HomeMy WebLinkAboutPROJECT INFORMATION (2)SCANNED BY St. Lucie Countv Sims Wilkerson Cartier Engineering, Inc. SHOP DRAWING REVIEW COMMENTS October 17, 2017 Reference: SLC Rosser Blvd Library SWC #14035 Subject: Final Test and Balance Report Submittal Re -submittal 10/27/17 Re -submittal 12/7/17 Reviewed by: Kyle A. Wilkerson Kyle J. Cartier, P.E. Sam F. Siciliano Engineers review is for general conformance with the design concept and contract documents. Markings or comments shall not be construed as relieving the Contractor from compliance with the project plans and specifications, nor departures therefrom. The Contractor remains responsible for details and accuracy, compliance with the Contract Documents and intent, for confirming and correcting all quantities and dimensions, for selecting appropriate fabrication processes,for techniques of assembly, and for performance of work in a safe manner. OVERALL DISPOSITION: Ro4se and ResubmWNote Markings • ... NO . .. Supply... return aifflews fer AdiU - and q 4 ., ew .. ... .. ,_ w rates. and system. Pre Ade ..plated test And t...t....ee repe ft 2. Test and balance results for AHU-2 are provided by Absolutely Cool Air Conditioning and supersede the AHU-2 results provided in report from M&M Test and Balance of Florida. AHU-3: Nate Mafkiags 12124 High Tech Avenue • Suite 200. Orlando, Florida 32817 • (407) 380-0400 - FAX (407) 380-5900 ` 1 Det..m aiF Wet W is 1 Sq04 of design value Adjust air fle.., e f deyiee to within z 100/ e f Ae..:p value. 2. No exceptions taken to performance of air handling unit fan and coil. AHU-4: No Exceptions Taken AHU-5: t Nee nr,� N4arkings z AHU-6: e e Nt,c gs EF-1,2,3,6: No Exceptions Taken EF-4,5: Devise and De..ubff 4 1. Aetual airflews of eAaus} f ft 32 not d 27 6 belew design values a de �a ao c-rano-ai$Tovivmava—r-�riv-ooiwracar�.n�mncri[icvvv net satisfy -minimufn eiihaust iegtttremeats-for sgaee. Investigate and peffeFm M. adifie;4ions or repaifs to system neee......fy i artier to eet.:eye required ai f flew values. END OF DOCUMENT 12124 High Tech Avenue • Suite 200. Orlando, Florida 32817 • (407) 380-0400 • FAX (407) 380-5900 i �► /�►�I�IAT�M' C of-pu T 'R tW C .1117 3126 Fortune Way, Suite 13 • Wellington, Florida 33414 Rosser Library Renovation PROJECT NO.: # 100213VB All -Report Subm&W No. 19990 -002 Stamped TestRepoit By: Sims Wilkerson Cartier Engineering, Inc. NOTE MARKINGS Engineer's review is forgeneral conformance with the design concept and contract documents. Wrkings or comments shall not be cornwed as relieving the Contractor from compliance with the project plans and specllications,nor departures therefrom. The Contractor remains resporrsible for details and accuracy, compliance with the Contract Documents and Intent, for confirmhg and correcting all quantities and dimensions, for selecting appropriate fabrication processes, for techniques of assembly, and for performance ofwork In a safe manner. By: Kyle A. Wilkerson ec 7, 2017 (X) Reviewed with No Exceptions ( ) Reviewed as Noted ( ) Rejected ( ) Revised and Resubmit ( ) Submit Specified Item Review is for general conformance with the design concept and the information given in the Construction Documents. _A�,ze�msa�{ Date: 12/05/2017 NE1Pl ty0 Sid lole a Z' ��O/IAL P$$O TESTING, ADJUSTING. AND -BALANCING BUREAU THE PROFESSIONAL'S CHOICES" This certifies that Douglas Pence has completed the requirements of certification as a Testing, Adjusting and Balancing Technician on Ee6ruary 20, 2015 Lq�orCo-ChMrrnan (` 1�4 ICB Co -Chairman (DB042001C Certification No. MqOgernent Co -Chairman r . a�G /�XA 1C5.o-Chairman pecem6er 31. 2025 Expiration Date t. ABSOLUTELY COOL AIR CONDITIONING, LLC Air Conditioning — Heating — Refrigeration'— Installation Martin County Certified TABB # DBO42001C Rosser Library Rosser Library 2950 SW Rosser Blvd 2950 SW Rosser Blvd Port St Lucie FL Port St Lucie FL Air Handling Unit AHU-02 TEM3A0C605S1SA AHU-02 TEIN3A0C605S15A 164716K82V 164716K82V Supply Outlets Return Outlets Design Airflow Actual Airflow Design Airflow Actual Airflow Outlet 1 180 161 Outlet 1 157.5 151 Outlet 2 135 130 Outlet 2 112.5 109 Outlet 3 180 156 Outlet 3 157.5 153 Outlet 4 270 268 Outlet 4 225 219 Outlet 5 270 251 Outlet 5 225 220 Outlet 6 90 82 Outlet 6 67.5 63 Outlet 7 135 102 Outlet 7 225 227 Outlet 8 135 104 Outlet 8 135 121 Outlet 9 25 53 Outlet 9 135 120 Outlet 10 25 52 Outlet it 180 172 Total 1440 1383 Outlet 12 190 161 Total % 96% Total 1800 1692 Total % 94% Static Pressure 0.4 Absolutely Cool Air Conditioning, LLC 2311 NE 15th Court Jensen Beach, FL 34957 772.4754641 ABSOLUTELY:COOL AIR CONDITIONING, LLC Phone: (772) 475-4641 Fax: (772) 225-9872 Absolutelycoolair@gmail.com — www.Absolute]yC—no!Air.com License & Insured #CAC1815702 — Locally & Family Owned & Operated TABB Certificate # DB042001C National Environmental Balancing Bureau / Cert. #3249 March 2018 Broward County T.A.B./ Fire Safety 3-CTB-866-W 8-31-2016 State of Florida Class "A" Unlimited HVAC CAC-025401 NATE Certification 10-27521 Outdoor Conditions 91.7db / 80.7wb CERTIFIED TEST, ADJUST, AND BALANCE REPORT PROJECT # 17-1155-TB Rosser Library Remodel 2950 Rosser Boulevard Port St. Lucie Fl. 34953 Architect: Edlund Dritenbas Binkley 65 Royal Palm Pointe, Suite D Vero Beach, FL. 32960 P: 772.569.4320 General Contractor: Anatom construction Company 3125 Fortune Way # 13 Wellington, Fl. 33414 T-561.221.0226 October 24, 2017 Engineer: Sims Wilkerson Carter Eng. 12124 High Tech Avenue -Suite 200 Orlando, Fl. 32817 T-407.380.0400 Fx 407.380.5900 Mechanical Contractor: JB AC & Electrical 1000 36th Street Stuart, Fl. 34994 Cell: 772.353.0448 IM• Test and Balance of Florida Inc. '"Air & Hydronics Systems Testing 6 M & _M Test & - Balance of AL Table Of Contents PROJECT: Rosser Library Remodel DATE: 10/10/2017 LOCATION: CONTACT: Michael lacobacci PROJECT #: AUTHOR: Table Of Contents 1 Certification Page 171155TB102417.pdf................................................................................................................. 1 2 7_ NEBB certificate.pdf............................................................................................................................................ 2 3 Test and Balance of Florida Inc. Certification No. 3249........................................................................................... 3 3.1 0Air&HydronicsSystemsTesting0.......................................................................................... 3 4 Test and Balance of Florida Inc. NEEB Certification No. 3249................................................................................ 5 4.1 0Air&HydrenicsSystemsTesting0.......................................................................................... 5 5 CalibrationAbbev..pdf............................................................................................................................................... 7 5.1 Table Of Contents.............................................................................................................................................. 5.2 burtons boca.pdf................................................................................................................................................. 5.2.1 IPdf:7ce5c681-8d96-4500-ab73-c82d043e27cc........................................................................................... 5.2.2 Table Of Contents......................................................................................................................................... 5.2.3 Test and Balance of Florida Inc. Certification No. 3249......................................................... 5.2.3.1(Air(Hydronics Systems Testing(................................................................................ 5.2.4 Certification 171161TB ECRWRF.pdf........................................................................................................... 5.2.5 Inst Calib Report —Evergreen Telem 12017.pdf............................................................................................. 7 5.2.6 NEW Abbreviation Guide 161153TB.pdf...................................................................................................... 8 5.2.7 Air Handling Unit........................................................................................................................................... 5.2.7.1 AHU-1...................................................................................................................................................... 5.2.7.2 AHU-1/Main Supply................................................................................................................................. 5.2.8 Fan Unit........................................................................................................................................................ 5.2.8.1 EF-01....................................................................................................................................................... 5.2.9 DIAGRAM..................................................................................................................................................... 5.2.10 PB WATER UTILITIES ECRWRF PLANSTB.pdf....................................................................................... 5.3 Air Handling Unit................................................................................................................................................. 5.3.1 RTU-1........................................................................................................................................................... 5.3.2 RTU-1/SPP-01.............................................................................................................................................. 5.3.3 RTU-2........................................................................................................................................................... 5.3.4 RTU-3........................................................................................................................................................... 5.3.5 RTU-4........................................................................................................................................................... 5.3.6 RTU-5........................................................................................................................................................... 5.4 Fan Unit.............................................................................................................................................................. 5.4.1 EF-06............................................................................................................................................................ 5.4.2 EF-07............................................................................................................................................................ 5.5 BGB Boca TB Plans M2.pdf............................................................................................................................... 6 Air Handling Unit...................................................................................................................................................... 9 6.1 AHU-01............................................................................................................................................................... 9 6.2 AHU-01/SPP-01................................................................................................................................................. 10 6.3 AHU-01/Duct Smoke Detector-01 SA................................................................................................................. 11 6.4 AHU-02............................................................................................................................................................... 12 6.5 AHU-02/SPP-01................................................................................................................................................. 13 6.6 AHU-02/Main...................................................................................................................................................... 14 M & M Test & Balance of FL M & M Test &,: , Balan c e - of FL Table Of Contents M & M Test & Balance of FL NqeJ3 CERTIFICATION PROJECT: Rosser Library Remodel 2950 Rosser Boulevard Port St. Lucie, Fl. 34953 AIR AND HYDRONICS SYSTEMS DATA THE DATA PRESENTED IN THIS REPORT IS A RECORD OF SYSTEM MEASUREMENTS AND FINAL ADJUSTMENTS THAT HAVE BEEN OBTAINED IN ACCORDANCE WITH THE CURRENT EDITION OF THE NEBB PROCEDURAL STANDARD FOR TESTING, ADJUSTING AND BALANCING OF ENVIRONMENTAL SYSTEMS. THE MEASUREMENTS SHOWN, AND THE INFORMATION GIVEN, IN THIS REPORT ARE CERTIFIED TO BE ACCURATE AND COMPLETE, AT THE TIME AND DATE INFORMATION WAS GATHERED. ANY VARIANCES FROM DESIGN QUANTITIES, WHICH `-EXCEED NEBB TOLERENCES, ARE NOTED IN THE TAB REPORT PROJECT SUMMARY. NEBB CONTRACTOR: MM TEST & BALANCE OF Fl. INC. 814 W. Eau Gallic Blvd Melbourne, FL 32935 REG. NO: 3249 CERTIFIED BY. M i:cltia.eL A. lac� Michael Iacobacci SUBMITTED & CERTIFIED BY: NEBB CONTRACTOR: NM TEST & BALANCE OF Fl. INC. 814 W. Eau Gallie Blvd Melbourne, FL 32935 REG. NO: 3249 CERTIFIED BY: M �L A. I a eo{yacci Michael Iacobacci DATE: October 24, 2017 DATE: October 24, 2017 MOAN NEBB Certification Board NEBB Certified Professional J4ichaeCA.1acobacci 1AS MET ALL THE NEBB REQUIREMENTS FOR NEBB CERTIFIED PROFESSIONAL STATUS IN D'esting, Adjusting and.Balancing of Clyw ionr►�entalsystems This Certificate, as well as individual affiliation with a NEBB Certified Firm and associated NEBB Certification stamp are REQUIRED to provide a NEBB Certified Report. Participation in the NEBB Quality -Assurance Program requires that the holder of this certification also be affiliated with a NEBB Certified Firm. March 31, 2018 Expiration Date 23283 NEBB Certificant Number NEBB Certifica o Board Chairman NEBB Certification Director The NEBB Certification Board retains sole ownership of all certificates. Use of this certificate is governed by the NEBB Certification Board policy Manual. WI Test and Balance of Florida Inc. Certification Na 3249 ■�WM .-Air & Hydronics Systems Testing • Project Summary JB AC & Electrical 1000 36th Street Stuart, FI 34994 Tel: 772.934.6778 Cell: Email: jbrowningac@gmail.com Attn: John Browning Ref: Preliminary Test and Balance PROJECT: Rosser Library Remodel 2950 Rosser Boulevard Port St. Lucie, FL 34953 Overview: October 10, 2017 6-Commercial split system cooling and heating systems installed vertically in 3 mechanical rooms, with remote air cooled DX condensing units located outside. All the systems are operated through an onsite Building Management System. (BMS) Externally insulated sheet metal ductwork for 6 zones of air distribution. Toll Free: 800.649.9166 Melbourne FI.: 321.751.0123 National Environmental Balancing Bureau IWANTest and Balance of Florida Inc. certification No. 3249 -.Air & Hydronics Systems Testing • The construction project was behind schedule when test and balance began. The list of deficiencies was long and involved multiple subcontractors. Air Flow Monitor duct sizes at sensor locations: AHU-1: 36 x 18 AHU-2: 20 x 18 AHU-3: 24 x 20 AHU-4: 20 x20 AHU-5: 24 x 20 AHU-6: 24 x 20 AIR PRODUCTS AND CONTROLS INC. SL-2000 SERIES DUCT SMOKE DETECTORS. Duct smoke detector units are designed to operate in duct widths from 6" to 10' wide with an air velocity between 100 to 4,000 feet per minute. The pressure differential between the sampling tubes has an acceptable range of 0.01" and 1.2" inches of water gage. AHU-1: S/A-.012" R/A-.05" AHU-4: S/A-.11" R/A-0.16" AHU-2: S/A-.011" R/A-.01" AHU-5: S/A-.05" R/A-0.82" AHU-3: S/A-.030" R/A-.0111 AHU-6: S/A-0.13" R/A-0.90" All installed smoke detectors are within range. rVi l.G{n.AP.{. A. It Michael A. Iacobacci II M&M Test and Balance of FI. Inc. Tall Free: 800.549.9166 Local: 321.751.0123 National Environmental Balancing Bureau Fax: 866-295-4392 Test and Balance of Florida Inc. NEEB certification No. 3249 viffi»Air& Hydronics Systems Testing • October 23, 2017 Project Comments JB AC & Electrical 1000 36th Street Stuart, FI. 34994 Cell: 772.353.0448 Cell: 772.634.6315 Attn: John Browning Project: Rosser Library AHU-1: Supply Cfm 99% of Design 1). All supply terminals in this area that have design Cfm of 50 or less are over performing with branch damper 100% closed. AHU-2: 1). AHU-2: is under -performing supply Cfm has been proportionately balanced with the available airflow. AHU-3: Operating at 93% of Design Cfm. AHU-4: Operation at 103% of Design Cfm. 1). All supply terminals in this area that have design Cfm of 50 or less are over performing with branch damper 100% closed. Toll Free: 800.549.9166 Loral: 321.751.0123 Fax: 866-296-4392 National Environmental Balancing Bureau �s Test and Balance of Florida Inc. NEEB certification No. 3249 .AA .:Air& Hydronics Systems Testing AHU-05 & 06: Are ducted in parallel and were balanced together as one machine; final Cfm output at 98% of Design. Note: "AHU-05 & AHU-06" (develops the Fan and Coil performance for AHU-05; and the Cfm quantities of the air outlets associated with (AHU-05 and AHU-06) "as tested". AHU-06 reports the Fan and Coil performance of AHU-6. If you need additional information or have questions regarding the completeness of this proposal please contact our office @ 321.751.0123. Thank you, Mi c{n.ae.{, A. ta.� It Michael A. Iacobacci / President CP MM Test and Balance of FI. Inc. Toll Free: 800.549.9166 Local: 321.751.0123 Fax: 866-295-4392 National Environmental Balancing Bureau 2017-2018 INSTRUMENT CALIBRATION REPORT M&M Test and Balance of Florida, Inc. ACCURACY/ CATEGORY APPLICATION/RANGE RESOLUTION INSTRUMENT F DATE DUE DATE ROTATION Rotation and Linear Speeds 2% of Reading 32 RPM Dual Function Tachometer 12 0 to 5000 RPM I RPM Extech 461920 Ian-17 Jan-18 SN: Q364293 TEMPERATURE Au Dry Bulb Readings t0.5% of Reading 3:1.4o F EVERGREEN TEMPERATURE PROBE 12 AIR Range— 40F to+240o F 3 0.2" F MODEL S-H-3-5' : a Nov-16 Nov-17 SERIAL 1500353 TEMPERATURE Fluid Temperature t0.5% of Reading t1.4o F EVERGREEN IMMERSION PROBE 12 IMMERSION Range=-0OF to+240°F 30.2oF MODEL PR-T-2 R Aug-17 Aug -IS SERIAL NUMBER 1400109 TEMPERATURE Surface Temperature 0.5%oflteadingf1.4o17 EVERGREEN CONTACT PROBE 12 CONTACT Range= 40F to+240o F 0.2-F MODEL PR-T4-6" p Aug-17 Aug-18 SERIAL NUMBER 1500117 ELECTRICAL Electrical Measmemen-CAT III Digital Voltmeter 12 MEASUREMENT t 2% of Reading t 5 digits Fluke 374 ,'T. April-17 April 18 Tme RMS Volts AC 0 to600 VAC 1.0 Volt Amperes 0 to 100 Amps 0.1 Ampere SN: 26510388WS AIR PRESSURE Static Pressure 0to 10.00 In. Wg, ± 2% of Reading 3.001 in w.g. 0.001 in w.g.51 in w.g EVERGREEN/PRESSURE/VELOCITY MODELS-PVF-1 12 Nov-16 Nov-17 MEASUREMENT 0.01 in w.g> I in w.g. SERIAL 1500230 AIR VELOCITY Velocity 2% of Reading t 4 FPM Rotating Vane Aneomometer 12 MEASUREMENT 50 to 2500 FPM 1.0 FPM MODEL 5725 N--<-. Apr-17 Apr-18 SERIAL T57250723004 { "Q Velocity 5% of Reading 27 FPM EVERGREEN/PRESSURE/VELOCITY fg- 50 to 3900 FPM 1.0 FPM MODEL S-PVF-1 Nov 16 Nov-17 SERIAL 1500230 HUMIDITY Wet Bulb, Relative Humidity, Enthalpy t 3% RH EVERGREEN TEMPERATURE PROBE 12 MEASUREMENT 10 to 90% RH 1 % Evergreen Telemetry S-H-3-5" Nov-16 Nov-17 SN:1500353 DIRECT Air Quantities Q Terminal 5%of Reading Micromanometer w/Capture Hood 12 READING 100 to 2000 CFM t 7 CFM Evergreen Telemetry S-PVF-1 Jan17 Jan 18 HOOD Digital-ICFM SN:1400242 Analog -N/A HYDRONIC Fluid Pressure Shortridge Hydronic Manometer 12 PRESSURE -30" bg. To 60 PSI t 2% of Reading/0.5 PSI HUM 300 Jun-17 Jun-18 0 to 100 PSI ± 2% of Reading/1.0 PSI SN: W05131 0 to 200 PSI 2% of Reading/2.5 PSI HYDRONIC Fluid Pressure Differential 2% Shorlridge Hydronic Manometer 12 DELTA ^P 0 to 100 In. Wg. 1.0 In. Wg. HUM 300 Jun-17 Jun-18 0 to 100 Ft. 1.0 Ft. Wg. SN: W05131 PITOT Used with Manometer or Not Applicable Dwyer Stainless Steel 5116" Dia. N/A TUBE Magoehelic Gauge to read Not Applicable 18" Pilot Tube 0/0/000 010/000 Sp, Vp, and Tp 36" Pilot Tube AIR Measure Rate of Air leakage Pressure Far W/ Calibrated Orifice N/A LEAKAGE in Ducts, Equipment United McGill 5"Dia 'u'k'±y NA NA '2MARKS: F=Frequency of Calibration Date= Date of Calibration TEST DATE, I0/10/2017- i ABBREVIATIONN40 AC AIR CONDITIONING KW KILOWATT AF AS FOUND LAT LEAVING AIR TEMPERATURE AFT ABOVE FINISHED FLOOR LATN LATENT AG ABOVE GRADE LRA LOCKED ROTOR AMPS AHU AIR HANDLING UNIT LVG LEAVING AD ACCESS DOOR MAX MAXIMUM APPROX APPROXIMATELY NA No ACCESS BDD BACK DRAFT DAMPER NL NOT LISTED HOD BOTTOM OF DUCT NSN NO SERIAL NUMBER BTU BRITISH THERMAL UNIT NTS NOT TO SCALE CAP CAPACITY OA OUTSIDE AIR CD CONDENSATE DRAIN OAL OUTSIDE AIR LOUVER CFM CUBIC FEET PER MINUTE P PRELIMINARY CMU CONCRETE. MASONRY UNITY PD PRESSURE DIFFERENTIAL CONN CONNECTION PH PHASE CRE CENTRIFUGAL ROOF EXHAUST RA RETURN AIR CU CONDENSING UNIT RD RAW DUCT DG DOOR GRILLE REF REFRIGERANT EAT ENTERING AIR TEMPERATURE RG RETURN GRILLE EF EXHAUST FAN RLA RUNNING LOAD AMPS EG EXHAUST GRILLE RTU ROOFTOP A/C UNIT EMS ENERGY MGMT. SYSTEM RV ROTATING VANE ANEMOMETER ENT ENTERING SA SUPPLY AIR ESP EXTERNAL STATIC PRESSURE SD SUPPLY DIFFUSER EXH EXHAUST SEN SENSIBLE F FAHRENHEIT SG SUPPLY GRILLE FRCP FIRE ALARM CONTROL PANEL T TRANSFER GRILLE FD FIRE DAMPER TRV TRAVERSE FLA FULL LOAD AMPACITY UON UNLESS OTHERWISE NOTED FPMB FAN POWER MIXING Box VAR VARIABLE FS FIRE STAT VFD VARIABLE FREQUENCY DRIVE HP HORSEPOWER WOCFM WIDE OPEN CFM HZ HERTZ IN. WG. INCHES WATER GAUGE �� M &- -M Test .Balance of FZ Air Handling Unit PROJECT: Rosser Library Remodel DATE: 10/24/2017 LOCATION: CONTACT: Michaellacobacci PROJECT M AUTHOR: SYSTEM/UNIT: AHU-01 Location m.e. ffi 1 Rm 41 Unit Manufacturer Trane Unit Model Number TWE120E300AC Unit Serial Number 17021YWMBA Equipment Type Air Handler DX Unit Discharge Vertical AHU-01/SF Filter Bank Filter Manufacturer AAF Filter Type Fiberglass Filter Qty- S1 4 Filter Size - S1 16x25xl 1st Service Date 7-20-2017 2nd Service Date 8-1-17 3rd Service Date 8-7-17 4th Service Date 8-16-17 5th Service Date 9-5-17 6th Service Date 9-6-17 7th Service Date 9-15-17 8th Service Date 9-18-17 9th Service Date 10-2-17 10th Service Date 10-5-17, 10-10-17, 10-18-17, 10-23-17 Specified CFM 3600 CFM Design Airflow 3700 CFM Actual Airflow 3666 CFM Design Outside Airflow 600 CFM Actual Outside Airflow 638 CFM Design Return Airflow 3100 CFM Actual Return Airflow 3028 CFM Actual RPM 1041 RPM Motor Volts Ti-T2 209 Volts Motor Volts T2-T3 211 Volts Motor Volts T1-T3 214 Volts Motor Amps T1 6.1 Amps Motor Amps T2 7.0 Amps Motor Amps T3 6.5 Amps Brake Horsepower 1.88 BHP Refrigerant Type 410A Camp 1 Design 17.80 Comp 1 Actual 13.7-14.5-13.3 Camp 2 Design 17.80 Comp 2 Actual 13.3-15.3-13.2 Design Olt BTUH 116.1 BTUH Design Q/s BTUH 90.5 BTUH. BTU Capacity Total 110529.9 BTUH BTU Capacity Sensible 93439.008 BTUH M & M Test & Balance of FL Tested By: Michael lacobacci Date: 10/24/2017 il AHU-011Supply Fan Motor Manufacturer Century Motor Frame 56HZ Motor HP 3 HP Motor RPM 1750 RPM Motor Rated Volts 208 Volts Motor Phase 3 Motor Hertz 60 Hz Motor FL Amps 9.4 Amps Nominal Efficiency 0.84 Motor Power Factor 0.7 . ^ Y?x gSheave DKR,*,=.:"f AHU-01/Supply Fan Fan Type Forward Curved Operating Diam. 4.25 Motor Sheave MFG Browning Motor Sheave Diam. 5-1/2 in. Motor Sheave Bore 7/8 in. Fan Sheave MFG Browning Fan Sheave Diam. 6 314 in. Fan Sheave Bore 1 in. Number of Belts 1 Belt Size A51 Sheave Center Line 17 112 in. Tes4Pressuressr �` P-€= Suction SP -1.08 in. we Discharge SP 0.61 in. we TSP Actual 1.69 in. we Design ESP 1.00 in. we External Suction SP -0.70 in. we External Discharge SP 0.61 in. we ESP Actual 1.31 in. we Heater Type Electric Heater Model BAYHTRL325AB Heater Serial 16463WO3LA Heater Volts 208 Volts Heater KW 18.7 KW Design Heat Amps 52.0 Amps Actual Heat Amps 52.0 Page 9 of 30 M :& N Test & , Balance of FL Air Handling Unit PROJECT: Rosser Library Remodel LOCATION: , PROJECTM SYSTEM/UNIT: AHU-01 Design LAT DB 57.5 DB Actual LAT DB 55.7 DB Design LAT WB 56.2 WB Actual LAT WB 53.9 WB Design EAT DB 78.9 DS Actual EAT DB 79.3 DS Design EAT WB 66.1 WB Actual EAT WB 67.4 WB RIA Temp DB 73.7 DB RIA Temp WB 69.2 WB CIA Temp DB 82.9 DB O/A Temp WB 70.6 WB EAT Enthalpy 33.2 h LAT EnthalDv 26.5 h DATE: 10/24/2017 CONTACT: Michael lacobacci AUTHOR: Tested By: Michael lacobacci Date: 10/24/2017 1 SYSTEM/UNIT: AHU-01/SPP-01 Tested By: Michael lacobacci Date: 10/24/2017 Test Pressures DX Coil SP In -0.82 in. w.c. DX Coil SP Out -1.07 in. w.c. Electric Coil SP In 0.50 in. w.c. Electric Coil SP Out 0.61 in. w.c. Pre Filter SP In -0.70 in. w.c. Pre Filter SP Out -0.81 in, w.c. Supply Fan SP In -1.08 in. w.c. Supply Fan SP Out 0.49 in. w.c. Static Pressure Profile 0.12 0.26 1.58 0.11 E L E SF T )TiT7xT( -0.70 -0.82 -1.08 0.50 0.61 M & M Test & Balance of FL Page 10 of 30 M &: M Test & Balance of FL Air Handling Unit PROJECT: Rosser Library Remodel DATE: 10/24/2017 LOCATION: CONTACT: Michael lacobacci PROJECT M AUTHOR: AHU-01 Supply Outlet Summary System/Unit-. Area'Served- Outlet - Type Size. LxWd D: Design Airflow :-Prelim Airflow: %Prelim Diff. Final. Airflow %Final+ Diff. Outlet-01 Unisex 9 C 6 50 98 196 69 138 Outlet-02 Office 8 A 6 100 86 86 100 100 Outlet-03 Staff 7 A 8 200 161 81 187 94 Outlet-04 Staff 7 A 8 200 157 79 201 101 Outlet-05 Women 5 C 6 50 54 108 66 132 Outlet-06 Men 4 C 6 50 63 126 64 128 Outlet-07 Lobby A 10 250 145 58 225 90 Outlet-08 Lobby 1 A 10 250 139 56 236 94 Outlet-09 Storage 2A A 6 150 66 44 159 106 Outlet-10 Lobby 1 A 12 300 265 88 318 106 Outlet-11 New Books A 6 100 54 54 101 101 Ouflet-12 Meeting 2 X 48x6 825 771 93 784 95 Outlet-13 Meeting 2 X 48x6 825 392 48 801 97 Outlet-14 E.E.6 D 8 20 2261 131 207 104 Outlet-15 Mech 41 150 244 163 148 99 ..Totals, :�. �:;. i,y _." .°i ,' ne c5e -+3700,>"•t�2956a qV„-+i SO'a, �y,366fi�§.„; tag+? 994, AHU-01 Return Inlet Summary SystemNnit . " } r Area Servetl :,`; ,Inlet Typep Size LxW'l; D ," Design ,;-6 Airflow Prehm�t l%/ Prelim- ' Finalt �`fAirflow'+ %uFina1';:, 'Diff.• al- Inlet-01 Meeting X 48x6 775 168 22 613 79 Inlet-02 Meeting X 48x6 775 105 14 793 102 Inlet-03 Staff B 6 275 79 29 253 92 Inlet-04 Office 8 B 8 100 43 43 80 80 Inlet-05 Lobby 1 B 12 500 66 13 428 86 Inlet-06 New books B 6 100 65 65 86 86 Inlet-07 Lobby 1 B 12 475 0 0 436 92 Inlet-08 E.E.6 E 8 100 158 158 88 88 3100 -: ;- 684, .,; 22� ': :... - 2777 .. :r . go M & M Test & Balance of FL Page 11 of 30 M &: M Test & Balance of ILL Air Handling Unit PROJECT: Rosser Library Remodel DATE: 10124/2017 LOCATION: CONTACT: Michael lacobacci PROJECT#: AUTHOR: SYSTEM/UNIT: AHU-02 Location m.e. Rm 28 Unit Manufacturer Trane Unit Model Number TEM3AOC6OS51SAB Unit Serial Number 164716K82V Equipment Type Air Handling Unit Unit Discharge Vertical AHU-021SF Filter Bank Filler Manufacturer AAF Filter Type Pleated Filter Qty - S1 1 Filter Size - S1 20x24x1 2nd Service Date 9-14-2017 3rd Service Dale 9-15-2017 4th Service Date 10-2-2017 Specified CFM 2000 CFM Design Airflow 2000 CFM Actual Airflow 1458 CFM Design Outside Airflow, 400 CFM Actual Outside Airflow 433 CFM Design Return Airflow, 1600 CFM Actual Return Airflow 1025 CFM 021Supoly Fan Motor Volts T1-T2 210 Volts Motor Amps T1 6.0 Amps Brake Horsepower 0.95 BHP Comp 1 Design 15.60 Comp 1 Actual 12.70 Design Qft BTUH 59.2 BTUH Design Q/s BTUH 43.9 BTUH BTU Capacity Total 49863.6 BTUH BTU Capacity Sensible 29445.768 BTUH Actual LAT DB 57.9 DB Design LAT WB 58.3 VVB Actual LAT NB 56.6 VVB Design EAT DB 78.9 DB Actual EAT IDS 76.6 DB Design EAT WB 66.1 WB Actual EAT WB 68.3 WB R/A Temp DB 70.8 DB R/A Temp WB 68.3 WB O/A Temp DB 82.1 DB M & M Test & Balance of FL Tested By: Michael lacobacci Date: 10/13/2017 Motor'Data AHU-021Suooly Fan Motor HP 314 HP Motor RPM Not Legible RPM Motor Rated Volts 208-230 Volts Motor Phase 1 Motor Hertz 60 Hz Motor FL Amps 6.3 Amps Nominal Efficiency 0.8 Motor Power Factor 0.7 Sheave Data AHU-021Suooly Fan Fan Type Forward Curved Operating Diam. Hi Speed Motor Sheave MFG Direct Drive Motor Sheave Model Direct Drive Motor Sheave Diam. Direct Drive in. Motor Sheave Bore Direct Drive in. Fan Sheave MFG Direct Drive Fan Sheave Model Direct Drive Fan Sheave Diam. Direct Drive in. Fan Sheave Bore Direct Drive in. Belt Size Direct Drive TesfPressures Suction SP -1.59 in. we Discharge SP 0.15 in. we . TSP Actual 1.74 in. we Design ESP 1.00 in. we External Suction SP -0.11 in. we External Discharge SP 0.15 in. we ESP Actual 0.26 in. we Electric Heat Heater Type Electric Heater Volts 208 Volts Page 12 of 30 M & M Test & � Balance of AL Air Handling Unit PROJECT: Rosser Library Remodel LOCATION: , PROJECT #: SYSTEM/UNIT: AHU-02 R9°atl Airr TeRRW O/A Temp WB 71.7 WB FAT Enthalpy 31.7 h LAT Enthalpy 24.1 h DATE: 10/24/2017 CONTACT: Michael lacobacci AUTHOR: Tested By: Michael lacobacci Date: 10/13/2017 SYSTEM/UNIT: AHU-02/SPP-01 Tested By: Michael lacobacci Date: 10/24/2017 DX Coil SP In�-0.22 in. w.c. DX Coil SP Out -1.58 in. w.c. Heating Coil SP In 0.11 in. w.c. Heating Coil SP Out 0.15 in, w.c. Pre Filler SP In -0.11 in. w.c. Pre Filter SP Out -0.21 in. w.c. Supply Fan SP In -1.60 in. w.c. Supply Fan SP Out 0.10 in. w.c. Static Pressure Profile '�� 1 ` 'U. ' `° `� "` - 1 i 0.11 1.36 1.71 0.04 D7-/ T—T(`SF T —W -0.11 -0.22 -1.60 0.11 0.15 M & M Test & Balance of FL Page 13 of 30 M & M Test & , Balance of Fl Air Handling Unit PROJECT: Rosser Library Remodel DATE: 10/24/2017 LOCATION: CONTACT: Michael lacobacci PROJECT M AUTHOR: SYSTEM/UNIT: AHU-02/Main - rtiAata= " Type of Traverse Rectangular Inside Dimension H 16.00 in. Inside Dimension W 20.00 in. Air Flow Area 2.22 sq. ft. Number Of Rows 4 Readings Per Row 4 Total Readings 16 Location of Hales 1 Left Location of Hales 2 Bottom Tested By: Michael lacobacci Date: 10/12/2017 Final�Data Sum of Readings 10502 Average Reading 656 FPM Design Total Flow 2000 CFM Actual Total Flow 1456 CFM Duct Static Press. 0.13 in. we Traverse Data Points e� N 2 O ra o cn is Row 1 Row 2 ® ® 712 m Row 3 6 00 656 733 Row 4 ® 616 ® 670 20 M & M Test & Balance of FL Page 14 of 30 M & - M Test & :Balance of F, l Air Handling Unit PROJECT: Rosser Library Remodel DATE: 10/24/2017 LOCATION: CONTACT: Michael lacobacci PROJECT M AUTHOR: AHU-02 Supply Outlet Summary ", SystemlUnit - ", _;,'.Area Served. Outlet - Type Size LxW:/ -0`- . _: Design Airflow Prelim Airflow %I Prelim Diff, -<A Finale Airflow %Final -. Diff. Outlet-01 Lounge 10 A 24/24 200 158 79 126 63 Outlet-02 Office 11 A 24/24 150 147 98 98 65 Outlet-03 Office 12 A .24/24 200 138 69 136 68 Outlet-04 Seating 13 A 24/24 300 201 67 215 72 Outlet-05 Seating 13 A 24/24 300 171 57 225 75 Outlet-06 Corridor A 24/24 100 71 71 66 66 Outlet-07 Work 30 A 24/24 150 65: 43 81 54 Outlet-08 Work 30 A 24/24 150 69 46 78 52 Outlet-09 Unisex 31 A 24124 25 89 356 30 120 Outlet-10 Kitchen A 24/24 25 89 356 31 124 Outlet-11 Law Library A 24124 200 170 85 203 102 Outlet-12 Law Library A 24124 200 165 83 182 91 Totals: - ^:- I - -- s 2000 1533'. '77 ' 147.1% E 74_[. AHU-02 Return Inlet Summary System/Unit' t Area Served inletType LXW / D Design, ` Airflow Prelim, Airflow '' r % PrelimF Diff. `;Final Airflow "/' Final 5 Diff: Inlet-01 Lounge 10 B 24/24 175 86 49 86 49 Inlet-02 " Office 11 B 24/24 125 44 35 44 35 Inlet-03 Office 12 B 24124 175 94 54 94 54 Inlet-04 Seating 13 B 24124 250 91 36 91 36 In1et705 Sealing 13 B 24/24 250 95 38 95 38 Inlet-06 Corridor B 24/24 75 47 63 47 63 Inlet-07 Work 30 B 24124 - 250 95 38 95 38 Inlet-08 Law library B 1 24124 150 64 43 64 43 Inlet-09 Law library B 1 24124 150 75 50 75 1 50 Totals: - 1500, 691 Ij;: 43' 691 43 M & M Test & Balance of FL Page 15 of 30 M &- N Test & � Balance :of AL Air Handling Unit PROJECT: Rosser Library Remodel DATE: 10/24/2017 LOCATION: CONTACT: Michael lacobacci PROJECT M AUTHOR: SYSTEMIUNIT: AHU-03 Location m.e.1 Rm 41 Unit Manufacturer Trane Unit Model Number TWE180E300AA Unit Serial Number 16403NNBWA Equipment Type Air Handler Unit Dischame Vertical Filter Manufacturer AAF Filter Type Fiberglass Filter Oty- S1 8 Filter Size - S1 15x20x2 2nd Service Date 8-16-2017 3rd Service Date 8-17-2017 4th Service Date 9-5-2017 5th Service Date 9-6-2017 Specified CFM 5000 CFM Design Airflow 5000 CFM Actual Airflow 4639 CFM Design Outside Airflow 700 CFM Actual Outside Airflow 721 CFM Design Return Airflow 4300 CFM Actual Return Airflow 3918 CFM Actual RPM 940 RPM Motor Volts Tt-T2 211 Volts Motor Volts T2-T3 215 Volts Motor Volts Tt-T3 211 Volts Motor Amps T1 8.5 Amps Motor Amps T2 9.4 Amps Motor Amps T3 9.0 Amps Brake Horsenower 3.04 BHP Refrigerant Type 410A Comp 1 Design 25.00 Comp 1 Actual 17.5-20.5-15.3 Comp 2 Design 25.00 Comp 2 Actual 16.6-20.3-18.6 Design Olt BTUH 173.5 BTUH Design Ols BTUH 124.3 BTUH BTU Capacity Total 175354.2 BTUH BTU Caoacity Sensible 98699.364 BTUH Design LAT DB b5.1 UB Actual LAT DB 56.4 DB Design LAT WB 54.1 WB M & M Test & Balance of FL Tested By: Michael lacobacci Date: 10/24/2017 t(k�7,"�MoiitoDatax� AHU-0315uooly Fan Motor Manufacturer Marathon Motor Frame 56HZ Motor HP 3 HP Motor RPM 1725 RPM Motor Rated Volts 208-230 Volts Motor Phase 3 Motor Hertz 60 Hz Motor FL Amps 9.9 Amps Nominal Efficiency 0.84 Motor Power Factor 0.82 p aix ; zr,Shes"ve Dataw x: z zf, va # ..�,' AH1.1-03ISunely Fan Fan Type Forward Curved Operating Diam. 5-1/2 Motor Sheave MFG Browning Motor Sheave Diam. 5 112 in. Motor Sheave Bore 7/8 in. Fan Sheave MFG Browning Fan Sheave Diam. 7-1/8 in. Fan Sheave Bore 1 7116 in. Number of Belts 1 Belt Size BX 60 Sheave Center Line 20-3/4 in. Suction SP -1.21 in. we Discharge SP 0.86 in. we TSP Actual 2.07 in. we Design ESP 1.00 in, we External Suction SP -0.77 in. we External Discharge SP 0.86 in. we ESP Actual 1.63 in. we f'g'f„P, ' `, "r'ElectricyHeaf. ` `�w Heater Type Electric Healer Model BAYHTRM330AB Heater Serial 16355PTALA Heater Volts 208 Volts Heater KW 22.5 KW Design Heat Amps 62.4 Amps Page 16 of 30 M & W Test &,Balance of FL Air Handling Unit PROJECT: Rosser Library Remodel LOCATION: , PROJECTM SYSTEM/UNIT: AHU-03 "Air TesG_Data Actual LAT WB 54.1 WB Design EAT DB 77.8 DB Actual FAT IDS 76.1 DB Design EAT WB 65.1 WB Actual EAT WB 67.4 WB R/A Temp DB 72.6 DB R/A Temp WB 69.9 WB O/A Temp DB 85.6 DB O/A Temp WB 79.7 WB EAT Enthalpy 33.7 h LAT Enthalpy 25.3 h DATE: 10/24/2017 CONTACT: Michael lacobacci AUTHOR: Tested By: Michael lacobacci Date: 10124/2017 SYSTEM/UNIT: AHU-03/SPP-01 Tested By: Michael lacobacci Date: 10/24/2017 TestpFressuresw.?,:^'` DX Coil SP In -0.89 in. w.c. DX Coil SP Out -1.21 in. w.c. Heating Coil SP In 0.74 in. w.c. Heating Coil SP Out 0.86 in. w.c. Pre Filter SP In -0.77 in. w.c. Pre Filter SP Out -0.89 in. w.c. Supply Fan SP In -1.21 in. w.c. Supply Fan SP Out 0.74 in. w.c. TM ° `4� 4 R n'k«..., , 3.� a; a- s. ���,.af�"r:: 0.12 0.32 1.95 0.12 )TIT70 T—WD -0.77 -0.89 -1.21 0.74 0.86 M & M Test & Balance of FL Page 17 of 30 M &. M Test & Balance of FL Air Handling Unit PROJECT: Rosser Library Remodel DATE: 10/24/2017 LOCATION: CONTACT: Michael lacobacci PROJECT#: AUTHOR: AHU-03 Supply Outlet Summary System/Unit, ( Area:Seryed - . Outlet Type Size LxW l D Design Airflow -Prelim Airflow %prelim - Diff.. Final Airflow % Finat.-. DIff.' Outlet-01 Youth Desk A 24/24 435 386 89 409 94 Outlet-02 Youth Desk A 24/24 430 370 86 422 98 Outlet-03 Youth Desk A 24/24 435 324 74 401 92 Outlet-04 Youth Desk A 24124 100 34 34 93 93 Outlet-05 Work 17 A 24124 100 253 253 101 101 Outiet-06 Activity 19 A 24/24 350 244 70 328 94 Outlet-07 Activity 19 A 24/24 350 240 69 318 91 Outlet-08 Activity 19 A 24/24 350 225 64 315 90 Outlet-09 Activity, 19 A 24/24 350 27 8 321 92 Outlet-10 YA 16 A 24/24 425 396 93 378 89 Outlet-11 YA 16 A 24124 425 370 87 396 93 Outlet-12 YA 16 A 24124 425 449 106 401 94 Outlet-13 YA 16 A 24124 425 350 82 393 92 Ouflet-14 YA 16 A 24124 400 257 64 363 91 Totals; - , 3925'- - 79- 746W .77W7 AHU-03 Return Inlet Summary " Systerrl/Unit Area Served, ". Inlet Type: Size LxW I D Design '> Airflow, Prelim ..-. AlrBow- �.% Prelim.:` Diff. Final -Airflow, %o r FIOaI'.'.` Diff. Inlet-01 Youth Desk 550 477 87 562 102 Inlet-02 Youth Desk 550 522 95 557 101 Inlet-03 Youth Desk 550 161 29 536 97 Inlet-04 YA 16 550 113 21 493 90 Inlet-05 YA 16 635 872 137 558 88 Inlet-06 YA 16 630 851 135 581 92 Inlet-07 YA 16 635 929 146 586 92 Inlet-08 Work 17 100 0 0 94 94 Inlet-09 Youth Desk 100 0 0 91 91 Totals: 4300 3925 .. '' 91 4058 94. M & M Test & Balance of FL Page 18 of 30 M & N Test &, Balance of Al. Air Handling Unit PROJECT: Rosser Library Remodel DATE: 10/24/2017 LOCATION: CONTACT: Michael lacobacci PROJECT M AUTHOR: SYSTEM/UNIT: AHU-04 Location m.e. FFL rnl 2a Unit Manufacturer Trane Unit Model Number TWE120E300AC Unit Serial Number 16404T36BA Equipment Type Air Handler Unit Discharge Vertical AHU-041SF Filter Bank Filter Manufacturer AAF Filter Type Pleated Filter Oty - S1 4 Filter Size - S1 16x25xl 1st Service Date 8-1-2017 2nd Service Date 8-7-2017 3rd Service Date 8-16-2017 4th Service Date 9-13-2017 5th Service Date 9-14-2017 1 6th Service Date 9-18-2017 Specified CFM 3200 CFM Design Airflow 3300 CFM Actual Airflow 3393 CFM Design Outside Airflow 1250 CFM Actual Outside Airflow 1341 CFM Design Return Airflow 2050 CFM Actual Return Airflow 2052 CFM Actual RPM 889 RPM Motor Volts T1-T2 216 Volts Motor Volts T2-T3 211 Volts Motor Volts T1-T3 216 Volts Motor Amps T1 4.4 Amps Motor Amps T2 4.9 Amps Motor Amps T3 3.9 Amps Brake Homenower 1.47 SHP Comp 1 Design 17.80 Comp 1 Actual 14.3-14.4-12.0 Comp 2 Design 17.80 Comp 2 Actual 13.7-12.4-11.0 Design Olt BTUH 119.0 BTUH Design O/s BTUH 88.5 BTUH BTU Capacity Total 146577.6 BTUH BTU Capacity Sensible 81350.568 BTUH Actual LAT DB 57.1 DB M & M Test & Balance of FL Tested By: Michael lacobacci Date: 10/18/2017 Motor Data AHU-04/Supply Fan Motor Manufacturer Marathon Motor Frame 56HZ Motor HP 2 HP Motor RPM 1725 RPM Motor Rated Volts 208-230/460 Volts Motor Phase 3 Motor Hertz 60 Hz Motor FL Amps 6.2 Amps Nominal Efficiency 0.84 Motor Power Factor 0.8 Sheave Data AHU-04/Suoely Fan Fan Type Forward Curved Operating Diam. WOCFM Motor Sheave MFG Browning Motor Sheave Diam. 41/2 in. Motor Sheave Bore 7/8 in. Fan Sheave MFG Browning Fan Sheave Diam. 8 in. Fan Sheave Bore 1 in. Number of Belts 1 Belt Size A50 Sheave Center Line 16 3/4 in. Test Pressures Suction SP -0.90 in. we Discharge SP 0.71 in. we TSP Actual 1.61 in. we Design ESP 1.00 in. we External Suction SP -0.52 in. we External Discharge SP 0.71 in. we ESP Actual 1.23 in. we Electric Heat Heater Type Electric Heater Model BAYHTRL325AD Heater Sedal 17041 N46LA Heater Volts 208 Volts Heater KW 18.7 KW Design Heat Amps 52.0 Amps Page 19 of 30 M &:,M Test & ,Balance .of l-1 Air Handling Unit PROJECT: Rosser Library Remodel LOCATION: , PROJECTM SYSTEM/UNIT: AHU-04 Coil Atr Test Data Design LAT WB 57.5 WB Actual LAT WB 55.1 WB Design EAT DB 82.5 DB Actual FAT DB 79.3 DB Design FAT WB 68.6 WB Actual EAT VJB 72.8 WB R/A Temp DS 73.3 DB R/A Temp WB 63.8 WB O/A Temp DB 82.3 DB O/A Temp WB 79.7 WB EAT Enthalpy 32.9 h LAT Enthalpy 23.3 h SYSTEM/UNIT: AHU-04/SPP-01 DATE: 10/24/2017 CONTACT: Michaellacobacci AUTHOR: Tested By: Michael lacobacci Date: 10118/2017 Tested By: Michael lacobacci Date: 10/13/2017 �.. Tes4Fressures DX Coil SP In -0.63 in. w.c. DX Coil SP Out -0.89 in. w.c. Final Filter SP In -0.52 in. w.c. Final Filter SP Out -0.62 in. w.c. Heating Coil SP In 0.62 in. w.c. Heating Coil SP Out 0.71 in. w.c. Supply Fan SP In -0.90 in. w.c. Supply Fan SP Out 0.61 in. w.c. 0.11 0.27 1.52 0.09 F ' I aT—T T x T'SF L -0.52 -0.63 -0.90 0.62 0.71 M & M Test & Balance of FL Page 20 of 30 M &, M Test & ,Balance of R. Air Handling Unit PROJECT: Rosser Library Remodel DATE: 10124/2017 LOCATION: CONTACT: Michael lacobacci PROJECT #: AUTHOR: AHU-04 Supply Outlet Summary System/Unit Area Served Outlet Type Size LAW I D- Design 'Airflow Prelim -Airflow % Prelim Diff. Final, Airflow % Final, Diff. Outlet-01 Reading 15 A 24124 100 104 104 103 103 Outlet-02 Reading 15 A 24124 100 95 95 96 96 Outlet-03 Reading 15 A 24/24 100 91 91 103 103 Outlet-04 Reading 15 A 24124 100 73 73 109 109 Outlet-05 Reading 15 A M24 100 90 90 96 96 Outlet-06 Reading 15 A 24/24 100 109 109 102 102 Outlet-07 Reading 15 A 24/24 100 97 97 97 97 Outlet-08 Reading 15 A 24124 100 63 63 105 105 Outlet-09 Reading 15 A 24124 100 91 91 109 109 Outlet-1 0 Reading 15 A 24124 too 41 41 !to 110 Outlet-1 1 Reading 15 A 24/24 100 95 95 110 110 Outlet-12 Reading 15 A 24124 100 95 95 102 102 Outlet-13 Reading 15 A 24124 100 103 103 104 104 Outlet-14 Reading 15 A 24/24 100 Ill ill 101 101 Outlet-15 Study 32 A 24/24 100 117 117 102 102 Outlet-16 Hall A 24/24 25 68 272 46 184 Outlet-17 Stor 22 A 24124 50 77 154 97 194 Outlet-18 Hall A 24/24 25 51 204 41 164 Outlet-19 Open A 24124 150 145 97 158 105 Outlet-20 Open A 24124 150 51 34 147 98 Outlet-21 Open A 24124 150 86 57 140 93 Outlet-22 Hall 27 A 24124 50 83 166 48 96 Outlet-23 Women25 A 24124 1010 62 62 90 90 Outlet-24 Men 24 A 24124 100 64 64 95 95 Outlet-25 Open A 24/24 150 57 38 158 105 Outl Open A 24/24 150 155 103 144 96 Outlet-27 Open A 24/24 150 74 49 151 101 Outlet-28 Open A 24/24 200 72 36 200 100 Outlet-29 Study 34 A 24/24 100 99 99 97 97 Outlet-30 Study 35 A 24/24 100 99 99 96 96 Outlet-31 m.!. 28 A 24124 150 0 0 136 91 Fals: 3300• 2618 79 3393 103 AHU-04 Return Inlet Summary Systemlunit, Area Served... i5 Inlet Type; Size -LAW/.: Design, I w t, Prelim , - %Rrellmg ""Airflow z, Flna4 'W� %.FlnaP;, biff Inlet-01 Study 35 B 24/24 75 54 72 74 99 Inlet-02 Study 34 B 24/24 75 65 87 68 91 Inlet-03 Hall West B 24/24 175 123 70 163 93 Inlet-04 Study 32 B 24124 75 68 91 74 99 Inlet-05 Hall West B 24/24 150 65 43 150 100 Inlet-06 Hall West B 24/24 150 54 36 136 91 Inlet-07 Hall 27 B 24/24 50 90 180 45 90 Inlet-08 Hall East B 24124 122 108 140 93 Inlet-09 Hall East B 24/24 0 213 142 158 105 Inlet-10 Stor 22 B 24124 50 134 268 82 164 Inlet-11 Hall South B 24124 425 277 65 460 108 Inlet-12 Hall South B 24124 425 322 76 443 104 Totals: 1960 1627 83 1993 JC l(M M & M Test & Balance of FL Page 21 of 30 M & :M Test & Balance of Al. Air Handling Unit PROJECT: Rosser Library Remodel DATE: 10/24/2017 LOCATION: CONTACT: Michael lacobacci PROJECT M AUTHOR: SYSTEM/UNIT: AHU-05 (Fan Test) and AHU-05 & AHU-06 (combined air outlet test) Location m.e. #3 Rm 40 Unit Manufacturer Trane Unit Model Number TWE120E300AC Unit Serial Number 16404T9FBA Equipment Type Air Handler DX Unit Discharge Vertical Filter Manufacturer AAF Filter Type Fiberglass Filter Qty - S1 4 Filter Size - Si 16x25xl 2nd Service Date 8-1-2017 3rd Service Date 8-7-2017 4lh Service Date 8-16-2017 5lh Service Date 9-13-2017 Specified CFM 3200 CFM Design Airflow 3275 CFM Actual Airflow 3010 CFM Design Outside Airflow 425 / 850 CFM Actual Outside Airflow 458 CFM Design Return Airflow 3275 CFM Actual Return Airflow 2552 CFM Actual RPM 765 RPM Motor Volts T1-T2 212 Volts Motor Volts T2-T3 216 Volts Motor Volts T1-T3 213 Volts Motor Amps T1 2.8 Amps Motor Amps T2 3.9 Amps Motor Amps T3 2.9 Amps Brake Horsepower 1.02 BHP Comp 1 Design 17.80 Comp 1 Actual 11.2-13.3-12.2 Comp 2 Design 17.80 Comp 2 Actual 11.5-13.5-12.1 Design Of BTUH 117.4 BTUH Design Q/s BTUH 86.0 BTUH BTU Capacity Total 96169.5 BTUH RTII Canarihr Sensihte 67616.64 BTUH Actual LAT DB 57.4 DS M & M Test & Balance of FL Tested By: Michael lacobacci Date: 10/24/2017 AHU-05 (Fan Test) and AHU-05 & AHU-06 (combined air outlet test)/Suooly Fan Motor Manufacturer Marathon Motor Frame 56HZ Motor HP 2.0 HP Motor RPM 1725 RPM Motor Rated Volts 208 Volts Motor Phase 3 Motor Hertz 60 Hz Motor FL Amps 6.2 Amps Nominal Efficiency 0.8 Motor Power Factor 0.8 NXIM AHU•05 (Fan Test) and AHU-05 & AHU-06 (combined air outlet test)/Supply Fan Fan Type Forward Curved Operating Diam. WOCFM Motor Sheave MFG Browning Motor Sheave Model Not Legible Motor Sheave Diam. 3 314 in. Motor Sheave Bore 7/8 in. Fan Sheave MFG Browning Fan Sheave Model Not Legible Fan Sheave Diam. 8 in. Fan Sheave Bore 1 in. Number of Belts 1 Bell Size 4L 250 Sheave Center Line 17 114 in. Suction SP -0.90 in. we Discharge SP 0.40 in. we TSP Actual 1.30 in. we Design ESP 1.00 in. we External Suction SP -0.58 in. we External Discharge SP 0.40 in. we ESP Actual 0.98 in. we vy, 4MW APP Heater Type Electric Heater Model BAYHTRL325AB Heater Serial 16464MF8LA Heater Volts 208 Volts Heater KW 18.7 KW Design Heat Amps 52.0 Amps Page 22 of 30 M & N Test &. Balance .of /Fl Air Handling Unit PROJECT: Rosser Library Remodel LOCATION: , PROJECT M DATE: 10/24/2017 CONTACT: Michael lacobacci AUTHOR: SYSTEM/UNIT: AHU-05 (Fan Test) and AHU-05 & Tested By: Michael lacobacci AHU-06 (combined air outlet test) Date: 10/24/2017 Coil Air Test Data Design LAT WB 56.7 WB Actual LAT WB 56.8 WB Design EAT DB 80.9 DB Actual EAT DB 78.2 DB Design EAT WB 67.8 WB Actual EAT WB 69.7 WB R/A Temp DB 73.7 DB R/A Temp WB 63.4 WB O/A Temp DB 80.9 DB O/A Temp WB 72.4 WB EAT Enthalpy 32.3 h LAT Enthalpy 25.2 h SYSTEM/UNIT: AHU-05 (Fan Test) and AHU-05 & Tested By: Michael lacobacci AHU-06 (combined air outlet test)/SPP-01 Date: 10/13/2017 a TestiPressures. DX Coil SP In -0.69 in. w.c. DX Coil SP Out -0.89 in. w.c. Electric Coil SP In 0.31 in. w.c. Electric Coil SP Out 0.40 in. w.c. Final Filter SP In -0.58 in. w.c. Final Filter SP Out -0.68in. w.c. Supply Fan SP In -0.90 in. w.c. Supply Fan SP Out 0.30 in. w.c. Static PreSsure�iPi, oflli�� -. - - 0.11 0.21 1.21 0.09 F E I E N F T L 7 I T T T -0.58 -0.69 -0.90 0.31 0.40 M & M Test & Balance of FL Page 23 of 30 M & N Test &.Balance of ILL Air Handling Unit PROJECT: Rosser Library Remodel DATE: 10/24/2017 LOCATION: CONTACT: Michael lacobacci PROJECTM AUTHOR: AHU-05 (Fan Test) and AHU-05 & AHU-06 (combined air outlet test) Supply Outlet Summary System/Unit ! - Area Served (Outlet Type Size`LxW,I D +Design Airflow Prelim -Airflow %.Prelim . `DiM Final' Airflows % Final" Diff..: Outlet-01 Meeting 36 A 24/24 450 415 92 433 96 Outlet-02 Meeting 36 A 24124 450 427 95 435 97 Outlet-03 Meeting 36 A 24124 450 430 96 412 92 Outlet-04 Meeting 36 A 24124 450 407 90 432 96 Outlet-05 Meeting 36 A 24124 450 352 78 412 92 Outlet-06 Meeting 36 A 24124 450 382 85 453 101 Outlet-07 Meeting 36 A 24124 450 372 83 474 105 Outlet-08 Meeting 36 A 24124 450 445 99 431 96 Outlet-09 Meeting 36 A 24/24 450 451 100 448 100 Outlet-10 Meeting 36 A 24/24 450 437 97 436 _, 97 Outlet-11 Meeting 36 A 24124 450 466 104 488 108 Outlet-12 Meeting 36 A 24/24 450 375 83 431- 96 Outlet-13 Storage 3 A 24/24 200 207 104 203 102 Outlet-14 Storage 3 A 24/24 200 174 87 204 102 Outlet-15 Ha1138 A 24/24 400 498 125 404 101 Outlet-16 Kitchen 39 A 24/24 200 181 91 194 97 Outlet-17 A 24/24 150 0 0 136 91 Totals: 92 AHU-05 (Fan Test) and AHU-05 & AHU-06 (combined air outlet test) Return Inlet Summary System/Unit, €Area Served" Inlet Typei Size LxW / D Design = Airflow, ;—Prelims' is Airflow - MoPrelim .. Diff. - ;-;'Final .'Airflow'- -°%'Final.- P rDiff. :. Inlet-01 Meeting 36 B 24124 325 215 66 296 91 Inlet-02 Meeting 36 B 24/24 325 207 64 283 87 Inlet-03 Meeting 36 B 24/24 325 187 58 312 96 Inlet-04 Meeting 36 B 24/24 325 230 71 296 91 Inlet-05 Meeting 36 B 24124 325 197 61 276 85 Inlet-06 Meeting 36 B 24124 325 188 58 265 82 Inlet-07 Meeting 36 B 24/24 325 228 70 269 83 Inlet-08 Meeting 36 B 24124 325 266 82 273 84 Inlet-09 Meeting 36 B 24124 325 285 88 274 84 Inlet-10 Meeting 36 B 24/24 325 311 96 263 81 Inlet-11 Meeting 36 B 24/24 325 338 104 267 82 Inlet-12 Meeting 36 B 24/24 325 341 105 281 86 Inlet-13 kitchen 39 B 24/24 150 250 167 136 91 Inlet-14 Hall38 B 24/24 325 408 126 261 80 Inlet-15 Storage 37 B 24/24 325 281 86 265 82 tals: `• 4700 - 3932 ,.. ,:': 84 774017;� r�';; 85 . M & M Test & Balance of FL Page 24 of 30 M &W Test &.-.Balance .of Al. Air Handling Unit PROJECT: Rosser Library Remodel DATE: 10/24/2017 LOCATION: CONTACT: Michael lacobacci PROJECT#: AUTHOR: SYSTEM/UNIT: AHU-06 (Fan test only) Location m.e. A Km 4U Unit Manufacturer Trans Unit Model Number TWE120E300AG Unit Serial Number 163443U6BA Equipment Type Air Handler Unit Discharge Vertical AHU-06 (Fan test only)/SF Filter Bank Filter Manufacturer AAF Filter Type Pleated Filler Qty - S1 4 Filler Size - S1 16x25xl 1st Service Date 7-19-17 2nd Service Date 7-20-17 3rd Service Date 9-14-17 4th Service Date 9-18-17 Specified CFM 3600 CFM Design Airflow 3275 CFM Actual Airflow 3213 CFM Design Outside Airflow 4251850 CFM Actual Outside Airflow 861 CFM Design Return Airflow 3275 CFM Actual Return Airflow, 2352 CFM Actual RPM 801 RPM Motor Volts Tt-T2 211 Volts Motor Volts T2-T3 212 Volts Motor Volts T1-T3 214 Volts Motor Amps T1 3.8 Amps Motor Amps T2 4.6 Amps Motor Amps T3 3.9 Amps Brake Horsepower 1.36 BHP Refrigerant Type 410A Comp 1.Design 17.80 Comp 1 Actual 13.3-12.8-11.4 Comp 2 Design 17.80 Comp 2 Actual 11.2-12.6-11.4 Design OR BTUH 117.4 BTUH Design Q/s BTUH 86.0 BTUH BTU Capacity Total 117113.85 BTUH BTU Canacitv Sensible 71482.824 BTUH Design LAT DB 57.8 UB Actual LAT DB 58.8 DB Design LAT WB 56.7 WB —' Actual LAT WB 58.3 WB M & M Test & Balance of FL Tested By: Michael lacobacci Date: 10/24/2017 AHU-06 (Fan test onlvl/Supply Fan Motor Manufacturer Marathon Motor Frame 56HZ Motor HP 2 HP Motor RPM 1725 RPM Motor Rated Volts 208 Volts Motor Phase 3 Motor Hertz 60 Hz Motor FL Amps 6.2 Amps Nominal Efficiency 0.84 Motor Power Factor 0.8 AHU-06 (Fan test only)ISupply Fan Fan Type Forward Curved Operating Diam. 3.0 Motor Sheave MFG Browning Motor Sheave Diam. 3 3/4in. Motor Sheave Bore 718 in. Fan Sheave MFG Browning Fan Sheave Diam. 8 in. Fan Sheave Bore 1 in. Number of Belts 1 Belt Size A49 Sheave Center Line 18 in. Test PressuresrT,2, Suction SP -0.91 in. we Discharge SP 0.38 in. we TSP Actual 1.29 in. we Design ESP 1.00 in. we External Suction SP -0.58 in. we External Discharge SP 0.38 in. we ESP Actual 0.96 in. we rry$ fitn to eat Heater Type Electric Heater Model BAYHTRL325AB Heater Serial 17041POWLA Heater Volts 208 Volts Heater KW 18.7 KW Design Heat Amps 52.0 Amps Page 25 of 30 M &.M Test &-Balance of FL Air Handling Unit PROJECT: Rosser Library Remodel LOCATION: , PROJECTM DATE: 10/24/2017 CONTACT: Michael lacobacci AUTHOR: SYSTEM/UNIT: AHU-06 (Fan test only) Tested By: Michael lacobacci Date: 10/24/2017 Design EAT IDS 80.9 DBE Actual EAT DB 79.4 DB Design EAT WB 67.8 WB Actual EAT WB 68.3 WB R/A Temp DB 72.5 DB R/A Temp WB 63.5 WB O/A Temp DB 82.6 DB O/A Temp WB 73.3 WB EAT Enthalpy 33.4 h LAT Enthalpy 25.3 h SYSTEM/UNIT: AHU-06 (Fan test only)/SPP Tested By: Michael lacobacci Date: 10/13/2017 DX Coil SP In -0.69 in. w.c. DX Coil SP Out -0.90 in. w.c. Electric Coil SP In 0.29 in. w.c. Electric Coil SP Out 0.38 in. w.c. Final Filter SP In -0.58 in. w.c. Final Filter SP Out -0.68 in. w.c. Supply Fan SP In -0.91 in. w.c. Supply Fan SP Out 0.28 in. w.c. Statie�Pressur„e Profile �'- t �' - - - '*�-.u• mod' aa'3N?�+rH�3a�'r3�wi3�'t ivct?��6:�, �`�rm..�i' 0.11 0.22 1.20 0'.09 F E I E N `SF LT Tcl —0.58 —0.69 —0.91 0.29 0.38 M & M Test & Balance of FL Page 26 of 30 M & M Test & Balance- of ILL Fan Unit PROJECT: Rosser Library Remodel LOCATION: , PROJECT #: SYSTEM/UNIT: EF-1 UnitData Area Served unisex4 Test data Design Airflow 50 CFM Actual Airflow 75 CFM SYSTEM/UNIT: EF-2 Unit Data . Location ceiling Area Served women 5 Test Data Design Airflow 50 CFM Actual Airflow 52 CFM SYSTEM/UNIT: EF-3 Unit Data " - Location Ceiling Area Served Unisex 9 Test Data - Design Airflow 50 CFM Actual Airflow 64 CFM SYSTEM/UNIT: EF4 Unit Data,, Location Ceiling Area Served Women 25 Test oata:# Design Airflow 250 CFM Actual Airflow 170 CFM M & M Test & Balance of FL DATE: 10/24/2017 CONTACT: Michael lacobacci AUTHOR: Tested By: Michael lacobacci Date: 10/12/2017 Rated Airflow Capacity 50 CFM Tested By: Michael lacobacci Date: 10/12/2017 Motor Data; ` Rated Airflow Capacity 50 CFM Tested By: Michael lacobacci Date: 10/12/2017 Motor Data' _ Rated Airflow Capacity 50 CFM Tested By: Michael lacobacci Date: 10/12/2017 Page 27 of 30 M & - M Test & . Balance of FL Fan Unit PROJECT: Rosser Library Remodel DATE: 10/24/2017 LOCATION: CONTACT: Michael lacobacci PROJECT M AUTHOR: SYSTEMIUNIT: EF-5 Unit Data Location cieling Area Served Men RR 24 Fan Manufacturer Cook Fan Model Number Gemini 400 Series Classification Inline Exhaust Starter Data Starter Manufacturer Not applicable Tost Data Design Airflow 250 CFM Actual Airflow 181 CFM Design RPM 1350 RPM Actual RPM Hi Speed RPM Motor Volts T1-T2 123 Volts Motor Amps T1 0.70 Amps Design ESP 0.50 in. we SYSTEM/UNIT: EF-5 Uriit7Data _ _ Location ceiling Area Served Unisex 31 _ _ Test Data Design Airflow 50 CFM Actual Airflow 76 CFM Tested By: Michael lacobacci Date: 10/2/2017 Motor Data Rated Airflow Capacity 250 CFM Motor HP 1/23 HP Motor Rated Volts 115 Volts Motor Phase 1 Motor Hertz 60 Hz Motor FL Amps 1.00 Amps Motor Service Factor 1.00 Corrected FL Amps 0.93 Amps Operating Diam. Direct Sheave Data Motor Sheave MFG Direct Drive Motor Sheave Model Direct Drive Motor Sheave Diam. Direct Drive in. Motor Sheave Bore Direct Drive in. Fan Sheave MFG Direct Drive Fan Sheave Model Direct Drive Fan Sheave Diam. Direct Drive in. Fan Sheave Bore Direct Drive in. Belt Size Direct Drive Sheave Center Line Direct Drive in. Tested By: Michael lacobacci Date: 10/1212017 lowNwormlew Motor Data Rated Airflow Capacity, 50 CFM Motor Hertz 60 Hz M & M Test & Balance of FL Page 28 of 30 O ME e� 7.1 � w ILI an� e MM Test and Balance Of Fl. Inc. i 614 W. Eau Gallle Blvd ----- MclDounne, FI. 32935 T-600.649.9166 0 0 0 @ wI gPLN-6ECHAMAL O f1EFM3ENCE NOTES -NEW > o Ya o � . n i III O� MEr.�a I SII,Y J I 0 0 PY•!L•]N14 a w a' Y § ® e Q I. F � O ]OIrYNIYP m J e � ar utn�xr]] nmM CONSTRUCTION PLANS FOR ROSSER LIBRARY IN SECTION 14, TOWNSHIP 37 SOUTH, RANGE 39 EAST PORT ST. LUCIE, FLORIDA PREPARED FOR LOCATION MAP N.T.s. sernox le ... 3a S..... 99 . �I Pp$NIIR'19-131.100'LOPB➢lG ST. LUCIE COUNTY I INDEX TO SHEETS NO. DRSMIMUON 1 CoMt I= 2 = ID ROI'6lQ+NT PI 3 DSI'AD. SRRRP LEGAL DESCRIPTION m..wu n*mL swn. .mm nuax. w`>rT n I. —El .."ea:r'µvvwI rwen'.1.I. 1m; a ...a 6 1-11 Rnro`n`rtgs`am ar azmm.v 6 mE auenrw oisw®�anm°M` uvrie• E..vwv :.io u.Y. A om xw s eiam REr: nm� e2anr . Rm. Exu¢ a wmrr x. osrww a Ram REr. ra..a i eT Ill iR azewa If 1. Ra now morn• w m R[ ro M ewE a.am`'ov: EwO�o"a`s eisinyi . oO1Pvr"..¢?o°Snwmiie.ea"`e.. a wmoawfp1� _-_.___ �I Ilummu. mnmw>v.aca wean VICR= MAP N.TS. UTILITIES m.m PER M I2/2/15 C'ULPEPPER & TERPENING INC CONSULTING ENGINEERS I LAND SURVEYORS cr SIN1fH1W SM6@T IOATPDXL&PLJIIIDAJ.9B1 VNON6 AJ1HSSf>. PAY77S11LV9). �.smmg.-® 9lAleOPPl[I90AP(NROOPPAORffiIONN. EW'Pl®]AVINO2DtTONN0..1y6 EI mucunn ri Ro�� CRY OP PSI. PROx:R X0. p(.�-1$S BOSS® IIDIUBT 19-121.100 d9aP 1 CP ]