HomeMy WebLinkAboutREVIEW COMMENTSPlanning & Development Services Building & Code Regulation Division 2300 Virginia Avenue Fort Pierce, FL 34982 Phone:(772)462.2172 Fax:(772A62-UM PROPERTY INFORMATION Address: 2902 Industrial 33 St City / State / Zip: Fort Pierce, FI 34946 Parcel111: 1428-702-1501-000/1 Zoning: IL APPLICATION INFORMATION Permit Number: 1602-0403 Permit Type: COMMERCIAL RENOVATION CONTRACTOR INFORMATION Contractor Name: David A Ricks Business Name: Schopke Enterprises Inc Business Addr: 1620 Tangerine St City / State / Zip: Melbourne, FI 32901 REVIEW COMMENTS SCANNED BY St, Lucie County Page 1 Owner(s): Creative Systems Uc Jurisdiction: SAINT LUCIE COUNTY Lot#: 4 Block: 65 Stories: Automatic Sprinkler System? No Fax Number: 321-723-1294 Email: I nfo@Brevardgrouting.Com Review Type Status Reviewed By Date Started Date Completed Date Released ADDRESSING ASSIGNMENT COMPLETE Lydia Galbraith 311/2016 3/112016 3/112016 Comment: DOCUMENTS MISSING PENDING 2129/2016 Comment: PLUMBING SUB AGREEMENT Comment: SUBMIT A VEGETATION REMOVAL/EXEMPTION APPLICATION WITH A LANDSCAPE PLAN OF WHAT IS ON 3/112016 LOCATION. FRONT COUNTER REVIEW COMPLETE Karen Nielsen 212312016 2123/2016 212312016 Comment: PE REVIEW COMMENTS (2) COMPLETE William Durden 4/29/2016 5/4/2016 5/4/2016 Comment: PE REVIEW COMMENTS (2) INCOMPLETE Carl Peterson 412912016 Comment: PE REVIEW COMMENTS (2) INCOMPLETE Greg Smyth 511/2016 Comment: PE REVIEW COMMENTS (3) INCOMPLETE William Durden 5/5/2016 4/2912016 Comment: PLEASE SHOW A BALANCED SYSTEM. Comment: PLEASE SHOW HI LO DRINKING FOUNTAINS PER TABLE 403.1 FL PLUMBING CODE 2014 AND FL 5IM016 ACCESSABILITY CODE 2014 SECTION 211 Planning & Development Services Building & Code Regulation Division 2300 Virginia Avenue Fort Pierce, FL 34982 Phone:(772)462.2172 Faz:(772)462.6443 REVIEW COMMENTS t Comment: PLEASE SHOW A PLUMBING PAGE WITH PROPER ISOMETRICS FOR SANITARY AND POTABLE WATER 5/212016 DISTRIBUTION PER SECTION 107.3.5 FLORIDA BLD CODE 2014 Comment: PLEASE SHOW VEHICLE BARRIER LOCATIONS ON PLANS. AT EACH COLUMN AND DRIVE LANE. AS PER 5/5I2016 SECTION 1607.8.3 OF THE 2014 FLORIDA BUILDING CODE. Comment: A3 OCCUPANCY LOAD OF GREATER THAN 300 REQUIRES A SPRINKLER SYSTEM. PLEASE SEE 903.2.1.3 OF 515/2016 THE 2014 FLORIDA BUILDING CODE. PLANS EXAMINER ELECTRIC COMPLETE 3110/2016 5/412016 5/4/2016 Comment: PLANS EXAMINER MECHANICAL INCOMPLETE Carl Peterson 3/2112016 311812016 Comment: PLEASE SHOW A BALANCED SYSTEM. PLANS EXAMINER PLUMBING INCOMPLETE Greg Smyth 3/21/2016 Comment: PLEASE SHOW A PLUMBING PAGE WITH PROPER ISOMETRICS FOR SANITARY AND POTABLE WATER DISTRIBUTION PER SECTION 107.3.5 FLORIDA SLID CODE 2014 3/2112016 Comment: PLEASE SHOW HI LO DRINKING FOUNTAINS PER TABLE 403.1 FL PLUMBING CODE 2014 AND FL ACCESSABILITY CODE 2014 SECTION 211 PLANS EXAMINER REVIEW COMPLETE William Durden 3/17/2016 4129/2016 4129/2016 Comment: ZONING REVIEW INCOMPLETE Lydia Galbraith 212612016 2/29/2016 Comment: PLEASE PROVIDE A COPY OF THE HEALTH DEPARTMENT PERMIT FOR THE SEPTIC. Comment: PLEASE PROVIDE (3) FLOOR PLANS AND SITE PLANS STAMPED BY THE HEALTH DEP. FOR APPROVAL. 2/29/2016 PLEASE INDICATE ON THE SITE PLAN THE DRAIN FIELD AND LOCATION OF THE SEPTIC. 2/29/2016 Comment: PLEASE BE AWARE THAT THE FENCE REQUIRES A SEPARATE PERMIT. Comment: PLEASE BE AWARE THAT INDUSTRIAL AVE ONE IS NOT AN OPEN ROAD, AN ACCESS OR EXIT WILL NOT BE 212912016 ALLOWED UNTIL THE ROAD HAS BEEN IMPROVED. A GATE WILL NOT BE ALLOWED. Comment: THE HANDICAP PARKING SPACES DON'T MEET THE MIN. REQUIRED SIZE. A HC PARKING IS 12' BY 18, WITH 2/29/2016 A V ACCESS AISLE. SEE ST LUCIE COUNTY LAND DEVELOPMENT CODE CHAPTER 7.06.02 B. 2/P9/Y016 Comment: PLEASE INDICATE THE DRIVEWAY ON THE SITE PLAN. 212912016 Comment: PARKING SPACES SHOULD NOT BE LOCATED ON THE DRIVEWAY. Comment: A ZONING COMPLIANCE APPLICATION IS REQUIRED TO BE SUBMITTED BEFORE FINAL INSPECTION CAN 2129/2016 BE APPROVED. Comment: PLEASE BE AWARE THAT IMPACT FEE RETAIL/WHOLE SALE WILL BE APPLICABLE FOR THE ENCLOSED 2129/2016 AREA FOR THE OFFICE.THE OPEN COVERED AREA AND THE STORAGE AREA WILL BE CONSIDERED ACCESSORY TO THE MAIN USE AND THERE FOR WILL NOT RECEIVE IMPACT FEES. 3IM016 Comment: SEE ATTACHED EMAIL FROM PATRICK DAYAN FOR REQUIREMENTS UPDATE DRIVEWAY. 3/2/2016 Comment: PLEASE BE AWARE THAT ABOVE COMMENTS ONLY REFLECTS THE ZONING REVIEW. THE PLANS EXAMINER MIGHT HAVE ADDITIONAL COMMENTS. 3/1412016 Comment: 3114116 CONTRACTOR PICKED UP ONE SET OF PLANS TO GO TO HEALTH DEP. Planning & Development Services Building & Code Regulation Division 2300 Virginia Avenue Fort Pierce, FL 34982 Phone:(772)462-2172 Fax:(772)462.6443 PROPERTY INFORMATION Address: 2902 Industrial 33 St City / State / Zip: Fort Pierce, FI 34946 Parcel#: 1428-702-1501-000/1 Zoning: IL APPLICATION INFORMATION Permit Number: 1602-0403 Permit Type: COMMERCIAL RENOVATION CONTRACTOR INFORMATION Contractor Name: David A Ricks Business Name: Schopke Enterprises Inc Business Addr: 1620 Tangerine St City.I State / Zip: Melbourne, FI 32901 REVIEWS AND COMMENTS REVIEW COMMENTS SCANNED BY St. Owner(s): Creative Systems Llc Jurisdiction: SAINT LUCIE COUNTY Lot#: 4 Block: 65 Stories: Automatic Sprinkler System? No Fax Number: 321-723-1294 Email: Info@B revardgrouting. Com Review Type Status Reviewed By Date Started Date Completed Date Released ADDRESSING ASSIGNMENT COMPLETE Lydia Galbraith 3/1/2016 311/2016 3/1/2016 Comment: DOCUMENTS MISSING PENDING 2/29/2016 Comment: PLUMBING SUB AGREEMENT 3/1/2016 Comment: SUBMIT A VEGETATION REMOVALIEXEMPTION APPLICATION WITH A LANDSCAPE PLAN OF WHAT IS ON LOCATION. ' FRONT COUNTER REVIEW COMPLETE Karen Nielsen 212312016 2/2312016 212312016 Comment: PE REVIEW COMMENTS (2) COMPLETE William Durden 412912016 5/412016 514/2016 Comment: PE REVIEW COMMENTS (2) INCOMPLETE Carl Peterson 412912016 Comment: PE REVIEW COMMENTS (2) INCOMPLETE Greg Smyth 511/2016 Comment: PE REVIEW COMMENTS (3) INCOMPLETE William Durden 5/5/2016 4/29/2016 Comment: PLEASE SHOW A BALANCED SYSTEM. 5/2/2016 Comment: PLEASE SHOW HI LO DRINKING FOUNTAINS PER TABLE 403.1 FL PLUMBING CODE 2014 AND FL ACCESSABILITY CODE 2014 SECTION 211 Planning & Development Services Building & Code Regulation Division 2300 Virginia Avenue Fort Pierce, FL. 34982 Phone:(772)462.2172 Fax:(772)462.6"3 REVIEW COMMENTS U 5/2/2016 Comment: PLEASE SHOW A PLUMBING PAGE WITH PROPER ISOMETRICS FOR SANITARY AND POTABLE WATER DISTRIBUTION PER SECTION 107.3.5 FLORIDA BLD CODE 2014 5/5/2016 Comment: PLEASE SHOW VEHICLE BARRIER LOCATIONS ON PLANS. AT EACH COLUMN AND DRIVE LANE. AS PER SECTION 1607.8.3 OF THE 2014 FLORIDA BUILDING CODE. 5/52016 Comment: A3 OCCUPANCY LOAD OF GREATER THAN 300 REQUIRES A SPRINKLER SYSTEM. PLEASE SEE 903.2.1.3 OF THE 2014 FLORIDA BUILDING CODE. PLEASE SUBMIT SPRINKLER SYSTEM DRAWINGS. PLANS EXAMINER ELECTRIC COMPLETE 3/10/2016 51412016 5/412016 Comment: PLANS EXAMINER MECHANICAL INCOMPLETE Carl Peterson 3/2112016 3118/2016 Comment: PLEASE SHOW A BALANCED SYSTEM. PLANS EXAMINER PLUMBING INCOMPLETE Greg Smyth 3/21/2016 Comment: PLEASE SHOW A PLUMBING PAGE WITH PROPER ISOMETRICS FOR SANITARY AND POTABLE WATER DISTRIBUTION PER SECTION 107.3.5 FLORIDA BLD CODE 2014 312112016 Comment: PLEASE SHOW HI LO DRINKING FOUNTAINS PER TABLE 403.1 FL PLUMBING CODE 2014 AND FL ACCESSABILITY CODE 2014 SECTION 211 PLANS EXAMINER REVIEW COMPLETE William Durden 311712016 4/2912016 4/29/2016 Comment: ZONING REVIEW INCOMPLETE Lydia Galbraith 2J2612016 229/2016 Comment: PLEASE PROVIDE A COPY OF THE HEALTH DEPARTMENT PERMIT FOR THE SEPTIC. 2129/2016 Comment: PLEASE PROVIDE (3) FLOOR PLANS AND SITE PLANS STAMPED BY THE HEALTH DEP. FOR APPROVAL. PLEASE INDICATE ON THE SITE PLAN THE DRAIN FIELD AND LOCATION OF THE SEPTIC. 2129/2016 Comment: PLEASE BE AWARE THAT THE FENCE REQUIRES A SEPARATE PERMIT. 212912016 . Comment: PLEASE BE AWARE THAT INDUSTRIAL AVE ONE IS NOT AN OPEN ROAD, AN ACCESS OR EXIT WILL NOT BE ALLOWED UNTIL THE ROAD HAS BEEN IMPROVED. A GATE WILL NOT BE ALLOWED. 2129/2016 Comment: THE HANDICAP PARKING SPACES DON'T MEET THE MIN. REQUIRED SIZE. A HC PARKING IS 12' BY 18' WITH A V ACCESS AISLE. SEE ST LUCIE COUNTY LAND DEVELOPMENT CODE CHAPTER 7.06.02 B. 2129/2016 Comment: PLEASE INDICATE THE DRIVEWAY ON THE SITE PLAN. 2/29/2016 Comment: PARKING SPACES SHOULD NOT BE LOCATED ON THE DRIVEWAY. 2/29/2016 Comment: AZONING COMPLIANCE APPLICATION IS REQUIRED TO BE SUBMITTED BEFORE FINAL INSPECTION CAN BE APPROVED. Comment: PLEASE BE AWARE THAT IMPACT FEE RETAILIWHOLE SALE WILL BE APPLICABLE FOR THE ENCLOSED 2129/2016 AREA FOR THE OFFICE.THE OPEN COVERED AREA AND THE STORAGE AREA WILL BE CONSIDERED ACCESSORY TO THE MAIN USE AND THERE FOR WILL NOT RECEIVE IMPACT FEES. 32/2016 Comment: SEE ATTACHED EMAIL FROM PATRICK DAYAN FOR REQUIREMENTS UPDATE DRIVEWAY. 312/2016 Comment: PLEASE BE AWARE THAT ABOVE COMMENTS ONLY REFLECTS THE ZONING REVIEW. THE PLANS EXAMINER MIGHT HAVE ADDITIONAL COMMENTS. 3/14/2016 Comment: 3114116 CONTRACTOR PICKED UP ONE SET OF PLANS TO GO TO HEALTH DEP. Planning & Development Services Building & Code Regulation Division 2300 Virginia Avenue Fort Pierce, FL. 34982 Phone:V72)462.2172 Fax:(772)462.6443 Address: City / State / Zip: • Parcel #: Zoning: 2902 Industrial 33 St Fort Pierce, FI 34946 1428-702-1501-000/1 IL REVIEW COMMENTS SCANNED By St. Lucie County Owner(s): Creative Systems Lie Jurisdiction: SAINT LUCIE COUNTY Lot#: 4 Block: 65 1 APPLICATION INFORMATION Permit Number: 1602-0403 Stories: Automatic Sprinkler System? No Permit Type: COMMERCIAL RENOVATION CONTRACTOR INFORMATION Contractor Name: David A Ricks Fax Number: 321-723-1294 Business Name: Schopke Enterprises Inc Business Addr: 1620'Tangerine St Email: Info@Brevardgrouting.Com City / State / Zip: Melbourne, FI 32901 REVIEWS AND COMMENTS Review Type Status Reviewed By Date Started Date Completed Date Released ADDRESSING ASSIGNMENT COMPLETE Lydia Galbraith 3/112016 3/1/2016 3/112016 Comment: DOCUMENTS MISSING PENDING 2129/2016 Comment: PLUMBING SUB AGREEMENT • 3/12016 Comment: SUBMIT A VEGETATION REMOVAUEXEMPTION APPLICATION WITH A LANDSCAPE PLAN OF WHAT IS ON LOCATION. FRONT COUNTER REVIEW COMPLETE Karen Nielsen 212312016 2/23/2016 2123/2016 Comment: - PE REVIEW COMMENTS (2) COMPLETE William Durden 4/2912016 51412016 5/4/2016 Comment: PE REVIEW COMMENTS (2) INCOMPLETE Carl Peterson 412912016 Comment: . PE REVIEW COMMENTS (2) INCOMPLETE Greg Smyth 511/2016 Comment: PE REVIEW COMMENTS (3) INCOMPLETE William Durden 515/2016 412MO16 Comment: PLEASE SHOW A BALANCED SYSTEM. 512/2016 Comment: PLEASE SHOW HI LO DRINKING FOUNTAINS PER TABLE 403.1 FL PLUMBING CODE 2014 AND FL ACCESSABILITY CODE 2014 SECTION 211 Planning & Development Services Building & Code Regulation Division 2300 Virginia Avenue Fort Pierce, FL 34982 Phone:(772(462.2172 Fax:(772(462-6443 REVIEW COMMENTS 2 5/2/2016 Comment: PLEASE SHOW A PLUMBING PAGE WITH PROPER ISOMETRICS FOR SANITARY AND POTABLE WATER DISTRIBUTION PER SECTION 107.3.6 FLORIDA BUD CODE 2014 5/5/2016 Comment: PLEASE SHOW VEHICLE BARRIER LOCATIONS ON PLANS. AT EACH COLUMN AND DRIVE LANE. AS PER SECTION 1607.8.3 OF THE 2014 FLORIDA BUILDING CODE. Comment: A3 OCCUPANCY LOAD OF GREATER THAN 300 REQUIRES A SPRINKLER SYSTEM. PLEASE SEE 903.2.1.3 OF 5/5/2016 THE 2014 FLORIDA BUILDING CODE. PLEASE SUBMIT SPRINKLER SYSTEM DRAWINGS. PLANS EXAMINER ELECTRIC COMPLETE 3110/2016 5/412016 514/2016 Comment: PLANS EXAMINER MECHANICAL INCOMPLETE Carl Peterson 312112016 3/18/2016 Comment: PLEASE SHOW A BALANCED SYSTEM. PLANS EXAMINER PLUMBING INCOMPLETE Greg Smyth 3/21/2016 Comment: PLEASE SHOW A PLUMBING PAGE WITH PROPER ISOMETRICS FOR SANITARY AND POTABLE WATER DISTRIBUTION PER SECTION 107.3.6 FLORIDA BLD CODE 2014 3/2112016 Comment: PLEASE SHOW HI LO DRINKING FOUNTAINS PER TABLE 403.1 FL PLUMBING CODE 2014 AND FL ACCESSABILITY CODE 2014 SECTION 211 PLANS EXAMINER REVIEW COMPLETE William Durden 3/1712016 4129/2016 4129/2016 Comment: ZONING REVIEW INCOMPLETE Lydia Galbraith 2126/2016 2/29/2016 Comment: PLEASE PROVIDE A COPY OF THE HEALTH DEPARTMENT PERMIT FOR THE SEPTIC. 2/29/2016 Comment: PLEASE PROVIDE (3) FLOOR PLANS AND SITE PLANS STAMPED BY THE HEALTH DEP. FOR APPROVAL. PLEASE INDICATE ON THE SITE PLAN THE DRAIN FIELD AND LOCATION OF THE SEPTIC. 2/29/2016 Comment: PLEASE BE AWARE THAT THE FENCE REQUIRES A SEPARATE PERMIT. 212912016 Comment: PLEASE BE AWARE THAT INDUSTRIAL AVE ONE IS NOT AN OPEN ROAD, AN ACCESS OR EXIT WILL NOT BE ALLOWED UNTIL THE ROAD HAS BEEN IMPROVED. A GATE WILL NOT BE ALLOWED. 2129/2016 Comment: THE HANDICAP PARKING SPACES DON'T MEET THE MIN. REQUIRED SIZE. A HC PARKING IS 12, BY 18, WITH A V ACCESS AISLE. SEE ST LUCIE COUNTY LAND DEVELOPMENT CODE CHAPTER 7.06.02 B. 2129/2016 Comment: PLEASE INDICATE THE DRIVEWAY ON THE SITE PLAN. 212912016 Comment: PARKING SPACES SHOULD NOT BE LOCATED ON THE DRIVEWAY. 2/29/2016 Comment: A ZONING COMPLIANCE APPLICATION IS REQUIRED TO BE SUBMITTED BEFORE FINAL INSPECTION CAN BE APPROVED. Comment: PLEASE BE AWARE THAT IMPACT FEE RETAILIWHOLE SALE WILL BE APPLICABLE FOR THE ENCLOSED 2/29/2016 AREA FOR THE OFFICE.THE OPEN COVERED AREA AND THE STORAGE AREA WILL BE CONSIDERED ACCESSORY TO THE MAIN USE AND THERE FOR WILL NOT RECEIVE IMPACT FEES. 3/2/2016 Comment: SEE ATTACHED EMAIL FROM PATRICK DAYAN FOR REQUIREMENTS UPDATE DRIVEWAY. 3Y212016 Comment: PLEASE BE AWARE THAT ABOVE COMMENTS ONLY REFLECTS THE ZONING REVIEW. THE PLANS EXAMINER MIGHT HAVE ADDITIONAL COMMENTS. 3/14/2016 Comment: 3114/16 CONTRACTOR PICKED UP ONE SET OF PLANS TO GO TO HEALTH DEP. Planning & Development Services Building & Code Regulation Division 2300 Virginia Avenue Fort Pierce, FL 34962 Phone:(772)462.2172 Fax:(772)462.6443 Address: 2902 Industrial 33 St City / State / Zip: Fort Pierce, FI 34946 Parcel#: 1428-702-1501-000/1 Zoning: IL APPLICATION INFORMATION Permit Number: 1602-0403 Permit Type: COMMERCIAL RENOVATION Contractor Name: Business Name: Business Addr: City / State / Zip: David A Ricks Schopke Enterprises Inc 1620 Tangerine St Melbourne, FI 32901 REVIEW COMMENTS SCANNED BY St. Lucie Countv 1 Owner(s): Creative Systems Uc Jurisdiction: SAINT LUCIE COUNTY Lot#: 4 Block: 65 Stories: Automatic Sprinkler System? No Fax Number: 321-723-1294 Email: Info@ B revard g ro uti n g. Co m Review Tvoe Status Reviewed By Date Started Date Completed Date Released ADDRESSING ASSIGNMENT COMPLETE Lydia Galbraith 311/2016 3/1/2016 3/112016 Comment: DOCUMENTS MISSING PENDING 2/29/2016 Comment: PLUMBING SUB AGREEMENT 3/1/2016 Comment: SUBMIT A VEGETATION REMOVA11EXEMPTION APPLICATION WITH A LANDSCAPE PLAN OF WHAT IS ON LOCATION. FRONT COUNTER REVIEW COMPLETE Karen Nielsen 2/2312016 2/2312016 212312016 Comment: PE REVIEW COMMENTS (2) COMPLETE William Durden 4/29/2016 6/412016 514/2016 Comment: PE REVIEW COMMENTS (2) INCOMPLETE Carl Peterson 4129/2016 Comment: PE REVIEW COMMENTS (2) INCOMPLETE Greg Smyth 5/112016 Comment: PE REVIEW COMMENTS (3) INCOMPLETE William Durden 51512016 4/29/2016 Comment: PLEASE SHOW A BALANCED SYSTEM. 5/212016 Comment: PLEASE SHOW HI LO DRINKING FOUNTAINS PER TABLE 403.1 FL PLUMBING CODE 2014 AND FL ACCESSABILITY CODE 2014 SECTION 211 Planning & Development Services Building & Code Regulation Division 2300 Virginia Avenue Fort Pierce, FL 34982 Phone:(772)462.2172 Fax:(772)462.6443 REVIEW COMMENTS 2 5/2/2016 Comment: PLEASE SHOW A PLUMBING PAGE WITH PROPER ISOMETRICS FOR SANITARY AND POTABLE WATER DISTRIBUTION PER SECTION 107.3.5 FLORIDA BLD CODE 2014 515/2016 Comment: PLEASE SHOW VEHICLE BARRIER LOCATIONS ON PLANS. AT EACH COLUMN AND DRIVE LANE. AS PER SECTION 1607.8.3 OF THE 2014 FLORIDA BUILDING CODE. 5/5/2016 Comment: A3 OCCUPANCY LOAD OF GREATER THAN 300 REQUIRES A SPRINKLER SYSTEM. PLEASE SEE 903.2.1.3 OF THE 2014 FLORIDA BUILDING CODE. PLEASE SUBMIT SPRINKLER SYSTEM DRAWINGS. PLANS EXAMINER ELECTRIC COMPLETE 3/1012016 5/412016 5/4/2016 Comment: PLANS EXAMINER MECHANICAL INCOMPLETE Carl Peterson 3121/2016 3/18/2016 Comment: PLEASE SHOW A BALANCED SYSTEM. PLANS EXAMINER PLUMBING INCOMPLETE Greg Smyth 3/21/2016 Comment: PLEASE SHOW A PLUMBING PAGE WITH PROPER ISOMETRICS FOR SANITARY AND POTABLE WATER DISTRIBUTION PER SECTION 107.3.5 FLORIDA BUD CODE 2014 312112016 Comment: PLEASE SHOW HI LO DRINKING FOUNTAINS PER TABLE 403.1 FL PLUMBING CODE 2014 AND FL ACCESSABILITY CODE 2014 SECTION 211 PLANS EXAMINER REVIEW COMPLETE William Durden 3117/2016 412912016 4/2912016 Comment: ZONING REVIEW INCOMPLETE Lydia Galbraith 212612016 2129/2016 Comment: PLEASE PROVIDE A COPY OF THE HEALTH DEPARTMENT PERMIT FOR THE SEPTIC. 2/29/2016 Comment: PLEASE PROVIDE (3) FLOOR PLANS AND SITE PLANS STAMPED BY THE HEALTH DEP. FOR APPROVAL. PLEASE INDICATE ON THE SITE PLAN THE DRAIN FIELD AND LOCATION OF THE SEPTIC. 2129/2016 Comment: PLEASE BE AWARE THAT THE FENCE REQUIRES A SEPARATE PERMIT. 2/29/2016 Comment: PLEASE BE AWARE THAT INDUSTRIAL AVE ONE IS NOT AN OPEN ROAD, AN ACCESS OR EXIT WILL NOT BE ALLOWED UNTIL THE ROAD HAS BEEN IMPROVED. A GATE WILL NOT BE ALLOWED. 2/29/2016 Comment: THE HANDICAP PARKING SPACES DON'T MEET THE MIN. REQUIRED SIZE. A HC PARKING IS 12' BY 18' WITH A V ACCESS AISLE. SEE ST LUCIE COUNTY LAND DEVELOPMENT CODE CHAPTER 7.06.02 B. 2/29/2016 Comment: PLEASE INDICATE THE DRIVEWAY ON THE SITE PLAN. 2/29/2016 Comment: PARKING SPACES SHOULD NOT BE LOCATED ON THE DRIVEWAY. 2/2912016 Comment: A ZONING COMPLIANCE APPLICATION IS REQUIRED TO BE SUBMITTED BEFORE FINAL INSPECTION CAN BE APPROVED. Comment: PLEASE BE AWARE THAT IMPACT FEE RETAIL(WHOLE SALE WILL BE APPLICABLE FOR THE ENCLOSED 2129/2016 AREA FOR THE OFFICE.THE OPEN COVERED AREA AND THE STORAGE AREA WILL BE CONSIDERED ACCESSORY TO THE MAIN USE AND THERE FOR WILL NOT RECEIVE IMPACT FEES. 3/2/2016 Comment: SEE ATTACHED EMAIL FROM PATRICK DAYAN FOR REQUIREMENTS UPDATE DRIVEWAY. 312/2016 Comment: PLEASE BE AWARE THAT ABOVE COMMENTS ONLY REFLECTS THE ZONING REVIEW. THE PLANS EXAMINER MIGHT HAVE ADDITIONAL COMMENTS. 3/1412016 Comment: 3/14/16 CONTRACTOR PICKED UP ONE SET OF PLANS TO GO TO HEALTH DEP. i Planning & Development Services Building & Code Regulation Division 2300 Virginia Avenue Fort Pierce, FL 34982 Phone:(772)462.2172 Fax:(772)462.6443 PROPERTY INFORMATION Address: 2902 Industrial 33 St City / State / Zip: Fort Pierce, FI 34946 Parcel M 1428-702-1501-000/1 Zoning: IL APPLICATION INFORMATION Permit Number: 1602-0403 Permit Type: COMMERCIAL RENOVATION Contractor Name: ,.,,.,.David A Ricks Business Name: Schopke Enterprises Inc Business Addr: 1620 Tangerine St City / State / Zip: Melbourne, FI 32901 REVIEWS AND COMMENTS Review Tvpe Status ADDRESSING ASSIGNMENT COMPLETE Comment: REVIEW COMMENTS SCANNED By St. Lucie County Page 1 Owner(s): Creative Systems Llc Jurisdiction: SAINT LUCIE COUNTY Lot#: 4 Block: 65 Stories: Automatic Sprinkler System? No Fax Number: 321=723-1`294 1 ` Email: Info@Brevardgrouti ng;Coin , Reviewed By Date Started Date Completed Date Released Lydia Galbraith 3/1/2016 3M12016 3M/2016 DOCUMENTS MISSING PENDING 2129/2016 Comment: PLUMBING SUB AGREEMENT • 3/1/2016 Comment: SUBMIT A VEGETATION REMOVALIEXEMPTION APPLICATION WITH A LANDSCAPE PLAN OF WHAT IS ON LOCATION. FRONT COUNTER REVIEW COMPLETE Karen Nielsen 212312016 2123/2016 212312016 Comment: • PLANS EXAMINER ELECTRIC INCOMPLETE 3/11/2016 Comment: EXITS LIGHTS NEEDED,E.M.LIGHTS NEEDED,EXITS AND E.M. CAN BE COMBO TYPE.WALT PRIDE SR. PLANS EXAMINER MECHANICAL INCOMPLETE Carl Peterson • 3/18/2016 Comment: PLEASE SHOW A BALANCED SYSTEM. PLANS EXAMINER PLUMBING INCOMPLETE Greg Smyth 3/21/2016 Comment: PLUMBING REVIEW CANNOT RESUME UNTIL ALL OCCUPANT LOADS ARE CORRECTED PER STRUCTURAL PLAN REVIEWER COMMENTS.PLUMBING FIXTURE REQUIREMENTS MAY CHANGE. 3/21/2016 Comment: PLEASE ADDRESS POTTY PARITY PER SECTION403.1.3 OF THE FLORIDA PLUMBING CODE 2014 3/2112016 Comment: PLEASE SHOW A PLUMBING PAGE WITH PROPER ISOMETRICS FOR SANITARY AND POTABLE WATER DISTRIBUTION PER SECTION 107.3.5 FLORIDA BLD CODE 2014 312112016 Comment: PLEASE SHOW HOT WATER TO ALL SINKS PER SECTION 607.1 FL PLUMBING CODE 2014 Planning & Development Services Building & Code Regulation Division 2300 Virginia Avenue - Fort Pierce, FL. 34982 Phone:(772)462-2172 Fax:V72)462.6443 REVIEW COMMENTS 3/21/2016 Comment: PLEASE SHOW SERVICE SINK PER TABLE 403.1 FL PLUMBING CODE 2014 3/21/2016 Comment: PLEASE SHOW HI LO DRINKING FOUNTAINS PER TABLE 403.1 FL PLUMBING CODE 2014 AND FL ACCESSABILITY CODE 2014 SECTION 211 PLANS EXAMINER REVIEW INCOMPLETE William Durden 3117/2016 3/17/2016 Comment: • FORMS AND DOCUMENTS SUCH AS PRODUCT APPROVAL, ENERGY CALC'S, AND MANUAL J'S MUST BE SUBMITTED IN TRIPLICATE. ONLY ONE COPY WAS SUBMITTED. 3117/2016 Comment: • OVER ALL DIMENSIONS ON PLANS DO NOT MATCH THE DIMENSIONS ON THE SURVEY PAGE. PLEASE CORRECT DRAWINGS TO REFLECT THE ACTUAL DIMENSIONS. Comment: • I HAVE CALCULATED SQUARE FOOTAGE FOR EACH OCCUPANCY AND THERE SEEMS TO BE A 3/17/2016 DIFFERENCE IN THE CALCULATION. PLEASE CHECK OVERALL SQUARE FOOTAGE AND THE CORRESPONDING AREA CALCULATIONS AS THESE CALCULATIONS WILL REFLECT IN THE OCCUPANCY LOADS FOR EACH AREA. 3/17/2016 Comment: • PLEASE NOTE SECTION C508 AND TABLE C508.4 OF THE 2014 FLORIDA BUILDING CODE. PLEASE SHOW ON PLANS REQUIRED SEPARATION OF OCCUPANCIES FOR THE RATED SEPARATION WALLS. 3/17/2016 Comment: • SEE NOTE FOR GROUP B OCCUPANCY MAXIMUM EXIT DISTANCE REFERS TO F-2 OCCUPANCY. PLEASE SEE SECTION C1016.2 OF THE 2014 FLORIDA BUILDING CODE. 3117/2016 Comment: PLEASE SHOW DETAIL FOR THE AUCTION STANDS. AND THE ADDITIONAL OCCUPANT LOAD IN THE A-3 LOCATION. Comment: • PLEASE SEE TABLE 503 ALLOWABLE BUILDING HEIGHTS AND AREA FOR THE A-3 LOCATIONS..A SINGLE 3/17/2016 STORY ASSEMBLY GROUP A-3 WITH TYPE V CONSTRUCTION UN -SPRINKLED ALLOWS UP TO 6000 SQUARE FEET. AREA CALCULATIONS FOR THE A-3 LOCATION SHOWS 8752 SQUARE FEET. 3117/2016 Comment: • PLEASE SUBMIT 3 COPIES OF REFLECTIVE CEILING PLANS. 3/17/2016 Comment: • PLEASE SHOW DETAIL FOR CONCRETE OVERLAY LOCATED AT OFFICE AREA. 3/1712016 Comment: • PLEASE SHOW ALL OCCUPANCIES AND OCCUPANCY LOAD CALCULATIONS ON THE PLANS. 3/17/2016 Comment: • PLEASE SEE SECTION C1010.7 OF THE 2014 FLORIDA BUILDING CODE. RAMPS SHALL HAVE LANDINGS AT THE BOTTOM AND TOP OF EACH RAMP ENTRANCE. 3117/2016 Comment: • PLEASE SHOW DETAIL FOR REINFORCED CONCRETE RAMP. 3117/2016 Comment: • PLEASE SEE SECTION 1003.5 ELEVATION CHANGE FOR THE CONCRETE RAMP LOCATIONS OF THE 2014 FLORIDA BUILDING CODE. , Comment: • PLEASE NOTE THAT THE COMMENTS ARE FOR THE CLARIFICATION OR CORRECTION OF THE 3/17/2016 SUBMITTED DOCUMENTS. ADDITIONAL REVIEW MAY BE REQUIRED AFTER SUBMITTING CORRECTED DOCUMENTS. ZONING REVIEW INCOMPLETE Lydia Galbraith 2/2612016 2129/2016 Comment: PLEASE PROVIDE A COPY OF THE HEALTH DEPARTMENT PERMIT FOR THE SEPTIC. 2/2912016 Comment: PLEASE PROVIDE (3) FLOOR PLANS AND SITE PLANS STAMPED BY THE HEALTH DEP. FOR APPROVAL. PLEASE INDICATE ON THE SITE PLAN THE DRAIN FIELD AND LOCATION OF THE SEPTIC. 2/2912016 Comment: PLEASE BE AWARE THAT THE FENCE REQUIRES A SEPARATE PERMIT. 2/29/2016 Comment: PLEASE BE AWARE THAT INDUSTRIAL AVE ONE IS NOT AN OPEN ROAD, AN ACCESS OR EXIT WILL NOT BE ALLOWED UNTIL THE ROAD HAS BEEN IMPROVED. A GATE WILL NOT BE ALLOWED. 2/29/2016 Comment: THE HANDICAP PARKING SPACES DON'T MEET THE MIN. REQUIRED SIZE. A HC PARKING IS 12, BY 18, WITH A V ACCESS AISLE. SEE ST LUCIE COUNTY LAND DEVELOPMENT CODE CHAPTER 7.06.02 B. 2/29/2016 Comment: PLEASE INDICATE THE DRIVEWAY ON THE SITE PLAN. 2/29/2016 Comment: PARKING SPACES SHOULD NOT BE LOCATED ON THE DRIVEWAY. 2/29/2016 Comment: A ZONING COMPLIANCE APPLICATION IS REQUIRED TO BE SUBMITTED BEFORE FINAL INSPECTION CAN BE APPROVED. Comment: PLEASE BE AWARE THAT IMPACT FEE RETAILNJHOLE SALE WILL BE APPLICABLE FOR THE ENCLOSED 2/29/2016 AREA FOR THE OFFICE.THE OPEN COVERED AREA AND THE STORAGE AREA W ILL BE CONSIDERED ACCESSORY TO THE MAIN USE AND THERE FOR WILL NOT RECEIVE IMPACT FEES. 3/2/E016 Comment: SEE ATTACHED EMAIL FROM PATRICK DAYAN FOR REQUIREMENTS UPDATE DRIVEWAY. 3/2/2016 Comment: PLEASE BE AWARE THAT ABOVE COMMENTS ONLY REFLECTS THE ZONING REVIEW. THE PLANS EXAMINER MIGHT HAVE ADDITIONAL COMMENTS. Planning& Development Services REVIEW COMMENTS Building & Code Regulation Division 2300 Virginia Avenue Fort Pierce, FL 34982 Phone:(772)462.2172 Fax:(772(462.6443 3/14/2016 Comment: 3/14116 CONTRACTOR PICKED UP ONE SET OF PLANS TO GO TO HEALTH DER J Planning & Development Services Building & Code Regulation Division 2300 Virginia Avenue Fort Pierce, FL 34982 Phone:(772)462-2172 Fax:(772)462.6443 Address: City / State / Zip: Parcel #: Zoning: 2902 Industrial 33 St Fort Pierce, FI 34946 1428-702-1501-000/1 IL APPLICATION INFORMATION Permit Number: 1602-0403 Permit Type: COMMERCIAL RENOVATION CONTRACTOR INFORMATION Contractor Name: David A Ricks Business Name: Schopke Enterprises Inc Business Addr: 1620 Tangerine St City / State / Zip: Melbourne, FI 32901 REVIEWS AND COMMENTS Review Typ Status ADDRESSING ASSIGNMENT COMPLETE Comment: REVIEW COMMENTS SCANNED By St. Lucie COunty L Owner(s): Creative Systems LIC Jurisdiction: SAINT LUCIE COUNTY Lot#: 4 Block: 65 Stories: Automatic Sprinkler System? No Fax Number: 321-723-1294 Email: Info@ Brevardgrouting. Com Reviewed By Date Started Date Completed Date Released Lydia Galbraith 3/1/2016 3/1/2016 31112016 DOCUMENTS MISSING PENDING 2/29/2016 Comment: PLUMBING SUB AGREEMENT Comment: SUBMIT A VEGETATION REMOVALIEXEMPTION APPLICATION WITH A LANDSCAPE PLAN OF WHAT IS ON 311/2016 LOCATION. FRONT COUNTER REVIEW COMPLETE Karen Nielsen 2123/2016 2/23/2016 212312016 Comment: PLANS EXAMINER ELECTRIC INCOMPLETE 3/11/2016 Comment: EXITS LIGHTS NEEDED,E.M.LIGHTS NEEDED,EXITS AND E.M. CAN BE COMBO TYPE.WALT PRIDE SR. PLANS EXAMINER MECHANICAL INCOMPLETE Carl Peterson 3/18/2016 Comment: PLEASE SHOW A BALANCED SYSTEM. PLANS EXAMINER PLUMBING INCOMPLETE Greg Smyth Comment: PLUMBING REVIEW CANNOT RESUME UNTIL ALL OCCUPANT LOADS ARE CORRECTED PER STRUCTURAL 3/21/2016 PLAN REVIEWER COMMENTS.PLUMBING FIXTURE REQUIREMENTS MAY CHANGE. 3/21/2016 Comment: PLEASE ADDRESS POTTY PARITY PER SECTION403.1.3 OF THE FLORIDA PLUMBING CODE 2014 Comment: PLEASE SHOW A PLUMBING PAGE WITH PROPER ISOMETRICS FOR SANITARYAND POTABLE WATER 3/2112016 DISTRIBUTION PER SECTION 107.3.5 FLORIDA BLD CODE 2014 3/21/2016 Comment: PLEASE SHOW HOT WATER TO ALL SINKS PER SECTION 607.1 FL PLUMBING CODE 2014 S—�ewt�" G' Planning &Development Services Building & Code Regulation Division 2300 Virginia Avenue Fort Pierce, FL 34982 Phone:(772)462.2172 Fax:(772)462.6"3 REVIEW COMMENTS 2 3/21/2016 Comment: PLEASE SHOW SERVICE SINK PER TABLE 403.1 FL PLUMBING CODE 2014 3121/2016 Comment: PLEASE SHOW HI LO DRINKING FOUNTAINS PER TABLE 403.1 FL PLUMBING CODE 2014 AND FL ACCESSABILITY CODE 2014 SECTION 211 PLANS EXAMINER REVIEW INCOMPLETE William Durden 3/17/2016 3117/2016 Comment: • FORMS AND DOCUMENTS SUCH AS PRODUCT APPROVAL, ENERGY CALC'S, AND MANUAL TS MUST BE SUBMITTED IN TRIPLICATE. ONLY ONE COPY WAS SUBMITTED. 3/17/2016 Comment: • OVER ALL DIMENSIONS ON PLANS DO NOT MATCH THE DIMENSIONS ON THE SURVEY PAGE. PLEASE CORRECT DRAWINGS TO REFLECT THE ACTUAL DIMENSIONS. Comment: • I HAVE CALCULATED SQUARE FOOTAGE FOR EACH OCCUPANCY AND THERE SEEMS TO BE A 3/17/2016 DIFFERENCE IN THE CALCULATION. PLEASE CHECK OVERALL SQUARE FOOTAGE AND THE CORRESPONDING AREA CALCULATIONS AS THESE CALCULATIONS WILL REFLECT IN THE OCCUPANCY LOADS FOR EACH AREA. 3/1712016 Comment: • PLEASE NOTE SECTION C508 AND TABLE C508.4 OF THE 2014 FLORIDA BUILDING CODE. PLEASE SHOW ON PLANS REQUIRED SEPARATION OF OCCUPANCIES FOR THE RATED SEPARATION WALLS. 3/17/2016 Comment: • SEE NOTE FOR GROUP B OCCUPANCY MAXIMUM EXIT DISTANCE REFERS TO F-2 OCCUPANCY. PLEASE SEE SECTION C1016.2 OF THE 2014 FLORIDA BUILDING CODE. 3/17/2016 Comment: PLEASE SHOW DETAIL FOR THE AUCTION STANDS. AND THE ADDITIONAL OCCUPANT LOAD IN THE A-3 LOCATION. Comment: • PLEASE SEE TABLE 503 ALLOWABLE BUILDING HEIGHTS AND AREA FOR THE A-3 LOCATIONS. A SINGLE 3/17/2016 STORYASSEMBLY GROUP A-3 WITH TYPE V CONSTRUCTION UN -SPRINKLED ALLOWS UP TO 6000 SQUARE FEET. AREA CALCULATIONS FOR THE A-3 LOCATION SHOWS 8752 SQUARE FEET. 3117/2016 Comment: • PLEASE SUBMIT 3 COPIES OF REFLECTIVE CEILING PLANS. 3117/2016 Comment: •PLEASE SHOW DETAIL FOR CONCRETE OVERLAY LOCATED AT OFFICE AREA. 3/17/2016 Comment: • PLEASE SHOW ALL OCCUPANCIES AND OCCUPANCY LOAD CALCULATIONS ON THE PLANS. 3/17/2016 Comment: • PLEASE SEE SECTION C1010.7 OF THE 2014 FLORIDA BUILDING CODE. RAMPS SHALL HAVE LANDINGS AT THE BOTTOM AND TOP OF EACH RAMP ENTRANCE. 3/1712016 Comment: - PLEASE SHOW DETAIL FOR REINFORCED CONCRETE RAMP. 3/17/2016 Comment: • PLEASE SEE SECTION 1003.5 ELEVATION CHANGE FOR THE CONCRETE RAMP LOCATIONS OF THE 2014 FLORIDA BUILDING CODE. Comment: • PLEASE NOTE THAT THE COMMENTS ARE FOR THE CLARIFICATION OR CORRECTION OF THE 3/17/2016 SUBMITTED DOCUMENTS. ADDITIONAL REVIEW MAY BE REQUIRED AFTER SUBMITTING CORRECTED DOCUMENTS. ZONING REVIEW INCOMPLETE Lydia Galbraith 2126/2016 2/29/2016 Comment: PLEASE PROVIDE A COPY OF THE HEALTH DEPARTMENT PERMIT FOR THE SEPTIC. 2/29/2016 Comment: PLEASE PROVIDE (3) FLOOR PLANS AND SITE PLANS STAMPED BY THE HEALTH DEP. FOR APPROVAL. PLEASE INDICATE ON THE SITE PLAN THE DRAIN FIELD AND LOCATION OF THE SEPTIC. 212912016 Comment: PLEASE BE AWARE THAT THE FENCE REQUIRES A SEPARATE PERMIT. 2/29/2016 Comment: PLEASE BE AWARE THAT INDUSTRIAL AVE ONE IS NOT AN OPEN ROAD, AN ACCESS OR EXIT WILL NOT BE ALLOWED UNTIL THE ROAD HAS BEEN IMPROVED. A GATE WILL NOT BE ALLOWED. 2129/2016 Comment: THE HANDICAP PARKING SPACES DON'T MEET THE MIN. REQUIRED SIZE. A HC PARKING IS 12, BY 18, WITH A 5' ACCESS AISLE. SEE ST LUCIE COUNTY LAND DEVELOPMENT CODE CHAPTER 7.06.02 B. 2/2912016 Comment: PLEASE INDICATE THE DRIVEWAY ON THE SITE PLAN. 2/29/2016 Comment: PARKING SPACES SHOULD NOT BE LOCATED ON THE DRIVEWAY. 212912016 Comment: A ZONING COMPLIANCE APPLICATION IS REQUIRED TO BE SUBMITTED BEFORE FINAL INSPECTION CAN BE APPROVED. Comment: PLEASE BE AWARE THAT IMPACT FEE RETAIUW HOLE SALE WILL BE APPLICABLE FOR THE ENCLOSED 2129/2016 AREA FOR THE OFFICE.THE OPEN COVERED AREA AND THE STORAGE AREA WILL BE CONSIDERED ACCESSORY TO THE MAIN USE AND THERE FOR WILL NOT RECEIVE IMPACT FEES. 3/2/2016 Comment: SEE ATTACHED EMAIL FROM PATRICK DAYAN FOR REQUIREMENTS UPDATE DRIVEWAY. 3/2/2016 Comment: PLEASE BE AWARE THAT ABOVE COMMENTS ONLY REFLECTS THE ZONING REVIEW. THE PLANS EXAMINER MIGHT HAVE ADDITIONAL COMMENTS. Planning& Development Services REVIEW COMMENTS Building & Code Regulation Division 2300 Virginia Avenue Fort Pierce, FL 34982 Phone:(772)462.2172 Fax:(772)462-6443 3/14/2016 Comment: 3/14/16 CONTRACTOR PICKED UP ONE SET OF PLANS TO GO TO HEALTH DER