April 19, 2016 Job Order #: 16-1253
SCANNED
CP Rankin, Inc. BY
4359 County Line Road St. Lucie Count,
Chalfont, PA 18914
RE: FIELD WITHDRAWAL RESISTANCE TESTING (TAS 105-11)
Advance Auto Parts # 9507
353 E. Prima Vista Blvd.; Port Saint Lucie, FL
Dear Sir or Madam:
Pursuant to your request, Florida Engineering & Testing, Inc. (FE&T) has performed a field
withdrawal resistance test in compliance with Testing Application Standard TAS-105 and the
Florida Building Code High Velocity Hurricane Zone at the above referenced site. The purpose of
our inspection was to determine the uplift capacity of the mechanical fasteners at the above
referenced project. FE&T is a Miami Dade Certified Testing Laboratory (Certification #14-
1022.01).
On April 13, 2016, our field representative visited the site and conducted ten (10) field withdrawal
resistance tests on the 8" long Firestone Heavy Duty fasteners into the steel deck. All tests were
found in compliance with the Florida Building Code and TAS-105. Enclosed find copies of TAS-
105 forms with test results.
The test results presented reflect the condition of the roof system at the -time of the test. These
results are time and sample dependent since roof conditions are continuously changing due to
exposure to the elements. All tests were conducted according to Dade County TAS-105 using a
calibrated Force -Test Fastener Tester Model No. SP2-2K (see attached calibration).
Florida Engineering & Testing, Inc. (FE&T) is an independent third party providing un-biased
testing information and results. FE&T is not affiliated with our client nor do we have any financial
interest in the project or determination of the test results.
Florida Engineering & Testing, Inc., appreciates the opportunity to be of service to you at this phase
of your project. If you have any questions or comments, please give us a call. It has been a pleasure
working with you and look forward to doing so in the near future.
Sincerely,
� y�Zo•lc
Mark A. Mesian6; P.E.
Floridwngineerihg & Testing, Inc.
Florida Reg. No.-48202
Certificate`af Authorization No. 6923
Attachments:
Field Withdrawal Resistance Test Results
Field Sketch
Comten Calibration
\� Q 'B
Quality �1 A � Iws ance
��� —I—,.
,4/19/16, Job Order # 16-1253
CP Rankin, Inc
Advance Auto Parts # 9507
353 E. Prima Vista Blvd.; Port Saint Lucie, FL:
DADE COUNTY
BUILDING CODE COMPLIANCE OFFICE
TESTING APPLICATION STANDARD TAS 105
FIELD WITHDRAWAL RESISTANCE TEST RESULTS
GENERAL INFORMATION:
Client Name: CP Rankin, Inc.
Job Address: Advance Auto Parts # 9507
353 E. Prima Vista Blvd.: Port Saint Lucie, FL
Contact Individual
at Job Site (if any):
TESTING AGENCY / EQUIPMENT INFORMATION:
FLO A
Note: The undersigned acknowledges that all testing has been conducted and results have been
reported in compliance with Dade County TAS 105.
Testing Agency Name: Florida Engineering & Testing, Inc. (Cert. # 6923)
Address: 250 S.W. 13'h Avenue
Pompano Beach, FL 33069
Telephone: (954) 781-6889
Fax: (954) 784=8550
Representative Name: Mark A. Mesiano, P.E.
Title: Professional Engineer (Florida Reg. No. 48202)
Signature:
yZv)C
Test Apparatus (General Description):
Force -Test Fastener Tester Model No. SP2-2K
Page -1
,4/19/16, Job Order # 16-125340
CP Ranldn, Inc. FLO A
Advance Auto Parts # 9507
353 E. Prima Vista Blvd.; Port Saint Lucie, FL:
BUILDING / ROOF SYSTEM INFORMATION: Area No.: 1
RoofArea Height: Height: 16 ft
RoofArea Dimensions: Length: 104 ft
Second Largest Dimension: 63 ft
Total Roof Area: 6,552 ft2
66 sq
Perimeter Area: 2,002 ft2
(See RASH 7)
BUILDING / ROOF SYSTEM INFORMATION: Area No.
RoofArea Height: Height: ft
RoofArea Dimensions: Length: ft
Second Largest Dimension: ft
Total Roof Area: ft2
sq
Perimeter Area: ft2
(see RAS117)
BUILDING / ROOF SYSTEM INFORMATION: Area No.
RoofArea Height: Height: ft
RoofArea Dimensions: Length: ft
Second Largest Dimension: ft
Total Roof Area: ft2
sq
Perimeter Area: ft2
(See RAS717)
Page 2
,4/19/16, Job Order # 16-1253�
CP Ranldn, Inc.
Advance Auto Parts # 9507
353 E. Prima Vista Blvd.; Port Saint Lucie, FL:
FASTENER INSTALLATION INFORMATION:
Is the fastener a self -driller? Yes [X] No. [ ]
0 FLO A
If yes, list the type of tool used for fastener installation: Electric Drill
Speed of Tool: 350-450 rp&s
TEST INFORMATION:
Number of Tests Conducted: n = 10
*See Section 8 TAS 105-98
*Note the locations ofall tests on 'Building Information "Detail 42, attached
Page - 3
4/19/16, Job Order # ki16-1253�
CP Rankin, Inc. FLO A
Advance Auto Parts # 9507
353 E. Prima Vista Blvd.; Port Saint Lucie, FL:
FIELD WITHDRAWAL RESISTANCE TEST RECORDING SHEET
Area No.: 1
(Refer to deck dimensions referred on Page No. 2)
Component to be secured:
Insulation [X ]
Membrane [ ]
Anchor or Basesheet [ ]
Woodblocking [ ]
Metal Profiles [ ]
Fastener Type: 8" Long Heavy Du
Fastener Manufacturer: Firestone
Predrilled: Yes [ ] No [X]
If Yes: Drill Bit Size: " diameter
Hole Depth: "
See Section 8 to determine number of tests (If drill is high tolerance include range in 1/1000" tolerance)
Sample No.
Plan Identi5er
Initial Failure Load Obt)
Field or Perimeter Area
1
1
517
Corner
2
2
576
Corner
3
3
529
Perimeter
4
4
586
Comer
5
5
503
Perimeter
6
6
537
Comer
7
7
539
Perimeter
8
8
557
Field
9
9
590
Field
10
10
561
Field
FLORIDA BUILDING CODE — TEST PROTOCOL HVHZ
Page — 4
(TAS) 105-11
4/19/16, Job Order # 16-1253#
CP Rankin, Inc.
Advance Auto Parts # 9507
353 E. Prima Vista Blvd.; Port Saint Lucie, FL:
STATISTICAL ANALYSIS:
Mean Failure Load:
Sample Standard Deviation:
Minimum Characteristic Resistance Force:
Go 5N�101'
FLO A
F = 549.5 lbf
SF = 29.4 lbf
F' = 537.3 lbf
Notes: I. Use of the results herein to determine the required number of fasteners for insulation attachment or an
acceptable anchor or base sheet fastener spacing, as outlined in RAS 117, shall utilize the minimum
characteristic resistance force (17% determined in compliance with Section 9 of TAS 105-98. No margin of
safety shall be applied to field withdrawal resistance test results determined in compliance with TAS 105-98.
Notes:
2. A safety of factor of 2 to 1 shall be applied to all results of laboratory testing.
3. The following pages shall be completed for each roof area and included with all Field Withdrawal Resistance
Test Recording Sheets.
ROOF AREA NO. 1
Insert Building and Parapet Heights
(Ijno Parapet Wall exist Insert "NIA)
<3 feet
16 feet
Ground Level
Building Information - Detail #1
Page — 5
* 8 9 *10 5
104'
LEGEND
Test Location
HVAC
® Scuppers
0 Vents
63'
FLORIDA ENGINEERING & TESTING, INC.
FIL A
FIELD
SKETCH
Approximate Dimensions - Not to Scale
Advance Auto Parts # 9507
353 E. Prima Vista Blvd.; Port Saint Lucie, FL
s
s