HomeMy WebLinkAboutREVIEW COMMENTSr Planning & Development Services Building & Code Regulation Division 2300 Virginia Avenue Fort Pierce, FL 34982 Phone:(772)462-2172 Fax:(772)462.6443 PRUP&HI Y INPURMAI /UN Address: 4451 St Lucie Blvd City / State / Zip: Fort Pierce, FI 34946 Parcel#: 1431-112-0001-000/8 Zoning: IL APPLICATION INFORMATION Permit Number: 1604-0567 Permit Type: COMMERCIAL ADDITION CONTRACTOR INFORMATION Contractor Name: Michael E Jacquin Business Name: Paul Jacquin & Sons Inc Business Addr: P O Box 4343 City / State / Zip: Ft Pierce, FI 34948 REVIEWS AND COMMENTS REVIEW COMMENTS SCANNED BY MAY�--'�10"� 4 2016 �PF�JIttpITUI'ING St. Lu�dJl'"e� County, FL Owner(s): Betkor Properties LIc Jurisdiction: SAINT LUCIE COUNTY Lot#: Block: a Stories: Automatic Sprinkler System? No Fax Number: 772-466-2806 Email: N/A Review Type Status Reviewed By Date Started Date Completed Date Released DOCUMENTS MISSING PENDING Angela Huff 4/2912016 4/29/2016 Comment: SUB CONTRACTOR AGREEMENTS FOR MECHANICAL, PLUMBING, ELECTRIC AND ROOF 4/29/2016 Comment: SUB CONTRACTOR SUMMARY Comment: A VEGETATION REMOVAL PERMIT OR EXEMPTION IS REQUIRED AT TIME OF PICK UP. PLEASE SUBMIT A 5/2J2016 VEGETATION REMOVALIEXEMPTION PERMIT APPLICATION AS SOON AS POSSIBLE IF YOU HAVEN'T SUBMIT ONE YET. 502016 Comment: FILLED LANDS AFFIDAVIT ENVIRONMENTAL REVIEW PENDING Comment: FRONT COUNTER REVIEW COMPLETE Angela Huff 4129/2016 4/29/2016 4/29/2016 Comment: PLANS EXAMINER REVIEW PENDING Comment: ZONING REVIEW INCOMPLETE 5/2I2016 Lydia Galbraith 5/2/201I6 5/2/2016 Comment: PLEASE BE AWARE THAT SEPARATE BUILDING PERMIT APPLICATIONS ARE REQUIRED TO FOR THE PROPOSED STORAGE BUILDING(S). - Planning S Development Services REVIEW COMMENTS -Buittling8 Code Regulation Division 2300 Virginia Avenue Fort Pierce, FL 34982 Phone:(772)462.2172 Fax:(772)462-6443 2 Comment: BASED ON ST LUCIE COUNTY LAND DEVELOPMENT CODE CHAPTER 7.04.01 C-2, THE PROPOSED FINISHED FLOOR ELEVATION IS REQUIRED TO BE 18° ABOVE THE CENTER LINE OF THE ROAD. IT SEEMS 5/2/2016 THAT THE PROPOSED FFE ON THE PLAN IS NOT MEETING. BASED ON SLC LDC CHAPTER 7.04.01 C3 YOU HAVE THE OPTION TO REQUEST A RELIEF OF THE CODE. PLEASE SEND A LETTER ATTN. LESLIE OLSON, AICP, PLANNING & DEVELOPMENT DIRECTOR. PLEASE INCLUDE THE PROPOSED FLOOR ELEVATION, THE ELEVATION OF THE CENTER LINE OF THE ROAD AND THE REASON FOR THE REQUEST. 5/3/2016 Comment: SEE ATTACHED COMMENTS FROM PATRICK DAYAN IN WATER QUALITY DIVISION. 5/3/2016 Comment: PLEASE BE AWARE THAT ABOVE COMMENTS ONLY REFLECTS THE ZONING REVIEW. THE PLANS EXAMINER MIGHT HAVE ADDITIONAL COMMENTS. Planning & Development Services Building & Code Regulation Division 2300 Virginia Avenue Fort Pierce, FL 34982 Phone:(772)462.2172 Fax:(772)462-6443 PROPERTY INFORMATION Address: 4451 St Lucie Blvd City / State / Zip: Fort Pierce, FI 34946 Parcel#: 1431-112-0001-000/8 Zoning: IL APPLICATION INFORMATION Permit Number: 1604-0567 Permit Type: COMMERCIAL ADDITION Contractor Name: Michael E Jacquin Business Name: Paul Jacquin & Sons Inc Business Addr: P O Box 4343 City / State / Zip: Ft Pierce, FI 34948 REVIEWS AND COMMENTS REVIEW COMMENTS -SCANNED BY I.lC/e C 1 Owner(s): Betkor Properties Llc Jurisdiction: SAINT LUCIE COUNTY Lot#: Block: Stories: Automatic Sprinkler System? No Fax Number: 772-466-2806 Email: N/A Review Tvoe Status Reviewed By Date Started Date Completed Date Released DOCUMENTS MISSING PENDING Angela Huff 4/2912016 4/29/2016 Comment: SUB CONTRACTOR AGREEMENTS FOR MECHANICAL, PLUMBING, ELECTRIC AND ROOF 4/29/2016 Comment: SUB CONTRACTOR SUMMARY Comment: A VEGETATION REMOVAL PERMIT OR EXEMPTION IS REQUIRED AT TIME OF PICK UP. PLEASE SUBMIT A 5/2/2016 VEGETATION REMOVALIEXEMPTION PERMIT APPLICATION AS SOON AS POSSIBLE IF YOU HAVENT SUBMIT ONE YET. 5/2/2016 Comment: FILLED LANDS AFFIDAVIT 5/9/2016 Comment: VEG PERMIT IN DRAWER UNDER "P" PROPERTIES ENGINEERING DEPARTMENT COMPLETE 51912016 519/2016 Comment: ENVIRONMENTAL REVIEW COMPLETE Ben Balcer 5/912016 5/9/2016 Comment: FIRE DEPARTMENT REVIEW PENDING Tony Jerger. Comment: FRONT COUNTER REVIEW COMPLETE Angela Huff 4/29/2016 4/29/2016 4129/2016 Comment: PLANS EXAMINER ELECTRIC COMPLETE Walter Pride 514/2016 515/2016 515/2016 Comment: ��taC�1P (/Oraavwz Planning & Development Services Building & Code Regulation Division 2300 Virginia Avenue Fort Pierce, FL 34982 Phone:(772)4622172 Fax:(772)462.6443 REVIEW COMMENTS PLANS EXAMINER MECHANICAL INCOMPLETE Carl Peterson 51912016 5/10/2016 Comment: PLEASE REFERANCE THE 2014 FLORIDA MECHANICAL CODE IN THE DESIGN CRITERIA ON PLANS PAGE M1 IN ACCORDANCE WITH 107.2.1 OF THE 2014 FLORIDA BUILDING CODE. 5/10/2016 Comment: PLEASE SHOW LOCATION OF ROOF TOP UNITS ON PLANS ROOF PLANS IN ACCORDANCE WITH 107.2.1 OF THE 2014 FLORIDA BUILDING CODE. 5/1012016 Comment: PLEASE SHOW ACCESS TO THE ROOF TOP UNITS IN ACCORDANCE WITH 306.5 OF THE 2014 FLORIDA MECHANICAL CODE. 5/1012016 Comment: PLEASE FURNISH EQUIPMENT SCHEDULE WITH ALL EQUIPMENT SIZING IN ACCORDANCE WITH 107.2.1 OF THE 2014 FLORIDA BUILDING CODE. 5/1012016 Comment: PLEASE SHOW GUARDS IF UNIT IS LOCATED WITHIN 10 FOOT OF AND OPEN SIDE OR ROOF EDGE IN ACCORDANCE WITH 304.11 OF THE 2014 FLORIDA MECHANICAL CODE. 5/10/2016 Comment: PLEASE SHOW REST ROOM VENTILATION IN ACCORDANCE WITH TABLE 403.3 OF THE 2014 FLORIDA MECHANICAL CODE. PLANS EXAMINER PLUMBING COMPLETE Greg Smyth 51912016 51912016 Comment: PLANS EXAMINER REVIEW INCOMPLETE Joe Cicio 5/412016 Comment: SUBMIT THE MANUFACTURERS SPECIFICATIONS, IN TRIPLICATE, FOR THE ELEVATOR LIFT SHOWNIG COMPLIANCE WITH FBC 3001 AND FLORIDA ACCESSIBILITY CODE SECTION 407 / 410' NEED A DETAIL ON 5/4/2016 PLANS FOR THE CAR ATTACHMENT FRAMING WALL' PLAN SIZE DOES NOT MATCH THE REQUIRED SIZES W/ DOOR OPENING SIZES' ALL MUST BE REVIEWED AND APPROVED BY DESIGN PROFESSIONAL OF RECORD 5/4/2016 Comment: DESIGN PROFESSIONAL TO INCLUDE THE TESTING CRITERIA ON PLANS FOR THE ACOUSTICAL CEILING SYSTEM PER FBC 808.1.1.1 5/5/2016 Comment: INCLUDE AN INTERIOR FINISH TABLE ON PLANS PER FBC 803.9' NOTES ON A-1 DO NOT MATCH WITH TABLE SPECIFICATIONS IN CODE 5/5/2016 Comment: DESIGN PROFESSIONAL TO SHOW THE BUILDING ATTACHMENT DETAILS ON THE PLANS FOR THE AEGIS FRONTCANOPY 5/5/2016 Comment: SUBMIT AN ORIGINAL SIGNED, DATED AND SEALED S01 L TEST FROM A GEOTEC TESTING AGENCY' SEE PLAN NOTES ON St ' FBC 1803.1 ` FBC 107.1 Comment: ELIMINATE THE NOTES FROM THE PLANS" HANGERS BY BUILDER" ETCFBC 107.3.5 ` DESIGN 5/5/2016 PROFESSIONAL TO DESIGN THE HANGARS FOR THE FG02 AND A01 G GIRDER TRUSS SYSTEM ON PLANS AND SHOW THE LOADS ` DESIGN PROFESSIONAL OF RECORD TO APPROVE THE TRUSS LAYOUTS AND ENGINEERING CUT SHEETS 5/5/2016 Comment: COLUMN SCHEDULES ON PLAN S1, MARK 3 AND 4, NEEDS CLARIFICATION `THERE ARE NO CUSTOM CONNECTION DETAILS ON PLANS AS STATED AND SHOW THE TIE TO THE GIRDERS' FBC 107.3.5 5/5/2016 Comment: DESIGN PROFESSIONAL TO SPECIFY THE SIZES AND O.C. SPACING OF THE STUD WELDS TO THE STEEL BEAM FOR THE WOOD PLATE ATTACHMENT' FBC 107.3.5 5/5/2016 Comment: SHOW A DETAIL ON PLANS 4 PLY GIRDERS INTERSECT THE EXISTING GIRDERS AND STEEL W24 BEAM ` FBC 107.3.5 Comment: SHOW THE WOOD FRAME BEARING WALL DETAILS ON PLANS " FOOTING SCHEDULE F2 SPECS A 16" 5/5/2016 WIDE FOOTING AND BEARING WALL FOOTING DETAIL SPECS 30" ???????? PLS CORRECT ONE OR THE OTHER Comment: PLEASE REMOVE ANY ADDITIONAL SHEETS IN THE TRUSS ENGINEERING PACKAGE THAT DO NOT APPLY 5/5/2016 TO THIS PERMITAND THE ADDITIONAL SHEETS BY JULIUS LEE MUST BE ORIGINAL SIGNED, SEALED AND DATED IF APPLICABLE TO THIS PROJECT 5/5/2016 Comment: IDENTIFY THE GYPSUM BOARD MATERIALS W/ ACCESSORIES ON PLANS PER FBC TABLE -2506.2 W/ APPROVED TESTING STANDARDS AND FASTENERS 5/5/2016 Comment: IDENTIFY THE EXTERIOR PLASTER TESTING CRITERIA ON PLANS FBC 2512 5/5/2016 Comment: NEED TRIPLICATE S.S.D. MANUFACTURERS SHOP DRAWINGS FOR THE EXTERIOR STAIRWAY REVIEWED AND APPROVED BY THE DESIGN PROFESSIONAL OF RECORD' PLANS STATE SEE SHOP DRAWINGS 5/6/2016 Comment: PLANS TO SHOW THE ACCESSIBLE SERVICE COUNTER PER FBC ACCESS. 904.4.1 OR 904.4.2 Comment: PRODUCT APPROVAL ON COVER PAGE::: SCREW CLUSTERS PER N.O.A.::: NEED THESE DETAILS ON 5/6/2016 PLANS OR SUBMIT THE DETAIL PAGES FROM THE APPROPRIATE N.O.A. HIGHLIGHTED AND REVIEWED AND APPROVED BY DESIGN PROFESSIONAL OF RECORD 6/1012016 Comment: COMMENTS E-MAILED AS OF THIS DATE I Planning & Development Services Building & Code Regulation Division 2300 Virginia Avenue Fort Pierce, FL 34982 Phone:(772)462-2172 Fax:(772)462.6443 REVIEW COMMENTS 3 5/10/2016 Comment: PLEASE RE -SUBMIT ALL PLANS IN ORIGINAL, SIGNED, DATED AND SEALED FORMAT W/ [ 21 PDF DISCS ZONING REVIEW INCOMPLETE Lydia Galbraith 5/212016 5/2/2016 Comment: PLEASE BE AWARE THAT SEPARATE BUILDING PERMIT APPLICATIONS ARE REQUIRED TO FOR THE PROPOSED STORAGE BUILDING(S). Comment: BASED ON ST LUCIE COUNTY LAND DEVELOPMENT CODE CHAPTER 7.04.01 C-2, THE PROPOSED FINISHED FLOOR ELEVATION IS REQUIRED TO BE 18" ABOVE THE CENTER LINE OF THE ROAD. IT SEEMS 5/2/2016 THAT THE PROPOSED FFE ON THE PLAN IS NOT MEETING. BASED ON SLC LDC CHAPTER 7.04.01 C3 YOU HAVE THE OPTION TO REQUEST A RELIEF OF THE CODE. PLEASE SEND A LETTER ATTN. LESLIE OLSON, AICP, PLANNING & DEVELOPMENT DIRECTOR. PLEASE INCLUDE THE PROPOSED FLOOR ELEVATION, THE ELEVATION OF THE CENTER LINE OF THE ROAD AND THE REASON FOR THE REQUEST. 5/3/2016 Comment: SEE ATTACHED COMMENTS FROM PATRICK DAYAN IN WATER QUALITY DIVISION. 5/3/2016 Comment: PLEASE BE AWARE THAT ABOVE COMMENTS ONLY REFLECTS THE ZONING REVIEW. THE PLANS EXAMINER MIGHT HAVE ADDITIONAL COMMENTS. 5/3/2016 Comment: FILE WILL NEED TO RETURN TO ZONING FOR RIF CREDIT APPROVAL. r S.t~f.crfilG (fOt� `=L Planning & Development Services Building & Code Regulation Division 2300 Virginia Avenue Fort Pierce, FL. 34962 Phone:(772)462.2172 Fax:(772)462.6443 D17A0F17TV IIVFr1DMATIr1xl Address: 4451 St Lucie Blvd City I State I Zip: Fort Pierce, FI 34946 Parcel#: 1431-112-0001-000/8 Zoning: IL APPLICATION INFORMATION Permit Number: 1604-0567 Permit Type: COMMERCIAL ADDITION CONTRACTOR INFORMATION Contractor Name: Michael E Jacquin Business Name: Paul Jacquin & Sons Inc Business Addr: P O Box 4343 City I State I Zip: Ft Pierce, FI 34948 REVIEW COMMENTS SCANNED REECE V MAY 2 6 2016 PERtIITTING St. Lucie County, FL 1 (:!L inhl Owner(s): Betkor Properties Llc Jurisdiction: SAINT LUCIE COUNTY Lot#: Block: Stories: Automatic Sprinkler System? No Fax Number: 772-466-2806 Email: N/A Review Type Status Reviewed By Date Started Date Completed Date Released DOCUMENTS MISSING PENDING Angela Huff 412912016 4/2912016 Comment: SUB CONTRACTOR AGREEMENTS FOR MECHANICAL, PLUMBING, ELECTRIC AND ROOF 4/29/2016 Comment: SUB CONTRACTOR SUMMARY Comment: A VEGETATION REMOVAL PERMIT OR EXEMPTION IS REQUIRED AT TIME OF PICK UP. PLEASE SUBMIT A 5/2/2016 VEGETATION REMOVAL/EXEMPTION PERMIT APPLICATION AS SOON AS POSSIBLE IF YOU HAVEN'T SUBMIT ONE YET. 5/2/2016 Comment: FILLED LANDS AFFIDAVIT 5/9/2016 Comment: VEG PERMIT IN DRAWER UNDER °P" PROPERTIES ENGINEERING DEPARTMENT COMPLETE 519/2016 5/9/2016 Comment: ENVIRONMENTAL REVIEW COMPLETE Ben Balcer 519/2016 5/912016 Comment: FIRE DEPARTMENT REVIEW PENDING Tony Jerger Comment: FRONT COUNTER REVIEW COMPLETE Angela Huff 4/29/2016 412912016 4129/2016 Comment: PLANS EXAMINER ELECTRIC COMPLETE Walter Pride 5/412016 51512016 5/5/21)76 Comment: .its• �t1GZG UOwiwx O � Planning & Development Services Building S, Code Regulation Division 2300 Virginia Avenue Fort Pierce, FL. 34982 Phone:(772)462-2172 Fox:(772)462-6443 REVIEW COMMENTS PLANS EXAMINER MECHANICAL INCOMPLETE Carl Peterson 519/2016 5/10/2016 Comment: PLEASE REFERANCE THE 2014 FLORDA MECHANICAL CODE IN THE DESIGN CRITERIA ON PLANS PAGE M1 IN ACCORDANCE WITH 107.2.1 OF THE 2014 FLORIDA BUILDING CODE. 5/10/2016 Comment: PLEASE SHOW LOCATION OF ROOF TOP UNITS ON PLANS ROOF PLANS IN ACCORDANCE WITH 107.2.1 OF THE 2014 FLORIDA BUILDING CODE. 5/10/2016 Comment: PLEASE SHOW ACCESS TO THE ROOF TOP UNITS IN ACCORDANCE WITH 306.5 OF THE 2014 FLORIDA MECHANICAL CODE. 5/10/2016 Comment: PLEASE FURNISH EQUIPMENT SCHEDULE WITH ALL EQUIPMENT SIZING IN ACCORDANCE WITH 107.2.1 OF THE 2014 FLORIDA BUILDING CODE. 5/10/2016 Comment: PLEASE SHOW GUARDS IF UNIT IS LOCATED WITHIN 10 FOOT OF AND OPEN SIDE OR ROOF EDGE IN ACCORDANCE WITH 304.11 OF THE 2014 FLORIDA MECHANICAL CODE. 511012016 Comment: PLEASE SHOW REST ROOM VENTILATION IN ACCORDANCE WITH TABLE 403.3 OF THE 2014 FLORIDA MECHANICAL CODE. PLANS EXAMINER PLUMBING COMPLETE Greg Smyth 519/2016 51912016 Comment: PLANS EXAMINER REVIEW INCOMPLETE Joe Clclo 5/4/2016 Comment: SUBMIT THE MANUFACTURERS SPECIFICATIONS, IN TRIPLICATE, FOR THE ELEVATOR LIFT SHOWNIG COMPLIANCE WITH FBC 3001 AND FLORIDA ACCESSIBILITY CODE SECTION 4071410 • NEED A DETAIL ON 5/Q2016 PLANS FOR THE CAR ATTACHMENT FRAMING WALL • PLAN SIZE DOES NOT MATCH THE REQUIRED SIZES W/ DOOR OPENING SIZES' ALL MUST BE REVIEWED AND APPROVED BY DESIGN PROFESSIONAL OF RECORD 5/4/2016 Comment: DESIGN PROFESSIONAL TO INCLUDE THE TESTING CRITERIA ON PLANS FOR THE ACOUSTICAL CEILING SYSTEM PER FBC 808.1.1.1 5/5/2016 Comment: INCLUDE AN INTERIOR FINISH TABLE ON PLANS PER FBC 803.9 • NOTES ON A-1 DO NOT MATCH WITH TABLE SPECIFICATIONS IN CODE 5/5/2016 Comment: DESIGN PROFESSIONAL TO SHOW THE BUILDING ATTACHMENT DETAILS ON THE PLANS FOR THE AEGIS FRONT CANOPY 5/5/2016 Comment: SUBMIT AN ORIGINAL SIGNED, DATED AND SEALED S01 L TEST FROM A GEOTEC TESTING AGENCY' SEE PLAN NOTES ON S1 ' FBC 1803.1 • FBC 107.1 Comment: ELIMINATE THE NOTES FROM THE PLANS' HANGERS BY BUILDER" ETC' FBC 107.3.5' DESIGN 5/5/2016 PROFESSIONAL TO DESIGN THE HANGARS FOR THE FG02 AND AO),G-GIR„DEF_TRUSS.SYSTEM-ON-_RLANS AND SHOW 7HELOADS CDE51GN PROF.ESSIONALCF'RECORD TO APPROVE THEtTRUSS LAYOUTS AND '--" '_'"'+�" 'ENGINEERING'CUTSHBETS Comment: COLUMN SCHEDULES ON'jPLAN St. MARK 3 AND 4, NEEDS CLARIFICATION • THERE ARE NO CUSTOM 5/5/2016 CONNECTION DETAILS ON PLANS AS STATED AND SHOW THE TIE TO THE GIRDERS' FBC 107.3.5 5/5/2016 Comment: DESIGN PROFESSIONAL TO SPECIFY THE SIZES AND O.C. SPACING OF THE STUD WELDS TO THE STEEL BEAM FOR THE WOOD PLATE ATTACHMENT • FBC 107.3.5 5/5/2016 Comment: SHOW A DETAIL ON PLANS 4 PLY GIRDERS INTERSECT THE EXISTING GIRDERS AND STEEL W24 BEAM FBC 107.3.5 Comment: SHOW THE WOOD FRAME BEARING WALL DETAILS ON PLANS •' FOOTING SCHEDULE F2 SPECS A 16" 5/5/2016 WIDE FOOTING AND BEARING WALL FOOTING DETAIL SPECS 30" ???????? PLS CORRECT ONE OR THE OTHER Comment: PLEASE REMOVE ANY ADDITIONAL SHEETS IN THE TRUSS ENGINEERING PACKAGE THAT DO NOT APPLY 5/5/2016 TO THIS PERMITAND THE ADDITIONAL SHEETS BY JULIUS LEE MUST BE ORIGINAL SIGNED, SEALED AND DATED IF APPLICABLE TO THIS PROJECT 5/5/2016 Comment: IDENTIFY THE GYPSUM BOARD MATERIALS W/ ACCESSORIES ON PLANS PER FBC TABLE 2506.2 W/ APPROVED TESTING STANDARDS AND FASTENERS 5/5/2016 Comment: IDENTIFY THE EXTERIOR PLASTER TESTING CRITERIA ON PLANS FBC 2512 Comment: NEED TRIPLICATE S.S.D. MANUFACTURERS SHOP DRAWINGS FOR THE EXTERIOR STAIRWAY REVIEWED -I �f/7 t/ 5/5/2016 Q AND APPROVED BY THE DESIGN PROFESSIONAL OF RECORD' PLANS STATE SEE SHOP DRAWINGS 5/6/2016 Comment: PLANS TO SHOW THE ACCESSIBLE SERVICE COUNTER PER FBC ACCESS. 904.4.1 OR 904.4.2 Comment: PRODUCT APPROVAL ON COVER PAGE ::: SCREW CLUSTERS PER N.O.A.::: NEED THESE DETAILS ON 5/6/2016 PLANS OR SUBMIT THE DETAIL PAGES FROM THE APPROPRIATE N.O.A. HIGHLIGHTED AND REVIEWED AND APPROVED BY DESIGN PROFESSIONAL OF RECORD 5/10/2016 Comment: COMMENTS E-MAILED AS OF THIS DATE Planning & Development Services Building & Code Regulation Division 2300Virginia Avenue Fort Pierce, FL. 34982 Phone:(772)462.2172 Fax:(772)462.6443 REVIEW COMMENTS 5/10/2016 Comment: PLEASE RE -SUBMIT ALL PLANS IN ORIGINAL, SIGNED, DATED AND SEALED FORMAT W/ [ 2 ] PDF DISCS ZONING REVIEW INCOMPLETE Lydia Galbraith 5/212016 5/2/2016 Comment: PLEASE BE AWARE THAT SEPARATE BUILDING PERMIT APPLICATIONS ARE REQUIRED TO FOR THE PROPOSED STORAGE BUILDING(S). Comment: BASED ON ST LUCIE COUNTY LAND DEVELOPMENT CODE CHAPTER 7.04.01 C-2, THE PROPOSED FINISHED FLOOR ELEVATION IS REQUIRED TO BE 18" ABOVE THE CENTER LINE OF THE ROAD. IT SEEMS 5/2/2016 THAT THE PROPOSED FFE ON THE PLAN IS NOT MEETING. BASED ON SLC LDC CHAPTER 7.04.01 C3 YOU HAVE THE OPTION TO REQUEST A RELIEF OF THE CODE. PLEASE SEND A LETTER ATTN. LESLIE OLSON, AICP, PLANNING & DEVELOPMENT DIRECTOR. PLEASE INCLUDE THE PROPOSED FLOOR ELEVATION, THE ELEVATION OF THE CENTER LINE OF THE ROAD AND THE REASON FOR THE REQUEST. 5/3/2016 Comment: SEE ATTACHED COMMENTS FROM PATRICK DAYAN IN WATER QUALITY DIVISION. 5/3/2016 Comment: PLEASE BE AWARE THAT ABOVE COMMENTS ONLY REFLECTS THE ZONING REVIEW. THE PLANS EXAMINER MIGHT HAVE ADDITIONAL COMMENTS. 5/3/2016 Comment: FILE WILL NEED TO RETURN TO ZONING FOR RIF CREDIT APPROVAL.