HomeMy WebLinkAboutBASE SHEET ATTACHEMNT CALCULATIONSForensic Engineering Consultants, Inc. BASE SHEET ATTACHMENT CALCULATIONS Project Name Rosser Library Report No.: TRS-BS-16.001 Project Address 2950 SW Rosser Boulevard Port St. Lucie, FL - 34953 Deck Substrate Steel Insulated SCANNED Mean Roof Height 16.0 Feet Configuration Low Slope BY Roof Area (Approx.) 18733 Sq.Ft. Category III St, LUCIe COU"ty Roof Width 107.0 Feet Exposure Condition C Perimeter Width 6.4 Feet Building Type Enclosed Parapet Height 4.0 Feet Base Wind Speed 180 mph Slope V 0.0 Slope H 12.0 Slope Angle° 0.00 Uplift Pressures q� = 0.00256 K� Kr Kd V2 P ' = q, (GCP - GCP;) qz K. Kn Kd V GCP GCP; COMB FAST S OR OMM 0.85 180 -1.00 0.18 Field -1.80 0.18 Perimeter ARE THE RESPONSIBILlf Y OF THE -1.80 0.18 Corner Field CONTRAq•�OR OF R 1.95 psf P1 asd -43.17 psf THESE PLANS AND ALL PROPOSED WORK Perimeter P2un.-120.72 psf P2asd -72.43 psf ,` ARE SUBJECT TO ANY CORRECTIONS Corner P3 un.-120.72 psf P3 asd -72.43 psf REQUIRED BY FIELD INSPECTORS THAT Proposed System Johns Manville Modified Bitumen SBS R&WeNMUM68IMORDER TO =m Product Approval No. FL2948-R10 (Page 17 of 48) System'G@{WITH ALLAPPLICA®LE CODES.'' System Design Pressure -60 psf Fasteners-UltraFast Fasteners or All Purpose Fasteners with UltraFast Metal Plates Base Sheet Width 39 inches Side Lap 4 inches Net Width 35 inches Fastener Spacing in Lap of Base Sheet 9 inches # Rows 1 Fastener Spacing in Field of Base Sheet 18 inches # Rows 2 Min. Characteristic Resistance Force -65.63 Ibf Verify with TAS-105 Tests Fastener Spacing {(MCRF/P;) x 144)/Row Spacing No. of Rows of Fasteners 3 4 5 6 Field Fastener Spacing 18.76 25.02 31.27 37.53 Perimeter Fastener Spacing 11.18 14.91 18.64 22.37 Corner Fastener Spacing 11.18 14.91 18.64 22.37 RECOMMENDED BASE SHEET ATTACHMENT PATTERN Field 1 row in the laps at 9 inches o.c. 2 rows in the center of the sheet at 18" o.c. Perimeter 1 row in the laps at 9 inches o.c. 2 rows in the center of the sheet at 11" o.c. Corner 1 row in the laps at 9 inches o.c. 2 rows in the center of the sheet at 11" o.c. These calculations have been done in accordance with ASCE 7-10 per the Florida Building Code (2014), based on the information provided by the contractor. The roof system must be installed in accordance with the FBC and the manufacturer's recommendations. b�� -00 ST. LUCirF• C UNTY BUIL)02T . DMSIO REVIEWED FACOLANiSincerely REVIEIED F re is En gi eying Consults 1 q RMIT MUST BE KEPT ON 70B 1// N O INSPECTION WILL BE hZADE. R. N. Rapp n, P.E. �I Principal Engineer Florida Registration No. 46696 Forensic Engineering Consultants, Inc. (CA #8265), P.O.Box 970034, Boca Raton, FL - 33497 Ph (561) 901 8490 Fax (561) 218 3830 _ � f Forensic Engineering Consultants, Inc. BASE SHEET ATTACHMENT CALCULATIONS Project Name Rosser Library Report No.: TRS-BS-16.001 Project Address 2950 SW Rosser Boulevard Port St. Lucie, FL - 34953 Deck Substrate Steel Insulated,' Mean Roof Height ' 16.0 Feet Configuration Low Slope Roof Area (Approx.) 18733 Sq.Ft. Category III Roof Width 107.0 Feet Exposure Condition C Perimeter Width 6.4 Feet Building Type Enclosed Parapet Height 4.0 Feet Base Wind Speed 180 mph Slope V 0.0 Slope H 12.0 Slope Angle' 0.00 Uplift Pressures q� = 0.00256 K, Ks Kd Vz P = q, (GCP - GCp;) qz K. Kt Kd V GCP GCP1 60.970 0.860 1.005 0.85 180 -1.00 0.18 Field -1.80 0.18 Perimeter -1.80 0.18 Corner Field P1 an -71.95 psf P1 asd -43.17 psf Perimeter P2an. -120.72 psf P2asd -72.43 psf Corner P3WL -120.72 psf P3asd -72.43 psf Proposed System Johns Manville Modified Bitumen SBS Roof System over Wood Decks Product Approval No. FL2948-R10 (Page 17 of 48) System No. S-70 System Design Pressure -60 psf Fasteners UltraFasf Fasteners or All Purpose Fasteners with UltraFast Metal Plates Base Sheet Width 39 inches Side Lap 4 inches Net Width 35 inches Fastener Spacing in Lap of Base Sheet 9 inches # Rows 1 Fastener Spacing in Field of Base Sheet 18 inches # Rows 2 Min. Characteristic Resistance Force -65.63 Ibf Verify with TAS-105 Tests Fastener Spacing {(MCRF/Pi) x 144}/Row Spacing No. of Rows of Fasteners 3 4 5 6 Field Fastener Spacing 18.76 25.02 31.27 37.53 Perimeter Fastener Spacing 11.18 14.91 18.64 22.37 Comer Fastener Spacing 11.18 14.91 18.64 22.37 RECOMMENDED BASE SHEET ATTACHMENT PATTERN Field 'I row in the laps at 9 inches o.c. 2 rows in the center of the sheet at 18" o.c. Perimeter 1 row in the laps at 9 inches o.c. 2 rows in the center of the sheet at 11" o.c. Comer 1 row.in the laps at 9 inches G.G. 2 rows in the center of the sheet at 11" o.c. These calculations have been done in accordance with ASCE 7-10 per the Florida Building Code (2014), based on the information provided by the contractor. The roof system must be installed in accordance wit �}FF and the manufacturer's recommendations. MgVi a � f1 4 Sincerely ° F re Engin eying Consultants, Inc. R. N. S� ppan, P.E. ZIIDI ��A Principal Engineer Florida Registration No. 46696 Forensic Engineering Consultants, Inc. FL - 33497 Ph (561) 9018490 Fax (561) 218