REPORT NUMBER: 100810057MID-002C
ORIGINAL ISSUE DATE: July 12, 2012
REVISED DATE: N/A
EVALUATION CENTER
Intertek
8431 Murphy Drive
Middleton, VVI 53562
RENDERED TO
Glen Raven Technical Fabrics
1821 North Park Ave
Glen Raven, NC 27217
PRODUCT EVALUATED: Patio
EVALUATION PROPERTY: NFPA 701-10, Method 2
Report of testing Patio for compliance with the applicable requirements
of the following criteria: NFPA 701-10, METHOD 2 Standard Methods of
Fire Tests for Flame Propagation of Textiles and Films
-This report is for the exclusive use of Intertek's Client and is provided pursuant to the agreement between Intertek
and its Client. Intertek's responsibility and liability are limited to the terms and conditions of the agreement. Intertek
assumes no liability to any party, other than to the Client in accordance with the agreement, for any loss, expense or
damage occasioned by the use of this report. Only the Client Is authorized to permit copying or distribution of this
report and then only in its entirety. Any use of the Intertek name or one of its marks for the sale or advertisement of
the tested material, product or service must first be approved in writing by Intertek. The observations and test results
in this report are relevant only to the sample tested. This report by itself does not Imply that the material, product, or
service is or has ever been under an Intertek certification program."
Glen Raven Technical Fabrics July 12, 2012
Report No. 100810057MID-002C Page 2 of 6
1 Table of Contents
1 TABLE OF CONTENTS...........................................................................................2
2 INTRODUCTION...................................................................................................... 3
3 TEST SAMPLES......................................................................................................3
3.1. SAMPLE SELECTION...................................................................................... 3
3.2. SAMPLE AND ASSEMBLY DESCRIPTION.....................................................3
4 TESTING AND EVALUATION METHODS..............................................................3
4.1. TEST STANDARD 1......................................................................................... 3
5 TESTING AND EVALUATION RESULTS................................................................4
5.1. RESULTS AND OBSERVATIONS....................................................................4
6 CONCLUSION......................................................................................................... 5
Intertek
Glen Raven Technical Fabrics
Report No. 100810057MID-002C
2 Introduction
July 12, 2012
Page 3 of 6
Intertek has conducted testing for Glen Raven Technical Fabrics, on Patio to assess the
propagation of flame beyond the area exposed to the ignition source. Testing was conducted in
accordance with NFPA 701-10, Method 2 - Standard Methods of Fire Tests for Flame
Propagation of Textiles and Films. This evaluation began July 11, 2012 and was completed July
11, 2012.
3 Test
3.1. SAMPLE SELECTION
Samples were submitted to Intertek directly from the client. Samples were not independently
selected for testing. Samples were received at the Evaluation Center July 5, 2012.
3.2. SAMPLE AND ASSEMBLY DESCRIPTION
Four (4) pieces of Patio were prepared by client. Samples measuring 610 mm x 1200 mm t 25
mm were tested. Samples were conditioned in an oven at 105'C t 3'C for no less than 1 hour
but no more than 3 hours before testing.
4 Testing and Evaluation Methods
4.1. TEST STANDARD 1
Four (4) specimens of material 24 in. x 47.25 in. are cut with their long dimension parallel to the
length direction ("with" machine). The test specimens are conditioned to 220-225OF (105-1080C)
for not less than one hour, and not more than 3 hours. Specimens are removed from the oven
one at a time and tested immediately. The specimens are supported with clips in a three -sided
vertical column and exposed to an 1 V flame for two minutes. The flame impinges approximately
7 inches on the specimen.
No specimen shall continue flaming for more than two seconds. Length of char shall not exceed
41.3 inches from the bottom edge of the specimen. There shall be no flaming on the floor of the
apparatus for longer than two seconds.,
Intertek
Glen Raven Technical Fabrics
Report No. 100810057MID-002C
5
and Evaluation Results
5.1. RESULTS AND OBSERVATIONS
July 12, 2012
Page 4 of 6
Sample contracted away from the point of the flame. No other flaming events were observed.
TEST RESULTS
Specimen
Afterflame
Duration (sec)
Floor
Flaming (sec)
Char
Length (in.)
1
0
0
6.00
2
0
0
6.75
3
0
0
4.88
4
0
0
4.37
Average
0
0
5.50
The specimen passes the test criteria for NFPA 701-10, Method 2 Standard
Methods of Fire Tests for Flame Propagation of Textiles and Films.
.
Glen Raven Technical Fabrics July 12, 2012
Report No. 100810057MID-002C Page 5 of 6
6 Conclusion
Intertek has conducted testing for Glen Raven Technical Fabrics, to assess the propagation of
flame beyond the area exposed to the ignition source. Testing was conducted in accordance
with NFPA 701-10, Method 2- Standard Methods of Fire Tests for Flame Propagation of Textiles
and Films.
The specimen passes the test criteria of NFPA 701-10, Method 2 Standard
Methods of Fire Tests for Flame Propagation of Textiles and Films.
The conclusions of this test report may not be used as part of the requirements for Intertek
product certification. Authority to Mark must be issued for a product to become certified.
INTERTEK
Reported by:
Andrew Maximiuk
Lab Technician i, Verification Center
9j� Reviewed by:
Stewart Relyea
Engineering Team Leader, Verification Center
tlnterfelr
Glen Raven Technical Fabrics
Report No. 100810057MID-002C
REVISION SUMMARY
DATE SUMMARY
July 12, 2012 -Original Report
July 12, 2012