HomeMy WebLinkAboutPROJECT INFORMATION 2Ri ht-Suite® Universal 2017 Short Form
Job:
2900 Industrial 33rd Sir...
g
Date:
April 8th, 2016
NEW OFFICES
By:
Craig C Brooks
y
Plan:
2900 Industrial 33rd Stre
WebReps LLC. Rf�CEi4'�71) AN 2 0
1892 Commerce Avenue, Vero Beach, FL 32960 Phone: 800-8103280 Email: manualj@webmpshvae.com License: CAC064709
For: Treasure Coast Wholesale Auction, LLC
2900 Industrial 33rd Street, Fort Pierce, FL
Htg Clg
Htg Clg
Outside db
(OF)
42 88
Inside db
(OF)
70 75
Outside RH
(%)
- 63
Inside RH
(%)
- 50
Outsidewb
(OF)
- 78
SCANNED
Insidewb
(OF)
- 63
Daily range
(OF)
- 20
BY
Design TD
(OF)
28 13
Moisture diff.
(gr/lb)
- 61
St. Lucie County
Heating Equipment
Make
Model
Type
Efficiency
Heating Input
Heating Output
Humidifier
Leaving Air Temp
Actual Heating Fan
Gas furnace
80 AFUE
0
MBtuh
0
MBtuh
5.3
gpd
70.0
OF
1571
cfm
Equipment Location
System Type
Fan Motor Heat Type
Fan & Motor Combined Efficiency
Static Pressure Across Fan
Cooling Equipment
Make
Model
Type
COP/EER/SEER
Sensible Cooling
Latent Cooling
Total Cooling
Leaving Air Temp
Actual Cooling Fan
NEW OFFICES
PEAKCV
PACKAGE
0 %
0 in H2O
Split AC
0
0
MBtuh
0
MBtuh
0
MBtuh
55.0
OF
1571
cfm
NAME
Area
ft2
Heat
Loss
Sensible
Gain
Latent
Gain
Htg
cfm
Clg
cfm
Time
Office 1
94
1118
2125
354
96
94
Jul 1700 LST
Office 2
94
733
1997
354
61
88
Jul 1700 LST
Conference Room
175
1648
3353
684
139
148
Jul 1700 LST
HVAC
14
183
249
70
16
11
Jul 1700 LST
Office 3
142
803
2110
534
65
93
Jul 1700 LST
Hall
63
193
886
251
14
39
Jul 1700 LST
Entry
667
6726
11816
4258
528
523
Jul 1700 LST
Computer
23
227
362
87
19
16
Jul 1700 LST
Hall 2
88
270
1239
343
20
55
Jul 1700 LST
Supply Clst
66
815
1152
257
70
51
Jul 1700 LST
Breakroom
84
716
1504
335
60
67
Jul 1700 LST
Employee Restroom
92
685
1502
351
57
66
Jul 1700 LST
Ladies Restroom
155
2354
3304
1438
182
146
Jul 1700 LST
e A__-
onAQ
9nna
AGOA
OA9
Awe
r..l i7nn i eT
JulenJ
IOG JV V JJVI 11J G-IJ IIJ JYI IIVV 1V 1
+ wrightsoft' RlghtSufte® Universal 201717.0.01 RSU16998
...ice 2900 Industrial 33 rd StmetFort Pierce.mp Calc = RTS Fmnt Door faces: SE
NEW OFFICES 1937 1 19517 1 35507 1 10851 1 1571 1571 Jul 1700 LST
2016-Apr-08 13:02:49
wrightsofC RightSuite® Univemal201717.0.01 RSU16996 Page 2
...ice 2900 Industrial 33 rd StreetFort Plerce.rup Cale = RTS Front Door faces: SE
Right -Suite® Universal 2017 Load Summary
Job:
2900 Industrial 33rd Str...
Date:
April 8th, 2016
NEW OFFICES
By:
Craig C Bmoks
WebRepS LLC.
Plan:
2900 Industrial 33rd Stre
1892 Commerce Avenue, Vera Beach, FL 32960 Phone: 800-810-3280 Email: manualj@webrepshvac.com License: CAC054709
Project• •
For: Treasure Coast Wholesale Auction, LLC
2900 Industrial 33rd Street, Fort Pierce, FL
ne NEW FILES,
1.
DESIGN CONDITIONS at Jul 1700 LST Peak load at Jul
1700 LST
Inside: 75 OF Outside: 88 OF TD: 13 OF
RH: 63 % MoistDiff: 61.5 gr/lb Mult: 1.0
Ins.wb
63 OF
Sensible
Latent
2.
SOLAR RADIATION THROUGH GLASS
1943
3.
TRANSMISSION GAINS Sensible
8487
Walls: 2601
-
-
Glass: 467
-
-
Doors: 1490
-
-
Partitions: 0
-
-
Floors: 0
-
-
Ceilings: 3930
4.
INTERNAL HEAT GAIN Sensible Latent
20060
3875
Occupants: 4550 3875
-
-
Lights: 11036 -
-
Motors: 0 -
-
Appliances: 4474 0
5.
INFILTRATION: Outside air cfm: 167
2386
6976
6.
SUBTOTAL: Space load Sensible Latent
32877
10851
Envelope 32877 10851
-
-
Less external 0 -
-
Redistribution 0 0
-
7.
SUPPLYDI7CT
1644
-
S.
SUBTOTAL: Space load + supply duct
34521
-
Actual cfm: 1571 at supply TD: 20
-
-
9.
VENTILATION: Make-up air cfm: 0
0
0
10.
RETURNAIR LOAD: Lighting + plenum (net)
0
-
11.
RETURN DUCT
986
-
12.
TOTAL LOADS ON EQUIPMENT
35507
10851
M1? N HE4TING_L'OAD=...w.f. s a t
13.
DESIGN CONDITIONS
Mult: 1.0
Inside: 70 OF Outside: 42 OF
TD: 28 OF
14.
TRANSMISSION LOSSES
11054
Walls: 3101
-
Glass: 1206
-
Doors: 1154
-
Partitions: 0
-
Floors: 3746
-
Ceilings: 1847
15.
INFILTRATION: Outside air cfm:
167 5144
16.
SUBTOTAL: Space load
16198
Envelope 16198
-
Less external 0
-
Less transfer 0
-
Redistribution 0
-
17.
SUPPLYDUCT,
810
18.
VENTILATION: Make-up air cfm:
0 0
19.
HUMIDIFICATION
2023
Piping
0
20.
RETURN DUCT
486
21.
TOTAL HEATING LOAD ON EQUIPMENT
19517
-"��- 2016-Apr-08 13:02:49
vvr1ght501fC RightSuReS Univemal20l7l7.0.01 RSU16998 page 1
...ice 2900 Industrial 33 rd SlreelFort Pierce.mp Calc = RTS Fmnt Doorfaces: SE
Job #: 2900 Industrial 33rd Street
Performed by Craig C Brooks for:
Treasure Coast Wholesale Auction, LLC
2900 Industrial 33rd Street
Fort Pierce, FL
WebReps LLC.
1892 Commerce Avenue
Vero Beach, FL 32960
Phone: 800-810-3280
manualj@webrepshvac.com
Scale: 1 : 91
Page 1
RightSuAe® Universal 2017
17.0.01 RSU16998
2016-Apr-08 13:03:12
...vial 33 rd StreetFort Pierce.rup
Project Name: TC Wholesale Auction
Project Title: New Project
Address: 2900 Industrial 33rd Street
State: FL
Zip: 34946
Owner: Boa Riggins
EnergyGauge Summit® v5.10
INPUT DATA REPOR
Proiect Information
Orientation: North
Building Type: Office
Building Classification: New Finished building
No.of Stories: I
GrossArea: 1939 SF
Zones
No Acronym Description Type
Area
Isfl
Multiplier
Total Area
[sfl
1 TC Wholesale Offices CONDITIONED
1938.6
1
1938.6 ❑
Spaces
No Acronym Description Type Depth
[ft]
Width Height Multi
[ft] [ft] plier
Total Area
[sf]
Total Volume
[cf]
4/8/2016
EnergyGauge Summit® v5.10
1
In Zone: TC Wholesale
1 TC Wholesale Offices
Office - Open Plan
44.03 44.03
9.00 1 1938.6
17447.8 ❑
Lighting
No Type
Category
No. of Watts per
Power Control Type
No.of
Luminaires Luminaire
[W]
Ctrl pts
In Zone: TC Wholesale
In Space: TC Wholesale
I Compact Fluorescent General Lighting
17 40
680 Manual On/Off
19 ❑
Walls
No Description
Type Width H (Effec) Multi Area DirectionConductance Heat
Dens. R-Value
[ft]
[ft] plier [sf]
[Btu/hr. sf F] Capacity
[lb/cf] [h.sf.FBtu]
[Btu/s£F]
In Zone: TC Wholesale
1 Offices
Metal 176.00
9.00 1 1584.0
North 0.0920 1.072
19.38 10.9 ❑
siding/2x4@24"+R1
1Batt/5/8"Gyp
Windows
No Description Type Shaded
U SHGC Vis.Tra
W H (Effec) Multi
Total Area
[Btu/hr sf F]
IN [ft] plier
Isfl
In Zone: TC Wholesale
In Wall: TC Wholesale
1 Offices
User Defined Yes
1.2500 0.82 0.76
3.00 4.00 11
132.0
Doors
No Description
Type Shaded? Width H (Effec) Mufti Area Cond. Dens. Heat Cap. R-Value
IN [ft] plier
[sf] [Btulhr. sf. F] [lb/cf] [Btu/sf. F] [h.sf.FBtu]
4/8/2016 EnergyGauge Summit® v5.10
In Zone:
In Wall:
Roofs
No Description
Type
Width
Vt]
H (Effec) Multi
[ft] pher
Area
[sf]
Tilt Cond. Heat Cap
[deg] [Btu/hr. Sf. F] [Btu/sf. F]
Dens. R-Value
[Ib/cf] [h.sf.FBtu]
In Zone: TC Wholesale
1 Offices
Mtl Bldg Roof/R-19
Batt
44.03
44.03 1
1938.6
0.00 0.0492 1.34
9.49 20.3
❑
Skylights
No Description Type
U SHGC Vis.Trans
[Btu/hr sf F]
W H (Effec) Multiplier
[ft] [ft]
Area Total Area
[SfJ [Sf]
In Zone,
In Roof:
Floors
No Description
Type
Width
[ft]
H (Effec) Multi
[ft] plier
Area
[sf[
Cond. Heat Cap. Dens.
[Btu/hr. sf. F] [Btu/sG F] [lb/cf[
R-Value
[h.sf.FBtu]
In Zone: TC Wholesale
1 Offices
1 ft. soil, concrete
floor, carpet and
rubber pad
44.03
44.03 1
1938.6 0.2681 34.00 113.33
3.73
❑
Systems
4/8/2016 EnergyGauge Summit® v5.10
TC Wholesale System 1
Constant Volume Air Cooled Split No. Of Units 1
System < 65000 Btu/hr
Component Category
Capacity Efficiency IPLV
1 Cooling System
2 Heating System
3 Air Handling System -Supply
59000.00 14.00 8.00
34130.00 1.00
1500.00 0.80
❑
❑
❑
Plant
Equipment
Category Size Inst.No Eff. IPLV
I Hermetic Centrifugal chiller
Cooling Equipment 5.0 [Tons] 1 5.90 [COP] 6.10
Water Heaters
W-Heater Description
CapacitlCap.Unit I/P Rt. Efficiency Loss
I Electric water heater
50 [Gal] 3000 [kW] [Ef] [Bm/h]
❑
Ext-Lighting
Description Category No. of
Luminaires
Watts per Area/Len/No. of units
Luminaire [sf/ft/No]
Control Type
Wattage
[W]
1 Ext Light 1 Uncovered Parking Areas — 1
Parking lots and Drives
750
0.00 Photo Sensor control
750.00 ❑
Piping
No Type Operating
Temperature
[F]
Insulation
Conductivity
[ Btu-in/h.sSF]
Nomonal pipe
Diameter
[in]
Insulation
Thickness
[in]
Is Runout?
4/8/2016 EnergyGauge Summit® v5.10
Fenestration Used
Name Glass Type No. of Glass SHGC VLT
Panes Conductance
[Btu/b.sLFJ
ASHULSglClrAll User Defined 1 1.2500 0.8200 0.7600 ❑
Frm
Materials Used
Mat No
Acronym
Description
Only R-Value
RValue Thickness
Conductivity
Density
SpecificHeat
Used
[h.sf.FBtu]
[ft]
[Btu/h.ft.F]
[lb/cf]
[Btu/1b.F]
187
Mat1187
UYP UK PLAN
No
BOARD,1/21N
178
Matl178
CARPET W/RUBBER PAD
Yes
1.2300
❑
265
Mat1265
Soil, 1 ft
No
2.0000
1.0000
0.5000
100.00
0.2000
❑
48
Mat148
6 in. Heavyweight concrete
No
0.5000
0.5000
1.0000
140.00
0.2000
❑
23
Matl23
6 in. Insulation
No
20.0000
0.5000
0.0250
5.70
0.2000
❑
4
Matl4
Steel siding
No
0.0002
0.0050
21,0000
480.00
0.1000
❑
271
Mat1271
2x4@24" oc+RII Batt
No
10.4179
0.2917
0.0280
7.11
0.2000
❑
94
Mat194
BUILT-UP ROOFING, 3/81N
No
0.3366
0.0313
0.0930
70.00
0.3500
❑
Constructs Used
No
Name
Simple
Massless Conductance Heat Capacity
Density
RValue
Construct
Construct [Btu/h.sf.F]
[Btu/sf.F]
[lb/cf]
[h.sf.F/Btu}
1055
Metal siding/2x4@24"+Rl lBatt/5/8 "Gyp
No
No
0.09
1.07
19.38
10.9
❑
Layer
Material Material
Thickness
Framing
No.
fit]
Factor
1
4 Steel siding
0.0050
0.000
❑
4/8/2016 EnergyGauge Summit® v5.10
No
Name
Simple
Massless Conductance Heat Capacity
Density
RValue
Construct
Construct [Btu/h.sf.F]
[Btu/sLF]
[lb/cf]
[h.sf.FBtu]
1055
Metal siding/2x4@24"+R11Batt/5/8"Gyp No
No 0.09
1.07
19.38
10.9
❑
Layer
Material
Material
Thickness
Framing
No.
N
Factor
2
271
2x4@24" oc+RII Batt
0.2917
0.000
❑
3
187
GYP OR PLAS BOARD,1/21N
0.0417
0.000
❑
No
Name
Simple
Massless Conductance Heat Capacity
Density
RValue
Construct
Construct [Btu/h.sf.F]
[Btu/sf.F]
[lb/cf]
[h.sf.FBtu]
1056
Mtl Bldg Roof/R-19 Batt
No
No 0.05
1.34
9.49
20.3
❑
Layer
Material
Material
Thickness
Framing
No.
A
Factor
1
94
BUILT-UP ROOFING, 3/81N
0.0313
0.000
❑
2
23
6 in. Insulation
0.5000
0.000
❑
No
Name
Simple
Massless Conductance Heat Capacity
Density
RValue
Construct
Construct [Btu/b.sf.F]
[Btu/sLF]
[lb/cf]
[h.sf.F/Btu]
1057
1 ft. soil, concrete floor, carpet and rubber pad No
No 0.27
34.00
113.33
3.7
❑
Layer
Material
Material
Thickness
Framing
No.
[ft]
Factor
1
265
Soil, 1 ft
1.0000
0.000
❑
2
48
6 in. Heavyweight concrete
0.5000
0.000
❑
3
178
CARPET W/RUBBER PAD
0.000
❑
4/8/2016 EnergyGauge Summit® v5.10 6
s i F
Check List
Applications for compliance with the Florida Building Code, Energy Conservation shall
include:
This Checklist
An Input report generated from the software just after completing compliance
calculations without any further changes
The full compliance report generated by the software that contains the project
summary, complaince summary, certifications and detailed component compliance
reports
Boxes appropriately checked in the Miscellanous report generated by the software at
the end of the compliance report
EnergyGauge Summit® FlafGom-2014. TAM 2014-1.0 Compliant Software. Effective Date: June 30, 2015
2/11/2016 Page 1 of 12
PROJECT SUMMARY
Short Desc:
TC Wholesale Auction
Description:
New Project
Owner.
Boa Riggins
Addressl:
2900 Industrial 33rd Street
City:
Fort Pierce
Address2:
State:
FL
Zip:
34946
Type:
Office
Class:
New Finished building
Jurisdiction:
FORT PIERCE, ST LUCIE COUNTY, FL (661100)
Conditioned Area:
1939 SF
Conditioned & UnConditioned Area:
1939 SF
No of Stories:
1
Area entered from Plans
1937 SF
Permit No:
0
Max Tonnage
5
If different, write in:
Component
Gross Energy Cost (in $)
LIGHTING CONTROLS
EXTERNAL LIGHTING
HVAC SYSTEM
PLANT
WATER HEATING SYSTEMS
PIPING SYSTEMS
Met all required compliance from Check List?
Design Criteria Result
1,138.0 1,290.0 PASSED
PASSES
PASSES
PASSES
PASSES
PASSES
No Entry
Yes/No/NA
IMPORTANT MESSAGE
Info 5009 — — — An input report of this design building must be submitted along with this
Compliance Report
EnergyGauge Summit® Fla/Com-2014. TAM 2014-1.0 Compliant Software. Effective Date: June 30, 2015
2/11/2016 Page 2 of 12
CERTIFICATIONS
I hereby certify that the plans and specifications covered by this calculation are in compliance with the
Florida Energy Code
c C.
Prepared By: MCraig C Brooks Building Official:
Date: 2/112016 Date:
I certify that this building is in compliance with the FLodda Energy Efficiency Code
Owner Agent: Date:
If Required by Florida law, I hereby certify (`) that the system design is in compliance with the Florida Energy
Efficiency Code
Architect Reg No:
Electrical Designer. Reg No:
Lighting Designer: Reg No:
Mechanical Designer: Reg No:
Plumbing Designer. Reg No:
(`) Signature is required where Florida Law requires design to be performed by registered design
professionals. Typed names and registration numbers may be used where all relevant information is
contained on signed/sealed plans.
EnergyGauge Summit® Fla/Com-2014. TAM 2014-1.0 Compliant Software. Effective Date: June 30, 2015
2/11/2016 Page 3 of 12
Project: TC Wholesale Auction
Title: New Project
Type: Office
Building End Uses
1) Proposed
2) Baseline
Total
72.90
97.20
$1,138
$1,518
ELECTRICITY(MBtulkWhl$)
72.90
97.20
21349
28478
$1,138
$1,518
AREA LIGHTS
7.10
20.30
2083
5937
$Ill
$316
MISC EQUIPMT
29.10
29.10
8521
8521
$454
$454
PUMPS & MISC
0.10
0.10
26
26
$1
$1
SPACE COOL
18.60
22.40
5458
6570
$291
$350
SPACE HEAT
1.40
1.60
396
474
$21
$25
VENT FANS
16.60
23.70
4865
6950
$259
$370
Credits Applied: None
PASSES
Passing Criteria =1290
Design (including any credits) =1138
Passing requires Proposed Building cost to be at most
85% of
Baseline cost. This Proposed Building is at 75%
EnergyGauge Summ * FlaICom-2014. TAM 2014-1.0 Compliant Software. Effective Dale: June 30, 2015
2/11/2016 Page 4 of 12
Project: TC Wholesale Auction
Title: New Project
Type: Office
(WEA Fite: DAYTONABEACH.TMY)
External Lighting Compliance
Description Category Tradable? Allowance AmorLength
ELPA CLP
(W/Unit) or No. of Units
(W) (W)
(Sgft or ft)
Ext Light I Uncovered Parking Areas — Yes 0.15
750
Parking lots and Drives
Tradable Surfaces: 750 (W) Allowance for Tradable: 750 (W)
PASSES
All External Lighting: 750 (W)
Complicance check includes a excess/Base allowance of 750.00(W)
Project: TC Wholesale Auction
Title: New Project
Type: Office
(WEA File. DAYTONABEACH.TMY)
Lighting Controls Compliance
Acronym Ashrae Description Area Design
Min Compli-
ID (sq.ft) CP
CP once
TC Wholesale 16 Office -Open Plan 1,939 19
1 PASSES
PASSES
Project: TC WholesaleAuction
Title: New Project
Type: Office
(WEA File: DAYTONABEACILTMY)
System Report Compliance
TC System 1 Constant Volume Air Cooled No. of Units
Wholesale Split System <65000 Btu/hr
1
Component Category Capacity Design Eft Design
IPLV Comp -
Elf Criteria IPLV
Criteria liance
Cooling System Air Conditioners Air Cooled 59000 14.00 12.23 8.00
PASSES
Split System <65000 Btu/b
Cooling Capacity
Heating System Electric Furnace 34130 1.00 1.00
PASSES
Air Handling Air Handler (Supply) - 1500 0.80 0.82
PASSES
System -Supply Constant Volume
PASSES
EnergyGauge Summit® FlalCom-2014. TAM 2014-1.0 Compliant Software. Effective Date: June 30, 2015
2/11/2016 Page 5 of 12
Plant Compliance
Description Installed Size Design Min Design
No Eff Eff IPLY
Min Category Comp
IPLY liance
Hermetic Centrifugal 1 5 5.900 5.547 6.100
chiller
5.901 Water Chilling Packages PASSES
(Elec), Water Cooled
(centrifugal), 0 to 300
tons
PASSES
Project: TC Wholesale Auction
Title: New Project
Type: Office
(WEA File: DAYTONABEACH.TMY)
Water Heater Compliance
D
Description Type
Design Min
Category
Eff Eff
Design Max Comp
Loss Loss fiance
Water Heater 1 Electric water heater > 12 [kW]
241.5C PASSES
PASSES
Piping System Compliance
Category
Pipe Din Is Operating Ins Cond
[inches] Runout? Temp [Btu-in/hr
IF] SF.F1
Ins Req Ins Compliance
Thick [in] Thick [in]
None
EnergyGauge Summit® FWGom-2014. TAM 2014-1.0 Compliant Software. Effective Date: June 30, 2015
2/11/2016 Page 6 of 12
Mandatory Requirements (as applicable) Mandatory requirements compiled by US Department
of Energy and Pacific Northwest National Laboratory.
Adopted with permission
Topic Section Component Description Yes N/A Ex
Air Leakage
C402.4.1,C402.4.2
Envelope
The building envelope contains a continuous air
U
U
u
barrier that is sealed in an approved manner and
either constructed or tested in an approved
manner. Air harrier penetrations are sealed in an
approved manner.
Air Leakage
C402.4.3,C402.4.4
Envelope
Factory -built fenestration and doom are labeled
❑
❑
❑
as meeting air leakage requirements.
Air Leakage
0402A.7
Envelope
Vestibules are installed on all building entrances.
Doors have self -closing devices.
Air Leakage
C402.4.1.1
Envelope
All sources of air leakage in the building thermal
envelope are sealed, caulked, gasketed, weather
shipped or wrapped with moisture
vapor -permeable wrapping material to minimize
air leakage.
Air Leakage
C402.4.6
Envelope
I*atherseals installed on all loading dock cargo
doors.
Air Leakage
C402.4.8
Envelope
Recessed luminaires in thermal envelope to limit
infiltration and be IC rated and labeled. Seal
between interior finish and luminaim housing.
Fenestrafion
C303.1.3
Envelope
Fenestration products rated in accordance with
❑
❑
❑
NFRC.
Fenestration
C303.1.3
Envelope
Fenestration products are certified as to
performance labels or certificates provided.
Fenestration
C402.2.7
Envelope
Urs -factor of opaque doom associated with the
building thermal envelope meets requirements.
Insulation
C303.2
Envelope
Below -grade wall insulation installed per
manufacturers instructions.
Insulation
C303.2
Envelope
Slab edge insulation installed per manufacturers
instructions.
Insulation
C402.2.6
Envelope
Slab edge insulation depWength. Slab insulation
❑
❑
❑
extending away from building is covered by
pavement or>= 10 inches of soil.
Insulation
C403.2.7,C408.2.8,C4i
Envelope
Exterior insulation protected against damage,
❑
❑
❑
sunlight, moisture, wind, landscaping and
equipment maintenance activities.
Insulation
C402.4.2.1
Envelope
Roof R-value. For some ceiling systems,
❑
❑
❑
verification may need to occur during Framing
Inspection.
Insulation
C303.2
Envelope
Roof insulation installed per manufacturers
❑
❑
❑
instructions. Blown or poured loose -fill insulation
is installed only where the roof slope is <=3 in 12.
Insulation
C402.2.1
Envelope
Skylight curbs are insulated to the level of roofs
❑
with insulation above deck or R-5.
Insulation
C402.2.1.1
Envelope
High-albedo roofs satisfy one of the following:
3-yearaged solar reflectance>= 0.55 and thermal
emittance>=0.75, 3-yearagedsolarreflectance
index>=64.0, initial year solar reflectance >=
0.70 and thermal emittance>= 0.75, or initial year
solar
Insulation
C303.2
Envelope
Above -grade wall insulation installed per
❑
❑
manufacturers instructions.
Insulation
C303.2
Envelope
Floor insulation installed per manufacturers
instructors.
Insulation
C303.1
Envelope
Building envelope insulation is labeled with
❑
El
R-value or insulation certificate providing R-value
and other relevant data.
EnergyGauge Summit® FWCom-2014. TAM 2014-1.0 Compliant Software. Effective Date: June 30, 2015
2/11/2016 Page 7 of 12
Insulation
C303.2.1
Envelope
Exterior insulation is protected! from damage with
-
a protective material. Verification for exposed
foundation insulation may need to occur during
Foundation Inspection.
Insulation
C402.2.1
Envelope
Insulation intended to meet the roof insulation
requirements cannot be installed on top of a
suspended ceiling. Mark this requirement
compliant if insulation is installed accordingly.
Controls
C4052.4
Exterior Lighting
Automatic lighting controls for exterior lighting
installed.
Wattage
C405.6
Exterior Lighting
Exterior grounds lighting over 100 W provides >60
❑
0
❑
Im/W unless on motion sensor or fixture is exempt
from scope of code or from external LPD.
Wattage
C405.6.2
Exterior Lighting
Exterior lighting power is consistent with what is
❑
❑
shown on the approved lighting plans,
demonstrating proposed watts are less than or
equal to allowed watts.
Controls
C4052.21
Interior Lighting
Automatic cols to shut off all building lighting
ntro
❑
❑
❑
installed in all buildings.
Controls
C405.2.1.1
Interior Lighting
Independent lighting controls installed per
❑
❑
11
approved lighting plans and all manual controls
readily accessible and visible to occupants.
Controls
C405.2.1.2
Interior Lighting
Lighting controls installed to uniformly reduce the
El
❑
❑
lighting load by at least 50%.
Controls
C4052.2.3
Interior Lighting
Daylight zones provided with individual controls
that control the lights independent of general area
lighting.
Controls
C405.2.3
Interior Lighting
Sleeping units have at least one master switch at
the main entry door that controls wired luminaires
and sreceptacles.
Controls
C405.2.2.2
Interior Lighting
Occupancypancy sensors installed in required spaces.
❑
El
❑
Controls
C405.2.2.3
Interior Lighting
Primary sidelighted areas are equipped with
❑
❑
required lighting controls.
Controls
C405.2.2.3
Interior Lighting
Enclosed spaces with daylight area under
❑
skylights and rooftop monitors are equipped with
required lighting controls.
Controls
C405.2.3
Interior Lighting
Separate lighting control devices for specific uses
❑
❑
❑
installed per approved lighting plans.
Controls
C405.3
Interior Lighting
Fluorescent luminaires within odd numbered lamp
configurations that are with 10 feet center to
center (if recess mounted) or are within 1 foot
edge to edge (if pendant or surface mounted)
shall be tandem wired.
Wattage
C405.4
Interior Lighting
Exit signs do not exceed 5 watts per face.
❑
❑
Wattage
C405.2.3
Interior Lighting
Additional interior lighting power allowed for
❑
❑
special functions per the approved lighting plans
and is automatically controlled and separated
from general lighting.
Wattage
C405.5.2
Interior Lighting
Interior installed lamp and fixture lighting power is
consistent with what is shown on the approved
lighting plans, demonstrating proposed watts are
less than or equal to allowed watts.
HVAC
C403.2.4.5
Mechanical
Freeze protection and snowlice melting system
sensors for future connection to controls.
HVAC
C403.2.3
Mechanical
HVAC equipment efficiency verified.
El
El
11
Air Leakage
C402.4.5.1
Envelope
Stair and elevator shaft vents have motorized
dampers that automatically dose.
Air Leakage
C402.4.5.2
Envelope
Outdoor air and exhaust systems have motorized
❑
dampers that automatically shut when not in use
and meet maximum leakage rates. Check gravity
dampers where allowed.
HVAC
C403.2.5.1
Mechanical
Demand control ventilation provided for spaces
0
El
El
>500 fit and >25 people/l000 ft2 occupant
density and served by systems with air side
economizer, auto modulating outside air damper
control, or design airflow>3,000 cfm.
EnergyGauge Summit® Fla/Com-2014. TAM 2014-1.0 Compliant Software. Effective Date: June 30, 2015
2/11/2016 Page 8 of 12
HVAC C403.2.8.1 Mechanical
Piping Insulation exposed to weather is protected
from damage (due to sun, moisture, wind, eta).
HVAC C403.2.7 Mechanical
HVAC ducts and plenums Insulated. Where ducts
❑
or plenums are installed in or under a slab,
verification may need to occur during Foundation
Inspection.
HVAC C403.2.8 Mechanical
Thermally ineffective panel surfaces of sensible
❑
❑
❑
heating panels have insulation >= R-3.5.
HVAC C403.2.7 Mechanical
Ducts and plenums sealed based on static
pressure and location.
HVAC C408.2.2.1 Mechanical
Air outlets and zone terminal devices have means
for air balancing.
HVAC C403.2.6 Mechanical
Exhaust air energy recovery on systems meeting
Table C403.2.6
HVAC C403.2.11 Mechanical
Unendosed spaces that are heated use only
radiant heat
HVAC C403.2.4.1 Mechanical
Heating and cooling to each zone is controlled by
❑
El
a thermostat control.
HVAC C403.2.4.2 Mechanical
Thermostatic controls have a 5 °F deadband.
HVAC C403.2A.2 Mechanical
Temperature controls have setpomt overlap
❑
El
❑
restrictions.
HVAC C403.2A.3 Mechanical
Each zone equipped with setback controls using
1:1
El
El
automatic time dock or programmable control
system.
HVAC C403.2.4.3 Mechanical
Automatic Controls: Setback to 55°F(heat)and
❑
❑
85°F (cool); 7-day dock, 2-hour occupant
override, o backup
SYSTEM —SPECIFIC C404.3 Mechanical
ure n
Temperature controls installed on service water
❑
❑
❑
heating systems (110 °F for dwelling units and
lavatories in public restrooms and 90 °F for other
occupancies.)
SYSTEM_SPECIFIC C404.4 Mechanical
Automatic time switches installed to automatically
switch off the recirculating hot-water system or
heat trace.
SYSTEM —SPECIFIC C404.2 Mechanical
Heat traps installed on non -circulating storage
water tanks.
SYSTEM —SPECIFIC C403.2.3 Mechanical
PTAC and PTHP with sleeves 16 in. by 42 in.
labeled for replacement only as per Footnote b to
Table C403.2.3(3).
SYSTEM —SPECIFIC C403.4.2 Mechanical
VAV fan >= 7.5 hp are driven by mechanical or
electrical variable speed drive, or driven by
vane -axial with variable speed blades, or operate
with motor demand <=30 % design kW at 50
design flow - calculations required
SYSTEM —SPECIFIC C403.2.8 Mechanical
HVAC piping insulation thickness. Where piping
0
El
is installed in or under a slab, verification may
need to occur during Foundation Inspection.
SYSTEM —SPECIFIC C403.27.1.3 Mechanical
Ductwork operating>3 in. water column requires
1-1
El
El
air leakage testing.
SYSTEM —SPECIFIC C403.3.1,C403.3.1.1 Mechanical
Air economizers provided where required, meet
11
❑
the requirements for design capacity, control
signal, ventilation controls, high -limit shut-off,
integrated economizer control, and provide a
means to relieve excess outside air dudng
operation.
SYSTEM —SPECIFIC C403.3.1,C403.4.1 Mechanical
Water economizers provided where required,
meet the requirements for design capacity,
maximum pressure drop and integrated
economizer control.
SYSTEM —SPECIFIC C403.4.1A Mechanical
Economizer operation will not increase heating
energy use during normal operation.
SYSTEM —SPECIFIC C403.4.5 Mechanical
Zone controls can limit simultaneous heating and
El
cooling and sequence heating and cooling to each
zone.
SYSTEM —SPECIFIC C403.4.3.1 Mechanical
Three -pipe hydronic systems using a common
11
El
El
return for hot and chilled water are not used.
EnergyGauge Summit® FlalGom-2014. TAM 2014-1.0 Compliant Software. Effective Date: June 30, 2015
2/11/2016 Page 9 of 12
SYSTEM -SPECIFIC C403.4.3.2
Mechanical Two -pipe hydronic systems using a common
1__I
U
❑
distribution system have controls to allow a
deadband >=15 °F, allow operation in one mode
for at least 4 him before changeover, and have
rest controls to limit heating and cooling supply
temperature to —30 -F.
SYSTEM -SPECIFIC C403.4.3.3.1
Mechanical Hydronic heat pump systems connected to
common water loop meet heat rejection and heat
addition requirements.
SYSTEM -SPECIFIC C408.2.2.2
Mechanical HVAC hydronic heating and cooling coils have
means to balance and have pressure test
connections.
SYSTEM -SPECIFIC C403.2.10.1
Mechanical HVAC fan systems at design conditions do not
exceed allowable fan system motor nameplate hp
or fan system bhp.
SYSTEM -SPECIFIC C403.2.10.2
Mechanical HVAC fan motors not larger than allowable limits.
SYSTEM -SPECIFIC C403.4.2
Mechanical VAV fan motors>=7.5 hp to be driven by variable
speed drive, have a vane -axial fan with variable
pitch blades, or have controls to limit fan motor
demand.
SYSTEM -SPECIFIC C403.4.2.1
Mechanical VAV fans have static pressure sensors positioned
so setpoint <=1/3 total design pressure.
SYSTEM -SPECIFIC C403.4.2.2
Mechanical Reset static pressure setpoint for DDC controlled
VAV boxes reporting to central controller based on
the zones requiring the most pressure.
SYSTEM -SPECIFIC C403.4.5A
Mechanical Multiple zone HVAC systems have supply air
temperature reset controls.
SYSTEM -SPECIFIC C403.4.3.4
Mechanical Hydronic systems greater than 300,000 BtWh
designed for variable fluid flow.
SYSTEM -SPECIFIC C403.4.3.5
Mechanical Reduce flow in pumping systems >10 hp to
multiple chillers or boilers when others are shut
down.
SYSTEM -SPECIFIC C403A.3.4
Mechanical Temperature reset by representative building
1:1
El
El
loads in pumping systems for chiller and boiler
systems Btu/h.
SYSTEM -SPECIFIC C403.4.3.3.3
Mechanical Two-posNon automatic valve interlocked to shut
wo-pos>on auto
❑
❑
❑
off water flow when hydronic heat pump with
pumping system>70 hp Is off.
SYSTEM -SPECIFIC C403.4.4
Mechanical Fan systems with motors>=7.5 hp associated
El
❑
❑
with heat rejection equipment to have capability to
operate at 213 of full -speed and auto speed
controls to control the leaving fluid temperature or
condensing temp/pressure of heat rejection
device.
SYSTEM -SPECIFIC C403.4.6
Mechanical Condenser heat recovery system that can heat
❑
water to 85 °F or provide 60°% of peak heat
rejection is installed for preheating of service hot
water in 24/7 facility, water cooled systems reject
>6 MMBtu, SHW load >=1 MMBtu.
C403.4.7
Mechanical Hot gas bypass limited to:
El
1-1
El
<=240 kBtu/h - 50%
>240 k8lu/h-25%
SYSTEM -SPECIFIC C404.2
Mechanical Service water heating equipment meets efficiency
requirements -
SYSTEM -SPECIFIC C403.2A2
Mechanical Heating and cooling to each zone is controlled by
❑
a thermostat control. Minimum one humidity
control device per installed
humidificationtdehumidification system.
SYSTEM -SPECIFIC C403.2A.3.3
Mechanical Systems include optimum start controls.
❑
❑
El
SYSTEM -SPECIFIC C403.2.4.1.1
Mechanical Heal pump controls prevent supplemental electric
El
❑
❑
resistance heat from coming on when not needed.
SYSTEM -SPECIFIC C404.3
Mechanical Public lavatory faucet water temperature —110°F.
El
El
0
SYSTEM -SPECIFIC C404.5
Mechanical All piping in circulating system insulated
❑
SYSTEM -SPECIFIC C404.5
Mechanical First 8 ft of outlet piping is insulated
El
El
❑
EnergyGauge Summit® Fla/Com-2014. TAM 2014-1.0 Compliant Software. Effective Date: June 30, 2015
2/11/2016 Page 10 of 12
SYSTEM —SPECIFIC
SYSTEM_ SPECIFIC
SYSTEM —SPECIFIC
SYSTEM —SPECIFIC
SYSTEM —SPECIFIC
SYSTEM —SPECIFIC
Testing
C404.5
C404.6
C404.7.1
C404.7.3
C404.7.2
r403.2.3
C408.2.3.2
MandatoryAdditional Ell
C406
Insulation
C402.2.8
Plan Review -
C103.2
Plan Review
C103.2
Plan Review
C103.2
Plan Review
C103.2
Plan Review
C103.2
Plan Review
0406
Plan Review
C4023.22
Post Construction C408.2.5.1
Mechanical
All heat traced or externally heated piping
insulated
Mechanical
Controls are installed that limit the operation of a
recirculation pump installed to maintain
temperature of a storage tank
Mechanical
Pool heaters are equipped with ontoff switch and
no continuously burning pilot light
Mechanical
Vapor retardant pool covers are provided for
heated pools and permanently installed spas.
Mechanical
Time switches are installed on all pool heaters
and pumps.
Mechanical
Centrifugal fan openrircuit cooling towers having
combined rated capacity>= 1100 gpm meets
minimum efficiency requirement: >=38.2 gpnVhp.
Mechanical
HVAC control systems have been tested to
ensure proper operation, calibration and
adjustment of controls.
Project
Efficient HVAC performance, efficient lighting
system, or on -site supply of renewable energy
consistent with what is shown the approved plans.
Project
Bottom surface of floor structures incorporating
radiant heating insulated to >=R-3.5.
Envelope
Plans and/or specifications provide all information
with which compliance can be determined for the
building envelope and document where
exceptions to the standard are claimed.
Exterior Lighting
Plans, specifications, and/or calculations provide
all information with which compliance can be
determined for the exterior lighting and electrical
systems and equipment and document where
exceptions to the standard are claimed.
Information provided shout
Interior Lighting
Plans, specifications. and/or calculations provide
all information with which compliance can be
determined for the interior lighting and electrical
systems and equipment and document where
exceptions to the standard are claimed.
Information provided shout
Mechanical
Plans, specifications, and/or calculations provide
all information with which compliance can be
determined for the mechanical systems and
equipment and document where exceptions to the
standard are claimed. Load calculations per
acceptable engineering st
Mechanical
Plans, specifications, and/or calculations provide
all Infomhation with which compliance can be
determined for the service water heating systems
andequipmentand documentwhereexrxptions
to the standard are claimed. Hot water system
sized per manufact
Project
Plans, specincaflons, and/or calculations provide
all information with which compliance can be
determined for the additional energy efficiency
package options.
Envelope
Skylights in office, storage, automotive service,
manufacturing, non -refrigerated warehouse, retail
store, and distribution/soring area have a
measured haze value> 90 percent unless
designed to exclude direct sunlight
Exterior Lighting Lighting systems have been tested to ensure
proper calibration, adjustment, programming, and
operation.
Interior Lighting Furnished as -built drawings for electric power
systems within 30 days of system acceptance.
❑ ❑ ❑
❑ ❑ ❑
❑ ❑ ❑
❑ ❑ ❑
❑ ❑ ❑
❑ ❑ ❑
❑ ❑ ❑
❑ ❑ ❑
�Ni
EnergyGauge Summit®Fla/Cbm-2014. TAM 2014-1.0 Compliant Software. Effective Date: June 30, 2015
2/1112016 Page 11 of 12
Post Construction
C303.3,C408.2.5.2
Interior Lighfing
Furnished O&M instructions for systems and
equipment to the building owner or designated
Post Construction
0408.3
Interior Lighting
representative.
Lighting systems have been tested to ensure
El
❑
❑
propercelibmtion, adjustment, programming, and
Post Construction
C408.2.5.7
Mechanical
operation.
Famished HVAC as -built drawings submitted
❑
❑
❑
within 90 days of system acceptance.
Post Construction
C303.3,C408.2.5.2
Mechanical
Famished O&M manuals for HVAC systems
❑
❑
❑
within 90 days of system acceptance.
Post Construction
C408.2.5.3
Mechanical
An air and/or hydronic system balancing report is
❑
❑
❑
provided for HVAC systems.
Post Construction
C408.2.1
Mechanical
Commissioning plan developed by registered
❑
❑
❑
design professional or approved agency.
Post Construction
C408.2.4
Mechanical
Preliminary commissioning report completed and
❑
❑
❑
certified by registered design professional or
Post Construction
C408.2.5.4
Mechanical
approved agency.
Final commissioning report due to building owner
El
❑
❑
Within 90 days of receipt of certificate of
Post Construction
C406.2.3.1
Mechanical
occupancy.❑
HVAC equipment has been tested to ensure
❑
❑
proper operation.
Post Construction
C408.2.3.3
Mechanical
Economizers have been tested to ensure proper
❑
❑
❑
operation.
EnergyGauge SummirM Fis/Com-2014. TAM 2014-1.0 Compliant Software. Effective Date: June 30, 2015
2/11/2016 Page 12 of 12
- Duct System Details Job: April8Industrial33rd Street
Y Date: April th, 2616
NEW OFFICES By: Craig C Brooks
WebREPS WebReps LLC. Plan: 2900 Industrial 33rd stre
1-800-810-3280
1892 Commerce Aenue, Vero Beach, FL 32960 Phone: 800-8103280 Email: manuall@mbrepshv c.eom License: CAC054709
Calculation method: EqualFric
Equipment pressure losses ( in H2O ):
Duct system losses ( in H2O ):
Total fan pressure ( in H2O ):
Fan air flow( cfm ):
Supply FR ( in/100ft ): 0.100
Heating 0.230 SCANNED
0.183 BY
0.413 St. Lucie County
1600
Supply Branch Details
Return FR ( in/100ft ): 0.100
Cooling
0.230
0.160
0.390
1600
Duct Name
HtgLoad
HtgAVF
Dsn AVF
Veloc
Wdth
Length
F.Loss
Tot.Loss
(Btuh)
(cfm)
(cfm)
(fpm)
(in)
(ft)
(in H2O)
(in H2O)
Parent Trunk Name
ClgLoad
ClgAVF
Shape
Matl
Hght
S.Loss
Aj+Vav
Cum.Loss
(Btuh)
(cfm)
(in)
(in H2O)
(in H2O)
(in H2O)
Breakroom .
1039
47
c 110
560
6
9.5
0.011
0.027
st11
2363
107
Rect
VinlFlx
0.016
0
0.125
Computer
401
18
h 40
460
4
9.5
0.007
0.025
st9
735
33
Rect
VinlFlx
0.0.18
0
0.112
Conference Room
1448
66
c 158
593
7
16.0
0.012
0.037
st6
3407
155
Rect
VinlFlx
0.025
0
0.103
Employee Restroom
637
29
c 81
597
5
6.0
0.012
0.026
st12
1749
80
Rect
VinlFIX
0.014
0
0.131
Entry
2784
127
c 283
518
10
4.5
0.011
0.015
st8
6079
276
Rect
VinlFlx
0.003
0
0.100
Entry -A
2784
127
c 283
518
10
5.5
0.011
0.015
st7
6079
276
Rect
VInIFIX
0.004
0
0.088
Ladies Restroom
1894
86
h 190
544
8
3.0
0.004
0.007
st13
3313
151
Rect
VinlFlx
0.003
0
0.128
Mens Restroom
2507
114
h 251
569
9
3.0
0.005
0.008
st14
3799
173
Rect
VinlFlx
0.003
0
0.140
Office 1
1030
47
c 107
543
6
9.0
0.003
0.017
2293
104
Rect
VinlFlx
0.014
0
0.017
Office 2
645
29
c 99
506
6
7.5
0.009
0.019
st4
2135
97
Rect
VinlFlx
0.010
0
0.040
Office 3
783
36
c 114
580
6
10.9
0.004
0.023
2449
111
Rect
VinlFlx
0.019
0
0.023
Wrightsoft° RightSuiteO Unhereal 201717.0.03 RSU169M
...ice 29M lndushial 33 rd SheetFad Pimce.rup Calc = RTS Front Doorfacec: SE
201&Apr-21 12:04:04
Page 1
F�-k Duct System Summary
Job:
2900 Industrial 33rd Street
NEW OFFICES
Date:
By:
April 8th, 2016
Craig C Brooks
WebREPS
WebReps LLC.
pan:
2 00Industrial 33rd Stre
1-800-810-3280
1892 Commerce Annue, Vero Beach, FL 32960 Phone: B00-Bl"280
Email: mamm1j@Mbrepslnac.com License: CAC054709
Calculation method: EqualFric
Supply FR ( in/100ft ): 0.100
Return FR ( in/10Oft ):0.100
Heating
Cooling
Equipment pressure losses ( in H2O ):
0.230
0.230
Duct system losses ( in H2O ):
0.183
0.160
Total fan pressure ( in H2O ):
0.413
0.390
Fan air flow ( cfm ):
1600
1600
Supply
Name
Htg
Load
(Btuh)
Clg
Load
(Btuh)
Design
AVF
(cfm)
Veloc
(fpm)
Shape
Duct
Size
(in)
Duct
Mall
Cumm.
Loss
(in H2O)
Breakroom
1039
2363
c 110
560
Round
6
VinlFlx
0.125
Computer
401
735
h 40
460
Round
4
VinIFIX
0.112
Conference Room
1448
3407
c 158
593
Round
7
VinlFlx
0.103
Employee Restroom
637
1749
c 81
597
Round
5
VinlFlx
0.131
Entry
2784
6079
c 283
518
Round
10
VinlFlx
0.100
Entry -A
2784
6079
c 283
518
Round
10
Vin1Flx
0.088
Ladies Restroom
1894
3313
h 190
544
Round
8
VinlFlx
0.128
Mens Restroom
2507
3799
h 251
569
Round
9
VinlFlx
0.140
Office 1
1030
2293
c 107
543
Round
6
VinlFlx
0.017
Office 2
645
2135
c 99
506
Round
6
VinlFlx
0.040
Office 3
783
2449
c 114
580
Round
6
VinlFlx
0.023
Name
Htg
Load
(Btuh)
Clg
Load
(Btuh)
Design
AVF
(cfm)
Veloc
(fpm)
Shape
Duct
Size
(in)
Duct
Matl
Pres
Loss
(in H2O)
st1
14139
29658
h 1418
681
Rect
25 x 12
RectFbg
0.001
st2
14139
29658
h 1418
681
Rect
25 x 12
RectFbg
0.001
stl2
5038
8861
h 505
606
Rect
10 x 12
RectFbg
0.007
st11
6077
11224
h 610
610
Rect
12 x 12
RectFbg
0.002
st7
12045
24117
h 1208
690
Rect
21 x 12
RectFbg
0.006
st6
13493
27524
h 1353
677
Rect
24 x 12
RectFbg
0.003
st5
13493
27524
h 1353
677
Rect
24 x 12
RectFbg
0.002
st4
14139
29658
h 1418
681
Rect
25 x 12
RectFbg
0.004
st3
14139
29658
h 1418
681
Rect
25 x 12
RectFbg
0.002
st8
9262
18038
h 929
697
Rect
16 x 12
RectFbg
0.013
st9
6478
11959
h 650
557
Rect
14 x 12
RectFbg
0.003
st10
6077
11224
h 610
610
Rect
12 x 12
RectFbg
0.004
stl3
4401
7111
h 441
662
Rect
8 x 12
RectFbg
0.015
st14
2607
3799
h 251
503
Rect
6 x 12
RectFbg
0.012
LIJ
2016-Aar-21 12:04:04
wrightsOft' RighlSuile® Uniwma1201717.0.03 RSU16998 Page 1
...ice 2900 industrial 33 rd StreetFW Pieme.mp Calc = RTS Front Door faces: SE
Htg
Clg
Design
Veloc
Shape
Duct
Duct
Cumm.
Name
Load
Load
AVF
Size
Matt
Loss
(Btuh)
(Btuh)
(cfm)
(fpm)
(in)
(in H2O)
rbi
15952
34400
1 c 1600
686
Rect
28 x 12
VinlFlx
0.043
2016-Apr21 12:04:04
wrightsofr RightSuOe® Uniwmgl201717.0.03 RSU16998 Page 2
...Ice 2900 industrial 33 rd Stro tFortPime.mP Calc = RTS Front Dow faces: SE
Supply Trunk ;Details
Duct Name
HtgLoad
HtgAVF
Dsn AVF
Veloc
Wdth
Length
F.Loss
Tot.Loss
(Btuh)
(cfm)
(cfm)
(fpm)
(in)
(ft)
(in H2O)
(in H2O)
Parent Trunk Name
ClgLoad
ClgAVF
Shape
Mat[
Hght
Sloss
Aj+Vav
Cum.Loss
(Btuh)
(cfm)
(in)
(in H2O)
(in H2O)
(in H2O)
st1
14139
643
h 1418
681
25
1.0
0.014
0.014
29658
1348
Rect
RectFbg
12
0.001
0
st2
14139
643
h 1418
681
25
1.5
0
0.001
st1
29658
1348
Rect
RectFbg 1
12
0.001
0
st12
5038
229
h 505
606
10
7.5
0.000
0.007
st11
8861
403
Rect
RectFbg
12
0.007
0
st11
6077
276
h 610
610
12
2.5
0.005
0.007
st10
11224
510
Rect
RectFbg
12
0.002
0
st7
12045
548
h 1208
690
21
8.0
0.001
0.007
st6
24117
1096
Rect
RectFbg
12
0.006
0
SW
13493
613
h 1353
677
24
4.5
0.039
0.043
st5
27524
1251
Rect
RectFbg
12
0.003
0
st5
13493
613
h 1353
677
24
2.5
0.000
0.002
st4
27524
1251
Rect
RectFbg
12
0.002
0
st4
14139
643
h 1418
681
25
6.0
0
0.004
st3
29658
1348
Rect
RectFbg
12
0.004
0
st3
14139
643
h 1418
681
25
2.5
0
0.002
st2
29658
1348
Rect
RectFbg
12
0.002
0
st8
9262
421
h 929
697
16
14.0
0.000
0.012
st7
18038
820
Rect
RectFbg
12
0.013
0
SO
6478
294
h 650
557
14
5.0
-0.001
0.002
st8
11959
544
Rect
RectFbg
12
0.003
0
st10
6077
276
h 610
610
12
4.5
0.001
0.004
st9
11224
510
Rect
RectFbg
12
0.004
0
st13
4401
200
h 441
662
18
11.5
0.001
0.016
st12
7111
323
Rect
RectFbg
12
0.015
0
sit
2507
114
h 251
503
6
12.5
-0.001
0.011
st13
3799
173
Rect
RectFbg
1 12
0.012
0
2016-Apr-21 12:04:04
wrightSOft• RlghtSuite®Uniwma12017 17.0.03 RSU16998 Page 2
...Ice 29DO Industrial 33 rd StreetFort Pierce.tup Cale = RTS Fmrd Dwrfaces: SE
Return Branch Details
Duct Name
HtgLoad
HtgAVF
Dsn AVF
Veloc
Wdth
Length
F.Loss
Tot.Loss
(Btuh)
(cfm)
(cfm)
(fpm)
(in)
(ft)
(in H2O)
(in H2O)
Parent Trunk Name
ClgLoad
CIgAVF
Shape
Matl
Hght
S.Loss
Aj+Vav
Cum.Loss .
(Btuh)
(cfm)
(in)
(in H2O)
(in H2O)
(in H2O)
rb1
15952
725
c 1600
686
28
1.0
0.043
0.043
34400
1564
Rect
VinIFIx
12
0.001
0
0.043
2016Apr-21 12:04:04
wrightsoft• RightSuge® Unix rsa12017 17.0.03 RSU16998 Page 3
...Ice 2900 ]ndustriat 33 rd Str tFott Pi e.mp Calc = RTS Front D= faces: SE