HomeMy WebLinkAboutTEST AND BALANCE REPORTs
CERTIFIED TEST AND BALANCE REPORT
PERFECT BALANCE, INC.,
P. O. Box 1584 (561) 575-4919
Jupiter, Florida 33468-1584 SCANNED (561) 746-0726 (fax)
BY
St. Lucie Countv
PROJECT:
Uncle Bob's Self Storage
8531 South US Hwy,1
Port St. Lucie, Florida
®
ARCHITECT:
Stinard Architecture, Inc.
i
E
322 East Main Street
i
Cartersville, Georgia 30120
�'
`°
ENGINEER:
Stinard Architecture, Inc.
N
�
O
U
322 East Main Street
Q
*U
Cartersville, Georgia 30120
LU
E
HVAC:
D& H/ Magic Air
4180 Dow Road
Melbourne, Florida 32934 .
This is to certify that Perfect Balance, Inc. has balanced the systems described herein
to their optimum performance capabilities. The test and balancing has been performed
in accordance with the standard requirements and procedures of the Associated Air
Balance Council and the results of these tests are herein recorded.
Associated Air Balance Council Certification Number 91-09-22
illiam C. Halm
Test and Balance Engineer
July 23, 2018
Project: Uncle Bob's Self Storage
Location: 8531 S. US Hwy 1, Port St. Lucie, Florida
Split System Unit
Test Report
System: FC-1/HP-1
Make
Carrier
Make/Frame
Marathon I NA
Model Number
FV4CNB006
H.P./RPM
%11075
Serial Number
0318FO8094
Volts/Phase/Hertz
208-230 /1 / 60
Make Sheave
Direct Drive
Full Load Amps/S.F.
6.8 / NA
Sheave Diam/Bore
NAP
Make Sheave
Direct Drive
No. Belts/Size
NAP
Sheave Diam/Bore
NAP
No. Filters/Size
(1) 21)(23X1
Sheave CL Distance
NAP
Type Heating Section
Reverse Cycle
EyaporatoiUataDesign_
Actualpawq
Supply Air CFM
2000
1993
Condensor Manufacturer
Carrier
Outside Air CFM
525
517
Condensor Model No.
25HCE460A
Return Air CFM
1475
1476
Condensor Serial No.
0518E23354
Compressor Model No.
ZP51KCETF5
-NAP
Compressor Serial No.
18A5115FL
NAP
Outside Air DB/WB
NA
90.1/80.0
Return Air DBMB
NA
73.2/63.1
Entering Air DBIWB
NA
77.6/67.5
Condensor Fan HP
Leaving Air DBMB
NA
57.3/56.6
No. of Fans/Fan RPM
1/1100
Cond Fan Volt/Phase/Hz
208-23011 /60
Fan RPM
NA
1075
Condensor Fan Amps
1.52
Motor Voltage T1 T2 T3
208
200
Compr. Volts TI T2 T3
200-20I-200
NAP
Motor Amperage TI
T2
T3
6.8
6A
Compr. Amps T1
12
n
15.3
15.5
15.4
NAP
Remarks:
rAMCN
12=
'Raw
AIMAIIASPIC
MULIAM Q HALM
NL TBE A
91-0
- 094'�
Test Date: 07-23-20IS Readings By: Chillerm Page 1 of 12
Project: Uncle Bob's Self Storage
Location. 8531 S. US Hwy 1, Port St. Lucie, Florida
Air Outlet
Test Report
System: FC-1
Test Apparatus: Flowhood
AN
Units 104
1
S-1
10X6
175
55
174
Units 104
2
S-1
I0X6
200
69
187
Units 104
3
S-1
I0X6
175
51
173
Units 104
4
S-1
10X6
175
77
177
Units 104
5
S-1
1 OX6
175
95
168
Units 104
6
8-1
I0X6
175
53
170
Units 104
7
S-1
1 OX6
175
69
179
Units 104
8
S-1
I0X6
175
63
183
Units 104
9
S-1
I0X6
200
175
199
Units 104
10
S-1
1 OX6
175
207
188
Units 104
11
S-1
1 OX6
200
64
195
SUPPLY TOTAL
2000
1993
Remarks:
ANSIALM31=
MILUIAM Q HAW
t, TEE A
Test Date: 07-23-2018 Readings By: Chilleml Page 2 of 12
ANIL
-
System Unit
Test Report
Split
Project: Uncle Bob's Self Storage
Location: 853j3.U8Hwy 1.Port St. Lucie, Florida
System: FC-2/HP-2
Make
Carrier
Make/Frame
Marathon / NA
Make Sheave
Direct Drive
Full Load Amps/S.F.
6.8 / NA
Sheave Diam/Bore
NAP
Make Sheave
Direct Drive
No. Belts/Size
NAP
Sheave Diam/Bore
NAP
pe Heating Section
Reverse Cycle
TNA
Compressor Model No.
ZP51KCETF5
NAP
Compressor Serial No.
18A4843FL
NAP
Outside Air DBNVB
90.1180.0
Return Air DBNVB
NA
72.8162.6
Entering Air DB/WB
NA
77.2/67.1
Condensor Fan HP
1/4
Leaving Air DBAIVB
NA
57.0156.4
No. of Fans/Fan RPM
1/1100
Fan RPM
NA
1075
Condensor Fan Amps
1.52
test Date: 07-23.2018 Readings By: Chi|lemi Page 3of12
Project: Uncle Bob's Self Storage
Location: 8531 S. US Hwy 1, Port St. Lucie, Florida
Air Outlet
Test Report
System: FC-2
Test Apparatus: Flowhood
k 4a,Servedl
t �`�oohrNumdi+r
No
�TYPa�
�
5ize�'
at Jgn
PfehPfellm,�+
F1�eemadce,
Units 104
1
S-1
10X6
200
43
199
Units 104
2
S-1
10X6
175
97
173
Units 104
3
S-1
10X6
200
104
212
Units 104
4
S-1
10X6
175
273
177
Units 104
5
S-1
10X6
175
264
179
Units 104
6
S-1
10X6
175
87
184
Units 104
7
S-1
10X6
175
63
161
Units 104
8
S-1
10X6
175
99
174
Units 104
9
S-1
10X6
175
94
171
Units 104
10
S-1
10X6
200
57
202
Units 104
11
S-1
10X6
175
53
165
SUPPLY TOTAL
2000
1997
Remarks:
Test Date: 07-23-2018 Readings By: Chillemi Page 4 of 12
AMIL
.AMEEWWIP�
AABC
Project: Uncle Bob's Self Storage
Location: 8531 S. US Hwy 1, Port St. Lucie, Florida
Spilt System Unit
Test Report
w
System: FC-3/HP-3
V-
Make
Carrier
Make/Frame
Marathon NA
'Model Number
FV4CNB006
H.P./RPM
%/1076
Serial Number
0618F0B558
Volts/Phase/Hertz
208-230 /1 /60
Make Sheave
Direct Drive
Full Load Amps/S.F.
6.8 / NA
Sheave Diam/Bore
NAP
Make Sheave
Direct Drive
No. Belts/Size
NAP
Sheave Diam/Bare
NAP
No. Filters/Size
(1) 21X23X1
Sheave CL Distance
NAP
Type Heating Section
Reverse Cycle
i2M
ia-�ED
064010PO 9_
Supply Air CFM
2000
1986
Condensor Manufacturer
Carder
Outside Air CFM
525
533
Condensor Model No.
26HCE460A
Return Air CFM
1475
1453
Condensor Serial No.
0518E23346
Compressor Model No.
ZP51KCETF5
NA
Compressor Serial No.
13SL122FL
NAP
Outside Air DBMS
NA
90.1/80.0
Return Air DBAAfB
NA
73.0162.7
Entering Air DBAAIB
NA
77.6/67.3
Condensor Fan HP
Leaving Air DB/WB
NA
57.0156.0
No. of Fans/Fan RPM
11/1100
Cond Fan Volt/Phase/Hz
208-230/1 /60
Fan RPM
NA
1075
Condensor Fan Amps
1.52
Motor Voltage TI T2 T3
208
200
Compr. Volts TI T2 T3
200-201-200
NAP
Motor Amperage TI
T2
T3
6.8
5.7
Compr. Amps TI
T2
T3
15.2
15.4
15.2
NAP
Remarks:
rAft"Nfl
o
MAMAMN= 0
CMLUAM Q HALM
ARE
91. - - , 09 29
Test Date: 07-23-2018 Readings By: Chillemi Page 5 of 12
NW
AABC
Project: Uncle Bob's Self Storage
Location: 8531 S. US Hwy 1, Port St. Lucie, Florida
Air Outlet
Test Report
System: FC-3
Test Apparatus: Flowhood
Area`ServEdl r
3 ,�
x loam Number 1
,z _.Yfm ='g✓v- �.t.� �s.?`�"-,..-.k
No i
u''.p
J pe
,r r
—0l.....
size
3
Derr n
9 _1m
rtFM`
s P i
CPM
Pre ilm
3£CFM
y7 r
FirlaI
CFM
`M marker
. µ� k
Units 104
1
S-1
10X6
200
272
194
Units 104
2
8-1
10X6
175
184
165
Units 104
3
6-1
10X6
175
255
178
Units 104
4
S-1
10X6
175
223
171
Units 104
5
S-1
10X6
175
263
181
Units 104
6
8-1
10X6
175
165
173
Units 104
7
S-1
10X6
175
234
179
Units 104
8
S-1
10X6
175
87
181
Units 104
9
S-1
10X6
200
92
189
Units 104
10
S-1
10X6
176
83
173
Units 104
11
S-1
10X6
200
74
202
SUPPLY TOTAL
2000
1986
Remarks:
Wt
L s
n
N�
C.
LME
HALM
91. .092-
Test Date: 07-23-2018 Readings By: Chillemi Page 6 of 12
Project: Uncle Bob's Self Storage
Location: 8531 S. US Hwy 1, Part St. Lucie, Florida
Split System Unit
Test Report
FC-gHP-4
Make
Carrier
Make/Frame
Marathon / NA
Make Sheave
Direct Drive
Full Load Amps/S.F.
6.8 / NA
Sheave Diam/Bore
NAP
Make Sheave
Direct Drive
No. Belts/Size
NAP
Sheave Diam/Bore
NAP
No. Filters/Size
(1) 21X23X1
Sheave CL Distance
NAP
Type Heating Section
Reverse Cycle
Compressor Model No.
ZP51KCETFB
NAP
Compressor Serial No.
18AB414FL
NAP
Outside Air DBMB
NA
90.1180.0
Return Air DBNVB
NA
72.5/62.4
Leaving Air DBANB
NA
52.8162.0
No. of Fans/Fan RPM
II1100
Fan RPM
NA
1075
Condensor Fan Amps
1.52
Test Date: 07^23^2018 Readings By: Ch0enli PoQa7of12
Project: Uncle Bob's Self Storage
Location: 8531 S. US Hwy 1, Port St. Lucie, Florida
Air Outlet
Test Report
System: FC-4
Test Apparatus: Flowhood
k C Flff
pi,00,
vil W"M
--l"0
IN"' M-5
Units 104
1
S-1
10X6
170
93
179
Units 104
2
SA
10X6
170
51
174
Units 104
3
S-1
10X6
170
99
170
Units 104
4
S-1
10X6
170
73
172
Units 104
5
S-1
10X6
165
64
168
Units 104
6
S-1
10X6
165
85
169
Units 104
7
S-1
10X6
165
82
170
Units 104
8
S-1
10X6
165
71
153
Units 104
9
S-1
10X6
165
264
159
Units 104
10
S-1
10X6
165
312
167
Units 104
11
S-1
10X6
165
33
161
Units 104
12
S-1
10X6
165
94
167
SUPPLY TOTAL
2000
2009
Remarks:
rAMWN
:01MEW
1qW
JI&AMEMOU
MLUAM C. HALM
kh, TEE J
91
Test Date: 07-23-2018 Readings By: Chillemi Page 8 of 12
Project: Uncle Bob's Self Storage
Location: 8531 S. US Hwy 1, Port St. Lucie, Florida
Split System Unit
Test Report
System: FC-5/HP-5
NX
Make
Carrier
Make/Frame
Marathon / NA
Model Number
FV4CNB006
H.P./RPM-
%/1075
Serial Number
0518F24888
Volts/Phase/Hertz
208-230 /1 / 60
Make Sheave
Direct Drive
Full Load Amps/S.F.
6.8 / NA
Sheave Diam/Bore
NAP
Make Sheave
Direct Drive
No. Belts/Size.
NAP
Sheave Dlam/Bore
NAP
No. Filters/Size
(1)21X23XI
Sheave CL Distance
NAP
Type Heating Section
Reverse Cycle
9v
IPWA POP
Ifd en90XA?AI*I' F-C
-.-I V_ 9
Supply Air CFM
2000
1938
Condensor Manufacturer
Carrier
Outside Air CFM
525
503
Condensor Model No.
25HCE460A
Return Air CFM
1475
1435
Condensor Serial No.
051BE16570
Compressor Model No.
ZP51KCETF5
NAP
Compressor Serial No.
118A4806FL
NAP
Outside Air DBMB
NA
90.1/80.0
Return Air DB/WB
NA
73.5/63.6
Entering Air DBNVB
NA
77.8/67.9
Condensor Fan HP
Leaving Air D8AAfB
NA
57.5/66.9
No. of Fans/Fan RPM
1/1100
Cord Fan Volt/Phase/Hz
208-230 / I / 60
Fan RPM
NA
1075
Condensor Fan Amps
1.52
Motor Voltage TI T2 T3
208
200
Compr. Volts T1 T2 T3
200-201-200
NAP
Motor Amperage Ti
T2
T3
6.8
8.2
Compr. Amps TI
T2
T3
14.7
14.9
14.7
NAP
Remarks;
-0
91
� 094
Test Date: 07-23-2018 Readings By: Chill6ml Page 9 of 12
Project: Uncle Bob's Self Storage
Location: 8531 S. US Hwy 1, Port St. Lucie, Florida
Air Outlet
Test Report
System: FC-5
Test Apparatus: Flowhood
-, � Area Served,[. `� �s
�,
., v ... �.n'.Y n .r.-. ..—s .. ..
Nai
•
�,rtypa�
�.
�s �ize'�
�D@sjg��
pr�l�m
;Pretlrr�
Diu
.. �--v ..
�F nal =_
• � %
„Remarks -
wi n v....
Units 104
1
S-1
10X6
200
89
194
Units 104
2
S-1
1oX6
175
59
162
Units 104
3
S-1
10X6
200
163
180
Units 104
4
S-1
10X6
175
72
177
Units 104
5
S-1
10X6
175
88
175
Units 104
6
S-1
10X6
175
91
159
Units 104
7
8-1
10X6
175
263
170
Units 104
8
S-1
Me
175
194
171
Units 104
9
S-1
1oX6
175
63
184
Units 104
10
8-1
1oX6
200
74
187
Units 104
11
S-1
1oX6
175
77
179
SUPPLY TOTAL
2000
1938
Remarks:
Wrim,, Agkw
+0
a
1 \ 113E / I
97,09.22
Test Date: 07-23-2018 Readings By: Chillemi Page 10 of 12
Project: Uncle Bob's Self Storage
Location: 8531 S. US Hwy 1, Port St. Lucie, Florida
Air Outlet
Test Report
System: Exhaust Fans
Test Apparatus: Flowhood
ea'Se tl/
No
Typp
Size
pe�s�gr
Prelims
Pnllr
Flnel
Remarks
EF-1
150
144
144
EF-2
150
148
148
Remarks:
Test Date: 07-23-2018 Readings By: Chillemi Page 11 of 12
Instrument Calibration Report
Project: Uncle Bob's Self Storage, 8531 S. US Hwy 1, Port St. Lucie, Florida
r Instriitment�
.--
;tNanufacturer�
Ilocel
BenalNumber�,-"ngersrat�n
Id
20 db to 140 db
01-29-18
Sound LevetMetef '
Quest Tea
2900
HWB070002
Octave Band Analyzer
Quest Tech
2900
HWBO70002
31.5 to 16khz
01-29-18
Sound Level Calibrator
Quest Tech
QC-10/20
QIB070041
lkhz (114db)
01-29-18
Vibration Meter
Quest Tech
VI-100
QHB110007
.01-19.99 in/sec
01-29-18
Hydrodata Multimeter
Shortridge
HDM-300
W94078
.01" to 150 psi
02-16-18
Transit Time Flowmeter
Polysonics
DCT7088
B02KCO23
0 TO 50 R/sec
NAP
Flowhood
Shortridge
ADM-860
M88982
20 to 2500 CFM
10-04-17
Velometer
Shortridge
ADM-860
M88982
0 to 30000 FPM
10-04-17
Pyrometer
Fluke
52 K/J
474502
-328 to +1400 F
12-21-17
Electronic Tachometer
Pioneer
36
357M
0 to 12000 RPM
12-21-17
VolUAmpmeter
AWS
DSA2007
DD712313
0 to 600 amps
12-13-17
Duct Leakage Kit
United McGill
LTK-8
NA
NA
NAP
Digital Light Meter
Greenlee
93-172
00000826
.01 to 5000 Fe
NAP
Mercury Thermometer
Taylor
6301
NAP
-40 to +120 F
NAP
Mercury Thermometer
Taylor
630
NAP
0 to +220 F
NAP
Dial Thermometer
Universal
H23-039
NAP
-40 to +120 F
NAP
Dial Thermometer
Universal
H23-040
NAP
0 to +220 F
NAP
Incline Manometer
Dwyer
100.5
3575-1
0" to 1.0"
NAP
Incline Vertical Manometer
Dwyer
400-51-
3575-2
0" to 5.0"
NAP
U-Tube Manometer
Dwyer
1223-36WM
3575-8
0" to 36.0"
NAP
Pilot Tube
Dwyer
NAP
3575-3
18"
NAP
Pilot Tube
Dwyer
NAP
35754
36"
NAP
VelGdd
Shortridge
VLG84
1406-7
14"X14"
NAP
VelProbe
Shortridge
SVP18
1406-8
18"
NAP
Magnehelic Gauge
Dwyer
2000-0
R70902CS73
0"tow
NAP
Magnehelic Gauge
Dwyer
2001
R8062311I67
Onto 1"
NAP
Magnehelic Gauge
Dwyer
2005
R8042511128
0" to 5"
NAP
Remarks:
�-y%I
� 2
WR JAM C. HALM
TEE
9r-09-22
Test Date: 07-23-2018 Readings By: Chillemi Page 12 of 12