March 21, 2016
St Lucie County
Building Department
2300 Virgina Avenue
Fort Pierce, Florida 34982
Re: Permit Comments: Permit # 1602-0153
Plan Review:
SCANNED
BY RECEn
St. Lucie Countv
OAR 292016
PER "VT 1771{!r
St. Lucie Courtky. CL
Comment #1: Submit [ 3 ] sets of original signed, sealed and dated shop drawings for the concrete filled steel
.stair system designed by a Florida licensed design professional,* must be reviewed and approved by weider
engineering
Response: Contractor to submit drawings
Comment #2: Need triplicate UL design WP 1200 test sheets reviewed and approved by design professional of
record
Response: The partition type detail was mislabeled. The assembly is a GA File No WP 1200. Please see revised
sheet A-4 and a copy of the approved assembly.
Comment #3: Submit [ 3 ] sets of original, signed, sealed and dated engineered shop drawings from the steel
joist fabricator / must be reviewed and approved by weider engineering
Response: Contractor to submit drawings
Comment #4: Submit [ 3 ] commercial energy calculations w/ manual n's attached
Response: Contractor to submit drawings
Comment #5: submit the manufacturers specifications for the " lift " in triplicate meeting the asme
specifications as cited in chapter 30, 2014 FBC
Response: Contractor to submit drawings
Comment #6: Will need a set of the fire sprinkler plans for our file
Response: Contractor to submit drawings
Comment #7: Need a detail on plans for the 1 hour rated deck supporting the mechanical system
5707 S. DIXIE HIGHWAY • SUITE 8 • WEST PALM BEACH • FLORIDA • 33405 • WWW.YRA-DESIGN. COM
TELEPHONE: (561) 493-1500 FAX: (561) 493-1560 AA-0002536
Y R A D E S I G N I N C.
ARCHITECTURE + PLANNING • INTERIORS
(561) 4.93-1500 WWW.YRA- DESIGN. CO
Response: A rated ceiling is not required since the entire mechanical space is within the tenant space and the
tenant space is separated by 1 hour walls. Note number 10 on Sheet A-1 has been revised to remove the 1 hour
rated floor requirement.
Kind regards,
"7-) 'L�
Kermit C. White, NCARB, LEED AP
,YRA Design, Inc
Principal Architect