Project No. 16-175 Report No. 1
cc: Gene Ross Elliott Merrill
Bob Stark Structure -Con.
Joe Cicio SLC Bldg Dept
File
OCEAN HARBOR SOUTH CONDOMINIUMS CONCRETE REPAIRS°
4200 NORTH HIGHWAY AIA, FT. PIERCE, FLORIDA
THRESHOLD INSPECTION REPORT
SLC BUILDING PERMIT NUMBER: 1608-0115
PROJECT NAME: Ocean Harbor South- Bldg B DATE: May 11, 2017
CLIENT:
Elliott Merrill Community Mgt.
LOCATION:
Ft. Pierce, Florida
CONTRACTOR:
Structure -Con
PROJECT MGR:
Khris McConnell
INSPECTED BY:
Mike Lue
WEATHER:
clear , hot 900
WORK INSPECTED:
Building B — South Building — Unit 209
Demolition has been in progress an almost complete except that at the east door additional excavation is
required due to severely corroded bars found under the east door track.
Observations
Slab edges
The slab edges and surface spalls have been excavated. There are (4) pt cables along the north edge that
where the existing anchors were located too far back in from the slab edges. New cables and anchors
were placed by the PT specialist to repair the slab edge. All reinforcing at these areas have been cleaned
and coated with a corrosion inhibitor and this area can be poured.
Surface spalls
East Door
The bars are severely corroded with a greater than 20% loss of sections under the door going into the unit.
New #6 additional reinforcing is required to be either spliced with the proper lap lengths or epoxy anchor
new dowels with a minimum of 6" epoxy embedment. A dust wall will be required at this door.
North Door
The reinforcing at these areas do not need replacement and the existing bars can be cleaned and coated.
The sliding glass doors can remain, however the door track anchors in the bottom track are to be replaced
with new diameter stainless steel tapcons with 1" max embedment in holes sealed with polyurethane
sealant. It appears that moisture was migrating into the slab through the existing fastener holes which
contributed to the deterioration.
North wall
There is one deteriorated bar in the north south direction coming out of the wall that needs replacement.
Provide new #4 dowel with 4" epoxy embedment and lapped to the existing bar.
L
M L Engineering, Inc.
Consulting Engineers
2030 37" Avenue
Vero Beach, Florida 32960
Phone (772) 569-1257
Fax (772)569-4041
mleagineeringine.com
f;
._ '�:r rosriti
i
�r'zw
Project No. 16-175 Report No.1
cc: Gene Ross Elliott Merrill
Bob Stark Structure -Con.
Joe Cicio SLC Bldg Dept
File
Plc2
East Door
Corroded bars under door
that will require additional
bars.
See closer view in Pic 3
Pic 3
Bar is corroded almost
completely through under
the door pan
2
M L Engineering, Inc. jI ANNED Project No. 16-175 Report No. 2
Consulting Engineers cc: Gene Ross Elliott Merrill
2030 37° Avenue BY Bob Stark Structure -Con.
Vern Beach, Florida 32960 St. Lucie County Joe Cicio SLC Bldg Dept
Phone (772) 569-1257 File
Fax (772)569-4041
mlengineeringinc.com
OCEAN HARBOR SOUTH CONDOMINIUMS CONCRETE REPAIRS
4200 NORTH HIGHWAY AIA, FT. PIERCE, FLORIDA
THRESHOLD INSPECTION REPORT
SLC BUILDING PERMIT NUMBER: 1608-0115
PROJECT NAME: Ocean Harbor South- Bldg B DATE: May 30, 2017
CLIENT:
Elliott Merrill Community Mgt.
LOCATION:
Ft. Pierce, Florida
CONTRACTOR:
Structure -Con
PROJECT MGR:
Khris McConnell
INSPECTED BY:
Mike Lue
WEATHER:
clear, hot 90'
WORK INSPECTED:
Building B — South Building
Unit 209 Final
All concrete repairs to unit has been completed. The aluminum screen enclosure at unit 109 below is to be
painted and re -screened.
Unit 410 — Work in progress
The demolition is complete and the reinforcing bars have been cleaned and coated with corrosion
inhibitor. The floor spall has been approved for concrete pour. The column dowels are to be moved
within the column ties and bent back into the column to provide the maximum possible concrete cover,
prior to placing concrete.
Column Repair
M L Engineering, Inc.
Project No. 16-175
Report No. 3
Consulting Engineers
cc: Gene Ross
Elliott Merrill
2030 37" Avenue
SCANNED
Bob Stark
Structure -Con.
Vero Beach, Florida 32960
Joe Cicio
SLC Bldg Dept
Phone (772) 569-1257
BY
File
Fax (772)5694041
mlengineeringinc.mm
St. Lucie Gounb
OCEAN HARBOR SOUTH CONDOMINIUMS CONCRETE REPAIRS
4200 NORTH HIGHWAY AIA, FT. PIERCE, FLORIDA
THRESHOLD INSPECTION REPORT
SLC BUILDING PERMIT NUMBER: 1608-0115
PROJECT NAME: Ocean Harbor South- Bldg B DATE: June 9, 2017
CLIENT: Elliott Merrill Community Mgt.
CONTRACTOR: Structure -Con
INSPECTED BY: Mike Lue
WORK INSPECTED:
Building B — South Building
Unit 209 Final -Completed
LOCATION: Ft. Pierce, Florida
PROJECT MGR: Khris McConnell
WEATHER: clear, hot 90'
Unit 410 Final- Completed except the bottom shutter track is to be placed. Note inserts to be placed in
holes filled with urethane sealant.
Unit 411 Work in progress
All deteriorated areas have been excavated and the existing reinf cleaned and coated with
corrosion inhibitor per plans.
Add a #4 bar in ceiling area next to corroded bar with 24" lap each side of corroded
section.
Remove section of dove tail extrusion in column section
Pour areas with the specified repair mortars
M L Engineering, Inc.
Consulting Engineers
2030 37" Avenue
Vero Beach, Florida 32960
Phone (772)569-1257
Fax (772) 5694041
mlengineeringinc.com
Project No. 16-175 Report No. 3
cc: Gene Ross Elliott Merrill
Bob Stark Structure -Con.
Joe Cicio SLC Bldg Dept
File
Unit 411— ceiling spall
Add #4 bar next to corroded bar
with 24" lap each side
Corroded bar above door head
2
M L Engineering, Inc.
Project No. 16-175
Report No. 4
Consulting Engineers
SCANNED
cc: Gene Ross
Elliott Merrill
2030 3r Avenue
B
Bob Stark
Structure -Con.
Vero Beach, Florida 32960
Phone (772) 569-1257
r
r
St. Lucie County
Joe Cicio
File
SLC Bldg Dept
Fax (772)569-4041
mlengineeringine.com
OCEAN HARBOR SOUTH CONDOMINIUMS CONCRETE REPAIRS
4200 NORTH HIGHWAY AIA, FT. PIERCE, FLORIDA
THRESHOLD INSPECTION REPORT
SLC BUILDING PERMIT NUMBER: 1608-0115
PROJECT NAME: Ocean Harbor South- Bldg B DATE: June 19, 2017
CLIENT:
Elliott Merrill Community Mgt.
LOCATION:
Ft. Pierce, Florida
CONTRACTOR:
Structure -Con
PROJECT MGR:
Khris McConnell
INSPECTED BY:
Mike Lue
WEATHER:
clear, hot 90'
WORK INSPECTED:
Building B
Unit 809 South Building
Observations
Demolition was complete at the balcony edges but further demolition is required at the ceiling and surface
areas noted on the repair plan.
Reinforcing has been cleaned and coated as per specs, additional support chairs are required under bottom
bars
There are 14 post tension cables affected, most of which have been locked off and spliced, others have
been block out to be spliced after the first pour. Note that this repair has affected all (14) the post tension
cables on the entire balcony edge.
Recommendations
Provide support chairs under the bottom bars to insure a minimum concrete cover of 1 '/2".
Clean and coat all reinforcing bars with corrosion inhibitor as per plans.
Pour between the cables as sequenced by the post tension sub -contractor. PT cables may be restressed
only after a minimum compressive strength of 3,000 psi has been achieved.
Continue demolition at other deteriorated areas as plan.
Provide new stainless steel anchors for railing posts base plates
:.ia.G Til401urig�c�-ida®1_1i.` �_\A� -_
M L Engineering, Inc.
Consulting Engineers
2030 37� Avenue
Vero Beach, Florida 32960
Phone (772) 569-1257
Fax (772)569-4041
ndengineeringinc.com
SCANNED
BY
St. Lucie County
Project No. 16-175
cc: Gene Ross
Bob Stark
Joe Cicio
File
OCEAN HARBOR SOUTH CONDOMINIUMS CONCRETE REPAIRS
4200 NORTH HIGHWAY AIA, FT. PIERCE, FLORIDA
THRESHOLD INSPECTION REPORT
SLC BUILDING PERMIT NUMBER: 1608-0115
Report No. 5
Elliott Merrill
Structure -Con.
SLC Bldg Dept
PROJECT NAME: Ocean Harbor South- Bldg B DATE: September 29, 2017
CLIENT:
Elliott Merrill Community Mgt.
LOCATION:
Ft. Pierce, Florida
CONTRACTOR:
Structure -Con
PROJECT MGR:
Khris McConnell
INSPECTED BY:
Mike Lue
WEATHER:
Overcast
WORK INSPECTED:
Building B
Unit 411 & 809 South Building
Observations
Unit 411
There was a ceiling repair which was located on each side of the sliding glass door. The contractor has
repaired the stucco at the repair and painted to match existing surrounding areas.
The door track does not have any caulking on the exterior side of door. The contractor shall provide a
strip of caulking to match existing.
Unit 809
All repairs are complete and guardrails were re -installed with new fasteners. The hurricane shutter track
was set too high and the shutters are in -operable. The track shall be adjusted so the shutters work
properly.
M L Engineering, Inc.
Consulting Engineers
203037' Avenue
Vero Beach, Florida 32960
Phone(772) 569-1257
Fax (772) 569-4041
mlengineeringinc.com
Project No. 16-175
cc: Gene Ross
Bob Stark
Joe Cicio
File
Report No. 5
Elliott Merrill
Structure -Con.
SLC Bldg Dept
Plc 1
Unit 411 -balcony ceiling repair
with no caulking at door track
2
M L Engineering, Inc. Project No. 16-175 Report No. 6
Consulting Engineers Jl ANNED cc: Gene Ross Elliott Merrill
2030 37' Avenue Bob Stark structure -Con.
Vero Beach, Florida 32960 Lucie
Joe Cicio SLC Bldg Dept
Phone (772) 569-1257 3t Lucie County File
Fax (772) 5694041 `Y
mlengineeringinc.com
OCEAN HARBOR SOUTH CONDOMINIUMS CONCRETE REPAIRS
4200 NORTH HIGHWAY AIA, FT. PIERCE, FLORIDA
THRESHOLD INSPECTION REPORT
SLC BUILDING PERMIT NUMBER: 1608-0115
PROJECT NAME: Ocean Harbor South- Bldg B - DATE: October 11, 2017
CLIENT:
Elliott Merrill Community Mgt.
LOCATION:
Ft. Pierce, Florida
CONTRACTOR:
Structure -Con
PROJECT MGR:
Khris McConnell
INSPECTED BY:
Mike Lue
WEATHER:
Sunny
WORK INSPECTED:
Building B
Unit 411 & 809 South Building
Observations
The contractor has corrected the deficiencies from the last report as follows:
Unit 411
A strip of caulking has been placed along the sliding glass door top track to match existing.
Unit 809
The hurricane shutter track has been adjusted and the shutters work properly.
r{.urrtCA
rry AN7
v�CEIV
�Ti4TE OF ..
.40ye, P.E.
s0/.�R1� G
ANAL"EN .
�rr�rrer>fi���
1
M L Engineering, Inc. '
Consulting Engineers
2030 371h Avenue SCANNED
Vero Beach, Florida 32960
Phone (772) 569-1257 BY
Fax (772) 5694041 St. Lucie County
mlengineeringinc.com
Proi:,le. No. 16-175 Report No. 5
cc: Gene Ross Elliott Merrill
Bob Stark Structure -Con.
Joe Cicio SLC Bldg Dept
File
OCEAN HARBOR SOUTH CONDOMINIUMS CONCRETE REPAIRS
4200 NORTH HIGHWAY AlA, FT. PIERCE, FLORIDA
THRESHOLD INSPECTION REPORT
SLC BUILDING PERMIT NUMBER 1608-Oi 15
PROJECT NAME: Ocean Harbor South- Bldg B DATE: September 29, 2017
CLIENT: Elliott Merrill Community Mgt. LOCATION: Ft. Pierce, Florida
CONTRACTOR: Structure -Con PROJECT MGR: Khris McConnell
INSPECTED BY: Mike Lue WEATHER: Overcast
WORK INSPECTED:
Building B FILtz Unit in & 809 South Building0 Py
Observations
Unit 411
There was a ceiling repair which was located on each side of the sliding glass door. The contractor has
repaired the stucco at the repair and painted to match existing surrounding areas.
The door track does not have any caulking on the exterior side of door. The contractor shall provide a
strip of caulking to match existing.
Unit 809
All repairs are complete and guardrails were re -installed with new fasteners. The hurricane shutter track
was set too high and the shutters are in -operable. The track shall be adjusted so the shutters work
properly.
FE9
OCT - 9 =
4
M L Engineering, Inc.
Consulting Engineers
2030 371h Avenue
Vero Beach, Florida 32960
Phone (772) 569-1257
Fax (772)569-4041
mlengineeringinc.com
Pr ioi ' No. 16-175 Report No. 5
cc: Gene Ross Elliott Merrill
Bob Stark Structure -Con.
Joe Cicio SLC Bldg Dept
File
Pic 1
Unit 411 -balcony ceiling repair
with no caulking at door track
M L Engineering, Inc. Pr(q..:. No. 16-175 Report No. 5
Consulting Engineers SCANNED cc: Gene Ross Elliott Merrill
2030 371h Avenue BY Bob Stark Structure -Con.
Vero Beach, Florida 32960 Joe Cicio SLC Bldg Dept
Phone (772) 569-1257 St. Lucie Countv File
Fax (772) 569-4041
mlengineeringinc.com
OCEAN HARBOR SOUTH CONDOMINIUMS CONCRETE REPAIRS
4200 NORTH HIGHWAY AIA, FT. PIERCE, FLORIDA
THRESHOLD INSPECTION REPORT
SLC BUILDING PERMIT NUMBER: 1608-0115
PROJECT NAME:
Ocean Harbor South- Bldg B DATE: September 29, 2017
CLIENT:
Elliott Merrill Community Mgt. LOCATION: Ft. Pierce, Florida
CONTRACTOR:
Structure -Con PROJECT MGR: Khris McConnell
INSPECTED BY:
Mike Lue WEATHER: Overcast
WORK INSPECTED:
Building B FILE
Unit 411 & 809 South Building
Observations
Unit 411
There was a ceiling repair which was located on each side of the sliding glass door. The contractor has
repaired the stucco at the repair and painted to match existing surrounding areas.
The door track does not have any caulking on the exterior side of door. The contractor shall provide a
strip of caulking to match existing.
Unit 809
All repairs are complete and guardrails were re -installed with new fasteners. The hurricane shutter track
was set too high and the shutters are in -operable. The track shall be adjusted so the shutters work
properly.
-.4k
M L Engineering, Inc.
Consulting Engineers
2030 37" Avenue
Vero Beach, Florida 32960
Phone(772) 569-1257
Fax (772) 5694041
mlengineeringinc.com
PrGj ," No. 16-175
cc: Gene Ross
Bob Stark
Joe Cicio
File
Report No. 5
Elliott Merrill
Structure -Con.
SLC Bldg Dept
Pic 1
Unit 411 -balcony ceiling repair
with no caulking at door track
M L Engineering, Inc.
Prq,- , No. 16-175
Report No. 5
Consulting Engineers
cc: Gene Ross
Elliott Merrill
2030371°Avenue
�I:HI�INED
Bob Stark
Structure -Con.
Vero Beach, Florida 32960
Phone 569-1257
pv
B
Joe Cicio
SLC Bldg Dept
(772)
T
File
Fax (772)5694041
�t.LucieCounty
ndengineeringinc.com
1 HARBOR SOUTH CONDOMINIUMS CONCRETE REPAIRS
4200 NORTH HIGHWAY AIA, FT. PIERCE, FLORIDA
THRESHOLD INSPECTION REPORT
SLC BUILDING PERMIT NUMBER: 1608-0115
PROJECT NAME: Ocean Harbor South- Bldg B DATE: September 29, 2017
CLIENT: Elliott Merrill Community Mgt. LOCATION: Ft. Pierce, Florida
CONTRACTOR: Structure -Con PROJECT MGR: Khris McConnell
INSPECTED BY: Mike Lue WEATHER: Overcast
WORK INSPECTED:
Building B
Unit 411 & 809 South Building 00F)PY
Observations � � _
Unit 411
There was a ceiling repair which was located on each side of the sliding glass door. The contractor has
repaired the stucco at the repair and painted to match existing surrounding areas.
The door track does not have any caulking on the exterior side of door. The contractor shall provide a
strip of caulking to match existing.
Unit 809
All repairs are complete and guardrails were re -installed with new fasteners. The hurricane shutter track
was set too high and the shutters are in -operable. The track shall be adjusted so the shutters work
properly.
M V
OCT - 9 =
M L Engineering, Inc. '
Consulting Engineers
2030 371h Avenue
Vero Beach, Florida 32960
Phone (772) 569-1257
Fax (772) 5694041
mlengineeringinc.com
Pru' juut No. 16-175
cc: Gene Ross
Bob Stark
Joe Cicio
File
Report No. 5
Elliott Merrill
Slrucmre-Con.
SLC Bldg Dept
Plc 1
Unit 411 -balcony ceiling repair
with no caulking at door track
2
r
M L Engineering, Inc.
Consulting Engineers
SCANNED
2030 37" Avenue
BY
Vero Beach, Florida 32960
Phone (772) 569-1257
St. Lucie Count%,
Fax (772)569-4041
mlengineeringinc.com
Project iio. 16-175 Report No. 4
cc: Gene Ross Elliott Merrill
Bob Stark Structure -Con.
Joe Cicio SLC Bldg Dept
File
OCEAN HARBOR SOUTH CONDOMINIUMS CONCRETE REPAIRS
4200 NORTH HIGHWAY AIA, FT. PIERCE, FLORIDA
THRESHOLD INSPECTION REPORT
SLC BUILDING PERMIT NUMBER: 1608-0115
PROJECT NAME: Ocean Harbor South- Bldg B DATE: June 19, 2017
CLIENT:
Elliott Merrill Community Mgt.
LOCATION:
Ft. Pierce, Florida
CONTRACTOR:
Structure -Con
PROJECT MGR:
Khris McConnell
INSPECTED BY:
Mike Luc
WEATHER:
clear, hot 90'
WORK INSPECTED:
Building B
Unit 809 South Building
Observations
Demolition was complete at the balcony edges but further demolition is required at the ceiling and surface
areas noted on the repair plan.
Reinforcing has been cleaned and coated as per specs, additional support chairs are required under bottom
bars
There are 14 post tension cables affected, most of which have been locked off and spliced, others have
been block out to be spliced after the first pour. Note that this repair has affected all (14) the post tension
cables on the entire balcony edge.
Recommendations
Provide support chairs under the bottom bars to insure a minimum concrete cover of 1 r/z".
Clean and coat all reinforcing bars with corrosion inhibitor as per plans.
Pour between the cables as sequenced by the post tension sub -contractor. PT cables may be restressed
only after a minimum compressive strength of 3,000 psi has been achieved.
Continue demolition at other deteriorated areas as plan.
Provide new stainless steel anchors for railing posts base plates
M L Engineering, Inc.
Consulting Engineers
2030 37"Avenue
Vero Beach, Florida 32960
Phone(772) 569-1257
Fax (772)569-4041
mlengineeringinc.com
Project i4o. 16-175 Report No. 4
cc: Gene Ross Elliott Merrill
Bob Stark Structure -Con.
Joe Cicio SLC Bldg Dept
File
Plc 1
East balcony edge showing extent
of pt cable splices
Pic 2
North balcony edge
Pic 3
Ceiling spall require further
demolition
2
M L Engineering, Inc. $(,(�NIVtu
Consulting Engineers
203037' Avenue BY
Vero Beach, Florida 32960 St. Lucie County
Phone (772) 569-1257
Fax (772) 5694041
mlenginmringinc.com
Project No. 16-175 Report No. 4
cc: Gene Ross Elliott Merrill
Bob Stark Structure -Con.
Joe Cicio SLC Bldg Dept
File
OCEAN HARBOR SOUTH CONDOMINIUMS CONCRETE REPAIRS
4200 NORTH HIGHWAY AIA, FT. PIERCE, FLORIDA
THRESHOLD INSPECTION REPORT
SLC BUILDING PERMIT NUMBER: 1608-0115
PROJECT NAME: Ocean Harbor South- Bldg B DATE: June 19, 2017
CLIENT: Elliott Merrill Community Mgt.
CONTRACTOR: Structure -Con
INSPECTED BY: Mike Lue
WORK INSPECTED:
Building B
Unit 809 South Building
LOCATION: Ft. Pierce, Florida
PROJECT MGR: Khris McConnell
WEATHER: clear, hot 90'
Observations
Demolition was complete at the balcony edges but further demolition is required at the ceiling and surface
areas noted on the repair plan.
Reinforcing has been cleaned and coated as per specs, additional support chairs are required under bottom
bars
There are 14 post tension cables affected, most of which have been locked off and spliced, others have
been block out to be spliced after the first pour. Note that this repair has affected all (14) the post tension
cables on the entire balcony edge.
Recommendations
Provide support chairs under the bottom bars to insure a minimum concrete cover of 1 %2".
Clean and coat all reinforcing bars with corrosion inhibitor as per plans.
Pour between the cables as sequenced by the post tension sub -contractor. PT cables may be restressed
only after a minimum compressive strength of 3,000 psi has been achieved.
Continue demolition at other deteriorated areas as plan.
Provide new stainless steel anchors for railing posts base plates
M L Engineering, Inc.
Consulting Engineers
2030 37a Avenue
Vero Beach, Florida 32960
Phone (772) 569-1257
Fax (772) 569AO41
n lengineeringinc.com
Project No. 16-175 Report No. 4
cc: Gene Ross Elliott Merrill
Bob Stark Structure -Con.
Joe Cicio SLC Bldg Dept
File
Plc 1
East balcony edge showing extent
of pt cable splices
Pic 2
North balcony edge
Pic 3
Ceiling spall require further
demolition
M L Engineering, Inc.
�)UANNED
ProjecTNo. 16-175
Report No. 4
Consulting Engineers
BY
cc: Gene Ross
Elliott Merrill
2030 37" Avenue
7l ucle CQljn�y
Bob Stark
Structure -Con.
Vero Beach, Florida 32960
Joe Cicio
SLC Bldg Dept
Phone (772) 569-1257
File
Fax (772) 5694041
mlengineeringine.com
OCEAN HARBOR SOUTH CONDOMINIUMS CONCRETE REPAIRS
4200 NORTH HIGHWAY AIA, FT. PIERCE, FLORIDA
THRESHOLD INSPECTION REPORT
SLC BUILDING PERMIT NUMBER: 1608-0115
PROJECT NAME: Ocean Harbor South- Bldg B
CLIENT: Elliott Merrill Community Mgt.
CONTRACTOR: Structure -Con
INSPECTED BY: Mike Lue
WORK INSPECTED:
Building B
Unit 809 South Building
DATE: June 19, 2017
LOCATION: Ft. Pierce, Florida
PROJECT MGR: Khris McConnell
WEATHER: clear. hot 90'
Observations
Demolition was complete at the balcony edges but further demolition is required at the ceiling and surface
areas noted on the repair plan.
Reinforcing has been cleaned and coated as per specs, additional support chairs are required under bottom
bars
There are 14 post tension cables affected, most of which have been locked off and spliced, others have
been block out to be spliced after the first pour. Note that this repair has affected all (14) the post tension
cables on the entire balcony edge.
Recommendations
Provide support chairs under the bottom bars to insure a minimum concrete cover of 1 %".
Clean and coat all reinforcing bars with corrosion inhibitor as per plans.
Pour between the cables as sequenced by the post tension sub -contractor. PT cables may be restressed
only after a minimum compressive strength of 3,000 psi has been achieved.
Continue demolition at other deteriorated areas as plan.
Provide new stainless steel anchors for railing posts base plates
, ,/;F
NOW F
M L Engineering, Inc. Pra.: i No. 16-175 Report No. 3
Consulting Engineers cc: Gene Ross Elliott Merrill
203037u Avenue SCANNED Bob Stark Structure -Con.
Vero Beach, Florida 32960 V Joe Cicio SLC Bldg Dept
Phone (772) 569-1257 BY File
Fax (772) 569-4041 St. Lucie Countv
mlengineeringi nc. com
OCEAN HARBOR SOUTH CONDOMINIUMS CONCRETE REPAIRS
4200 NORTH HIGHWAY AIA, FT. PIERCE, FLORIDA
THRESHOLD INSPECTION REPORT
SLC BUILDING PERMIT NUMBER: 1608-0115
PROJECT NAME: Ocean Harbor South- Bldg B DATE: June 9, 2017
CLIENT:
Elliott Merrill Community Mgt.
LOCATION:
Ft. Pierce, Florida
CONTRACTOR:
Structure -Con
PROJECT MGR:
Khris McConnell
INSPECTED BY:
Mike Lue
WEATHER:
clear, hot 90'
WORK INSPECTED:
Building B — South Building
Unit 209 Final -Completed
Unit 410 Final- Completed except the bottom shutter track is to be placed. Note inserts to be placed in
holes filled with urethane sealant.
Unit 411 Work in progress
All deteriorated areas have been excavated and the existing reinf cleaned and coated with
corrosion inhibitor per plans.
Add a #4 bar in ceiling area next to corroded bar with 24" lap each side of corroded
section.
Remove section of dove tail extrusion in column section
Pour areas with the specified repair mortars
M L Engineering, Inc.
Consulting Engineers
2030 376 Avenue
Vero Beach, Florida 32960
Phone (772) 569-1257
Fax (772)569-4041
mlengineeringinc.com
Proj_ No. 16-175 Report No. 3
cc: Gene Ross Elliott Merrill
Bob Stark Structure -Con.
Joe Cicio SLC Bldg Dept
File
2
M L Engineering, Inc.
Consulting Engineers
2030 371h Avenue
Vero Beach, Florida 32960
Phone (772) 569-1257
Fax (772) 569-4041
mlengineeringinc.com
SCANNED
BY
St. Lucie Counh/
Prc,j� ,. No. 16-175
cc: Gene Ross
Bob Stark
Joe Cicio
File
OCEAN HARBOR SOUTH CONDOMINIUMS CONCRETE REPAIRS
4200 NORTH HIGHWAY AlA, FT. PIERCE, FLORIDA
THRESHOLD INSPECTION REPORT
SLC BUILDING PERMIT NUMBER: 1608-0115
PROJECT NAME: Ocean Harbor South- Bldg B
CLIENT: Elliott Merrill Community Mgt.
CONTRACTOR: Structure -Con
INSPECTED BY: Mike Lue
WORK INSPECTED:
Building B — South Building
Unit 209 Final -Completed
Report No. 3
Elliott Merrill
Structure -Con.
SLC Bldg Dept
DATE: June 9, 2017
LOCATION: Ft. Pierce, Florida
PROJECT MGR: Kkris McConnell
WEATHER: clear, hot 90'
Unit 410 Final- Completed except the bottom shutter track is to be placed. Note inserts to be placed in
holes filled with urethane sealant.
Unit 411 Work in progress
All deteriorated areas have been excavated and the existing reinf cleaned and coated with
corrosion inhibitor per plans.
Add a #4 bar in ceiling area next to corroded bar with 24" lap each side of corroded
section.
Remove section of dove tail extrusion in column section
Pour areas with the specified repair mortars
L0
M L Engineering, Inc.
Consulting Engineers
2030 37" Avenue
Vero Beach, Florida 32960
Phone (772) 569-1257
Fax (772)569-4041
mlengineeringinc, com
Project No. 16-175 Report No. 3
cc: Gene Ross Elliott Merrill
Bob Stark Structure -Con.
Joe Cicio SLC Bldg Dept
File
Unit 411— ceiling spall
Add #4 bar next to corroded bar
with 24" lap each side
Corroded bar above door head
`A
M L Engineering, Inc.
Coflsulting Engineers
2030 371h Avenue
Vero Beach, Florida 32960
Phone (772) 569-1257
Fax (772) 569-4041
;mlengineeringinc.com
�UTANNED
BY
it liripCour
Project Nc-'5-175 Report No. 2
cr die Ross Elliott Merrill
: w Stark Structure -Con.
Joe Cicio SLC Bldg Dept
File
OCEAN HARBOR SOUTH CONDOMINIUMS CONCRETE REPAIRS
4200 NORTH HIGHWAY AlA, FT. PIERCE, FLORIDA
THRESHOLD INSPECTION REPORT
SLC BUILDING PERMIT NUMBER: 1608-0115
PROJECT NAME: Ocean Harbor South- Bldg B DATE: May 30, 2017
CLIENT: Elliott Merrill Community Mgt. LOCATION: Ft. Pierce, Florida
CONTRACTOR: Structure -Con PROJECT MqR: Khris McConnell
INSPECTED BY: Mike Lue WEATHER: clear, hot 90'
WORK INSPECTED:
Building B — South Building
Unit 209 Final
All concrete repairs to unit has been completed. The aluminum screen enclosure at unit 109 below is to be
painted, and re -screened.
Unit 410 — Work in progress
The demolition is complete and the reinforcing bars have been cleaned and coated with corrosion
inhibitor. The floor spall has been approved for concrete pour. The column dowels are to be moved
within the column ties and bent back into the column to provide the maximum possible concrete cover,
prior to placing concrete.
Move dowels
inside ties for more
concrete cover
Surface Spall
8
I
M L Engineering, Inc. Project Nr, -'6-175 Report No. 2
Cotlsulting Engineers C, to Ross Elliott Merrill
SCANNED
' 2030 37" Avenue -a Stark Structure -Con.
Vero Beach, Florida 32960 S i Joe Cicio SLC Bldg Dept
Phone (772) 569-1257 ;t. Lucie County File
Fax (772)569-4041
emlengineerhrginc.corn
OCEAN HARBOR SOUTH CONDOMINIUMS CONCRETE REPAIRS
4200 NORTH HIGHWAY AIA, FT. PIERCE, FLORIDA
THRESHOLD INSPECTION REPORT
SLC BUILDING PERMIT NUMBER: 1608-0115
PROJECT NAME: Ocean Harbor South- Bldg B DATE: May 30, 2017
CLIENT: Elliott Merrill Community Mgt. LOCATION: Ft. Pierce, Florida
CONTRACTOR: Structure -Con PROJECT MQR: Khris McConnell
INSPECTED BY: Mike Luc WEATHER: clear, hot 90'
WORK INSPECTED:
Building B - South Building
Unit 209 Final
All concrete repairs to unit has been completed. The aluminum screen enclosure at unit 109 below is to be
painted and re -screened.
Unit 410 - Work in progress
The demolition is complete and the reinforcing bars have been cleaned and coated with corrosion
inhibitor. The floor spall has been approved for concrete pour. The column dowels are to be moved
within the column ties and bent back into the column to provide the maximum possible concrete cover,
prior to placing concrete.
I 'n Move dowels
inside ties for more
1 concrete cover
Column
A. Lue,
•y�CENs�°�'
NY 4762'A
I
1VI L Engineering, Inc.
Project N "475
Report No. 2
Consulting Engineers
y�1
te- ��_ re Ross
Elliott Merrill
2030 37° Avenue
OuANNED
Bob Stark
Structure -Con.
Vero Beach, Florida 32960
BY
Joe Cicio
SLC Bldg Dept
Phone (772) 569-1257
County
File
Fax (772) 569-4041
if 1_ude
,mlengineeringinc.com
OCEAN HARBOR SOUTH CONDOMINIUMS CONCRETE REPAIRS
4200 NORTH HIGHWAY AIA, FT. PIERCE, FLORIDA
THRESHOLD INSPECTION REPORT
SLC BUILDING PERMIT NUMBER: 1608-0115
PROJECT NAME: Ocean Harbor South- Bldg B DATE: May 30, 2017
CLIENT: Elliott Merrill Community Mgt. LOCATION: Ft. Pierce, Florida
CONTRACTOR: Structure -Con PROJECT MGR: Khris McConnell
INSPECTED BY: Mike Luc WEATHER: clear, hot 90'
WORK INSPECTED:
Building B — South Building
Unit 209 Final
All concrete repairs to unit has been completed. The aluminum screen enclosure at unit 109 below is to be
painted and re -screened.
Unit 410 — Work in progress
The demolition is complete and the reinforcing bars have been cleaned and coated with corrosion
inhibitor. The floor spall ham s been approved for concrete pour. The column dowels are to be moved
within the column ties and bent back into the column to provide the maximum possible concrete cover,
prior to placing concrete.
Move dowels
inside ties for more
concrete cover
v,
(1.'e
M L Engineering, Inc.
Consulting Engineers
2030 37" Avenue
Vero Beach, Florida 32960
Phone (772) 569-1257
Fax (772) 569AO41
mlengineeringinc.com
SCANNED
BY
St. Lucie County
Projr___io.16-175
cc: Gene Ross
Bob Stark
Joe Cicio
File
OCEAN HARBOR SOUTH CONDOMINIUMS CONCRETE REPAIRS°
4200 NORTH HIGHWAY AIA, FT. PIERCE, FLORIDA
THRESHOLD INSPECTION REPORT
SLC BUILDING PERMIT NUMBER: 1608-0115
PROJECT NAME: Ocean Harbor South- Bldg B
CLIENT: Elliott Merrill Community Mgt.
CONTRACTOR: Structure -Con
INSPECTED BY: Mike Lue
Report No.1
Elliott Merrill
Structure -Con.
SLC Bldg Dept
DATE: May 11, 2017
LOCATION: Ft. Pierce, Florida
PROJECT MGR: Khris McConnell
WEATHER: clear, hot 90'
WORK INSPECTED:'
Building B — South'Building
Demolition has been -in progress an almost complete except that at the east door additional excavation is
required due to severely corroded bars found under the east door track.
Observations : - - -
Slab edges
The slab edges and surface "spalls have bien excavated. There are (4) pt cables along the north edge that
where the existing anchors were located too far back in from the slab edges. New cables and anchors
were placed by the PT specialist to repair the slab edge. All reinforcing at these areas have been cleaned
and coated with a corrosion inhibitor and this area can be poured.
Surface spalls
East Door
The bars are severely corroded with a greater than 20% loss of sections under the door going into the unit.
New #6 additional reinforcing is required to be either spliced with the proper lap lengths or epoxy anchor
new dowels with a minimum of 6" epoxy embedment. A dust wall will be required at this door.
North Door
The reinforcing at these areas do not need replacement and the existing bars can be cleaned and coated.
The sliding glass doors can remain, however the door track anchors in the bottom track are to be replaced
with new r/4" diameter stainless steel tapcons with 1" max embedment in holes sealed with polyurethane
sealant. It appears that moisture was migrating into the slab through the existing fastener holes which
contributed to the deterioration.
North wall
There is one deteriorated bar in the north south direction coming out of the wall that needs replacement.
Provide new 44 dowel with 4" epoxy embedment and lapped to the existing bar.
M L Engineering, Inc.
Consulting Engineers
203037' Avenue
Vero Beach, Florida 32960
Phone (772) 569-1257
Fax (772)569-4041
mlengineeringinc.00m
Proje �o. 16-175 Report No. 1
cc: Gene Ross Elliott Merrill
Bob Stark Structure -Con.
Joe Cicio SLC Bldg Dept
File
Pict
East Door
Corroded bars under door
that will require additional
bars.
See closer view in Pic 3
Pic 3
Bar is corroded almost
completely through under
the door pan