HomeMy WebLinkAboutFIRE DEPT PAPPERSSAINT LUCIE COUNTY FIRE DISTRICT
(,OUNTyO
PLAN REVIEW FORM
. 3`
rN
5160 N.W. Milner Drive
Port Saint Lucie, FL 34983
x y
Telephone:772-621-3322
�9f01�'
Fax: 772-621-3604
Web Address: www.slcfd.com
ScqN
St 4uCl@ C D U
Building Dept. ISLC FMO Permit #
Project Name Harbour Ridge Sales Center BLDG Permit It
Address 113396 NW Gilson Road
Contractor Proctor Construction Company
City Palm City
B-16-32
1511-0414
Address 2050 US Hwy 1 City Vero Beach
State FL Zip 32960 Telephone (772)234-8164
Architect/Engineer Peacock and Lewis & Planners LLC Telephone (561)626-9704
Occupancy Type Business Construction Type
Square Feet 1517
Occupant Load 13 per plans Number of Stories I Access Box Required Access Key Switch I
AFS Permit Required FAPermit Required FFP Permit
General Notes
r
1. An electronic copy of the construction documents submitted on a CD is required. The file format shall be .pdf only.
2. All revisions, including the electronic copy must be received prior to permitting.
3. The Fire Marshal requires 24 hour notice on all inspections.
4. The respective Building Department shall schedule all final inspections through the Fire Marshal's Office.
S. Failed inspections require payment of fee prior to rescheduling of further Inspections.
6. Penetrations through rated assemblies shall be of the proper UL design. Design criteria shall be submitted with the construction plans.
7. Fire alarm panels shall be located indoors within air conditioned space.
S. Plans and construction are subject to corrections In the field to maintain code compliance.
9. Automatic fan shutdown is required for HVAC systemis that exceed 2,000 cfm design capacity.
10. The Installation or Alteration of Fire Sprinklers, Fire Alarms, and Fixed Fire Protection Systems require a separate review and permit.
THE FLORIDA FIRE PREVENTION CODE, 2010 EDITION IS CURRENTLY ENFORCED.
BUILDINGS WITH LIGHT -FRAME TRUSS -TYPE CONSTRUCTION SHALL BE MARKED WITH APPROVED FIREFIGHTER SAFETY
WARNING SIGNS IN ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODES 69A-3.012 AND 69A-60.0081 PRIOR TO RECEIVING
A CERTIFICATE OF OCCUPANCY.
See General Notes Above and Required Revisions Below
1.The Installation of Fire Sprinkler, Fire Alarm, Systems require a separate review and permit.
2. Provide portable fire extinguishers from a license contractor.
Page of 1 Reviewed by TonyJerger Date 02/02/2016
ST. LUCIE COUNTY FINE IDISTRICT
FIRE PREVENTION BUREAU
Office of the Fire Marshal
SAINT LUCIE C®L1NTV FIRE DISTRICT
INSPECTION CHECK LIST
Telephone: (772) 621-3322
Fax: (772) 621-3604
FIRE WALLS
PENETRATIONS
HVAC/DAMPERS SMOKE TEST
SPRINKLERS UNDERGROUND HYDRO
SPRINKLERS ABOVEGROUND HYDRO
SPRINKLER FINAL
FIXED FIRE. SUPPRESSION SYSTEMS
FIRE ALARM FINAL
BUILDING FINAL
MISC. INSPECTIONS
"Our Family Serving Yours"
5160 N.W. Milner Drive, Port St. Lucie, Florida 34983-3392
Telephone: (772)_621-3400 o Fax: (772) 621-3500