BRYN MAWR CONDOMINIUMS - BLDG. B
5(:ANNtL
5059 NORTH HIGHWAY AIA, FT. PIERCE, FLORIDA
BY
THRESHOLD INSPECTION REPORT
SLC BUILDING PERM BE : 1 6-004
St. Lucie Countl-
PROJECTNAME: Bryn Mawr —Bldg. B
CLIENT: Elliott Merrill Community Mgt.
CONTRACTOR: Daniello & Assoc.
INSPECTED BY: Mike Lue
WORK INSPECTED:
Concrete balcony demo @ Units 501, 506 & 801
DATE: October 31, 2016
LOCATION: Ft. Pierce, Florida
PROJECT MGR: Chris Arias
WEATHER: Overcast
Loose concrete and spalling area has been chipped and corroded reinforcing bars exposed. We
found the following:
Unit 501— The reinforcing at the ceiling spall along the east balcony appears to be in serviceable
condition and only minor surface corrosion. The repair area is approximately 6 square feet.
Unit 501— ceiling spall
Unit 506 — The reinforcing at the surface spall along east balcony appear to be in serviceable
condition. There is one bar parallel to the sliding glass door which shall be chased further. This
will not require removing the doors or track. The area of repair is approximately 5 square feet.
M L Engineering, Inc.
Consulting Engineers
203037' Avenue
Vero Beach, Florida 32960
Unit 506 surface spall
Project No. 16-133B Report No. 1
cc: Gene Ross Elliott Merrill
Chris Arias Daniello Const.
Carl Peterson SLC Bldg Dept
File
Unit 801 — Reinforcing at the ceiling spalls along the east and west balcony are exposed and in
serviceable condition. The reinforcing at the west balcony will require further chipping to chase
the corrosion. This will require going into the unit and removing the sliding glass door. The area
of repair is approximately 7 square feet.
Unit 801 - east balcony
Once all corrosion is chased to clean reinforcing, bars shall be power tool cleaned and primed
with a corrosion inhibitor as per specifications. Allow for the primer to dry one full day and then
patch with repair mortar.