Loading...
HomeMy WebLinkAboutCERTIFIED TEST, ADJUST AND BALANCE REPORTSCANNED BY St. Lucie County CERTIFIED TEST, ADJUST AND BALANCE REPORT DATE: 03/30/17 PROJECT: ST. LUCIE COUNTY LOGISTICS - HYDRONIC BALANCE LOCATION: 3855 SOUTH FEDERAL HIGHWAY, FT. PIERCE, FLORIDA 34982 ARCHITECT: FPL SERVICES, LLC DESIGN ENGINEER: RGD CONSULTING ENGINEERS GENERAL CONTRACTOR: SEE CONTRACT DOCUMENTS MECHANICAL CONTRACTOR: FLORIDA MECHANICAL, LLC NEBB TAB CONTRACTOR: CERTIFIED TEST & BALANCE, INC. 1847 BANIGS ROAD MARGATE, FLORIDA 33063 DENNIS T. MIRANDA, PRESIDENT CERTIFICATION NUMBER: 3064 (561) 961-5068-PALM BEACH (954) 532-4772-BROWARD (954) 532-4774-FAX CERI+II=IED PROJECT: ST. LUCIE COUNTY LOGISTICS— HYDRONIC BALANCE LOCATION: 3855 SOUTH FEDERAL HIGHWAY, FT. PIERCE, FLOR1rDA 34982 THE DATA PRESENTED IN THIS REPORT IS A RECORD OF SYSTEM MEASUREMENTS AND FINAL ADJUSTMENTS THAT HAVE BEEN OBTAINED LN ACCORDANCE WITH THE, CURRENT EDITION OF THE NEBB PROCEDURAL STANDARDS FOR TESTING, ADJUSTING, AND BALANCING OF ENVIRONMENTAL SYSTEMS. ANY VARIANCES FROM DESIGN QUANTITIES, WHICH EXCEED NEEB TOLERANCES, ARE NOTED IN THE TEST —ADJUST —BALANCE REPORT PROJECT SUMMARY. NEBB CONTRACTOR: CERTIFED TEST & BALANCE, INC. REG. NO: NEBB 3064 CERTIFIED BY:. C DATE: 03/30/17 a n t Syr 4 Eli - SUBMITTED & CERTIFIED BY: BROWARDCO.NO.: 98—CI'B-833—W NEBB CONTRACTOR: CERTIFIED TFST & BALANCE, INC. TAB SUPERVISOR: DENNIS T. MIRANDA REG. NO.: NEBB 3064 DATE: 03/30/17 CCRTIFICD PROJECT: PSL LOGISTICS CHILLER DATA SHEET PAGE: 1 DATE: 3/29/77 CHILLER NUMBER CH-1 CH-2 MANUFACTURER TRANE TRANE - CAPACfIY 170.3 TON 170.3 TON MODEL NO RTAC 1854 RTAC 1854 SERIAL NUMBER U 16GO5385 U 16G05386 COOLER DESIGN MEASURED DESIGN MEASURED WATER TEMP ENT 52.9 46.4 52.9 46.3 WATER TEMP LVG 40 42.9 40 42.8 PRESS DROP FT 9.1 10 9.1 _ _ - 10 - GPM 342.7 359.2 342.7 359.2 CONDENSER DESIGN MEASURED DESIGN MEASURED WATER TEMP ENT AIR COOLED AIR COOLED WATER TEMP LVG AIR COOLED AIR COOLED PRESS DROP FT AIR COOLED AIR COOLED GPM- AIR COOLED AIR COOLED ELECTRICAL DESIGN MEASURED DESIGN MEASURED VOLTAGE TI-T2 460 478 460 478 VOLTAGES TI-T-3 460 477 460 477 VOLTAGES T2-T3 460 477 460 479 AMPERAGE TI 168/139 0/73 1681139 0/72 AMPERAGET2 168/139 0/76 168/139 AMPERAGE T3 168/139 0/75 168/139 0/77 Comments: Readings By: Fernando Franco CL{ RTIF�ILD PUMP DATA SHEET PROJECT: PSL LOGISTICS PAGE:2 DATE: 3/30/17 PUMP NO P-1 P-2 MFGR TACO TACO MODEL/SIZE C12510 / 3 X 2z C12510 / 3 X 214- IMPELLER 9.8 9.8 SERVICE DATA PRIMARY PRIMARY TEST RESULTS GPM FT HD GPM FT HD GPM FT HD DESIGN 340 90 340 90 ACTUAL 376 i. 73.5 375.2 73.9 DISCHARGE 82.5 83.1 SUCTION-- 9 9.2 - -� DIF'F PRESSURE 73.5 73.9 SHUT OFF HEAD 101 101 DISCHARGE 108.2 107.1 SUCTION 10 10.1 DIFF PRESSURE 98.2 97 MTR MFG BALDOR BALDOR FRAME TYPE 254JM 254JM HORSE POWER 15 15 RPM 1765 1765 DESIGN MEASURED DESIGN MEASURED DESIGN MEASURED VOLTAGE _ -- 460 477/479/ 480 460 460/477/ 478 AMPERAGE 18.1 9.4/9.9/ 10 -_ 16.1 9.8/9.7/ _. 9.6 - --- CERTIFIED PUMP DATA SHEET PROJECT: PSL LOGISTICS PAGE: 3 DATE: 3/30/17 - PUMP - NO CHWP-51 CHWP-52 MFGR TACO TACO MODEM/ C13007 / 4 X 3 C13007 / 4 X 3 -SIZE IMPELLER 7.5 7.5 SERVICE DATA SECONDARY SECONDARY TEST RESULTS GPM FT HD GPM FT HD GPM FT HD DESIGN 350 50 350 50 ACTUAL 325.5 57.8 337.1 53.9 DISCHARGE 147.8 144.2 SUCTION - 90 90.3 DIFF PRESSURE 57.8 53.9 SHUT OFF HEAD 56 56 DISCHARGE 149.2 148.3 SUCTION 90 90.4 DIFF PRESSURE 59.2 57.9 MTR MFG BALDOR BALDOR FRAME TYPE i 213JM 213JM- HORSE POWER 7.5 7.5 RPM 1770 1770 .DESIGN MEASURED DESIGN MEASURED DESIGN MEASURED VOLTAGE 460 477/478/ 460 460 480/479/ 478 AMPERAGE 9.5 5.4/6/ .5.7 9.5 /5.8/ 6 5.7 CERTIFIED Tk:S! & tBA;A?.1r..1_ Project: PSL LOGISTICS HEAT EXCHANGER DATA SHEET Date:3/30/17 Page:4 STYSTEM HX-I LOCATION BUILDING SERVICE CHILLED WATER MFGR CALMAC _ MODEL NUMBER 586-15-177 DESIGN MEASURED DESIGN `44EASURED DESIGN MEASURED PRIMARY GPM 340 375.2 WATER ENT F 40 40 WATERLVGF 54 48 m-,rm PRESSURE. 12 I 1 DELTA TEMP F 14 8 SECONDARY GPM 320 337.1 WATER ENT F 56 57 ,I WATER LVG F 42 42 Dr. fA PRGSSURE 12 7 DELTA TEMP F 14 15 Comments: 25% GLYCOL/WATER Readings By: Fernando Franco CLRTIFIL-D PROJECT: PSL Logistics MANUFACTURER: Taco FLOW STATION DATA SHEET PAGE: DATE: 3/31/17 COhA7ENTS : Readings By: CERTIFIED IE. 1 &. BALi lC IV PROJECT: PSL Logistics COOLING COIL DATA SHEET DATE: 3/31I17 PAGE: 6 SYSTEM AHU-1 - - AHU-2 - - -- AHU-3 MFGR TRANE TRANE TRANE DESIGN MEASURED DESIGN +' MEASURED DESIGN MEASURED GPM 94.7 94.7 94.7 90.7 10.6 11.1 WATER ENT F 42 44 42 44 42 44 WATER LVGF 56 54 56 55 56 55 AIR ENT DB F 77.2 70.8 77.2 71.2 77.8 70.9 AIR LVG DB F 55 54.2 55 53.9 55 517 OUTSIDE AIR 80 - 80 - 80 Comments: CERTIFIED IFai � !IAi��ANT L PROJECT: PSL Logistics COOLING COIL DATA SHEET DATE: 3/31/17 PAGE: 7 SYSTEM AHU-4 AHU-5 AHU-6 MFGR TRANE TRANE TRANE DESIGN MEASURED . DESIGN MEASURED DESIGN MEASURED GPM 42.8 43.8 12 12 12.4 12.8 WATER ENT F 42 44 42 44 42 44 WATER LVG F 56 54 56 55 56 55 AIR ENT DB F 78.6 71.8 77.3 72 79.2 71.9 AIR LVG DB F 55 54.2 55 53.1 55 53.4 OUTSIDE AIR - 80 80 80 Comments: CERTIFIED T; 'i I;, Ul!vI A IN C C PROJECT: PSL Logistics COOLING COIL DATA SHEET DATE: 3/31/17 PAGE: 8 SYSTEM AHU 7 - AHU 8 MFGR TRANE TRANS DESIGN MEASURED DESIGN MEASURED , DESIGN MEASURED! j GPM,. 7.3 7.7 62.3 64.4 WATER ENT F 42 44 42 44 WATER LVG F 56 52 56 54 AIR ENT DB F 78.8 71.8 78.8 71.8 AIR LVG DB F 55 54.2 55.3 54.2 OUTSIDE AIR - 80 = 80 Comments: iver'salfied Fluid Coutrols,me. 540111V1' tl"KAH M I F AAMMAk FL W: T M-= � nrwufivywid0ullanuNscoia PUMP SUBMITTAL JOB NAbTE: FP & L Logistics Bldg. TAG: CHWP Pl & 2 SUBMITTED BY: Dan Ellison MECHANICAL DATA: MODEL: QUANTITY: TYPE: Iiv1PF?LL FR DESIGN: IMPELLER DIAMETER: SEALJNG TYPE: DEARING LUBRICATIONS: SUCTION CONNECTION FLANGE. (SIZE I RATINgl: DISCHARGE CONNECTION FLANGE (SIZE / RATING): SHAFTSLEEVFS BASE PLATE: COUPLINGS: COUPLING GUARD; ROTATION: HYDRAULIC DATA: FLOW (GPM) TOTAL DYNAMIC HEAD (FT) PUMP EFFICIENCY (%) BHP AI' DUTY POINT SI-TL"C 01-F HEAD (FT) REQUIRED NPSH (FT) GENERAL MOTOR DATA: HORSEPOWER RPM VOL'TS'0/FiZ NEMA FRAME STZE ECLOSURE SF.RVTC.E FACTOR INSULATION CLASS PUMP DRY WEIGHT NOTES: Premium Efficient TEFL Motor 25% Glycol General Specifications Taco #C12510C 2 Close Coupled End Suction Bronze Enclosed 9.80" Mechanical Seal Grease 3" 175 PSIG 2 1!2" 175 PSIG Yes / Stainless Steel Yes Yes Yes N/A 340 GPM 2S% Glycol 90' TDH 78.5% 9.9 HP 107 FT 6 Ft 1511P Premium Efficient 1760 RPM 460/3/60 254T TF,FC 1.15 F 475 lbs. inIversilled Fluid 0011folSoNe. 54D111W 101HIERRACE 1 FT. WMFDDAIE. FL 3B991 RM 954-M-11E 1 FAX: 95449-M 1 dtitb3 all huaitr9 PUMP SUBMITTAL JOB NAME: FP & L Logistics Bldg. TAG: CFIWP S1 & 2 SUBMITTED BY: Dan Ellison MECIGAAAC.AL DATAc General Soeciiications MODEL: Taco 4CI3007 QUANTITY: 2 TYPE: Close Coupled Bed Suction i NIPELLER DESIGN: Bronze Enclosed IivfPELLER DIAMETER: 7.50" SF,ALING TYPE: Mechanical Seal BEARING LUBRICATIONS: Grease SUCTION CONNEcriON FLANGE (SIZE / RATING): '41' 175 PSIG DISCHARGE CONNECTIONFLANGE (SIZE / RATING): 3" 175 PSIG SHAFT SLEEVES Yes l Stainless Steel BASF PLATE: Yes COUPLINGS: Yes COUTLING GUARD: Yes ROTATION: N/A HYDRAUldC: DATA FLOW (GPM) 350 GPM TOTAI. DYNAMIC HEAD (FT) 50' TDF1 PUMP EFFICIENCY (°K) 79% BfIP :A'I' DUTY POINT 6.7 LIP SH17 OFF HEAD (FT) 56 FT REQUIRED NI'SH (FT) 6 Ft GENERAL. MOTOR DATA: HORSEPOWER 7 Il2 IN Premium Efficient 1UPD•1 1760 RPM VOLTS/0114Z 460/3/60 NE MA FRAME SIZE 2I3T ECLOSURE TEFL SERVICE FACTOR 1.15 1VSULATION CLASS F PUMP DRY UPTIGHT 240 lbs. NOT]GS: Premium Efficient TEFL: Motor FLU- F=Wled by Tram U..S:eic./Mstallad by Equip~SuhmlW - -- Page4oi21 Oftia Mares 26:2016 31C•t tics FP - - - - -- CO teChanger Performance Data -Performance ma AHU<k AHU 3 AHU•4` ; AHU-5 ANU•6 AHU=7 Tags AHU•2. . Unfflevel0 Nons - _.. - -- -'. PcGludn 149.875 108,250, 117500 113.250: _ 108.250 108.250, Leri tfi n 125.500 . '44.000 80.000_ -' :72.000t .. 44.000 '44,000: Width n R( iif Wei btOb - ' ` ` 6282.9' 1094.5 - - 2348 6 2068.6-1133.7 .1014;5' _ - - dnstalleH.wai bt b 5478.2 ', •1127.2 2464.9 2162,' 1178.1 1047:3 _ n tbfled.0ow c(m 22000'. ' 2500: 8000 5000 . 2600 1600 Stu inlit:1 viei ht (Ib _- - . 1:165:0 243:5. 42B.0 387.0 224.0 203.0 Stii io s lit2 rieI ht lb _ 11722 327.4 754.7 - _ 378.3 328.5 409.0 Shi iQ s Ilt3wet ht (to). 349:0 490.0 1127.0` 991.3 991.0 471.0 - Shipping it 41W ht Ibl' - s 2537.0 -, '= _ ' • - -- _ " - - - Fen section, - #4 - #4 - -. rr4 - 94- Rasition . Position W dnt - : narrf _ 22000, 2500 _. 9004 - BD00 - 2600 -' .1600 - ES OverallloW in -20Y 1:OD0 1.000 - '2.000__ 2.000 - 1.3D0 1.300 TotalstaGo ressure in H2O 2:032 - 3:508 - 3.468 3.623 2.228 2.908 _ : 1.300 2.855 .. . 1.300 Fan pressore crop tin(H2p - 1:000 1.334 2,199 _ _ _ - 3071 189D - Fanoutletveioci .. in, 3168- .I.. - 3100' - -I 1460 - 1743 3918 . 3046- .S eed m - h_ -- - . . 2965 8.950! - - 6.709 - 2.683 - . 1.225 Total brokehcrse r." _ .1S.075 . '� '52.47 - 44.44 - 54;67 Unit static.el8cien % - 46.74 46.63 . 55.30'- Outlet area A' - - 6.95 6o 60 60 60 Motor heriz,(Hzl 60 60 --- Discharge 1 to -face velocf itlmin - 1636 _-_• 1264 1354 - '^ • Discharge I Lo- ressuredrop kin H2O) .334 0.199 0.228 Discfia-alto -area :ft __.-, - -1.53._ . 7.12 5.91 --- Access`secUon _ ._"' Section len h:m, 19.000 19.000 , 19.0D0; 19:000` 19.000 19000 =: Call section' - #2_ _ - #2 - _: #Z _ -. #2 #2 #2 - ' Position. Coo ormancealrflow cfm' i rformaren 22D00 `- 2500 9000 8000 2800: "00 . Coiffe s l): _._ _ "- 56.89 4.51 20.81 16.81- 6.11- _ 4.51 Col (ace velocit tumin 387 -: 554" _. ' 432 - - 478 426' 354 Coil section air tessure:dr `, in H2O ,_-.= 0.284 0.928'. 0.462< 0.528 0.606 - 0.486 Coi1.n in me ht (Ib) - _ -, 574-7 10t.4 284,5 --: 245,0- -` 126.6- 102.4 ' Coil inatalled:wei -ht Ib)1 `77D(0'. _ 139.1 _ 400.6. 340.9- .171.0 . 135.2 To or sin ie coil d Wei hl. lb _ 281.4 _ 101.4 2B4.5 245!0 126.E 102 4 Middle or bodom`coil we ht. ib - 287.4 - Leavina d tiulb� 55.00' - - 55.00 _--- 55.00,--- 55.00 ' - 55.00. 55.00 Leavin viet bulb F : 54.04 ; 5C81 54.24' S4.31' S4.84 - 54.79. _ EnteringIdry bulbb -.`' 77.20: TTa-o _ - 78.60, - ., 77.30. ` 7920- - : 78.80 : Enterio wetOUlb. F 8420 64.70 65.30 __ 6420___ 65:80 65.40 Ftuki. - - --_ - - Water - Water. Water Water' Water '.Water �_.. - Enterirt fluid temperature F)' - 4200 42.00 42.00_.- 4200 _'. 4200• .. :4IN -_ Leavin fluid tem wr$( 56.00 56.00 56.00 - ' 68:00- 56.00 56.00 Flutdlem lure rise. . _ 74.00` `- ! 14.00 . _ _ 14.00: .14.00 14.00. 14.0(I O. - -: Standard fluid flow rate, m -�- 94.71 a 10.60, 42.79 33.59 _ _ . 12-39.- = 7,34 Fluid: essbre�dr ft H2O , 5.85 - 0.88 -"- 3.52. _ . 2.42 _ : '0.83 0.46 _ F.luld vatocil ftls 2,90" _ . 121 "- 7-16 1:86 • 1.06 _ 0.84 23.35 3.91 . 13188 - 11.47, . •'' &31' ca citv'(MBh): 537.07.-_: 62.70 233 75• .196.17 69:27 41.91 :Sensible Total>ca aCit : M8h 665.38 74.48 300.61 235.94 87.04- Alrmixin 'oection FLD=FunU~bylrene US rno/resraned by EgWpm ga.IMN. Pape if dal0 Odrers _ ma+eb M 2016 Tics FPL - - - ..acv •aw o - AHUrB Ja s _ Gail ' i wei ht Ib a022 Coil.inatalled we fit( Ib - 581.8 402.2 T or sin le7(41 d ':wel t Ib Geavin id ';:bulb : 53.27 _ _ Leavin wetbutb: F) _ EMeri d' bulb' E1 78.80 Emedn wetbulb' F `-.. 6550 _ Fluid t e_ _ Water:_ Enterin-'fluidteM etature : -. . _ "42.00 _ Lemin 'fluid'lem - rab)re F' S6:00 Fluid tem eretUm rise 14A0' :Standard fluid flow, rate . m ___.62:50_ FlUldL ressuie dro ft H2O 5.93. Fluid.velock 6rs'. - 261 21 Fluid volume all - - . Sensible:ca acl Mab - .1 323A8 Total cs ac' MBti AlIr, mixing section Posmon Opering.1 back -air8aw c(M , 11.1500 opening 1 tront-airflow" cfm _ 71500 O enln I;1 - at OW cfm " _ 22M :0 eni :1 back -area. ft 10.36- O -eni .1 front -.area, _.ft - - `. 29:03 , . _ O eni 1 t -area (s 10.36 O enfn 1 back -face wilac'- , tllminl -_ 1'110_- -_ O..eniri 1fa�evetocl : 1tlMiN .- _ ..... '212 O ntno' 1 back - rew pe d in H20: 0.103 . O anin 1 to- -- reseure dra in H2O) 0.004.. Back inlet e Ducted To inlet. _e ---'Ducted. -- GreatestentlY':PD n H2O 0:.103% _. Filter condmon - - -- Mid-life- ..._- .— FllterairfloMl cfm _ _ 11500 _ Fllterarea S It __ 0 - _- Filter race delod (ft/min - --:_.. 230- .. Fiiterp ressure,dro in NZUL 0.692 Total'c ,�section.Pressuradro In'H2O :0.795. - aow .. — s':r PE$ 161ATlQNS' *� i) Y ACU AIR CONDITIONING UNIT HPACU HEAT PUMP AIR CONDITIONING UNIT AHU AIR HANDLING UNIT HWR HEATED WATER RETURN B.S. BIRD SCREEN HWS HEATED WATER SUPPLY BDD BACK DRAFT DAMPER ID INSIDE DIAMETER BHP BRAKE HORSEPOWER INAC INACCESSIBLE CCW COUNTER CLOCKWISE LAT (DB) LEAVING AIR TEMP. (DRY BULB) CD CEILING SUPPLY DIFFUSER LAT (WB) LEAVING AIR TEMP. (WET BULB) CEG CEILING EXHAUST GRILLE LD LINEAR DIFFUSER CFLA CORRECTED FULL LOADAMPS LWT LEAVING WATER TEMPERATURE CFM CUBIC FEET PER MINUTE MAT MIXED AIR TEMPERATURE CHWR CHILLED WATER RETURN MAU MAKE-UP AIR UNIT CHWS CHILLED WATER SUPPLY MAX MAXIMUM CRG CEILING RETURN GRILLE MIN MINIMUM CW CLOCKWISE NAP NOT APPLICABLE CWR CONDENSER WATER RETURN OBD OPPOSED BLADE DAMPER CWS CONDENSER WATER SUPPLY OD OUTSIDE DIAMETER DID DIRECT DRIVE OSA OUTSIDEAIR DMPR DAMPER RA RETURN AIR DNA DATA NOT AVAILABLE REO'D REQUIRED DNG DATA NOT GIVEN RH RELATIVE HUMIDITY DNL DATA NOT LISTED RPM ROTATIONS PER MINUTE DNT DATA NOT TAKEN RTU ROOFTOP UNIT DP DIFFERENTIAL PRESSURE SA SUPPLY AIR DT DIFFERENTIAL TEMPERATURE SF SAFETY FACTOR DWDI DOUBLE WIDTH DOUBLE INLET SLOT SLOT DIFFUSER EAT (DB) ENTERING AIR TEMP. (DRY BULB) SP STATIC PRESSURE EAT (WB) ENTERING AIR TEMP, (WET BULB) SWDI SINGLE WIDTH DOUBLE INLET ECR EGG CRATE RETURN SWRG SIDE WALL RETURN GRILLE EF EXHAUST FAN SWSG SIDE WALL SUPPLY GRILLE ESP EXTERNAL STATIC PRESSURE SWSI SINGLE WIDTH SINGLE INLET EWT ENTERING WATER TEMPERATURE SWSR SIDE WALL SUPPLY REGISTER F.D.l S.D. FIRE I SMOKE DAMPER T.P. THERMALLY PROTECTED FCU FAN COIL UNIT TSP TOTAL STATIC PRESSURE FH FUME HOOD TSTAT THERMOSTATS OR SENSOR FLA FULL LOAD AMPS TYP TYPICAL FPS FAN POWERED BOX V.D. VOLUME DAMPER FPM FEET PER MINUTE VAV VARIABLE AIR VOLUME.. GPM GALLONS PER MINUTE VFD VARIABLE FREQUENCY DRIVE HP HORSEPOWER WSHP WATER SOURCE HEAT PUMP W ml CERTIFIED INSTRUMENT CALIBRATION DATA SHEET INSTRUMENTT SERIAL ' DATE DATES OF USE UMBER ' , CALIBRATED FLUKE902 IS160139 09/02/16 03/30/17 VOLTAGE/AMPERAGE SHORTRIDGE ADM- M95657 02/05/17 03/30/17 860 FLOO W HOOD SRIMPOMT-100 A122E505P 01/12/17 NA ROTATIONAL SPEED EXTECH AN-3W 1003375 03/22/17 NA AIR VELOCITY MEASUREMENT SHORTRIDGEBDM- W98051 09/02/16 NA 300 WATER FLOW MEASUREMENT