SHOP DRAWING REVIEW COMMENTS October 17, 2017
Reference: SLC Rosser Blvd Library
SWC #14035
Subject: Final Test and Balance Report Submittal
Re -submittal 10/27/17
Re -submittal 12/7/17
Reviewed by: Kyle A. Wilkerson
Kyle J. Cartier, P.E.
Sam F. Siciliano
Engineers review is for general conformance with the design concept and contract documents. Markings or comments
shall not be construed as relieving the Contractor from compliance with the project plans and specifications, nor
departures therefrom. The Contractor remains responsible for details and accuracy, compliance with the Contract
Documents and intent, for confirming and correcting all quantities and dimensions, for selecting appropriate fabrication
processes,for techniques of assembly, and for performance of work in a safe manner.
OVERALL DISPOSITION: Ro4se and ResubmWNote Markings
• ...
NO
.
..
Supply... return aifflews fer AdiU - and q 4 ., ew
.. ...
..
,_
w rates.
and system. Pre Ade ..plated test And t...t....ee repe ft
2. Test and balance results for AHU-2 are provided by Absolutely Cool Air
Conditioning and supersede the AHU-2 results provided in report from M&M
Test and Balance of Florida.
AHU-3: Nate Mafkiags
12124 High Tech Avenue • Suite 200. Orlando, Florida 32817 • (407) 380-0400 - FAX (407) 380-5900
` 1 Det..m aiF Wet W is 1 Sq04 of design value Adjust air fle.., e f deyiee to within
z
100/ e f Ae..:p value.
2. No exceptions taken to performance of air handling unit fan and coil.
AHU-4: No Exceptions Taken
AHU-5: t Nee nr,� N4arkings
z
AHU-6: e e Nt,c gs
EF-1,2,3,6: No Exceptions Taken
EF-4,5: Devise and De..ubff 4
1. Aetual airflews of eAaus} f ft 32 not d 27 6 belew design values a de
�a ao c-rano-ai$Tovivmava—r-�riv-ooiwracar�.n�mncri[icvvv
net satisfy -minimufn eiihaust iegtttremeats-for sgaee. Investigate and peffeFm
M. adifie;4ions or repaifs to system neee......fy i artier to eet.:eye required ai f flew
values.
END OF DOCUMENT
12124 High Tech Avenue • Suite 200. Orlando, Florida 32817 • (407) 380-0400 • FAX (407) 380-5900
i
�► /�►�I�IAT�M'
C of-pu T 'R tW C .1117
3126 Fortune Way, Suite 13 • Wellington, Florida 33414
Rosser Library
Renovation
PROJECT NO.: # 100213VB
All -Report
Subm&W No. 19990 -002
Stamped TestRepoit
By: Sims Wilkerson Cartier Engineering, Inc.
NOTE MARKINGS
Engineer's review is forgeneral conformance with the design concept and
contract documents. Wrkings or comments shall not be cornwed as
relieving the Contractor from compliance with the project plans and
specllications,nor departures therefrom.
The Contractor remains resporrsible for details and accuracy, compliance
with the Contract Documents and Intent, for confirmhg and correcting all
quantities and dimensions, for selecting appropriate fabrication processes,
for techniques of assembly, and for performance ofwork In a safe manner.
By: Kyle A. Wilkerson ec 7, 2017
(X) Reviewed with No Exceptions
( ) Reviewed as Noted
( ) Rejected
( ) Revised and Resubmit
( ) Submit Specified Item
Review is for general conformance with the design concept
and the information given in the Construction Documents.
_A�,ze�msa�{ Date: 12/05/2017
NE1Pl ty0
Sid lole
a Z'
��O/IAL P$$O
TESTING, ADJUSTING. AND -BALANCING BUREAU
THE PROFESSIONAL'S CHOICES"
This certifies that
Douglas Pence
has completed the requirements of certification as a
Testing, Adjusting and Balancing Technician
on
Ee6ruary 20, 2015
Lq�orCo-ChMrrnan
(` 1�4
ICB Co -Chairman
(DB042001C
Certification No.
MqOgernent Co -Chairman
r .
a�G
/�XA
1C5.o-Chairman
pecem6er 31. 2025
Expiration Date
t.
ABSOLUTELY COOL AIR CONDITIONING, LLC
Air Conditioning — Heating — Refrigeration'— Installation
Martin County Certified
TABB # DBO42001C
Rosser Library
Rosser Library
2950 SW Rosser Blvd
2950 SW Rosser Blvd
Port St Lucie FL
Port St Lucie FL
Air Handling Unit
AHU-02 TEM3A0C605S1SA
AHU-02 TEIN3A0C605S15A
164716K82V
164716K82V
Supply Outlets
Return Outlets
Design Airflow
Actual Airflow
Design Airflow
Actual Airflow
Outlet 1 180
161
Outlet 1 157.5
151
Outlet 2 135
130
Outlet 2 112.5
109
Outlet 3 180
156
Outlet 3 157.5
153
Outlet 4 270
268
Outlet 4 225
219
Outlet 5 270
251
Outlet 5 225
220
Outlet 6 90
82
Outlet 6 67.5
63
Outlet 7 135
102
Outlet 7 225
227
Outlet 8 135
104
Outlet 8 135
121
Outlet 9 25
53
Outlet 9 135
120
Outlet 10 25
52
Outlet it 180
172
Total 1440
1383
Outlet 12 190
161
Total % 96%
Total 1800
1692
Total % 94%
Static Pressure 0.4
Absolutely Cool Air Conditioning, LLC
2311 NE 15th Court
Jensen Beach, FL 34957
772.4754641
ABSOLUTELY:COOL AIR CONDITIONING, LLC
Phone: (772) 475-4641 Fax: (772) 225-9872
Absolutelycoolair@gmail.com — www.Absolute]yC—no!Air.com
License & Insured #CAC1815702 — Locally & Family Owned & Operated
TABB Certificate # DB042001C
National Environmental Balancing
Bureau / Cert. #3249 March 2018
Broward County T.A.B./ Fire Safety
3-CTB-866-W 8-31-2016
State of Florida Class "A" Unlimited HVAC
CAC-025401
NATE Certification
10-27521
Outdoor Conditions 91.7db / 80.7wb
CERTIFIED TEST, ADJUST, AND
BALANCE REPORT
PROJECT # 17-1155-TB
Rosser Library Remodel
2950 Rosser Boulevard Port St. Lucie Fl. 34953
Architect:
Edlund Dritenbas Binkley 65
Royal Palm Pointe, Suite D
Vero Beach, FL. 32960
P: 772.569.4320
General Contractor:
Anatom construction Company
3125 Fortune Way # 13
Wellington, Fl. 33414
T-561.221.0226
October 24, 2017
Engineer:
Sims Wilkerson Carter Eng.
12124 High Tech Avenue -Suite 200
Orlando, Fl. 32817
T-407.380.0400 Fx 407.380.5900
Mechanical Contractor:
JB AC & Electrical
1000 36th Street
Stuart, Fl. 34994
Cell: 772.353.0448
IM•
Test and Balance of Florida Inc.
'"Air & Hydronics Systems Testing 6
M & _M Test & - Balance of AL
Table Of Contents
PROJECT: Rosser Library Remodel DATE: 10/10/2017
LOCATION: CONTACT: Michael lacobacci
PROJECT #: AUTHOR:
Table Of Contents
1 Certification Page 171155TB102417.pdf.................................................................................................................
1
2 7_ NEBB certificate.pdf............................................................................................................................................
2
3 Test and Balance of Florida Inc. Certification No. 3249...........................................................................................
3
3.1 0Air&HydronicsSystemsTesting0..........................................................................................
3
4 Test and Balance of Florida Inc. NEEB Certification No. 3249................................................................................
5
4.1 0Air&HydrenicsSystemsTesting0..........................................................................................
5
5 CalibrationAbbev..pdf...............................................................................................................................................
7
5.1 Table Of Contents..............................................................................................................................................
5.2 burtons boca.pdf.................................................................................................................................................
5.2.1 IPdf:7ce5c681-8d96-4500-ab73-c82d043e27cc...........................................................................................
5.2.2 Table Of Contents.........................................................................................................................................
5.2.3 Test and Balance of Florida Inc. Certification No. 3249.........................................................
5.2.3.1(Air(Hydronics Systems Testing(................................................................................
5.2.4 Certification 171161TB ECRWRF.pdf...........................................................................................................
5.2.5 Inst Calib Report —Evergreen Telem 12017.pdf.............................................................................................
7
5.2.6 NEW Abbreviation Guide 161153TB.pdf......................................................................................................
8
5.2.7 Air Handling Unit...........................................................................................................................................
5.2.7.1 AHU-1......................................................................................................................................................
5.2.7.2 AHU-1/Main Supply.................................................................................................................................
5.2.8 Fan Unit........................................................................................................................................................
5.2.8.1 EF-01.......................................................................................................................................................
5.2.9 DIAGRAM.....................................................................................................................................................
5.2.10 PB WATER UTILITIES ECRWRF PLANSTB.pdf.......................................................................................
5.3 Air Handling Unit.................................................................................................................................................
5.3.1 RTU-1...........................................................................................................................................................
5.3.2 RTU-1/SPP-01..............................................................................................................................................
5.3.3 RTU-2...........................................................................................................................................................
5.3.4 RTU-3...........................................................................................................................................................
5.3.5 RTU-4...........................................................................................................................................................
5.3.6 RTU-5...........................................................................................................................................................
5.4 Fan Unit..............................................................................................................................................................
5.4.1 EF-06............................................................................................................................................................
5.4.2 EF-07............................................................................................................................................................
5.5 BGB Boca TB Plans M2.pdf...............................................................................................................................
6 Air Handling Unit......................................................................................................................................................
9
6.1 AHU-01...............................................................................................................................................................
9
6.2 AHU-01/SPP-01.................................................................................................................................................
10
6.3 AHU-01/Duct Smoke Detector-01 SA.................................................................................................................
11
6.4 AHU-02...............................................................................................................................................................
12
6.5 AHU-02/SPP-01.................................................................................................................................................
13
6.6 AHU-02/Main......................................................................................................................................................
14
M & M Test & Balance of FL
M & M Test &,: , Balan c e - of FL
Table Of Contents
M & M Test & Balance of FL
NqeJ3 CERTIFICATION
PROJECT: Rosser Library Remodel
2950 Rosser Boulevard
Port St. Lucie, Fl. 34953
AIR AND HYDRONICS SYSTEMS DATA
THE DATA PRESENTED IN THIS REPORT IS A RECORD OF SYSTEM MEASUREMENTS AND FINAL
ADJUSTMENTS THAT HAVE BEEN OBTAINED IN ACCORDANCE WITH THE CURRENT EDITION
OF THE NEBB PROCEDURAL STANDARD FOR TESTING, ADJUSTING AND BALANCING OF
ENVIRONMENTAL SYSTEMS. THE MEASUREMENTS SHOWN, AND THE INFORMATION GIVEN, IN
THIS REPORT ARE CERTIFIED TO BE ACCURATE AND COMPLETE, AT THE TIME AND DATE
INFORMATION WAS GATHERED. ANY VARIANCES FROM DESIGN QUANTITIES, WHICH
`-EXCEED NEBB TOLERENCES, ARE NOTED IN THE TAB REPORT PROJECT SUMMARY.
NEBB CONTRACTOR: MM TEST & BALANCE OF Fl. INC.
814 W. Eau Gallic Blvd
Melbourne, FL 32935
REG. NO: 3249 CERTIFIED BY. M i:cltia.eL A. lac�
Michael Iacobacci
SUBMITTED & CERTIFIED BY:
NEBB CONTRACTOR: NM TEST & BALANCE OF Fl. INC.
814 W. Eau Gallie Blvd
Melbourne, FL 32935
REG. NO: 3249 CERTIFIED BY: M �L A. I a eo{yacci
Michael Iacobacci
DATE: October 24, 2017
DATE: October 24, 2017
MOAN
NEBB Certification Board
NEBB Certified Professional
J4ichaeCA.1acobacci
1AS MET ALL THE NEBB REQUIREMENTS FOR
NEBB CERTIFIED PROFESSIONAL STATUS IN
D'esting, Adjusting and.Balancing of Clyw ionr►�entalsystems
This Certificate, as well as individual affiliation with a NEBB Certified Firm and associated NEBB Certification stamp
are REQUIRED to provide a NEBB Certified Report. Participation in the NEBB Quality -Assurance Program
requires that the holder of this certification also be affiliated with a NEBB Certified Firm.
March 31, 2018
Expiration Date
23283
NEBB Certificant Number
NEBB Certifica o Board Chairman
NEBB Certification Director
The NEBB Certification Board retains sole ownership of all certificates. Use of this certificate is governed by the NEBB Certification Board policy Manual.
WI Test and Balance of Florida Inc. Certification Na 3249
■�WM .-Air & Hydronics Systems Testing •
Project Summary
JB AC & Electrical
1000 36th Street
Stuart, FI 34994
Tel: 772.934.6778
Cell:
Email: jbrowningac@gmail.com
Attn: John Browning
Ref: Preliminary Test and Balance
PROJECT: Rosser Library Remodel
2950 Rosser Boulevard
Port St. Lucie, FL 34953
Overview:
October 10, 2017
6-Commercial split system cooling and heating systems installed vertically
in 3 mechanical rooms, with remote air cooled DX condensing units located
outside.
All the systems are operated through an onsite Building Management
System. (BMS)
Externally insulated sheet metal ductwork for 6 zones of air distribution.
Toll Free: 800.649.9166 Melbourne FI.: 321.751.0123
National Environmental Balancing Bureau
IWANTest and Balance of Florida Inc. certification No. 3249
-.Air & Hydronics Systems Testing •
The construction project was behind schedule when test and balance
began.
The list of deficiencies was long and involved multiple subcontractors.
Air Flow Monitor duct sizes at sensor locations:
AHU-1:
36 x 18
AHU-2:
20 x 18
AHU-3:
24 x 20
AHU-4:
20 x20
AHU-5:
24 x 20
AHU-6:
24 x 20
AIR PRODUCTS AND CONTROLS INC.
SL-2000 SERIES DUCT SMOKE DETECTORS.
Duct smoke detector units are designed to operate in duct widths from 6" to 10'
wide with an air velocity between 100 to 4,000 feet per minute.
The pressure differential between the sampling tubes has an acceptable range
of 0.01" and 1.2" inches of water gage.
AHU-1: S/A-.012" R/A-.05" AHU-4: S/A-.11" R/A-0.16"
AHU-2: S/A-.011" R/A-.01" AHU-5: S/A-.05" R/A-0.82"
AHU-3: S/A-.030" R/A-.0111 AHU-6: S/A-0.13" R/A-0.90"
All installed smoke detectors are within range.
rVi l.G{n.AP.{. A. It
Michael A. Iacobacci II
M&M Test and Balance of FI. Inc.
Tall Free: 800.549.9166 Local: 321.751.0123
National Environmental Balancing Bureau
Fax: 866-295-4392
Test and Balance of Florida Inc. NEEB certification No. 3249
viffi»Air& Hydronics Systems Testing •
October 23, 2017
Project Comments
JB AC & Electrical
1000 36th Street
Stuart, FI. 34994
Cell: 772.353.0448
Cell: 772.634.6315
Attn: John Browning
Project: Rosser Library
AHU-1: Supply Cfm 99% of Design
1). All supply terminals in this area that have design Cfm of 50 or less are
over performing with branch damper 100% closed.
AHU-2:
1). AHU-2: is under -performing supply Cfm has been proportionately
balanced with the available airflow.
AHU-3: Operating at 93% of Design Cfm.
AHU-4: Operation at 103% of Design Cfm.
1). All supply terminals in this area that have design Cfm of 50 or less are
over performing with branch damper 100% closed.
Toll Free: 800.549.9166 Loral: 321.751.0123 Fax: 866-296-4392
National Environmental Balancing Bureau
�s Test and Balance of Florida Inc. NEEB certification No. 3249
.AA .:Air& Hydronics Systems Testing
AHU-05 & 06: Are ducted in parallel and were balanced together as one
machine; final Cfm output at 98% of Design.
Note: "AHU-05 & AHU-06" (develops the Fan and Coil performance for
AHU-05; and the Cfm quantities of the air outlets associated with (AHU-05
and AHU-06) "as tested".
AHU-06 reports the Fan and Coil performance of AHU-6.
If you need additional information or have questions regarding the completeness of this
proposal please contact our office @ 321.751.0123.
Thank you,
Mi c{n.ae.{, A. ta.� It
Michael A. Iacobacci / President CP
MM Test and Balance of FI. Inc.
Toll Free: 800.549.9166 Local: 321.751.0123 Fax: 866-295-4392
National Environmental Balancing Bureau
2017-2018 INSTRUMENT CALIBRATION REPORT
M&M Test and Balance of Florida, Inc.
ACCURACY/
CATEGORY
APPLICATION/RANGE
RESOLUTION
INSTRUMENT
F
DATE
DUE DATE
ROTATION
Rotation and Linear Speeds
2% of Reading 32 RPM
Dual Function Tachometer
12
0 to 5000 RPM
I RPM
Extech 461920
Ian-17
Jan-18
SN: Q364293
TEMPERATURE
Au Dry Bulb Readings
t0.5% of Reading 3:1.4o F
EVERGREEN TEMPERATURE PROBE
12
AIR
Range— 40F to+240o F
3 0.2" F
MODEL S-H-3-5'
: a
Nov-16
Nov-17
SERIAL 1500353
TEMPERATURE
Fluid Temperature
t0.5% of Reading t1.4o F
EVERGREEN IMMERSION PROBE
12
IMMERSION
Range=-0OF to+240°F
30.2oF
MODEL PR-T-2
R
Aug-17
Aug -IS
SERIAL NUMBER 1400109
TEMPERATURE
Surface Temperature
0.5%oflteadingf1.4o17
EVERGREEN CONTACT PROBE
12
CONTACT
Range= 40F to+240o F
0.2-F
MODEL PR-T4-6"
p
Aug-17
Aug-18
SERIAL NUMBER 1500117
ELECTRICAL
Electrical Measmemen-CAT III
Digital Voltmeter
12
MEASUREMENT
t 2% of Reading t 5 digits
Fluke 374
,'T.
April-17
April 18
Tme RMS
Volts AC
0 to600 VAC
1.0 Volt
Amperes
0 to 100 Amps
0.1 Ampere
SN: 26510388WS
AIR PRESSURE
Static Pressure
0to 10.00 In. Wg,
± 2% of Reading 3.001 in w.g.
0.001 in w.g.51 in w.g
EVERGREEN/PRESSURE/VELOCITY
MODELS-PVF-1
12
Nov-16
Nov-17
MEASUREMENT
0.01 in w.g> I in w.g.
SERIAL 1500230
AIR VELOCITY
Velocity
2% of Reading t 4 FPM
Rotating Vane Aneomometer
12
MEASUREMENT
50 to 2500 FPM
1.0 FPM
MODEL 5725
N--<-.
Apr-17
Apr-18
SERIAL T57250723004
{ "Q
Velocity
5% of Reading 27 FPM
EVERGREEN/PRESSURE/VELOCITY
fg-
50 to 3900 FPM
1.0 FPM
MODEL S-PVF-1
Nov 16
Nov-17
SERIAL 1500230
HUMIDITY
Wet Bulb, Relative Humidity, Enthalpy
t 3% RH
EVERGREEN TEMPERATURE PROBE
12
MEASUREMENT
10 to 90% RH
1 %
Evergreen Telemetry S-H-3-5"
Nov-16
Nov-17
SN:1500353
DIRECT
Air Quantities Q Terminal
5%of Reading
Micromanometer w/Capture Hood
12
READING
100 to 2000 CFM
t 7 CFM
Evergreen Telemetry S-PVF-1
Jan17
Jan 18
HOOD
Digital-ICFM
SN:1400242
Analog -N/A
HYDRONIC
Fluid Pressure
Shortridge Hydronic Manometer
12
PRESSURE
-30" bg. To 60 PSI
t 2% of Reading/0.5 PSI
HUM 300
Jun-17
Jun-18
0 to 100 PSI
± 2% of Reading/1.0 PSI
SN: W05131
0 to 200 PSI
2% of Reading/2.5 PSI
HYDRONIC
Fluid Pressure Differential
2%
Shorlridge Hydronic Manometer
12
DELTA ^P
0 to 100 In. Wg.
1.0 In. Wg.
HUM 300
Jun-17
Jun-18
0 to 100 Ft.
1.0 Ft. Wg.
SN: W05131
PITOT
Used with Manometer or
Not Applicable
Dwyer Stainless Steel 5116" Dia.
N/A
TUBE
Magoehelic Gauge to read
Not Applicable
18" Pilot Tube
0/0/000
010/000
Sp, Vp, and Tp
36" Pilot Tube
AIR
Measure Rate of Air leakage
Pressure Far W/ Calibrated Orifice
N/A
LEAKAGE
in Ducts, Equipment
United McGill 5"Dia
'u'k'±y
NA
NA
'2MARKS: F=Frequency of Calibration Date= Date of Calibration TEST DATE, I0/10/2017-
i
ABBREVIATIONN40
AC
AIR CONDITIONING
KW
KILOWATT
AF
AS FOUND
LAT
LEAVING AIR TEMPERATURE
AFT
ABOVE FINISHED FLOOR
LATN
LATENT
AG
ABOVE GRADE
LRA
LOCKED ROTOR AMPS
AHU
AIR HANDLING UNIT
LVG
LEAVING
AD
ACCESS DOOR
MAX
MAXIMUM
APPROX
APPROXIMATELY
NA
No ACCESS
BDD
BACK DRAFT DAMPER
NL
NOT LISTED
HOD
BOTTOM OF DUCT
NSN
NO SERIAL NUMBER
BTU
BRITISH THERMAL UNIT
NTS
NOT TO SCALE
CAP
CAPACITY
OA
OUTSIDE AIR
CD
CONDENSATE DRAIN
OAL
OUTSIDE AIR LOUVER
CFM
CUBIC FEET PER MINUTE
P
PRELIMINARY
CMU
CONCRETE. MASONRY UNITY
PD
PRESSURE DIFFERENTIAL
CONN
CONNECTION
PH
PHASE
CRE
CENTRIFUGAL ROOF EXHAUST
RA
RETURN AIR
CU
CONDENSING UNIT
RD
RAW DUCT
DG
DOOR GRILLE
REF
REFRIGERANT
EAT
ENTERING AIR TEMPERATURE
RG
RETURN GRILLE
EF
EXHAUST FAN
RLA
RUNNING LOAD AMPS
EG
EXHAUST GRILLE
RTU
ROOFTOP A/C UNIT
EMS
ENERGY MGMT. SYSTEM
RV
ROTATING VANE ANEMOMETER
ENT
ENTERING
SA
SUPPLY AIR
ESP
EXTERNAL STATIC PRESSURE
SD
SUPPLY DIFFUSER
EXH
EXHAUST
SEN
SENSIBLE
F
FAHRENHEIT
SG
SUPPLY GRILLE
FRCP
FIRE ALARM CONTROL PANEL
T
TRANSFER GRILLE
FD
FIRE DAMPER
TRV
TRAVERSE
FLA
FULL LOAD AMPACITY
UON
UNLESS OTHERWISE NOTED
FPMB
FAN POWER MIXING Box
VAR
VARIABLE
FS
FIRE STAT
VFD
VARIABLE FREQUENCY DRIVE
HP
HORSEPOWER
WOCFM
WIDE OPEN CFM
HZ
HERTZ
IN. WG.
INCHES WATER GAUGE
��
M &- -M Test .Balance of FZ
Air Handling Unit
PROJECT: Rosser Library Remodel DATE: 10/24/2017
LOCATION: CONTACT: Michaellacobacci
PROJECT M AUTHOR:
SYSTEM/UNIT: AHU-01
Location
m.e. ffi 1 Rm 41
Unit Manufacturer
Trane
Unit Model Number
TWE120E300AC
Unit Serial Number
17021YWMBA
Equipment Type
Air Handler DX
Unit Discharge
Vertical
AHU-01/SF Filter Bank
Filter Manufacturer
AAF
Filter Type
Fiberglass
Filter Qty- S1
4
Filter Size - S1
16x25xl
1st Service Date
7-20-2017
2nd Service Date
8-1-17
3rd Service Date
8-7-17
4th Service Date
8-16-17
5th Service Date
9-5-17
6th Service Date
9-6-17
7th Service Date
9-15-17
8th Service Date
9-18-17
9th Service Date
10-2-17
10th Service Date
10-5-17, 10-10-17, 10-18-17,
10-23-17
Specified CFM
3600 CFM
Design Airflow
3700 CFM
Actual Airflow
3666 CFM
Design Outside Airflow
600 CFM
Actual Outside Airflow
638 CFM
Design Return Airflow
3100 CFM
Actual Return Airflow
3028 CFM
Actual RPM
1041 RPM
Motor Volts Ti-T2
209 Volts
Motor Volts T2-T3
211 Volts
Motor Volts T1-T3
214 Volts
Motor Amps T1
6.1 Amps
Motor Amps T2
7.0 Amps
Motor Amps T3
6.5 Amps
Brake Horsepower
1.88 BHP
Refrigerant Type
410A
Camp 1 Design
17.80
Comp 1 Actual
13.7-14.5-13.3
Camp 2 Design
17.80
Comp 2 Actual
13.3-15.3-13.2
Design Olt BTUH
116.1 BTUH
Design Q/s BTUH
90.5 BTUH.
BTU Capacity Total
110529.9 BTUH
BTU Capacity Sensible
93439.008 BTUH
M & M Test & Balance of FL
Tested By: Michael lacobacci
Date: 10/24/2017
il
AHU-011Supply Fan
Motor Manufacturer
Century
Motor Frame
56HZ
Motor HP
3 HP
Motor RPM
1750 RPM
Motor Rated Volts
208 Volts
Motor Phase
3
Motor Hertz
60 Hz
Motor FL Amps
9.4 Amps
Nominal Efficiency
0.84
Motor Power Factor
0.7
. ^ Y?x gSheave DKR,*,=.:"f
AHU-01/Supply Fan
Fan Type
Forward Curved
Operating Diam.
4.25
Motor Sheave MFG
Browning
Motor Sheave Diam.
5-1/2 in.
Motor Sheave Bore
7/8 in.
Fan Sheave MFG
Browning
Fan Sheave Diam.
6 314 in.
Fan Sheave Bore
1 in.
Number of Belts
1
Belt Size
A51
Sheave Center Line
17 112 in.
Tes4Pressuressr �` P-€=
Suction SP
-1.08 in. we
Discharge SP
0.61 in. we
TSP Actual
1.69 in. we
Design ESP
1.00 in. we
External Suction SP
-0.70 in. we
External Discharge SP
0.61 in. we
ESP Actual
1.31 in. we
Heater Type
Electric
Heater Model
BAYHTRL325AB
Heater Serial
16463WO3LA
Heater Volts
208 Volts
Heater KW
18.7 KW
Design Heat Amps
52.0 Amps
Actual Heat Amps
52.0
Page 9 of 30
M :& N Test & , Balance of FL
Air Handling Unit
PROJECT: Rosser Library Remodel
LOCATION: ,
PROJECTM
SYSTEM/UNIT: AHU-01
Design LAT DB
57.5 DB
Actual LAT DB
55.7 DB
Design LAT WB
56.2 WB
Actual LAT WB
53.9 WB
Design EAT DB
78.9 DS
Actual EAT DB
79.3 DS
Design EAT WB
66.1 WB
Actual EAT WB
67.4 WB
RIA Temp DB
73.7 DB
RIA Temp WB
69.2 WB
CIA Temp DB
82.9 DB
O/A Temp WB
70.6 WB
EAT Enthalpy
33.2 h
LAT EnthalDv
26.5 h
DATE: 10/24/2017
CONTACT: Michael lacobacci
AUTHOR:
Tested By: Michael lacobacci
Date: 10/24/2017
1
SYSTEM/UNIT: AHU-01/SPP-01 Tested By: Michael lacobacci
Date: 10/24/2017
Test Pressures
DX Coil SP In
-0.82 in. w.c.
DX Coil SP Out
-1.07 in. w.c.
Electric Coil SP In
0.50 in. w.c.
Electric Coil SP Out
0.61 in. w.c.
Pre Filter SP In
-0.70 in. w.c.
Pre Filter SP Out
-0.81 in, w.c.
Supply Fan SP In
-1.08 in. w.c.
Supply Fan SP Out
0.49 in. w.c.
Static Pressure Profile
0.12 0.26 1.58 0.11
E
L
E
SF T
)TiT7xT(
-0.70 -0.82 -1.08 0.50 0.61
M & M Test & Balance of FL Page 10 of 30
M &: M Test & Balance of FL
Air Handling Unit
PROJECT: Rosser Library Remodel DATE: 10/24/2017
LOCATION: CONTACT: Michael lacobacci
PROJECT M AUTHOR:
AHU-01 Supply Outlet Summary
System/Unit-.
Area'Served-
Outlet -
Type
Size. LxWd
D:
Design
Airflow
:-Prelim
Airflow:
%Prelim
Diff.
Final.
Airflow
%Final+
Diff.
Outlet-01
Unisex 9
C
6
50
98
196
69
138
Outlet-02
Office 8
A
6
100
86
86
100
100
Outlet-03
Staff 7
A
8
200
161
81
187
94
Outlet-04
Staff 7
A
8
200
157
79
201
101
Outlet-05
Women 5
C
6
50
54
108
66
132
Outlet-06
Men 4
C
6
50
63
126
64
128
Outlet-07
Lobby
A
10
250
145
58
225
90
Outlet-08
Lobby 1
A
10
250
139
56
236
94
Outlet-09
Storage 2A
A
6
150
66
44
159
106
Outlet-10
Lobby 1
A
12
300
265
88
318
106
Outlet-11
New Books
A
6
100
54
54
101
101
Ouflet-12
Meeting 2
X
48x6
825
771
93
784
95
Outlet-13
Meeting 2
X
48x6
825
392
48
801
97
Outlet-14
E.E.6
D
8
20
2261
131
207
104
Outlet-15
Mech 41
150
244
163
148
99
..Totals, :�.
�:;. i,y _." .°i
,'
ne c5e
-+3700,>"•t�2956a
qV„-+i
SO'a,
�y,366fi�§.„;
tag+? 994,
AHU-01 Return Inlet Summary
SystemNnit
. " }
r Area Servetl :,`;
,Inlet Typep
Size LxW'l;
D
," Design ,;-6
Airflow
Prehm�t
l%/ Prelim-
' Finalt
�`fAirflow'+
%uFina1';:,
'Diff.• al-
Inlet-01
Meeting
X
48x6
775
168
22
613
79
Inlet-02
Meeting
X
48x6
775
105
14
793
102
Inlet-03
Staff
B
6
275
79
29
253
92
Inlet-04
Office 8
B
8
100
43
43
80
80
Inlet-05
Lobby 1
B
12
500
66
13
428
86
Inlet-06
New books
B
6
100
65
65
86
86
Inlet-07
Lobby 1
B
12
475
0
0
436
92
Inlet-08
E.E.6
E
8
100
158
158
88
88
3100 -:
;- 684,
.,; 22� ':
:... - 2777 ..
:r . go
M & M Test & Balance of FL
Page 11 of 30
M &: M Test & Balance of ILL
Air Handling Unit
PROJECT: Rosser Library Remodel DATE: 10124/2017
LOCATION: CONTACT: Michael lacobacci
PROJECT#: AUTHOR:
SYSTEM/UNIT: AHU-02
Location
m.e. Rm 28
Unit Manufacturer
Trane
Unit Model Number
TEM3AOC6OS51SAB
Unit Serial Number
164716K82V
Equipment Type
Air Handling Unit
Unit Discharge
Vertical
AHU-021SF Filter Bank
Filler Manufacturer
AAF
Filter Type
Pleated
Filter Qty - S1
1
Filter Size - S1
20x24x1
2nd Service Date
9-14-2017
3rd Service Dale
9-15-2017
4th Service Date
10-2-2017
Specified CFM
2000 CFM
Design Airflow
2000 CFM
Actual Airflow
1458 CFM
Design Outside Airflow,
400 CFM
Actual Outside Airflow
433 CFM
Design Return Airflow,
1600 CFM
Actual Return Airflow
1025 CFM
021Supoly Fan
Motor Volts T1-T2
210 Volts
Motor Amps T1
6.0 Amps
Brake Horsepower
0.95 BHP
Comp 1 Design
15.60
Comp 1 Actual
12.70
Design Qft BTUH
59.2 BTUH
Design Q/s BTUH
43.9 BTUH
BTU Capacity Total
49863.6 BTUH
BTU Capacity Sensible
29445.768 BTUH
Actual LAT DB
57.9 DB
Design LAT WB
58.3 VVB
Actual LAT NB
56.6 VVB
Design EAT DB
78.9 DB
Actual EAT IDS
76.6 DB
Design EAT WB
66.1 WB
Actual EAT WB
68.3 WB
R/A Temp DB
70.8 DB
R/A Temp WB
68.3 WB
O/A Temp DB
82.1 DB
M & M Test & Balance of FL
Tested By: Michael lacobacci
Date: 10/13/2017
Motor'Data
AHU-021Suooly Fan
Motor HP
314 HP
Motor RPM
Not Legible RPM
Motor Rated Volts
208-230 Volts
Motor Phase
1
Motor Hertz
60 Hz
Motor FL Amps
6.3 Amps
Nominal Efficiency
0.8
Motor Power Factor
0.7
Sheave Data
AHU-021Suooly Fan
Fan Type
Forward Curved
Operating Diam.
Hi Speed
Motor Sheave MFG
Direct Drive
Motor Sheave Model
Direct Drive
Motor Sheave Diam.
Direct Drive in.
Motor Sheave Bore
Direct Drive in.
Fan Sheave MFG
Direct Drive
Fan Sheave Model
Direct Drive
Fan Sheave Diam.
Direct Drive in.
Fan Sheave Bore
Direct Drive in.
Belt Size
Direct Drive
TesfPressures
Suction SP
-1.59 in. we
Discharge SP
0.15 in. we .
TSP Actual
1.74 in. we
Design ESP
1.00 in. we
External Suction SP
-0.11 in. we
External Discharge SP 0.15 in. we
ESP Actual
0.26 in. we
Electric Heat
Heater Type
Electric
Heater Volts
208 Volts
Page 12 of 30
M & M Test & � Balance of AL
Air Handling Unit
PROJECT: Rosser Library Remodel
LOCATION: ,
PROJECT #:
SYSTEM/UNIT: AHU-02
R9°atl Airr TeRRW
O/A Temp WB 71.7 WB
FAT Enthalpy 31.7 h
LAT Enthalpy 24.1 h
DATE: 10/24/2017
CONTACT: Michael lacobacci
AUTHOR:
Tested By: Michael lacobacci
Date: 10/13/2017
SYSTEM/UNIT: AHU-02/SPP-01 Tested By: Michael lacobacci
Date: 10/24/2017
DX Coil SP In�-0.22
in. w.c.
DX Coil SP Out
-1.58 in. w.c.
Heating Coil SP In
0.11 in. w.c.
Heating Coil SP Out
0.15 in, w.c.
Pre Filler SP In
-0.11 in. w.c.
Pre Filter SP Out
-0.21 in. w.c.
Supply Fan SP In
-1.60 in. w.c.
Supply Fan SP Out
0.10 in. w.c.
Static Pressure Profile '�� 1 ` 'U.
' `° `� "` - 1 i
0.11 1.36 1.71 0.04
D7-/
T—T(`SF
T —W
-0.11 -0.22 -1.60 0.11 0.15
M & M Test & Balance of FL Page 13 of 30
M & M Test & , Balance of Fl
Air Handling Unit
PROJECT: Rosser Library Remodel DATE: 10/24/2017
LOCATION: CONTACT: Michael lacobacci
PROJECT M AUTHOR:
SYSTEM/UNIT: AHU-02/Main
- rtiAata= "
Type of Traverse
Rectangular
Inside Dimension H
16.00 in.
Inside Dimension W
20.00 in.
Air Flow Area
2.22 sq. ft.
Number Of Rows
4
Readings Per Row
4
Total Readings
16
Location of Hales 1
Left
Location of Hales 2
Bottom
Tested By: Michael lacobacci
Date: 10/12/2017
Final�Data
Sum of Readings
10502
Average Reading
656 FPM
Design Total Flow
2000 CFM
Actual Total Flow
1456 CFM
Duct Static Press.
0.13 in. we
Traverse Data Points
e� N 2 O
ra o cn is
Row 1
Row 2
® ® 712
m
Row 3
6 00 656 733
Row 4
® 616 ® 670
20
M & M Test & Balance of FL Page 14 of 30
M & - M Test & :Balance of F, l
Air Handling Unit
PROJECT: Rosser Library Remodel DATE: 10/24/2017
LOCATION: CONTACT: Michael lacobacci
PROJECT M AUTHOR:
AHU-02 Supply Outlet Summary
", SystemlUnit
-
", _;,'.Area Served.
Outlet
- Type
Size LxW:/
-0`- . _:
Design
Airflow
Prelim
Airflow
%I Prelim
Diff, -<A
Finale
Airflow
%Final
-. Diff.
Outlet-01
Lounge 10
A
24/24
200
158
79
126
63
Outlet-02
Office 11
A
24/24
150
147
98
98
65
Outlet-03
Office 12
A
.24/24
200
138
69
136
68
Outlet-04
Seating 13
A
24/24
300
201
67
215
72
Outlet-05
Seating 13
A
24/24
300
171
57
225
75
Outlet-06
Corridor
A
24/24
100
71
71
66
66
Outlet-07
Work 30
A
24/24
150
65:
43
81
54
Outlet-08
Work 30
A
24/24
150
69
46
78
52
Outlet-09
Unisex 31
A
24124
25
89
356
30
120
Outlet-10
Kitchen
A
24/24
25
89
356
31
124
Outlet-11
Law Library
A
24124
200
170
85
203
102
Outlet-12
Law Library
A
24124
200
165
83
182
91
Totals:
- ^:-
I -
--
s 2000
1533'.
'77 '
147.1%
E 74_[.
AHU-02 Return Inlet Summary
System/Unit'
t Area Served
inletType
LXW /
D
Design,
` Airflow
Prelim,
Airflow ''
r % PrelimF
Diff.
`;Final
Airflow
"/' Final 5
Diff:
Inlet-01
Lounge 10
B
24/24
175
86
49
86
49
Inlet-02
" Office 11
B
24/24
125
44
35
44
35
Inlet-03
Office 12
B
24124
175
94
54
94
54
Inlet-04
Seating 13
B
24124
250
91
36
91
36
In1et705
Sealing 13
B
24/24
250
95
38
95
38
Inlet-06
Corridor
B
24/24
75
47
63
47
63
Inlet-07
Work 30
B
24124 -
250
95
38
95
38
Inlet-08
Law library
B
1 24124
150
64
43
64
43
Inlet-09
Law library
B
1 24124
150
75
50
75
1 50
Totals:
- 1500,
691
Ij;: 43'
691
43
M & M Test & Balance of FL Page 15 of 30
M &- N Test & � Balance :of AL
Air Handling Unit
PROJECT: Rosser Library Remodel DATE: 10/24/2017
LOCATION: CONTACT: Michael lacobacci
PROJECT M AUTHOR:
SYSTEMIUNIT: AHU-03
Location
m.e.1 Rm 41
Unit Manufacturer
Trane
Unit Model Number
TWE180E300AA
Unit Serial Number
16403NNBWA
Equipment Type
Air Handler
Unit Dischame
Vertical
Filter Manufacturer
AAF
Filter Type
Fiberglass
Filter Oty- S1
8
Filter Size - S1
15x20x2
2nd Service Date
8-16-2017
3rd Service Date
8-17-2017
4th Service Date
9-5-2017
5th Service Date
9-6-2017
Specified CFM
5000 CFM
Design Airflow
5000 CFM
Actual Airflow
4639 CFM
Design Outside Airflow
700 CFM
Actual Outside Airflow
721 CFM
Design Return Airflow
4300 CFM
Actual Return Airflow
3918 CFM
Actual RPM
940 RPM
Motor Volts Tt-T2
211 Volts
Motor Volts T2-T3
215 Volts
Motor Volts Tt-T3
211 Volts
Motor Amps T1
8.5 Amps
Motor Amps T2
9.4 Amps
Motor Amps T3
9.0 Amps
Brake Horsenower
3.04 BHP
Refrigerant Type
410A
Comp 1 Design
25.00
Comp 1 Actual
17.5-20.5-15.3
Comp 2 Design
25.00
Comp 2 Actual
16.6-20.3-18.6
Design Olt BTUH
173.5 BTUH
Design Ols BTUH
124.3 BTUH
BTU Capacity Total
175354.2 BTUH
BTU Caoacity Sensible
98699.364 BTUH
Design LAT DB b5.1 UB
Actual LAT DB 56.4 DB
Design LAT WB 54.1 WB
M & M Test & Balance of FL
Tested By: Michael lacobacci
Date: 10/24/2017
t(k�7,"�MoiitoDatax�
AHU-0315uooly Fan
Motor Manufacturer
Marathon
Motor Frame
56HZ
Motor HP
3 HP
Motor RPM
1725 RPM
Motor Rated Volts
208-230 Volts
Motor Phase
3
Motor Hertz
60 Hz
Motor FL Amps
9.9 Amps
Nominal Efficiency
0.84
Motor Power Factor
0.82
p aix ; zr,Shes"ve Dataw x: z zf, va # ..�,'
AH1.1-03ISunely Fan
Fan Type
Forward Curved
Operating Diam.
5-1/2
Motor Sheave MFG
Browning
Motor Sheave Diam.
5 112 in.
Motor Sheave Bore
7/8 in.
Fan Sheave MFG
Browning
Fan Sheave Diam.
7-1/8 in.
Fan Sheave Bore
1 7116 in.
Number of Belts
1
Belt Size
BX 60
Sheave Center Line
20-3/4 in.
Suction SP
-1.21 in. we
Discharge SP
0.86 in. we
TSP Actual
2.07 in. we
Design ESP
1.00 in, we
External Suction SP
-0.77 in. we
External Discharge SP 0.86 in. we
ESP Actual
1.63 in. we
f'g'f„P, ' `, "r'ElectricyHeaf.
` `�w
Heater Type
Electric
Healer Model
BAYHTRM330AB
Heater Serial
16355PTALA
Heater Volts
208 Volts
Heater KW
22.5 KW
Design Heat Amps
62.4 Amps
Page 16 of 30
M & W Test &,Balance of FL
Air Handling Unit
PROJECT: Rosser Library Remodel
LOCATION: ,
PROJECTM
SYSTEM/UNIT: AHU-03
"Air TesG_Data
Actual LAT WB
54.1 WB
Design EAT DB
77.8 DB
Actual FAT IDS
76.1 DB
Design EAT WB
65.1 WB
Actual EAT WB
67.4 WB
R/A Temp DB
72.6 DB
R/A Temp WB
69.9 WB
O/A Temp DB
85.6 DB
O/A Temp WB
79.7 WB
EAT Enthalpy
33.7 h
LAT Enthalpy
25.3 h
DATE: 10/24/2017
CONTACT: Michael lacobacci
AUTHOR:
Tested By: Michael lacobacci
Date: 10124/2017
SYSTEM/UNIT: AHU-03/SPP-01 Tested By: Michael lacobacci
Date: 10/24/2017
TestpFressuresw.?,:^'`
DX Coil SP In
-0.89 in. w.c.
DX Coil SP Out
-1.21 in. w.c.
Heating Coil SP In
0.74 in. w.c.
Heating Coil SP Out
0.86 in. w.c.
Pre Filter SP In
-0.77 in. w.c.
Pre Filter SP Out
-0.89 in. w.c.
Supply Fan SP In
-1.21 in. w.c.
Supply Fan SP Out
0.74 in. w.c.
TM ° `4� 4 R
n'k«..., , 3.� a; a- s. ���,.af�"r::
0.12 0.32 1.95 0.12
)TIT70 T—WD
-0.77 -0.89 -1.21 0.74 0.86
M & M Test & Balance of FL Page 17 of 30
M &. M Test & Balance of FL
Air Handling Unit
PROJECT: Rosser Library Remodel DATE: 10/24/2017
LOCATION: CONTACT: Michael lacobacci
PROJECT#: AUTHOR:
AHU-03 Supply Outlet Summary
System/Unit,
( Area:Seryed -
.
Outlet
Type
Size LxW l
D
Design
Airflow
-Prelim
Airflow
%prelim
- Diff..
Final
Airflow
% Finat.-.
DIff.'
Outlet-01
Youth Desk
A
24/24
435
386
89
409
94
Outlet-02
Youth Desk
A
24/24
430
370
86
422
98
Outlet-03
Youth Desk
A
24/24
435
324
74
401
92
Outlet-04
Youth Desk
A
24124
100
34
34
93
93
Outlet-05
Work 17
A
24124
100
253
253
101
101
Outiet-06
Activity 19
A
24/24
350
244
70
328
94
Outlet-07
Activity 19
A
24/24
350
240
69
318
91
Outlet-08
Activity 19
A
24/24
350
225
64
315
90
Outlet-09
Activity, 19
A
24/24
350
27
8
321
92
Outlet-10
YA 16
A
24/24
425
396
93
378
89
Outlet-11
YA 16
A
24124
425
370
87
396
93
Outlet-12
YA 16
A
24124
425
449
106
401
94
Outlet-13
YA 16
A
24124
425
350
82
393
92
Ouflet-14
YA 16
A
24124
400
257
64
363
91
Totals;
- , 3925'-
- 79-
746W
.77W7
AHU-03 Return Inlet Summary
" Systerrl/Unit
Area Served, ".
Inlet Type:
Size LxW I
D
Design
'> Airflow,
Prelim
..-. AlrBow-
�.% Prelim.:`
Diff.
Final
-Airflow,
%o r FIOaI'.'.`
Diff.
Inlet-01
Youth Desk
550
477
87
562
102
Inlet-02
Youth Desk
550
522
95
557
101
Inlet-03
Youth Desk
550
161
29
536
97
Inlet-04
YA 16
550
113
21
493
90
Inlet-05
YA 16
635
872
137
558
88
Inlet-06
YA 16
630
851
135
581
92
Inlet-07
YA 16
635
929
146
586
92
Inlet-08
Work 17
100
0
0
94
94
Inlet-09
Youth Desk
100
0
0
91
91
Totals:
4300
3925 .. ''
91
4058
94.
M & M Test & Balance of FL
Page 18 of 30
M & N Test &, Balance of Al.
Air Handling Unit
PROJECT: Rosser Library Remodel DATE: 10/24/2017
LOCATION: CONTACT: Michael lacobacci
PROJECT M AUTHOR:
SYSTEM/UNIT: AHU-04
Location
m.e. FFL rnl 2a
Unit Manufacturer
Trane
Unit Model Number
TWE120E300AC
Unit Serial Number
16404T36BA
Equipment Type
Air Handler
Unit Discharge
Vertical
AHU-041SF Filter Bank
Filter Manufacturer
AAF
Filter Type
Pleated
Filter Oty - S1
4
Filter Size - S1
16x25xl
1st Service Date 8-1-2017
2nd Service Date 8-7-2017
3rd Service Date 8-16-2017
4th Service Date 9-13-2017
5th Service Date 9-14-2017
1
6th Service Date 9-18-2017
Specified CFM 3200 CFM
Design Airflow 3300 CFM
Actual Airflow 3393 CFM
Design Outside Airflow 1250 CFM
Actual Outside Airflow 1341 CFM
Design Return Airflow 2050 CFM
Actual Return Airflow 2052 CFM
Actual RPM
889 RPM
Motor Volts T1-T2
216 Volts
Motor Volts T2-T3
211 Volts
Motor Volts T1-T3
216 Volts
Motor Amps T1
4.4 Amps
Motor Amps T2
4.9 Amps
Motor Amps T3
3.9 Amps
Brake Homenower
1.47 SHP
Comp 1 Design
17.80
Comp 1 Actual
14.3-14.4-12.0
Comp 2 Design
17.80
Comp 2 Actual
13.7-12.4-11.0
Design Olt BTUH
119.0 BTUH
Design O/s BTUH
88.5 BTUH
BTU Capacity Total
146577.6 BTUH
BTU Capacity Sensible
81350.568 BTUH
Actual LAT DB 57.1 DB
M & M Test & Balance of FL
Tested By: Michael lacobacci
Date: 10/18/2017
Motor Data
AHU-04/Supply Fan
Motor Manufacturer
Marathon
Motor Frame
56HZ
Motor HP
2 HP
Motor RPM
1725 RPM
Motor Rated Volts
208-230/460 Volts
Motor Phase
3
Motor Hertz
60 Hz
Motor FL Amps
6.2 Amps
Nominal Efficiency
0.84
Motor Power Factor
0.8
Sheave Data
AHU-04/Suoely Fan
Fan Type
Forward Curved
Operating Diam.
WOCFM
Motor Sheave MFG
Browning
Motor Sheave Diam.
41/2 in.
Motor Sheave Bore
7/8 in.
Fan Sheave MFG
Browning
Fan Sheave Diam.
8 in.
Fan Sheave Bore
1 in.
Number of Belts
1
Belt Size
A50
Sheave Center Line
16 3/4 in.
Test Pressures
Suction SP
-0.90 in. we
Discharge SP
0.71 in. we
TSP Actual
1.61 in. we
Design ESP
1.00 in. we
External Suction SP
-0.52 in. we
External Discharge SP 0.71 in. we
ESP Actual
1.23 in. we
Electric Heat
Heater Type
Electric
Heater Model
BAYHTRL325AD
Heater Sedal
17041 N46LA
Heater Volts
208 Volts
Heater KW
18.7 KW
Design Heat Amps
52.0 Amps
Page 19 of 30
M &:,M Test & ,Balance .of l-1
Air Handling Unit
PROJECT: Rosser Library Remodel
LOCATION: ,
PROJECTM
SYSTEM/UNIT: AHU-04
Coil Atr Test Data
Design LAT WB
57.5 WB
Actual LAT WB
55.1 WB
Design EAT DB
82.5 DB
Actual FAT DB
79.3 DB
Design FAT WB
68.6 WB
Actual EAT VJB
72.8 WB
R/A Temp DS
73.3 DB
R/A Temp WB
63.8 WB
O/A Temp DB
82.3 DB
O/A Temp WB
79.7 WB
EAT Enthalpy
32.9 h
LAT Enthalpy
23.3 h
SYSTEM/UNIT: AHU-04/SPP-01
DATE: 10/24/2017
CONTACT: Michaellacobacci
AUTHOR:
Tested By: Michael lacobacci
Date: 10118/2017
Tested By: Michael lacobacci
Date: 10/13/2017
�..
Tes4Fressures
DX Coil SP In
-0.63 in. w.c.
DX Coil SP Out
-0.89 in. w.c.
Final Filter SP In
-0.52 in. w.c.
Final Filter SP Out
-0.62 in. w.c.
Heating Coil SP In
0.62 in. w.c.
Heating Coil SP Out
0.71 in. w.c.
Supply Fan SP In
-0.90 in. w.c.
Supply Fan SP Out
0.61 in. w.c.
0.11 0.27 1.52 0.09
F
' I
aT—T
T x T'SF
L
-0.52 -0.63 -0.90 0.62 0.71
M & M Test & Balance of FL
Page 20 of 30
M &, M Test & ,Balance of R.
Air Handling Unit
PROJECT: Rosser Library Remodel DATE: 10124/2017
LOCATION: CONTACT: Michael lacobacci
PROJECT #: AUTHOR:
AHU-04 Supply Outlet Summary
System/Unit
Area Served
Outlet
Type
Size LAW I
D-
Design
'Airflow
Prelim
-Airflow
% Prelim
Diff.
Final,
Airflow
% Final,
Diff.
Outlet-01
Reading 15
A
24124
100
104
104
103
103
Outlet-02
Reading 15
A
24124
100
95
95
96
96
Outlet-03
Reading 15
A
24/24
100
91
91
103
103
Outlet-04
Reading 15
A
24124
100
73
73
109
109
Outlet-05
Reading 15
A
M24
100
90
90
96
96
Outlet-06
Reading 15
A
24/24
100
109
109
102
102
Outlet-07
Reading 15
A
24/24
100
97
97
97
97
Outlet-08
Reading 15
A
24124
100
63
63
105
105
Outlet-09
Reading 15
A
24124
100
91
91
109
109
Outlet-1 0
Reading 15
A
24124
too
41
41
!to
110
Outlet-1 1
Reading 15
A
24/24
100
95
95
110
110
Outlet-12
Reading 15
A
24124
100
95
95
102
102
Outlet-13
Reading 15
A
24124
100
103
103
104
104
Outlet-14
Reading 15
A
24/24
100
Ill
ill
101
101
Outlet-15
Study 32
A
24/24
100
117
117
102
102
Outlet-16
Hall
A
24/24
25
68
272
46
184
Outlet-17
Stor 22
A
24124
50
77
154
97
194
Outlet-18
Hall
A
24/24
25
51
204
41
164
Outlet-19
Open
A
24124
150
145
97
158
105
Outlet-20
Open
A
24124
150
51
34
147
98
Outlet-21
Open
A
24124
150
86
57
140
93
Outlet-22
Hall 27
A
24124
50
83
166
48
96
Outlet-23
Women25
A
24124
1010
62
62
90
90
Outlet-24
Men 24
A
24124
100
64
64
95
95
Outlet-25
Open
A
24/24
150
57
38
158
105
Outl
Open
A
24/24
150
155
103
144
96
Outlet-27
Open
A
24/24
150
74
49
151
101
Outlet-28
Open
A
24/24
200
72
36
200
100
Outlet-29
Study 34
A
24/24
100
99
99
97
97
Outlet-30
Study 35
A
24/24
100
99
99
96
96
Outlet-31
m.!. 28
A
24124
150
0
0
136
91
Fals:
3300•
2618
79
3393
103
AHU-04 Return Inlet Summary
Systemlunit,
Area Served...
i5
Inlet Type;
Size -LAW/.:
Design,
I w
t, Prelim ,
-
%Rrellmg
""Airflow
z, Flna4
'W�
%.FlnaP;,
biff
Inlet-01
Study 35
B
24/24
75
54
72
74
99
Inlet-02
Study 34
B
24/24
75
65
87
68
91
Inlet-03
Hall West
B
24/24
175
123
70
163
93
Inlet-04
Study 32
B
24124
75
68
91
74
99
Inlet-05
Hall West
B
24/24
150
65
43
150
100
Inlet-06
Hall West
B
24/24
150
54
36
136
91
Inlet-07
Hall 27
B
24/24
50
90
180
45
90
Inlet-08
Hall East
B
24124
122
108
140
93
Inlet-09
Hall East
B
24/24
0
213
142
158
105
Inlet-10
Stor 22
B
24124
50
134
268
82
164
Inlet-11
Hall South
B
24124
425
277
65
460
108
Inlet-12
Hall South
B
24124
425
322
76
443
104
Totals:
1960
1627
83
1993
JC l(M
M & M Test & Balance of FL Page 21 of 30
M & :M Test & Balance of Al.
Air Handling Unit
PROJECT: Rosser Library Remodel DATE: 10/24/2017
LOCATION: CONTACT: Michael lacobacci
PROJECT M AUTHOR:
SYSTEM/UNIT: AHU-05 (Fan Test) and AHU-05 &
AHU-06 (combined air outlet test)
Location
m.e. #3 Rm 40
Unit Manufacturer
Trane
Unit Model Number
TWE120E300AC
Unit Serial Number
16404T9FBA
Equipment Type
Air Handler DX
Unit Discharge
Vertical
Filter Manufacturer
AAF
Filter Type
Fiberglass
Filter Qty - S1
4
Filter Size - Si
16x25xl
2nd Service Date 8-1-2017
3rd Service Date 8-7-2017
4lh Service Date 8-16-2017
5lh Service Date 9-13-2017
Specified CFM 3200 CFM
Design Airflow 3275 CFM
Actual Airflow 3010 CFM
Design Outside Airflow 425 / 850 CFM
Actual Outside Airflow 458 CFM
Design Return Airflow 3275 CFM
Actual Return Airflow 2552 CFM
Actual RPM
765 RPM
Motor Volts T1-T2
212 Volts
Motor Volts T2-T3
216 Volts
Motor Volts T1-T3
213 Volts
Motor Amps T1
2.8 Amps
Motor Amps T2
3.9 Amps
Motor Amps T3
2.9 Amps
Brake Horsepower
1.02 BHP
Comp 1 Design
17.80
Comp 1 Actual
11.2-13.3-12.2
Comp 2 Design
17.80
Comp 2 Actual
11.5-13.5-12.1
Design Of BTUH
117.4 BTUH
Design Q/s BTUH
86.0 BTUH
BTU Capacity Total
96169.5 BTUH
RTII Canarihr Sensihte
67616.64 BTUH
Actual LAT DB 57.4 DS
M & M Test & Balance of FL
Tested By: Michael lacobacci
Date: 10/24/2017
AHU-05 (Fan Test) and AHU-05 &
AHU-06 (combined air outlet
test)/Suooly Fan
Motor Manufacturer
Marathon
Motor Frame
56HZ
Motor HP
2.0 HP
Motor RPM
1725 RPM
Motor Rated Volts
208 Volts
Motor Phase
3
Motor Hertz
60 Hz
Motor FL Amps
6.2 Amps
Nominal Efficiency
0.8
Motor Power Factor
0.8
NXIM
AHU•05 (Fan Test) and AHU-05 &
AHU-06 (combined air outlet
test)/Supply Fan
Fan Type
Forward Curved
Operating Diam.
WOCFM
Motor Sheave MFG
Browning
Motor Sheave Model
Not Legible
Motor Sheave Diam.
3 314 in.
Motor Sheave Bore
7/8 in.
Fan Sheave MFG
Browning
Fan Sheave Model
Not Legible
Fan Sheave Diam.
8 in.
Fan Sheave Bore
1 in.
Number of Belts
1
Bell Size
4L 250
Sheave Center Line
17 114 in.
Suction SP
-0.90 in. we
Discharge SP
0.40 in. we
TSP Actual
1.30 in. we
Design ESP
1.00 in. we
External Suction SP
-0.58 in. we
External Discharge SP
0.40 in. we
ESP Actual
0.98 in. we
vy, 4MW APP
Heater Type
Electric
Heater Model
BAYHTRL325AB
Heater Serial
16464MF8LA
Heater Volts
208 Volts
Heater KW
18.7 KW
Design Heat Amps
52.0 Amps
Page 22 of 30
M & N Test &. Balance .of /Fl
Air Handling Unit
PROJECT: Rosser Library Remodel
LOCATION: ,
PROJECT M
DATE: 10/24/2017
CONTACT: Michael lacobacci
AUTHOR:
SYSTEM/UNIT: AHU-05 (Fan Test) and AHU-05 & Tested By: Michael lacobacci
AHU-06 (combined air outlet test) Date: 10/24/2017
Coil Air Test Data
Design LAT WB
56.7 WB
Actual LAT WB
56.8 WB
Design EAT DB
80.9 DB
Actual EAT DB
78.2 DB
Design EAT WB
67.8 WB
Actual EAT WB
69.7 WB
R/A Temp DB
73.7 DB
R/A Temp WB
63.4 WB
O/A Temp DB
80.9 DB
O/A Temp WB
72.4 WB
EAT Enthalpy
32.3 h
LAT Enthalpy
25.2 h
SYSTEM/UNIT: AHU-05 (Fan Test) and AHU-05 & Tested By: Michael lacobacci
AHU-06 (combined air outlet test)/SPP-01 Date: 10/13/2017
a
TestiPressures.
DX Coil SP In
-0.69 in. w.c.
DX Coil SP Out
-0.89 in. w.c.
Electric Coil SP In
0.31 in. w.c.
Electric Coil SP Out
0.40 in. w.c.
Final Filter SP In
-0.58 in. w.c.
Final Filter SP Out
-0.68in. w.c.
Supply Fan SP In
-0.90 in. w.c.
Supply Fan SP Out
0.30 in. w.c.
Static PreSsure�iPi, oflli�� -. - -
0.11 0.21 1.21 0.09
F E
I E
N F
T
L 7 I
T T T
-0.58 -0.69 -0.90 0.31 0.40
M & M Test & Balance of FL Page 23 of 30
M & N Test &.Balance of ILL
Air Handling Unit
PROJECT: Rosser Library Remodel DATE: 10/24/2017
LOCATION: CONTACT: Michael lacobacci
PROJECTM AUTHOR:
AHU-05 (Fan Test) and AHU-05 & AHU-06 (combined air outlet test) Supply Outlet Summary
System/Unit
! - Area Served
(Outlet
Type
Size`LxW,I
D
+Design
Airflow
Prelim
-Airflow
%.Prelim
. `DiM
Final'
Airflows
% Final"
Diff..:
Outlet-01
Meeting 36
A
24/24
450
415
92
433
96
Outlet-02
Meeting 36
A
24124
450
427
95
435
97
Outlet-03
Meeting 36
A
24124
450
430
96
412
92
Outlet-04
Meeting 36
A
24124
450
407
90
432
96
Outlet-05
Meeting 36
A
24124
450
352
78
412
92
Outlet-06
Meeting 36
A
24124
450
382
85
453
101
Outlet-07
Meeting 36
A
24124
450
372
83
474
105
Outlet-08
Meeting 36
A
24124
450
445
99
431
96
Outlet-09
Meeting 36
A
24/24
450
451
100
448
100
Outlet-10
Meeting 36
A
24/24
450
437
97
436
_, 97
Outlet-11
Meeting 36
A
24124
450
466
104
488
108
Outlet-12
Meeting 36
A
24/24
450
375
83
431-
96
Outlet-13
Storage 3
A
24/24
200
207
104
203
102
Outlet-14
Storage 3
A
24/24
200
174
87
204
102
Outlet-15
Ha1138
A
24/24
400
498
125
404
101
Outlet-16
Kitchen 39
A
24/24
200
181
91
194
97
Outlet-17
A
24/24
150
0
0
136
91
Totals:
92
AHU-05 (Fan Test) and AHU-05 & AHU-06 (combined air outlet test) Return Inlet Summary
System/Unit,
€Area Served"
Inlet Typei
Size LxW /
D
Design
= Airflow,
;—Prelims'
is Airflow -
MoPrelim
.. Diff. -
;-;'Final
.'Airflow'-
-°%'Final.-
P rDiff. :.
Inlet-01
Meeting 36
B
24124
325
215
66
296
91
Inlet-02
Meeting 36
B
24/24
325
207
64
283
87
Inlet-03
Meeting 36
B
24/24
325
187
58
312
96
Inlet-04
Meeting 36
B
24/24
325
230
71
296
91
Inlet-05
Meeting 36
B
24124
325
197
61
276
85
Inlet-06
Meeting 36
B
24124
325
188
58
265
82
Inlet-07
Meeting 36
B
24/24
325
228
70
269
83
Inlet-08
Meeting 36
B
24124
325
266
82
273
84
Inlet-09
Meeting 36
B
24124
325
285
88
274
84
Inlet-10
Meeting 36
B
24/24
325
311
96
263
81
Inlet-11
Meeting 36
B
24/24
325
338
104
267
82
Inlet-12
Meeting 36
B
24/24
325
341
105
281
86
Inlet-13
kitchen 39
B
24/24
150
250
167
136
91
Inlet-14
Hall38
B
24/24
325
408
126
261
80
Inlet-15
Storage 37
B
24/24
325
281
86
265
82
tals:
`• 4700
- 3932 ,..
,:': 84
774017;�
r�';; 85 .
M & M Test & Balance of FL Page 24 of 30
M &W Test &.-.Balance .of Al.
Air Handling Unit
PROJECT: Rosser Library Remodel DATE: 10/24/2017
LOCATION: CONTACT: Michael lacobacci
PROJECT#: AUTHOR:
SYSTEM/UNIT: AHU-06 (Fan test only)
Location
m.e. A Km 4U
Unit Manufacturer
Trans
Unit Model Number
TWE120E300AG
Unit Serial Number
163443U6BA
Equipment Type
Air Handler
Unit Discharge
Vertical
AHU-06 (Fan test only)/SF Filter
Bank
Filter Manufacturer
AAF
Filter Type
Pleated
Filler Qty - S1
4
Filler Size - S1
16x25xl
1st Service Date 7-19-17
2nd Service Date 7-20-17
3rd Service Date 9-14-17
4th Service Date 9-18-17
Specified CFM 3600 CFM
Design Airflow 3275 CFM
Actual Airflow 3213 CFM
Design Outside Airflow 4251850 CFM
Actual Outside Airflow 861 CFM
Design Return Airflow 3275 CFM
Actual Return Airflow, 2352 CFM
Actual RPM
801 RPM
Motor Volts Tt-T2
211 Volts
Motor Volts T2-T3
212 Volts
Motor Volts T1-T3
214 Volts
Motor Amps T1
3.8 Amps
Motor Amps T2
4.6 Amps
Motor Amps T3
3.9 Amps
Brake Horsepower
1.36 BHP
Refrigerant Type
410A
Comp 1.Design
17.80
Comp 1 Actual
13.3-12.8-11.4
Comp 2 Design
17.80
Comp 2 Actual
11.2-12.6-11.4
Design OR BTUH
117.4 BTUH
Design Q/s BTUH
86.0 BTUH
BTU Capacity Total
117113.85 BTUH
BTU Canacitv Sensible
71482.824 BTUH
Design LAT DB 57.8 UB
Actual LAT DB 58.8 DB
Design LAT WB 56.7 WB
—'
Actual LAT WB 58.3 WB
M & M Test & Balance of FL
Tested By: Michael lacobacci
Date: 10/24/2017
AHU-06 (Fan test onlvl/Supply
Fan
Motor Manufacturer
Marathon
Motor Frame
56HZ
Motor HP
2 HP
Motor RPM
1725 RPM
Motor Rated Volts
208 Volts
Motor Phase
3
Motor Hertz
60 Hz
Motor FL Amps
6.2 Amps
Nominal Efficiency
0.84
Motor Power Factor
0.8
AHU-06 (Fan test only)ISupply
Fan
Fan Type
Forward Curved
Operating Diam.
3.0
Motor Sheave MFG
Browning
Motor Sheave Diam.
3 3/4in.
Motor Sheave Bore
718 in.
Fan Sheave MFG
Browning
Fan Sheave Diam.
8 in.
Fan Sheave Bore
1 in.
Number of Belts
1
Belt Size
A49
Sheave Center Line
18 in.
Test PressuresrT,2,
Suction SP
-0.91 in. we
Discharge SP
0.38 in. we
TSP Actual
1.29 in. we
Design ESP
1.00 in. we
External Suction SP
-0.58 in. we
External Discharge SP
0.38 in. we
ESP Actual
0.96 in. we
rry$ fitn to eat
Heater Type
Electric
Heater Model
BAYHTRL325AB
Heater Serial
17041POWLA
Heater Volts
208 Volts
Heater KW
18.7 KW
Design Heat Amps
52.0 Amps
Page 25 of 30
M &.M Test &-Balance of FL
Air Handling Unit
PROJECT: Rosser Library Remodel
LOCATION: ,
PROJECTM
DATE: 10/24/2017
CONTACT: Michael lacobacci
AUTHOR:
SYSTEM/UNIT: AHU-06 (Fan test only) Tested By: Michael lacobacci
Date: 10/24/2017
Design EAT IDS
80.9 DBE
Actual EAT DB
79.4 DB
Design EAT WB
67.8 WB
Actual EAT WB
68.3 WB
R/A Temp DB
72.5 DB
R/A Temp WB
63.5 WB
O/A Temp DB
82.6 DB
O/A Temp WB
73.3 WB
EAT Enthalpy
33.4 h
LAT Enthalpy
25.3 h
SYSTEM/UNIT: AHU-06 (Fan test only)/SPP Tested By: Michael lacobacci
Date: 10/13/2017
DX Coil SP In
-0.69 in. w.c.
DX Coil SP Out
-0.90 in. w.c.
Electric Coil SP In
0.29 in. w.c.
Electric Coil SP Out
0.38 in. w.c.
Final Filter SP In
-0.58 in. w.c.
Final Filter SP Out
-0.68 in. w.c.
Supply Fan SP In
-0.91 in. w.c.
Supply Fan SP Out
0.28 in. w.c.
Statie�Pressur„e Profile �'- t �' - - - '*�-.u•
mod' aa'3N?�+rH�3a�'r3�wi3�'t ivct?��6:�, �`�rm..�i'
0.11 0.22 1.20 0'.09
F E
I E
N `SF
LT Tcl
—0.58 —0.69 —0.91 0.29 0.38
M & M Test & Balance of FL Page 26 of 30
M & M Test & Balance- of ILL
Fan Unit
PROJECT: Rosser Library Remodel
LOCATION: ,
PROJECT #:
SYSTEM/UNIT: EF-1
UnitData
Area Served unisex4
Test data
Design Airflow 50 CFM
Actual Airflow 75 CFM
SYSTEM/UNIT: EF-2
Unit Data .
Location
ceiling
Area Served
women 5
Test Data
Design Airflow
50 CFM
Actual Airflow
52 CFM
SYSTEM/UNIT: EF-3
Unit Data " -
Location
Ceiling
Area Served
Unisex 9
Test Data -
Design Airflow
50 CFM
Actual Airflow
64 CFM
SYSTEM/UNIT: EF4
Unit Data,,
Location Ceiling
Area Served Women 25
Test oata:#
Design Airflow 250 CFM
Actual Airflow 170 CFM
M & M Test & Balance of FL
DATE: 10/24/2017
CONTACT: Michael lacobacci
AUTHOR:
Tested By: Michael lacobacci
Date: 10/12/2017
Rated Airflow Capacity 50 CFM
Tested By: Michael lacobacci
Date: 10/12/2017
Motor Data; `
Rated Airflow Capacity 50 CFM
Tested By: Michael lacobacci
Date: 10/12/2017
Motor Data' _
Rated Airflow Capacity 50 CFM
Tested By: Michael lacobacci
Date: 10/12/2017
Page 27 of 30
M & - M Test & . Balance of FL
Fan Unit
PROJECT: Rosser Library Remodel DATE: 10/24/2017
LOCATION: CONTACT: Michael lacobacci
PROJECT M AUTHOR:
SYSTEMIUNIT: EF-5
Unit Data
Location
cieling
Area Served
Men RR 24
Fan Manufacturer
Cook
Fan Model Number
Gemini 400 Series
Classification
Inline Exhaust
Starter Data
Starter Manufacturer
Not applicable
Tost Data
Design Airflow
250 CFM
Actual Airflow
181 CFM
Design RPM
1350 RPM
Actual RPM
Hi Speed RPM
Motor Volts T1-T2
123 Volts
Motor Amps T1
0.70 Amps
Design ESP
0.50 in. we
SYSTEM/UNIT: EF-5
Uriit7Data _
_
Location
ceiling
Area Served
Unisex 31
_ _
Test Data
Design Airflow
50 CFM
Actual Airflow
76 CFM
Tested By: Michael lacobacci
Date: 10/2/2017
Motor Data
Rated Airflow Capacity
250 CFM
Motor HP
1/23 HP
Motor Rated Volts
115 Volts
Motor Phase
1
Motor Hertz
60 Hz
Motor FL Amps
1.00 Amps
Motor Service Factor
1.00
Corrected FL Amps
0.93 Amps
Operating Diam.
Direct
Sheave Data
Motor Sheave MFG
Direct Drive
Motor Sheave Model
Direct Drive
Motor Sheave Diam.
Direct Drive in.
Motor Sheave Bore
Direct Drive in.
Fan Sheave MFG
Direct Drive
Fan Sheave Model
Direct Drive
Fan Sheave Diam.
Direct Drive in.
Fan Sheave Bore
Direct Drive in.
Belt Size
Direct Drive
Sheave Center Line
Direct Drive in.
Tested By: Michael lacobacci
Date: 10/1212017
lowNwormlew
Motor Data
Rated Airflow Capacity, 50 CFM
Motor Hertz 60 Hz
M & M Test & Balance of FL Page 28 of 30
O
ME
e�
7.1
� w
ILI
an�
e
MM Test and Balance Of Fl. Inc. i
614 W. Eau Gallle Blvd -----
MclDounne, FI. 32935
T-600.649.9166
0
0
0
@ wI gPLN-6ECHAMAL
O
f1EFM3ENCE NOTES -NEW
>
o
Ya o
� .
n i
III
O� MEr.�a
I SII,Y
J
I
0
0
PY•!L•]N14
a
w
a'
Y
§
®
e
Q
I.
F
� O
]OIrYNIYP
m
J
e
� ar
utn�xr]]
nmM
CONSTRUCTION PLANS FOR
ROSSER LIBRARY
IN
SECTION 14, TOWNSHIP 37 SOUTH, RANGE 39 EAST
PORT ST. LUCIE, FLORIDA
PREPARED FOR
LOCATION MAP N.T.s.
sernox le ... 3a S..... 99 .
�I Pp$NIIR'19-131.100'LOPB➢lG
ST. LUCIE COUNTY
I
INDEX TO SHEETS
NO.
DRSMIMUON
1
CoMt I=
2
= ID ROI'6lQ+NT PI
3
DSI'AD. SRRRP
LEGAL DESCRIPTION
m..wu n*mL swn.
.mm nuax. w`>rT n I. —El .."ea:r'µvvwI rwen'.1.I. 1m;
a ...a 6 1-11 Rnro`n`rtgs`am ar
azmm.v 6 mE auenrw oisw®�anm°M`
uvrie• E..vwv :.io u.Y. A om xw s eiam REr: nm� e2anr .
Rm. Exu¢ a wmrr x. osrww a Ram REr. ra..a i eT
Ill iR azewa If 1. Ra now morn• w m R[ ro M
ewE a.am`'ov: EwO�o"a`s eisinyi . oO1Pvr"..¢?o°Snwmiie.ea"`e.. a wmoawfp1�
_-_.___ �I
Ilummu.
mnmw>v.aca wean
VICR= MAP N.TS.
UTILITIES
m.m
PER M I2/2/15
C'ULPEPPER & TERPENING INC
CONSULTING ENGINEERS I LAND SURVEYORS
cr
SIN1fH1W SM6@T IOATPDXL&PLJIIIDAJ.9B1
VNON6 AJ1HSSf>. PAY77S11LV9). �.smmg.-®
9lAleOPPl[I90AP(NROOPPAORffiIONN.
EW'Pl®]AVINO2DtTONN0..1y6
EI
mucunn ri Ro��
CRY OP PSI. PROx:R X0. p(.�-1$S
BOSS® IIDIUBT 19-121.100 d9aP 1 CP ]