HomeMy WebLinkAboutGFA PAPPERSFlorida's Leading Engineering Source
Environmental -Geotechnical - Construction Materials Testing -Threshold and Special Inspections -Plan Review & Code Compliance
A-1 Roof Truss
Attn: Caroline Santoni
4451 St. Lucie Blvd
Fort Pierce, Florida 34946
RE: Soil Exploration — Proposed Two -Story Attached Addition
4451 St. Lucie Blvd, Fort Pierce, Florida
GFA Project # 16-1322.00
June 6 2016
ECEodE 5
1 JUN 2 1 RECD
*16V - vSep 71
GFA International performed soil testing with three Standard Penetration Test (SPT) borings at the
above referenced project. Based on the test results, the soil on which the referenced structure is to
rest is capable of sustaining a safe bearing capacity of 2,500 psf. The subsurface exploration activities
were performed in accordance with Chapter 18 of the Florida Building Code (latest addition) and
applicable ASTM standards. For detailed information on subsurface conditions encountered, please
refer to the logs attached to this letter.
We recommend that the bottom of the footings be founded at a depth of at least 12 inches below
finish grade. The depth shall be measured from the lowest adjacent grade. We also recommend a
minimum footing width of 18 inches for spread footings and 16 inches for monolithic footings, but not
less than 8 inches more than the width of the imposed wall.
This report does not state or imply that the foundation soils at the bearing level will remain in the
original condition in which they were found during the subsurface exploration activities. Exposure to
the environment may weaken the foundation soils at the bearing level if the foundation excavations
remain open for a long period of time, or if the foundation soils are exposed to rainfall. Consequently,
it is recommended that the excavations for the wall and column footings be performed to final grade
and footings constructed as soon as possible to minimize potential damage of the bearing soils. GFA
estimates the site is at or near final grade. It is also recommended that the 2 feet below existing
grade, the bottom of all new footing excavations and slabs, and all fill material, be compacted to a
minimum density of 95% of the Modified Proctor (ASTM D-1557), prior to the placement of the
concrete for the footings.
Please be aware that differential settlement between existing and new structures is to be expected. A
construction joint between the existing and new structures should be considered if the addition will be
attached to existing structure.
New footing bottoms should not be below adjacent existing footings to prevent soil caving and
undermining of existing subgrade below footings and slabs. During excavation for construction of the
footings for the new buildings next to the existing building, care must be taken not to allow caving of
excavation to cause undermining of the nearby existing footings, slab, and foundation systems. In
order to prevent caving and undermining, it may be necessary to use chemical grouting soil
stabilization for stabilizing the surrounding soils. Grouting under existing footings adjacent to the new
footing excavations would prevent the loss of soil support and newly imposed loadings from affecting
existing foundation footing performance and limit settlement problems due to the new imposed
loadings.
521 NW Enterprise Drive � Port St. Lucie, Florida 34986 - (772) 924-3575 - (772) 924.3580 (fax) - www.teamgfa.com
OFFICES THROUGHOUT FLORIDA
Proposed Two -Story Attaches Addition
"51 St. Lucie Blvd., Fort Pierce, FL
GFA Project# 16-1322.00
June 6, 2016
Foundations and any below grade remains of any structures that are within the footprint of the new
construction should be removed so as to not affect structures.
Vo �6
� �C
one¢.,)N toler, P
-•.nen°ego
Copies: Client (2)
C ig an Collie, E.l.
P je Manager
cation Plan, Standard Penetration Test (SPT) Borings (3),
Related to Test Borings
GFA
Test Location Plan: 4451 St. Lucie Blvd, Fort Pierce, Florida
per...—.—.�.—�..��—.. ...e.4...—.....
Z.
�s........
El
DAWW
wr�tan ��
o❑s. ... �
I
I
-
W G V
1
i
MATCHLINE STA 22+50.00.
� i� I7
I
eo..00rvw�
".u.srnar
w
art*
!
I
eurtn
j
SPT-2
I
!I
'O
- L =I
i
-
ya
II IT '
\` 1N�f—• -•-
I
J g __�'
P
nr. �* �I
Gt
w
JI
nm
— __--
-----
— ___
--Approximate Standard Penetration Test (SPT) Locations
GFA INTERNATIONAL
521 N.W. ENTERPRISE DRIVE, PORT ST. LOctE, FLORIDA 34986
PHONE: (772) 924-3575 - FAx: (772) 924-3580
STANDARD PENETRATION TEST BORING (ASTM D-1586)
Client:
A-1 Roof Truss
Project No.:16-1322.00
Lab No.:
Project:
4451 St. Lucie Blvd.
Page:
1 of 1
Fort Pierce, Florida
Date:
6/2/2016
Elevation:
Existing Grade
Drill Rig:
Simco-24
Water Level:
2.7 feet after 0 hours Drilling Fluid commenced at depth of 8 feet
Field Party:
PM/ES/JS
Hand Auger with Hand Cone Pentrometer Test (HCP in ksf) performed in top 4 feet
TEST LOCATION: SPT - 1 N27.482730 W80.368330
Laboratory Tests
Depth
Blows/
N
Sample
Layer:
USCS
D¢SCriliOII
p
Passing
Moisture
Organic
(feet)
6iu.
Value
No.
From/to
No. 200
Content
Content
0
0-1
Asphalt (2")
HCP=-80+.
Base Rock - Br fine sand, some rock frag. (10")
I
1
1 - 1'/2
SP
Brown fine sand, trace silt and clay
2
HCP=
.. ...........
80+
1'/2 - 3Y2
SP
Gray fine sand, trace silt
---
HCP=
80+
2
4
HCP=
80+
3%2 - 4
SM
Dark gray organic stained fine sand, some sil
---
6
4-7
SM
Dark brown organic stained fine sand, some silt
5
12 .....---
_
13
25
3
6
...8..........
7
8
7 - 10
SP
Gray fine sand, trace clay
11
19
4
g__10.....---
3
4
5
9
5
5
------
11
------
------
12
•------
-----•
13
-------
------
4
13%2 - 15
SP
Brown fine sand
14
--
4
—15
4
8
6
Boring Terminated at 15 feet
16
-------
-••••-
17
-------
------
18
-------
----•.
19
••-••••
------
GFA INTERNATIONAL
521 N.W. ENTERPRISE DRIVE, PORT ST. LUCrE, FLORIDA 34986
PHONE:(772) 924-3575 - F Ax: (772) 924-3580
I STANDARD PENETRATION TEST BORING (ASTM D-1586) I
Client: A-1 Roof Truss
Project: 4451 St. Lucie Blvd.
Fort Pierce, Florida
Elevation: Existing Grade
Water Level: 3.3 feet after 0 hours Drilling Fluid commenced at depth of 8 feet
Hand Auger with Hand Cone Pentrometer Test (HCP in ksf) performed in top 4 feet
Project No.:16-1322.00
Lab No.:
Page: 1 of 1
Date: 6/2/2016
Drill Rig: Simco-24
Field Party: PM/ES/JS
TEST LOCATION: SPT - 2 N27.482750 W80.368520
Laboratory Tests
Depth
Blows/
N
Sample
Layer:
USCS
Description
Passing
Moisture
Organic
(feet)
6 in.
Value
No.
From/to
No. 200
Content
Content
0
0-1
Asphalt (2")
HCP=
80+
Base Rock - Br fine sand, some rock frag. (10")
1
1 - 1 /z
SP
Brown fine sand, trace silt and clay
HCP=
80+
1'/z - 3
SP
Gray fine sand
-
HCP=
80+
2
3-4
SM
Dark brown organic stained fine, some silt
4
HCP=
80+
4-6
SP
Brown fine sand
1
2
5
7
3
7
6 - 10
SP
Gray fine sand
4
7
-----
--4
------
6
10
4
Lq--
8
------
9
8
9
10
18
5
6
10
_
11
-------
------
12
•------
------
13
-------
------
3
13% - 15
SP
Brown fine sand
14
...••
....
4
5
9
6
—15
Boring Terminated at 15 feet
16
-------
------
17
-------
------
l9-------
--•---
GFA INTERNATIONAL
521 N.W. ENTERPRISE DRIVE, PORT ST. Luc1E, FLORIDA 34986
PHONE:(772) 924-3575 - F Ax: (772) 924-3580
STANDARD PENETRATION TEST BORING (ASTM D-1586)
Client: A-1 Roof Truss Project No.:16-1322.00
Lab No.:
Project: 4451 St. Lucie Blvd. Page: 1 of 1
Fort Pierce, Florida Date: 6/2/2016
Elevation: Existing Grade Drill Rig: Simco-24
Water Level: 2.5 feet after 0 hours Drilling Fluid commenced at depth of 8 feet Field Party: PM/ES/JS
Hand Auger with Hand Cone Pentrometer Test (HCP in kst) performed in top 4 feet
TEST LOCATION: SPT - 3 N27.482860 W80.368590
Laboratory Tests
Depth
Blows/
N
Sample
Layer:
USCS
Description
Passing
Moisture
Organic
(feet)
6 in.
Value
No.
From/to
No. 200
Content
Content
0
0-1
Asphalt (2")
HCP=
, 80+
Base Rock - Br fine sand, some rock frag. (10")
I
1
1 - 1'/2
SP
Brown fine sand, trace silt and clay
HCP=
80+
1'/2 - 2
SP
Gray fine sand
2-3
SM
Dark brown organic stained fine, some silt
HCP=
60
2
3 - 4%2
SP
Brown fine sand, trace silt
--• 4
HCP=
80+
2
4
4'/2 - 7'/2
SP
Gray fine sand
5
9
3
6
6
6
8
7'/2 - 9
SP
Gray fine sand, trace clay
7
15
4
8
8
9
9
8
17
5
9 - 10
SP
Light gray fine sand
9
11
-------
------
12
-------
------
13
-------
------
2
13%2 - 15
SP
Gray fine sand
3
15
10.-
6
Boring Terminated at 15 feet
16
-------
------
17
-------
--•---
NOTES RELATED TO
RECORDS OF TEST BORING AND
GENERALIZED SUBSURFACE PROFILE
1. Groundwater level was encountered and recorded (if shown) following the completion of the soil test boring on
the date indicated. Fluctuations in groundwater levels are common; consult report text for a discussion.
2. The boring location was identified in the field by offsetting from existing reference marks and using a cloth tape
and survey wheel.
3. The borehole was backfilled to site grade following boring completion, and patched with asphalt cold patch mix
when pavement was encountered.
4. The Record of Test Boring represents our interpretation of field conditions based on engineering examination of
the soil samples.
5. The Record of Test Boring is subject to the limitations, conclusions and recommendations presented in the Report
text.
6. "Field Test Data" shown on the Record of Test Boring indicated as 11/6 refers to the Standard Penetration Test
(SPT) and means 11 hammer blows drove the sampler 6 inches. SPT uses a 140-pound hammer falling 30 inches.
7. The N-value from the SPT is the sum of the hammer blows required to drive the sampler the second and third 6-
inch increments.
8. The soil/rock strata interfaces shown on the Records of Test Boring are approximate and may vary from those
shown. The soil/rock conditions shown on the Records of Test Boring refer to conditions at the specific location
tested; soil/rock conditions may vary between test locations.
9. Relative density for sands/gravels and consistency for silts/clays are described as follows:
SPT
CPT
SANDS/GRAVELS
SPT
CPT
SILTS/CLAYS
BLOWS/FOOT
KG/CM
RELATIVE DENSITY
BLOWS/FOOT
KG/CM2
CONSISTENCY
0-4
0-16
Very loose
0-1
0-3
Very soft
5-10
17-40
Loose
2-4
4-6
Soft
11-30
41-120
Medium Dense
5-8
7-12
Firm
31-50
121-200
Dense
9-15
13-25
Stiff
50+
over 200
Very Dense
16-30
25-50
Very stiff
>30
>50
Hard
10. Grain size descriptions are as follows:
NAME
SIZE LIMITS
Boulder
12 Inches or more
Cobbles
3 to 12 Inches
Coarse Gravel
Y. to 3 Inches
Fine Gravel
No. 4 sieve to''% inch
Coarse Sand
No. 10 to No. 4 sieve
Medium Sand
No. 40 to No. 10 sieve
Fine Sand
No. 200 to No. 40 sieve
Fines
I Smaller than No. 200 sieve
11. Definitions related to adjectives used in soil/rock descriptions:
PROPORTION
ADJECTIVE
APPROXIMATE ROOT DIAMETER
ADJECTIVE
<5%
Trace
Less than 1/32"
Fine roots
5%to 12%
Little
1/32" to %d'
Small roots
12%to 30%
Some
W, to 1"
Medium roots
30% to 50%
And
Greater than 1"
Large roots
Organic Soils: Soils containing vegetable tissue in various stages of decomposition that has a fibrous to amorphous texture,
usually a dark brown to black color, and an organic odor.
Organic Content <25%: Slightly to Highly Organic; 25% to 75%: Muck; >75%: Peat
6FH