacock + Lewis Architects
From: Wenjun Li, PE
RGD Consulting Engineers
Re: Concrete Compressive Strength Testing
Harbour Ridge Lifestyle and Sales Center
12600 Harbour Ridge Blvd, Palm City, FL
Date: July 13, 2016
CONSULTING ENGINEERS
ALLCHANICAL I ELECTRICAL I PLUAIBING I FIRE PROTECTION I STRUCTUML
mm.rgdcngince".mm
AIAUI IN THE USA
Reference: Slab on grade, Compressive Test Report Sample 24481, 24484, 24498, 24508, 24516
Subject: Concrete Compressive Strength Test Report
Description:
As discussed previously, the concrete subcontractor used the wrong mix design for the concrete that
was poured at the slab of the main building. The concrete slab is required to have a psi of 4,000. The
mix design that was used was approved at 3,000psi. However, as shown in the attached file the 7 day
break results reached between 5,100 and 5,450 psi. Please confine the poured concrete is acceptable
as it exceeds the requirement of 4,ODOpsi. The county requires confirmation from the FOR stating that
the concrete used is acceptable for this application.
Response:
The compressive strength test results are reviewed. We found no exceptions for the
previously placed slab on grade.
RGD is responsible for the content within this response which only pertains to the RFI number
listed.
Sincerely,
;-,
Wenjun Li PE
FL#56104
Page 1 of 1
2151 S. Alt. AIA, Suite 2000, Jupiter Florida 33477
iL
561.743.0165 Fax 561.743.0193
2u1 q
a M
RFI Response RGD
To: Sean Sukhu
Peacock+ Lewis Architects CONSULTING ENGINEERS
MECHANICAL I ELE ]UR L I PLUMBING I FIRE PROTECTION I STRUCTURAL
From: Wenjun Li, PE wxnvrgdengineers.cam
RG D Consulting Engineers MADE IN THE USA
Re: Concrete Compressive Strength Testing
Harbour Ridge Lifestyle and Sales Center
12600 Harbour Ridge Blvd, Palm City, FL
Date: January 3, 2017
Reference: Concrete CIP Tie Beam, Compressive Test Report Sample 26427,
Subject: Concrete Compressive Strength Test Report
Description:
As discussed previously, the concrete subcontractor used the wrong mix design for the concrete that
was poured at the cast -in -place tie beam of the main building. The concrete beam is required to have a
compressive strength of 4,500 psi. The mix design that was used was approved at 4,000psi. However,
as shown in the attached testing report the 28 day break results reached between 6,250 and 6,100
psi. Please confirm the poured concrete is acceptable as it exceeds the requirement of 4,500psi. The
county requires confirmation from the FOR stating that the concrete used is acceptable for this
application.
Response:
The compressive strength test results are reviewed. We found no exceptions for the
previously placed cast -in -place tie beam.
RGD is responsible for the content within this response which only pertains to the RFI number
listed.
Sincerely,
Wenjun Li PE
FL #56104 `
2151 S. Alt. AIA, Suite 2000, Jupiter Florida 33477
561.743.0165 Fax 561.743.0193
Page 1 of 1
M J MASTELLER & __OLER, INC. �S -
M — CIVIL ENGINEERS —
January 11, 2017
Mr. Mike Halter, PE
St. Lucie County Engineering Department
2300 Virginia Avenue
Ft. Pierce, Florida 34982 -5652 SCANNED
BY
RE: Certification of Completion of Construction St. Lucie County
Harbor Ridge Yacht & Country Club Tennis Center Expansion
Stormwater Management System Permit
SLC # 2015-186
Dear Mike:
This letter is intended to serve as the Engineer's Certification that all drainage and paving
construction required under the St. Lucie County Stormwater Management System Permit for
the Harbor Ridge Yacht & Country Club Tennis Center Expansion project has been completed
in substantial conformance with the approved plans. This certification is based on our
observation of project construction and review of the as -built survey.
This letter is intended to formally request your Department to coordinate scheduling of the on -
site field inspection of the completed improvements. We are enclosing the following information
to support issuance of Certificate of Completion:
Three (3) sets of the "As -Built" Drawings.
Please let me know if you have any questions relative to the information contained herein.
Thank you for your assistance and cooperation.
Sincerely,
MASTELLER & MOLERf�I�CEiu,�,;r°y
�ai^s=SJo.57970 a
ohn M. Boy r, P STATE OF 1,.FL #57970
Senior Project EngiJMBIne„e[?