Allied Building Products Corp. Evaluation Report A42960.30.12-R3
dba TRI-BUILT Roofing Products
9050 Louisiana Street Date of Issuance: SO 25/2012
Merrillville, IN 46410 Revision 3: 10/08/2015
SCOPE:
This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of
construction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen,
P.E. for use of the product under the Florida Building Code and Florida Building Code, Residential Volume. The
products described herein have been evaluated for compliance with the 5th Edition (2014) Florida Building Code
sections noted herein.
SCANNED
BY
St. Lucie Counttl
DESCRIPTION: TRI-BUILT Roof Underlayments
LABELING: Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted
herein.
CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s) changes, the referenced
Quality Assurance documentation changes, or provisions of the Code that relate to the product change. Acceptance of
this Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. if the product
changes or the referenced Quality Assurance documentation changes. Trinityl ERD requires a complete review of this
Evaluation Report relative tmupdaied Code requirements with each Code Cycle.
ADVERTISEMENT: The Evaluation: Reportnumberpreceded by the words "Trinityl ERD Evaluated" may bedisplayed in
advertising literature. If any portion of the Evaluation Report is displayed, then it shall be done in its entirety.
INSPECrION:.Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or
its distributors and shall be available for inspection atthejob site at the request of the Building Official.
This Evaluation Report consists of pages 1 through S.
Prepared by:
Robert J.M. Nieminen, P.E.
Florida Registration No. 59166, Florida DCA ANE1983
Thefaolinle seal apGearimy,as authorized by Robert Nieminen,
P.E on 10108/2025. Thisdoesnut.easaneledni dcallysigiied
document. Signed, sealedhardmpkzhave been tiannvkted to be
Pf oct ApWaval AdmiNlra randwbanamedfl m
CERTIFICATION OF INDEPENDENCE:
1. Trinityl ERD does nothave, nor does it intend to acquire or will it acquire, a financial interest in any company manufacturing or
distributing products it evaluates.
2. Trinityl ERD is not owned, operated or controlled by any company manufacturing or distributing products it evaluates.
3. Robert Nieminen, P.E. does not have nor will acquire, a financial interest in any company manufacturing or distributing products for
which the evaluation reports are being issued.
4. Robert Nieminen, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the
product.
5. This is a building code evaluation. Neither Trinityl ERD nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any
- project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained
specifically for that. purpose.
,• [ s 9 ` �'� '��i Ire$ 1
y ?2ti5
QOTPJNITYIERD
ROOFING COMPONENT EVALUATION:
1. SCOPE:
Product Category: Roofing
Sub -Category. Underlayment:
Compliance Statement: TRI-BUILT Roof Underlayments, as produced by TRI-BUILT, have demonstrated compliance
with the following sections of the Florida Building Code through testing in accordance with the following Standards.
Compliance is subject to the Installation Requirements and Limitations / Conditions of Use set forth herein.
2. STANDARDS:
Section Property. Standard Year
1507.2-.4, 1507.2.8, 1507:2.9.2, Physical Properties ASTM D1970 2009
1507.4.5.1, 1507.5.3, 1507.7.3
1504.6 Accelerated Weathering ASTMG155 2005
1507.3.3 Installation Practice FRSA/TRI April 2012(04-12) 2012
1523.6.5.2.1 Physical Properties TAS 103 1995
3. REFERENCES:.
Entity Examination Reference Date.
ERD (TST6049) Physical Properties S40540.02.13-1 02/19/2013
ERD (TST6049) Physical Properties 540540.11.13 11/19/2013
ERD (TST6049) Physical Properties S40540.03.14 03/26/2014
ERD (TST6049) Physical Properties 544870.04.14-2 04/02/2014
ERD (TST(5049) Physical Properties. S44870.04.14-3 04/02/2014
ERD (TST6049) Physical Properties S44870.04.14-1 04/10/2014
ERD (TST6049) Physical Properties S44870.04.14-4 04/10/2014
ERD (TST6049) Physical Properties S43530.02.14-1-R1 05/14/2014
ERD (TST6049) Physical Properties S43530.05.14 05/28/2014
ERD (TST6049) Physical Properties S40540.30.14 10/31/2014
ERD (TSTfi049) Physical Properties SC7645.02.15 02/13/2015
ERD (TST6049) Accelerated'Weathering 5C8520.04.15 05/27/2015
UL, LLC. (QUA9625) Quality Control Muhiple-Listing R16814 09 04 2015
UL, I.I.C. (QUA9625) Quality Control `Service Confirmation E , Oj16 014
4. PRODl1CT DESCRIPTION:
4.1 Self -Adhering Underlayments:
4.1.1 Tri-Built Sand-R SA Shingle Underlayment is a self -adhering, glass -mat reinforced, sand -surfaced, SBS
modified bitumen roof underlayment, with a'.36-inch.. sheet width.
4.1.2 Tri-Built S/A HT TU Underlaymentls a self -adhering, non -woven polyester fabric surfaced, SBS modified
bitumen roof underlayment
4.1.3 Tri-Built Smooth HT S/AUnderlayment is a self -adhering; glass -mat reinforced, film -surfaced, SBS modified
bitumen roof underlayment,
S. LIMITATIONS:
5.1 This is a building code evaluation. Neither Trinityl£RD nor Robert Nieminen, P.E. are, in any way, the
Designer of Record for any project on which this Evaluation Report, or previous versions thereof, is/was
used for permitting or design guidance unless retained specifically for that purpose, '
5.2 This Evaluation Report is not for use in the HVHZ.
5.3 Fire Classification is not part of this Evaluation .Report; refer to current Approved Roofing Materials
Directory for fire ratings of this product.
Exterior Research and. Design, LLC. Evaluation Report A42960.10.12-R3
Certificate ofAuthorizc0on 09503 F1.16048-113
Revision 3: 10/08/2015
- Page 2 of S
R
5A TRI-BUILT Roof Underiayments may beused with any prepared roof cover where the product is specifically
referenced within FBC approval documents. If not listed, a request may be made to the AHJ for approval
based on this evaluation combined with supporting data for the prepared roof covering.
5.5 Allowable roof covers applied atop the underlayments are as follows:
Underlayment
Asphalt
Nail -On Tile
Foam -On Tile
Metal
Wood Shakes
Slate
Shingles
& Shingles
Tri-Built Sand-R SA Shingle
Yes
No-
No
No
Yes
Yes
Underlayment
Tri-Built SJA HT TU
Yes
Yes
Yes
Yes
Yes
Yes
Underlayment
See 5.5.1
Tri-Built Smooth HT S/A
Yes
No
No
Yes
Yes
Yes
Underlayment
5.5.1. "Foam -On Tile" is limited to use of the. following Approved tile adhesives unless tensile adhesion / long
term aging data. from an,accredited testing laboratory is provided.
> Tri-Built S/A HT TU Underlayment with 3Mw 2-Component Roof Tile Adhesive AH-160 (FL6332) or Dow
TileBoncl " Roof Tile Adhesive (FL717)
5.6 Allowable substrates are noted below:'
5.6.1 Direct -.Bond to Deck:
Tri-Built Sand-R SA Shingle Underlayment, Tri-Built S/A HT TU Underlayment. or Tri-Built Smooth HT S/A
Underlayment applied to:
Plywood; ASTM D41 primed plywood; .OSB; ASTM D41 primed OSB; ASTM D41 primed structural
concrete.
While not required over plywood, OSB or Southern Yellow Pine substrates, TRI-BUILT recommends priming
the deck if the final roof cover is not slated for installation within 24 hours. Note: TRI-BUILT requires
tongue -and -groove board .decking be covered with plywood or OSB prior to installation of the self -
adhering underlayment.
5.6.2 Bond -to -Insulation:
Tri-BuiltS/A HTTU Underlayment applied to:
➢ Dens Deck Prime; SECUROCK Gypsum -Fiber Roof Board.
For installation under mechanically attached prepared roof coverings, insulation shall be attached per
minimum requirements of the prepared:. roof covering manufacturer's Product Approval. For installations
under foam -on tile systems, insulation attachment shall be designed by a qualified design professional and
installed based on testing of the insulation/underlayment system in accordance,with FM 4474, Appendix D
or TAS 114, Appendix J.
5.6.3 Bond to Mechanically Attached .Base Layer:
➢ ASTM D226, Type.I or 11 felt..
For installations under mechanically attached prepared roof coverings, base layer shall be attached per
minimum codified requirements. For installations under foam -on the systems, base layer shall be,attached
per minimum requirements of FRSA/TRIApril 2012 (04-12),
Exterior Research and Design, LLC. Evaluation Report A42960.10.1240
Cerfificvte ofAathorkafiv.M03 FL16048-113
Revision 3; 10/08/2015
Page 3 of 5
Q11UNIT1( FRa
5.6.4 Wind Resistance for Underlayment Systems in foam -On Tile Applications: FRSA/TRI April 2012 (04-12)
does not address wind uplift resistance of all underlayment systems beneath foam -on tile systems, where
the underlayment forms part of the load -path. The following wind uplift limitations apply to direct -deck
underlayment systems that are not addressed in FRSA/TRI April 2012 (04-12) and are used in foam -on the
applications. Maximum Design Pressure is the result of testing for wind load :resistance based on
allowable wind loads, and reflects the ultimate passing pressure divided by 2 (the 2 to 1 margin of safety
per FBC 1504.9 has already been applied). Refer ToTBC 1609 for determination of design wind pressures.
e3_c%w' xIm1A[D..f1(Si daa St�rE�-4: Sf.
Deck: .Min. 15/324nch p ywoodto meet project requirements to satisfaction of AHJ.
Primer: (Optional) ASTM D41
Underlayment: Tri-Built S/A HT TU Underlayment, self -adhered.
5.7 Exposure Limitations:
5.7.1 Tri-Built Sand-R SA Shingle Underlayment or Tri-Built Smooth HTS/A Underlayment shall not be left
exposed for longer than 30-days after installation
5.7.2 Tri-BuiltS/A. HT TU Underlayment shall not be left exposed forlonger than 180-days after installation.
6. INSTALLATION:
6.1 TRI-BUILT Roof Underlayments shall be installedin accordance with TRI-BUILT published installation
requirements subject to the Limitations set forth in Section 5 herein and the specifics noted below.
6.2 Re -fasten any loose decking panels, and check for protruding nail heads. Sweep the substrate thoroughly
to remove any dust and debrisprior to application, and prime the substrate (if applicable).
6.3 Tri-Built Sand-R SA Shingle Underlayment. Tri-Built S/A HTTU UnderiavmentorTri-Built Smooth HT S/A
Underlayment:
6.3.1 Shall be installed in compliance. with the requirements for.ASTM D1970 underlayment in FBC Sections
1507 for the type of prepared roof covering to be installed.
6.3.2 Non -Tile applications:
While priming is optional, TRI-BUILT recommends priming the deck if the final, roof cover is not slated for
installation within 24 hours.
Apply sheet parallel to the roof edge. Roil outrapprokimately 10 ft of membrane and peel back 'the first 3
ft of release film.
Adhere the exposed part. to the substrate and unroll theremaining membrane as far as possible.
Once the entire length of membrane is in place, peel -off the release film diagonally while holding the
membrane tight. Firmly roll the membrane into place to achieve a bond.
Horizontal seams should be minimum 3-inches, configured to shed water. Vertical seams should be 6-
inches and staggered not less than 2-ft from vertical seams in the course below. All over -granule end -laps
shall be sealed using either heat -welding hot air welding techniques.
When installing at slopes above 8:12, Allied Building Products Corp recommends back -nailing in the`
overlap area at the top of the sheet at 12 inch o.c.
For Valleys and Ridges: Cut underlayment into 4 to 6' foot lengths. Peel the release paper and center sheet
over valley or ridge. Drape and press sheet into place, working from the center of the valley or ridge in
each direction.' For valleys; apply the sheet starting at the lowest point and work upward.
63.3 Tile Applications (Tri-BuiltS/A HTTU Underlayment only):
Reference is made to FRSA/TRI.. April 2012 (04-12) Installation Manual and Table 1 herein, using the
instructions noted above asa guideline.
Tile shall be loaded and stagedin a manner thatprevents tile slippage and/or damage to the
underlayment.
Exterior Research and Design, LLr. Evaluation Report A42960.10.12-R3
rertifiiate of Authorization 09503 FL1604a-M
Revision 3: 10/08/2015
Page 4 of 5
PTRINIWIERD
7. BUILDING PERMIT REQUIREMENTS:
As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate the installation of
this product.
B. MANUFACTURING PLANTS:
Contact the noted CIA agency for information on product locations covered for F.A.C. Rule 9N-3 CIA requirements.
9. QUALITY. ASSURANCE ENTITY:
UL, LLC-QUA9625; (314) 578-3406; k.chancellor@us.ul.com
- END OF EVALUATION REPORT -
Exterior Research and Design, U.C. - Evaluation Report A82960.10.12-R3
Certificate offtthonzotko 09503 F1.I6048-113
Revision 3: 10/08/2015
Page 5 of 5
I
g�
I
I
l
CBUCK Engineering
Specialty Structural Englne2erinq
Evaluation Report
1" Dail Strip
Metal Roof Assembly
CBUCK, Inc. Certificate of Authorization #8064
Manufacturer:
Extreme Metal Fabricators, LLC.
2160 SW Poma Drive
Palm City, FL 34990
(772)872-8034
for
NTM. 20, r .
Florida Building Code 5th Edition (2014)
Method: 1- D
Category: Roofing
Sub - Category: Metal Roofing
SCANNED
BY
St. Lucie Countv
Product: 1" Nail Strip Roof Panel
Material: Steel
Panel Thickness: 26 gauge
Panel Width: 16"
Panel Seam: Snap -Lock
Support: Wood Deck
Digitally signed by James L. Buckner, P.E.
Electronically signed and sealed documents
shall comply with the provisions of FAC Rule
61G15-23.``It111111ftttr
Prepared by: �" • ��GENSF' • .Fp
James L. Buckner, P.E., SECB = * No 91242
Florida Professional Engineer # 31242
Florida Evaluation ANE ID: 1916
Project Manager: Youry Demosthenes STATE OF
Report No. 15-176-INS-S6W-ER
Date: 6 / 27 / 15
Contents:
Evaluation Report Pages 1-7
5. 7-04'00'
CBUCK, Inc.
1399 N. Killian Drive, Suite 4, West Palm Beach, Florida 33403
Phone: (561) 491-9927 • Email: cbuck@cbuckinc.net • Website: www.cbuckinc.net
CSUCK Engineering
SpecialN Structural Engineering
Manufacturer: Extreme Metal Fabricators, LLC.
Product Name: 1" Nail Strip
Product Category: Roofing
Product Sub -Category Metal Roofing
FL #: FL 17022.5 R2
Date: 6 / 27 / 15
Report No.: 15-176-1NS-S6W-ER
4
Page 2 of 7
CBUCK, Inc. Certificate of Authorization #8064
Compliance Method: State Product Approval Rule 61G20-3.005 (1) (d)
Product/System 1" Nail Strip Roof Panel, 26 gauge steel, 16" wide panel mechanically attached
Description: to Wood Deck „
Product Assembly as Refer to Page 4• of this report for product assembly components/materials &
Evaluated: standards:
1. Roof Panel
2. Fasteners
3. Adhesive (select system)
4. Underlayment
5. Insulation (Optional)
Support: Type:
Wood Deck
(Design of support system is outside the scope of this evaluation.)
Description:
• 15/32" or greater plywood,
• or Wood plank (min. specific gravity of 0.42)
Slope: Minimum slope shall be in compliance with FBC Chapter 15 Section 1507.4.2,
applicable code sections and in accordance with manufacturer's
recommendations.
Performance: Wind Uplift Resistance:
• Design Uplift Pressure (ASD): Refer to Table A
(Refer to `Table A" attachment details herein)
FL #: FL 17022.5 R2
Date: 6 / 27 / 15
CE3UCK Engineering Page Report No.: 3 of iN5-56W-ER
Spvciait,w Structural &ngineerInca CBUCK, inc. Certificate of Authorization #8064
Performance The product described herein has demonstrated compliance with:
Standards: • UL580-06—Testfor Uplift Resistance of Roof Assemblies
• UL 1897-04 —Uplift test for roof covering systems
Code Compliance: The product described herein has demonstrated compliance with Florida
Building Code 5th Edition (2014), Section 1504.3.2.
Evaluation Report This product evaluation is limited to compliance with the structural
Scope: requirements of the Florida Building Code, as related to the scope section to
Florida Product Approval Rule 61G20-3.001.
Limitations and Scope of "Limitations and Conditions of Use" for this evaluation:
Conditions of Use: This evaluation report for "Optional Statewide Approval" contains technical
documentation, specifications and installation method(s) which include
"Limitations and Conditions of Use" throughout the report in accordance
with Rule 61G20-3.005. Per Rule 61G20-3.004, the Florida Building
Commission is the authority to approve products under "Optional
Statewide Approval".
• Option for application outside "Limitations and Conditions of Use"
Rule 61G20-3.005(1)(e) allows engineering analysis for "project specific
approval by the local authorities having jurisdiction in accordance with the
alternate methods and materials authorized in the Code". Any modification
of the product as evaluated in this report and approved by the Florida
Building Commission is outside the scope of this evaluation and will be the
responsibility of others.
• Design of support system is outside the scope of this report.
• Fire Classification is outside the scope of Rule 61G20-3, and is therefore not
included in this evaluation.
• This evaluation report does not evaluate the use of this product for use in the
High Velocity Hurricane Zone code section. (Dade & Broward Counties)
Quality Assurance: The manufacturer has demonstrated compliance of roof panel products in
accordance with the Florida Building Code and Rule 61G20-3.005 (3) for
manufacturing under a quality assurance program audited by an approved
quality assurance entity through Keystone Certifications, Inc. (FBC Organization
ID# QUA 1824).
FL #: FL 17022.5 R2
Date: 6 / 27 / 15
g Page Report No.: 4 of 7 1N5 56W-ER
CSUCK Engineerin
Specialty Structural Engineerinq CBUCK, Inc. Certificate of Authorization #8064
Components/Materials Roof Panel: 1" Nail Strip
(by Manufacturer): Material: Steel
Thickness: 26 gauge (min.)
Panel Widths: 16" (max.) Coverage
Rib Height: 1"
Yield Strength: 40 ksi min.
Corrosion Resistance: Per FBC Section 1507.4.3
Fastener:
Type: Pancake -Head Wood Screw
Size: #10 x 1" (min.)
Corrosion Resistance: Per FBC Section 1506.6 and 1507.4.4
Standard: Per ANSI/ASME B18.6.1
Seam Adhesive/Sealant: (Select Systems)
Product Name: Bostik 915TM Chem -Chalk
Type: One component, polyurethane adhesive
Application Size: 3/16" continuous bead
Application Location: Along base of male rib vertical flange at each
panel seam. (Refer to Table `.'A" and drawing
Pg 6-7)
Components& Materials: Underlayment:
(by Others): Material and application shall be in compliance with FBC Section 1507.4.5.1 and
1507.4.5.2, applicable codes and in accordance with manufacturer's
recommendations.
Insulation (Optional):
Type:
Thickness:
Properties:
Density:
Or Compressive Strength:
Rigid Insulation Board
3" (max.)
2.25 pcf (lbs/ft3) min.
20 psi min.
Insulation Notes:
• Rigid Insulation shall meet minimum density OR compressive strength.
• Insulation shall comply with FBC Section 1508. When insulation is
incorporated, fastener length shall conform to penetrate thru bottom of
support a minimum of 3/16".
J
FL #: FL 17022.5 R2
®p t y Date: 6/27/15
CE3UCK Engin�rinc� Page rt No.: 5 of 7 1N5-S6W-ER
Speclalt j Structural Engineering CBUCK, Inc. Certificate of Authorization N8064
Installation: Installation Method:
(Refer to "TABLE A" below and drawings at the end of this evaluation report.)
• Fastener Spacing: Refer to "TABLE A" Below
(along the length of the panel)
• Rib Interlock: Snap -Lock
(Panel ribs shall be fully engaged to form an integral snap -lock.)
• Seam Adhesive: Refer to Table "A" & Drawing Page 6.
(Apply continuously along base of male rib vertical flange at each panel
seam.)
• Minimum fastener penetration thru bottom of support, 3/16".
• For panel construction at the end of panels, refer to manufacturer's
instructions and any site specific design.
TABLE "A"
ALLOWABLE LOADS
HOD 1
METHOD 2
Design Pressure (ASD)*:
- 97.25 PSF
Fastener Spacing:
6" o.c.
Seam Adhesive:
Not required
3/16" continuous bead
(Refer to pg. 6-7)
• Allowable design pressure(s) for allowable stress design (ASD) with a margin of
safety of 2 to 1.
Install the 1" Nail Strip roof panel assembly in compliance with the installation
method listed in this report and applicable code sections of FBC 5th Edition
(2014). The installation method described herein is in accordance with the
scope of this evaluation report. Refer to manufacturer's installation instructions
as a supplemental guide for attachment.
Referenced Data: 1. UL 580-06 & UL 1897-04— Uplift Test
By Architectural Testing, Inc. - West Palm Beach, FL
(FBC Organization #TST ID: 1527)
Report No. D8133.01-450-18, Date: 06/30/15, Specimens #1 & #2
2. Quality Assurance
Keystone Certifications, Inc. (FBC Organization ID# QUA 1824)
Extreme Metal Fabricators, Inc. Licensee #974
3. Certification of Independence
By James L. Buckner, P.E. @ CBUCK Engineering
(FBC Organization # ANE 1916)
FL #: FL 17022.5 R2
��//Repo
�f j j Date: 6 / 27 / 15
SUCK E gi neer•n� Page rt No.: 6 of 7 1NS-56W-ER
Specic ltLj Structural Englneerinq CBUCK, Inc. Certificate of Authorization #8064
Installation Method
Extreme Metal Fabricators, LLC.
1" Nail Strip (26 gauge steel) Roof Panel attached to Wood Deck
Drawings
16"
Panel Profile
16" o.c.
— —
3/4"
Deck:
-15132" or greater Plywood, or
- Wood plank
Integral Snap Lock
For METHOD 2:
Apply 3116" Bead Bostik 915' Sealant
Continuous Along Male Rib Vertical Flange
Fastener
#10 x 1" Min. per Table "A"
Pancake Head Wood Screw
Typical Assembly Profile View
(Typical Fastening Pattern Across Width)
J
FL #: FL 17022.5 R2
Date: 6 / 27 / 15
CHUCK Enginelzrinq Page Report No.: of 1N5-S6W-ER
SpcecialtLj Structural Engine2Prinq CBUCK, Inc. Certificate of Authorization #8064
V
Installation Method
Extreme Metal Fabricators, LLC.
1" Nail Strip (26 gauge Steel) Roof Panel attached to Wood Deck
rvl nrcmuu a
15/32" or greater Plywood, or Apply 3116" Bead Bostik 915T Sealant
- WaA plank Continuous Along Male Rib Vertical Flange
(Refer to Table "A)
Typical Roof Assembly
Isometric View
(Optional) Rigid Insulation Board per Page 4 of this report
TABLE "A"
ALLOWABLE LOADS
METHOD 1
METHOD 2
Design Pressure (ASD)*:
- 86 PSF
- 97.25 PSF
Fastener Spacing:
6" o.c.
6" o.c.
Seam Adhesive:
Not required
3/16" Continuous Bead
* Allowable design pressure(s) for allowable stress design (ASD) with a margin of
safety of 2 to 1.
il
ai WI.`f I� b Y
Speclalty Structural Englneering
Evaluation Report
1" Nail Strip
Metal Roof Assembly
Manufacturer:
CBUCK, Inc. Certificate of Authorization #8064
Extreme Metal Fabricators, LLC.
2160 SW Poma Drive
Palm City, FL 34990
(772)872-8034
for
Florida Product Approval
# FL 17022.5 R2
Florida Building Code 5th Edition (2014)
Method: 1- D
Category: Roofing
Sub - Category: Metal Roofing
Product:
Material:
Panel Thickness:
Panel Width:
Panel Seam:
Support:
Prepared by:
James L. Buckner, P.E., SECB
Florida Professional Engineer # 31242
Florida Evaluation ANE ID: 1916
Project Manager: Youry Demosthenes
Report No. 15-176-1NS-S6W-ER
Date: 6 / 27 / 15
Contents:
Evaluation Report Pages 1-7
SCANNED
BY
;l LUde County
1" Nail Strip Roof Panel
Steel
26 gouge
16"
Snap -Lock
Wood Deck
oigitallysigned by James L. Buckner, P.E.
Electronically signed and sealed documents
shall complywith the provisions of FAC Rule
61G15-23.11111111111
L. SUr, 6�ri
ENS�c'•.
*' No 31242 •'* `
7; 0 W =
B� AN STATE OF
tORID
2 ' 1: - 00,
CBUCK, Inc.
1399 N. Killian Drive, Suite 4, West Palm Beach, Florida 33403
Phone: (561) 491-9927 • Email: cbuck@cbuckinc.net • Website: www.cbuckinc.net
FL #: FL 17022.5 R2
g�j RRepo
Date: 6/ 27 / 15
CBUCK Engineering Pagert No.:2 of 7 1N5-56W-ER
Specianij Structural Enc =ring CBUCK, Inc. Certificate of Authorization f/8064
Manufacturer: Extreme Metal Fabricators, I LC.
Product Name: 1" Nail Strip
Product Category: Roofing
Product Sub -Category Metal Roofing
Compliance Method: State Product Approval Rule 61G20-3.005 (1) (d)
Product/System 1" Nail Strip Roof Panel, 26 gauge steel, 16" wide panel mechanically attached
Description: to Wood Deck
Product Assembly as Refer to Page 4 of this report for product assembly components/materials &
Evaluated: standards:
1. Roof Panel
2. Fasteners
3. Adhesive (select system)
4. Underlayment
5. Insulation (Optional)
Support: Type:
Wood Deck
(Design of support system is outside the scope of this evaluation.)
Description:
• 15/32" or greater plywood,
• or Wood plank (min. specific gravity of 0.42)
Slope: Minimum slope shall be in compliance with FBC Chapter 15 Section 1507.4.2,
applicable code sections and in accordance with manufacturer's
recommendations.
Performance: Wind Uplift Resistance:
• Design Uplift Pressure (ASD): Refer to Table A
}
(Refer to "Table A" attachment details herein)
FL M FL 17022.5 R2
Date: 6 / 27 / 15
Report No.: 15-176-INS-S6W-ER
Page 3 of 7
SpeclalW Structural Englneerincg CBUCK, Inc. Certificate of Authorization #8064
Performance The productdescribed herein has demonstrated compliance with:
Standards: • UL580-06 — Test for Uplift Resistance of Roof Assemblies
• UL 1897-04 — Uplift test for roof covering systems
Code Compliance: The product described herein has demonstrated compliance with Florida
Building Code 5th Edition (2014), Section 1504.3.2.
Evaluation Report This product evaluation is limited to compliance with the structural
Scope: requirements of the Florida Building Code, as related to the scope section to
Florida Product Approval Rule 61G20-3.001.
Limitations and • Scope of "Limitations and Conditions of Use" for this evaluation:
Conditions of Use: This evaluation report for "Optional Statewide Approval' contains technical
documentation, specifications and installation method(s) which include
"Limitations and Conditions of Use" throughout the report in accordance
with Rule 61G20-3.005. Per Rule 61G20-3.004, the Florida Building
Commission is the authority to approve products under "Optional
Statewide Approval'.
Quality Assurance:
• Ootion for aor lication outside "Limitations and Conditions of Use"
Rule 61G20-3.005(1)(e) allows engineering analysis for "project specific
approval by the local authorities having jurisdiction in accordance with .the
alternate methods and materials authorized in the Code". Any modification
of the product as evaluated in this report and approved by the Florida
Building Commission is outside the scope of this evaluation and will be the
responsibility of others.
• Design of support system is outside the scope of this report.
• Fire Classification is outside the scope of Rule 61G20-3, and is therefore not
included in this evaluation.
• This evaluation report does not evaluate the use of this product for use in the
High Velocity Hurricane Zone code section. (Dade & Broward Counties)
The manufacturer has demonstrated compliance of roof panel products in
accordance with the Florida Building Code and Rule 61G20-3.005 (3) for
manufacturing under a quality assurance program audited by an approved
quality assurance entity through Keystone Certifications, Inc. (FBC Organization
ID# QUA 1824).
a
FL #: FL 17022.5 R2
Date: 6 / 27 / 15
\,:E;UCK E in ri 4 of 7Report No.: -1N5-S6W-ER
Page 4 of 7
Speclalttd Structural Engineering CBUCK, Inc. Certificate of Authorization #8064
Components/Materials Roof Panel: 1" Nail Strip
(by Manufacturer): Material: Steel
Thickness: 26gauge (min.)
Panel Widths: 16" (max.) Coverage
Rib Height: 1"
Yield Strength: 40 ksi min.
Corrosion Resistance: Per FBC Section 1507.4.3
Fastener:
Type: Pancake -Head Wood Screw
Size: #10 x 1" (min.)
Corrosion Resistance: Per FBC Section 1506.6 and 1507.4.4
Standard: Per ANSI/ASME B38.6.1
Seam Adhesive/Sealant: (Select Systems)
Product Name: Bostik 915TM Chem -Chalk
Type: One component, polyurethane adhesive
Application Size: 3/16" continuous bead
Application Location: Along base of male rib vertical flange at each
panel seam. (Refer to Table "A" and drawing
Pg 6-7)
Components& Materials: Underlayment:
(by others): Material and application shall be in compliance with FBC Section 1507.4.5.1 and
1507.4.5.2, applicable codes and in accordance with manufacturer's
recommendations.
Insulation (Optional):
Type:
Thickness:
Properties:
Density:
Or Compressive Strength:
Rigid Insulation Board
3" (max.)
2.25 pcf (lbs/ft3) min.
20 psi min.
Insulation Notes:
• Rigid Insulation shall meet minimum density OR compressive strength.
• Insulation shall comply with FBC Section 1508. When insulation is
incorporated, fastener length shall conform to penetrate thru bottom of
support a minimum of 3/16".
FL #: FL 17022.5 R2
Date: 6 / 27 / 15
�� - �� Report No.: 15-176-INS-S6W-ER
Page 5 of 7
Spsalaffij Structural Englneerinq CBUCK, Inc. Certificate of Authorization #8054
Installation: Installation Method:
(Refer to `TABLE A" below and drawings at the end of this evaluation report.)
• Fastener Spacing: Refer to "TABLE A" Below
(along the length of the panel)
• Rib Interlock: Snap -Lock
(Panel ribs shall be fully engaged to form an integral snap -lock.)
• Seam Adhesive: Refer to Table "A" & Drawing Page 6.
(Apply continuously along base of male rib vertical flange at each panel
seam.)
• Minimum fastener penetration thru bottom of support, 3/16".
• For panel construction at the end of panels, refer to manufacturer's
instructions and any site specific design.
TABLE "A"
ALLOWABLE LOADS
METHOD 1
METHOD 2
Design Pressure (ASD)*:
- 86 PSF
- 97.25 PSF
Fastener Spacing:
6" o.c.
6" o.c.
3/16" continuous bead
Seam Adhesive:
Not required
(Refer to pg. 6-7)
* Allowable design pressure(s) for allowable stress design (ASD) with a margin of
safety of 2 to 1.
Install the 1" Nail Strip roof panel assembly in compliance with the installation
method listed in this report and applicable code sections of FBC 5th Edition
(2014). The installation method described herein is in accordance with the
scope of this evaluation report. Refer to manufacturer's installation instructions
as a supplemental guide for attachment.
Referenced Data: 1. UL580-06 & UL 1897-04 — Uplift Test
By Architectural Testing, Inc. - West Palm Beach, FL
(FBC Organization #TST ID: 1527)
Report No. D8133.01-450-18, Date: 06/30/15, Specimens #1 & #2
2. Quality Assurance
Keystone Certifications, Inc. (FBC Organization ID# QUA 1824)
Extreme Metal Fabricators, Inc. Licensee #974
3. Certification of Independence
By James L. Buckner, P.E. @ CBUCK Engineering 9
(FBC Organization # AN 1916) Lt W I
FL #: FL 17022.5 R2
Date: 6 / 27 / 15
g��� Report No.: 15-176-1NS-S6W-ER
tl Page 6 of 7
SpeclaltLj Structural EnglneErinq CBUCK, Inc. Certificate of Authorization #8064
Installation Method
Extreme Metal Fabricators, LLC.
1" Nail Strip (26 gauge Steel) Roof Panel attached to Wood Deck
Drawings
Panel Profile
16" o.c.
— —
3/4"
Deck:
-15/32" or greater Plywood, or
- Wood plank
Integral Snap Lock
For METHOD 2:
Apply 3/16" Bead Bostik 915TM Sealant
Continuous Along Male Rib Vertical Flange
fk
Fastener
#10 X 1" Min. per Table "A"
Pancake Head Wood Screw
Typical Assembly Profile View i tll
YP Y
(Typical Fastening Pattern Across Width
YP g ) ,
FL #: FL 17022.5 R2
BUCKBUCKe�f j p� Date: 6 / 27 / 15
E gineerl�"� PageReport No. 7 of 7 1NS-56W-ER
Specialty Structural EnglnslPrinq CBUCK, Inc. Certificate of Authorization #8064
1"
Installation Method
Extreme Metal Fabricators, LLC.
1" Nail Strip (26 gauge Steel) Roof Panel attached to Wood Deck
rur inemuu c
-15/32" or greater Plywood, or Apply 3116" Bead Bostik 915TM Sealant
- Wood plank Continuous Along Male Rib Vertical Flange
(Refer to Table "A")
Typical Roof Assembly
Isometric View
(Optional) i Rigid Insulation Board per Page 4 of this report
TABLE "A"
ALLOWABLE LOADS
METHOD 1
METHOD 2
Design Pressure (ASD)*:
- 86 PSF
- 97.25 PSF
Fastener Spacing:
6" o.c.
6" o.c.
Seam Adhesive:
Not required
3/16" Continu a
*Allowable design
safety of 2 to 1.
pressure(s) for allowable stress design (ASD) with o margmu
a ,.