HomeMy WebLinkAboutINSPECTION REPORTInspection Date: July 18, 2016
Saint Lucy County
Building & Code Regulation Division
2300 Virginia Avenue
Fort Pierce, FL 34982
Subject: Inspection Report 1 of 1— Final Certification
Verizon Site: 68858 (SBA Midway Road)
Site Address: 375 E Midway Road
Fort Pierce, FL 34982
CALTROP Project: 16-1069.02
Dear Building Official:
CALTROP Corporation performed a review of the field
telecommunication facility located at the above -referenced site,
inspect the following:
• Installation of six proposed antennas.
• Installation of three proposed antenna mounts.
• Installation of proposed power cabinet.
• Installation of proposed battery cabinet.
• Installation of proposed fiber cabinet.
• Installation of proposed diesel generator.
• Installation of proposed propane tank.
• Installation of concrete equipment pad.
• Installation of proposed equipment canopy.
• Installation of Verizon Wireless utility H-Frame.
1601.00 -one0�VX)X
ffigassupew
RECEIVE®
AUG 0 4120%
PERMITTING
St. Lucie County, FL
SCANNED
BY
St Lucie County
documentation of the Verizon Wireless
The purpose of these observations was to
• Installation of proposed cable bridge.
• Installation of (3)#3/0 and (1)#6GND in 4"C. for the 200A generator feed.
• Installation of final electrical work (conductors, grounding, and welds).
Tower documentation consisting of construction photographs depicting the connection of the above
mentioned installation(s) taken from the ground and from the top of the tower by a certified tower climber
as well as the CALTROP field documentation were reviewed and compared with the approved
construction drawings prepared by CALTROP Corporation dated February 10, 2016. Based on these
observations and to the best of my knowledge and belief, the above -described construction of all
structural load -bearing components complies with the permitted documents. In addition, the installation of
the #3/0 wires and #6gnd in 4"C. for a 200A feed complies with 2011 NEC.
Should you have any questions or wish to discuss any aspect of this letter,
contact the undersigned.
Sincerely,
CALTROP Corporation
Michael A. Phillips
Principal Engineer
Florida Registration #68312
�,
;4 eft re or. -..(q
r� si' '• Q & 1 D . '�a tie
� t^
a���Q� �icst�•
to