Loading...
HomeMy WebLinkAboutMISC EMAILFort Pierce Engineering, Inc. Dependable Mechanical, Electrical & Plumbing Design CA# 28173 dUANNEu October 11, 2016 BY RE: Pursuit Boats St. Lucie Counts 3901 St. Lucie Blvd, Fort Pierce, FL 34946 The purpose of this letter is to address the match -up of the indoor air handling unit with the outdoor condensing units for the split DX air conditioning system at the above address. The indoor air handling unit / coil being installed is a Trane model TWE061100A, rated at 5 tons (two 2.5 ton circuits), and the outdoor condensing units being installed are two Trane model 4TTR403OL1000A rated at 2.5 tons each. These are manufacturer recommended corresponding equipment being installed together and the outdoor condensing units are an acceptable match -up for cooling capacity and inter -operability with the indoor air handling unit (with proper expansion device). This manufacturer matched equipment should provide the minimum system efficiency required by the 2014, 51h Edition FBC Energy Conservation Code. ,o`ewa �S a urq��i Re U��, No 82 ,x -Eric 3, Svobdda, PE, L;EEB 315 South 7t1 Street ♦ Fort Pierce, FL 34950 ♦ Phone 772-6724636 ♦ Fax 772-6724637 www.fp-eng.com Zn Pam Fngin S\16 Noma AC 4nva\1693943 Scaromc. P t NauWVAC Appmnl.dm Pagc I dl