Loading...
HomeMy WebLinkAboutTEST AND BALANCE ANALYSIS REPORTI a Ihlo _ 6rq5 CONTRACTOR 6UANNED BY ;t i_urie County TEST AND BALANCE ANALYSIS REPORT FOR International Diamond Center Interior Renovation 2014 SE Port St Lucie Blvd Port St Lucie, FL 34952 SSI Mechnical LLC ARCHITECT Heilman Anccitecture, P.A. ENGINEER Engley Brooks Engineering CERTIFICATION Air distribution system has been completely balanced as per requirements of specifications and results of tests herein listed. Test and balance warranty one year. Certification No. 10506 by Orlando Test and Balance. Inc. Date May 22, 2018 Approved B j' Xa�" D. James Haddick Orlando Test and Balance, Inc. Testing, Adjusting and Balancing of Air Conditioning, Ventilating and Heating Systems P.O. Box 781227 Sebastian, FL. 32958 Toll Free 877-675-3582 ® Orlando Tcst and Balance, Inc. Orlando Test &` Balance Inc. INSTRUMENT LIST Testing, Adjusting and Balancing Air Conditioning, Ventilating and Heating Systems PHONE 877-675-3582 INSTRUMENT MANUFACTURER MODEL RANGE AIR MEASURING: Air Data Meter Shortridge ADM 870 50 - 8000 F.P.M. 0.001" - 50.0" H2O Micromanometer Alnor AXD 550 179 - 17910 F.P.M. 0.002" - 20.0" H2O Balometer Alnor 6463 0 - 2000 C.F.M. Flow Hoods Alnor 2x2 2x4 lx4 0 - 2000 C.F.M. Thermal Anemometer Dwyer 470-1 0 - 6000 F.P.M. Florite Bacharach 16-7001 0 - 1000 F.P.M. Florite Bacharach 16-7002 0 - 3000 F.P.M. Ma nehelics Dwyer 5 gauges 0 - 5.0" H2O Vel rid Shortridge ADM 870 50 - 2500 F.P.M. Airfoil Shortridge ADM 870 50 - 2500 F.P.M. Pitot Tubes Shortridge 18" - 36" 0 - 8000 F.P.M. TACHOMETERS: Optical / Digital Ametek 1726 6 - 99,999 R.P.M. Digital Infrared Tif 780 80 - 20,000 R.P.M. Contact Stewart -Warner Dial 50 - 4000 R.P.M. TEMPERATURE SENSING: Electronic Quad Probe Control Systems T-100 -50 to 300' Fahrenheit Thermometers Miller Glass / Mercury -30 to 120' Fahrenheit Sling Psychrometer Bacharach 12-7011 10 - 100 RH ELECTRICAL: Digital Meter Amprobe ACD-10 Super 0.1 - 600 Volts 0.1 - 300 Amps Analog Meter Amprobe Ultra 0.1 - 600 Volts 0.1 - 300 Amps SYSTEMS CONTROL: Notebook Computer Compaq Presario 1200-XL Windows 98 HYDRONICS: Hydro Data Meter Shortridge HDM 300 0 - 300 PSI H2O Analog Data Meter Florida Hydronics R-50IQ 0 - 50" H2O 0 Odend" Test end Belencc, lec. Orlando Test & "alance, Inc. Testing, Adjusting and Balancing Air Conditioning, Ventilating and Heating Systems PHONE 877-675-3582 May 22, 2018 International Diamond Center Interior Renovation 2014 SE Port St Lucie Blvd Port St Lucie, FL 34952 All systems were tested using a Shortridge Flowhood and AirData Multimeter Sincerely, B.�aartee. Jyaci" Orlando Test and Balance, Inc. P.O. Box 781227 • Sebastian, FL 32958 Toll Free 877-675-3582 0 Odande Test and Balance, Inc. Orlando Test & Jalance, Inc. SYSTEM DATA SHEET Testing, Adjusting and Balancing Air Conditioning, Ventilating and Heating Systems PHONE 877-675-3582 JOB NAME International Diamond Center Interior Renovation Port St Lucie DATE May 22, 2018 UNIT NUMBER AHU-1 AREA SERVED As Listed DESIGN DATA SPECIFIED ACTUAL SYSTEM DATA CFM: UNIT: SUPPLY 775 835 MANUFACTURER NorDYNE RETURN 714 770 MODEL NUMBER GB5BV-T25K-A OUTSIDE AIR 61 65 SERIAL NUMBER GBD071205548 STATIC PRESSURES:. MOTOR: EXTERNAL SUCTION Not Specified -0.14" MANUFACTURER TOTAL SUCTION Not Specified -0.43" MOTOR FRAME EXTERNAL DISCHARGE Not Specified 0.15" HORSEPOWER 115 TOTAL EXTERNAL Not Specified 0.29" RPM TOTAL STATIC Not Specified 0.58" VOLTAGE: OUTSIDE AIR: RATED VOLTAGE 208 / 230 DRY BULB / WET BULB Not Specified 1 76.00 / 74.00 ACTUAL VOLTAGE 242 COOLING: I AMPERAGE: BTU / HR Not Specified 23,484 RATED AMPERAGE 1.3 ENT. AIR / DRY BULB Not Specified 74.00 ACTUAL AMPERAGE 1.0 WET BULB Not Specified 63.00 SAFETY FACTOR LVG. AIR / DRY BULB Not Specified 55.00 OVERLOAD HEATERS: ' WET BULB Not Specified 53.50 HEATERS None CHILLED WATER: HEATER RATING Not Applicable GPM Not S ecified I DX MOTO_ R SHEAVE: ENT. WATER TEMP. Not S ecified I DX PULLEY SIZE Direct Drive LVG. WATER TEMP. Not Specified DX PITCH Direct Drive COIL PRESS. DROP Not Specified DX MTR. SLED ADJUSTMENT Direct Drive HEATING: FAN SHEAVE: BTU / HR Not Specified Electric Heat PULLEY SIZE Direct Drive ENT. AIR / DRY BULB Not Specified Electric Heat RPM Medium Speed LVG. AIR / DRY BULB Not Specified Electric Heat BELT (S) Direct Drive HOT WATER: GPM Not Specified Electric Heat ENT. WATER TEMP. Not Specified 1 Electric Heat LVG. WATER TEMP. Not Specified Electric Heat COIL PRESS. DROP Not Specified Electric Heat ELECTRIC_ HEAT: KW Not Specified 4.9 VOLTS / PHASE / STAGE Not Specified 242 / 1 / I NOTES: *Tag covered by motor bracket, information taken from unit tag. 0 Orlando Test end BaImce, Inc. Orlando Te Inc. Testing, Adjusting and Balancing Air Conditioning, Ventilating and Heating Systems PHONE 877-675-3582 JOB NAME International Diamond Center Interior Renovation Port St Lucie DATE May 22, 2018 UNIT NUMBER AHU-1 AREA SERVED As Listed Delivery Assembly 108 Inventory 0' ©©© • .•. =m=©=© Inventory !04nM�===MMMM Manager 03 NOTES *Grille not installed. **Balanced to rooms total design air flow. 0 Orlando Test and Balance, Inc. Orlando Test Inc. R Testing, Adjusting and Balancing Air Conditioning, Ventilating and Heating Systems JOB NAME International Diamond Center Interior Renovation Port St Lucie UNIT NUMBER AHU-2 AREA SERVED PHONE 877-675-3582 DATE May 22, 2018 As Listed DESIGN DATA SPECIFIED ACTUAL SYSTEM DATA CFM: UNIT: SUPPLY 1925 1755 MANUFACTURER Trane RETURN 1766 1600 MODEL NUMBER 4FWHF060AI000 OUTSIDE AIR 159 155 SERIAL NUMBER 13J33780T STATIC PRESSURES: MOTOR: - EXTERNAL SUCTION Not Specified -0.60" MANUFACTURER Gente TOTAL SUCTION Not Specified -1.10" MOTOR FRAME Not Listed EXTERNAL DISCHARGE Not Specified 0.12" HORSEPOWER 1.0 TOTAL EXTERNAL Not Specified 0.72" RPM 1050 TOTAL STATIC Not Specified 1.22" VOLTAGE: OUTSIDE AIR: RATED VOLTAGE 208 / 230 DRY BULB / WET BULB Not Specified 1 76.0° / 74.0e ACTUAL VOLTAGE 241 COOLING: AMPERAGE: BTU / HR Not Specified 54,019 RATED AMPERAGE 7.6 ENT. AIR / DRY BULB Not Specified 74.00 ACTUAL AMPERAGE 3.7 WET BULB Not Specified 63.00 SAFETY FACTOR Not Listed LVG. AIR / DRY BULB Not Specified 54.00 OVERLOAD HEATERS: WET BULB Not Stiecified 52.50 HEATERS None CHILLED_ WATER: HEATER RATING Not A licable GPM Not Sincified DX MOTOR SHEAVE: ENT. WATER TEMP. Not Sincified DX PULLEY SIZE Direct Drive LVG. WATER TEMP. Not Specified DX PITCH Direct Drive COIL PRESS. DROP Not S ecified DX MTR. SLED ADJUSTMENT Direct Drive HEATING: FAN SHEAVE: BTU / HR Not Specified Electric Heat PULLEY SIZE Direct Drive ENT. AIR / DRY BULB Not Specified Electric Heat RPM High Speed LVG. AIR / DRY BULB Not Specified Electric Heat BELT (S) Direct Drive HOT WATER: GPM Not S ecified Electric Heat ENT. WATER TEMP. Not Specified I Electric Heat LVG. WATER TEMP. Not S ecified Electric Heat COIL PRESS. DROP Not Specified Electric Heat ELECTRIC HEAT: KW Not Specified 8.1 VOLTS / PHASE / STAGE Not Specified 241 / 1 / 1 NOTES: 0 Orlmdo Test and Baluce, Inc. Orlando Test & balance, Inc. GRILLE DATA SHEET Testing, Adjusting and Balancing Air Conditioning, Ventilating and Heating Systems PHONE 877-675-3582 JOB NAME International Diamond Center Interior Renovation Port St Lucie DATE May 22, 2018 UNIT NUMBER AHU-2 AREA SERVED As Listed AREA" : __~ GRILLE' K' FACTOR ;REQUIRED : P.RE-LIM. .FINAL. # SIZE CODE _FPM CFM FP:M CFM_ ,FPM CFM Viewing 114 1 24 x 24 CD Flowhood -- 125 80 80* Viewing 113 2 24 x 24 CD Flowhood -- 125 -- 100 110* Diamond Rm 112 3 24 x 24 CD Flowhood -- 125 -- 150 150* Vault 111 4 8"0 CD Flowhood 50 -- 145 145* Safe Rm 110 5 8"0 CD Flowhood 150 165 130* I.T.Rm 109 6 ** CD Flowhood - 50 Show Rm 102 7 24 x 24 CD Flowhoodl 175 - 115 115* Show Rm 102 8 24 x 24 CD Flowhood -- 150 - 80 110 Show Rm 102 9 24 x 24 CD Flowhood 150 -- 190 195 Show Rm 102 10 24 x 24 CD Flowhood 150 -- 100 - 115* Show Rm 102 11 24 x 24 CD Flowhood 175 -- 135 - 130* Delivery Assembly 108 12 24 x 24 CD Flowhood 150 -- 100 - 100* Show Rm 102 13 24 x 24 CD Flowhood 150 100 -- 110 Show Rm 102 14 24 x 24 CD Flowhood - 200 140 135 Show Rm 102 15 24 x 24 CD Flowhood -- NS - 40 0 Delivery Assembly 108 16 124 x 24 CD Flowhood -- NS -- 130 - 130 Total 1925 1770 1755 NOTES *Manual volume damper not installed. **Grille not installed. e 0,1.do Test and Bals"ee, Inc. Orlando Test &.Aalance, Inc. SYSTEM DATA SHEET Testing, Adjusting and Balancing Air Conditioning, Ventilating and Heating Systems PHONE 877-675-3582 JOB NAME International Diamond Center Interior Renovation Port St Lucie DATE May 22, 2018 UNIT NUMBER AHU-3 AREA SERVED As Listed DESIGN DATA - . SPECIFIED .-, ACTUAL SYSTEM DATA CFM: _. UNIT: SUPPLY 1675 1040 * MANUFACTURER RUUD RETURN 1535.8 890 MODELNUMBER UBHA-21JIlSFC OUTSIDE AIR 139.2 150 SERIAL NUMBER TM220104488 STATIC PRESSURES: MOTOR. EXTERNAL SUCTION Not Specified -0.17" 1 MANUFACTURER General Electric TOTAL SUCTION Not Specified -0.37" MOTOR FRAME Not Listed EXTERNAL DISCHARGE Not Specified 0.13" HORSEPOWER 1/3 TOTAL EXTERNAL Not Specified 0.30" RPM 825 TOTAL STATIC Not S ecified 0.50" VOLTAGE: OUTSIAKAIR: RATED VOLTAGE 208 - 230 DRY BULB / WET BULB Not Specified 76.00 / 74.00 ACTUAL VOLTAGE 239 COOLING: AMPERAGES' BTU / HR Not Specified 34,117 RATED AMPERAGE 2.8 ENT. AIR / DRY BULB Not Specified 74.0" ACTUAL AMPERAGE 1.6 WET BULB Not Specified 64.00 SAFETY FACTOR Not Listed LVG. AIR / DRY BULB Not Specified 54.50 OVERLOAD BEATERS -.- WET BULB Not S ecified 1 53.00 HEATERS None CHILLED WATER: HEATER RATING Not Applicable GPM Not Specified DX MOTOR SHEAVE: _' ENT. WATER TEMP. Not Specified DX PULLEY SIZE Direct Drive LVG. WATER TEMP. Not Specified DX PITCH Direct Drive COIL PRESS. DROP Not Specified DX MTR. SLED ADJUSTMENT Direct Drive HEATING: FAN -SHEAVE: BTU / HR Not S ecified I Electric Heat PULLEY SIZE Direct Drive ENT. AIR / DRY BULB Not Specified Electric Heat RPM High Speed LVG. AIR / DRY BULB Not Specified Electric Heat BELT (S) Direct Drive HOB' WATER: GPM Not Specified Electric Heat ENT. WATER TEMP. Not Specified Electric Heat LVG. WATER TEMP. Not Specified Electric Heat COIL PRESS. DROP Not S ecified I Electric Heat ELECTRIC HEAT: ICW- Not S ecified 9.7 VOLTS / PHASE / STAGE Not Specified 239 / 1 / 1 NOTES: *Unit on high speed. 0 Orlando Test and Balance, Inc, i Orlando Test &Aalance, Inc. Testing, Adjusting and Balancing Air Conditioning, Ventilating and Heating Systems PHONE 877-675-3582 JOB NAME International Diamond Center Interior Renovation Port St Lucie DATE May 22, 2018 UNIT NUMBER AHU-3 AREA SERVED As Listed AREA SERVED " GRILLE K FACTOR REQUIRED , PRE-LIM: 'FINAL # s1ZE I CODE FPM CFM FPM I CFM_- _FPM, CFM Cash Wrap 115 1 * CD Flowhood 75 Cash Wrap 115 2 112 x 12 CD Flowhood 125 290 290** Buying 116 3 12 x 12 CD Flowhood 250 -- 60 - 60** Coffee 117 4 12 x 12 CD 1 Flowhood - 125 90 - 90** Coffee 117 5 * CD Flowhood -- 125 - * -- Coffee 117 6 * CD Flowhoodl 75 Bath RM 120 7 10 x 6 CD Flowhood - 50 120 - 120** Bath RM 121 8 10 x 6 CD Flowhood -- 50 - 30 30** Entry 101 9 10 x 10 CD Flowhood 100 85 85 Coffee 117 10 * CD Flowhood 50 -- Show Rm 102 11 124 x 24 CD Flowhood 150 65 - 65** Show Rm 102 12 124 x 24 CD Flowhoodl 150 - 95 - 95** Show Rm 102 13 124 x 24 CD Flowhood 200 90 90** Show Rm 102 14 24 x 24 CD Flowhood 150 -- 115 115** Total 1675 1 1040 1040 NOTES **Ville not installed. **Manual volume damper not installed, ® Orlando Test and Balance, Inc. Orlando Test & Aalance, Inc. _ FAN DATA SHEET Testing, Adjusting and Balancing Air Conditioning, Ventilating and Heating Systems PHONE 877-675-3582 JOB NAME International Diamond Center Interior Renovation Port St Lucie DATE May 22, 2018 UNIT NUMBER EF-I, EF-2 DESIGN DATA UNIT: FAN NUMBER EF-I EF-2 LOCATION Ceiling Ceiling AREA SERVED Bath RM Bath RM DESIGN CFM / ACT. CFM 75 / 80 75 / 80 DESIGN S.P. / ACT. S.P. 0.25" / 0.08" 0.25" / 0.08" SYSTEM DATA _ UNIT: MANUFACTURER Greenheck Greenheck MODEL NUMBER SP-1390- D SP-B90- D SERIAL NUMBER 69411640-0003 69411640-0006 MOTOR: MANUFACTURER Greenheck Greenheck MOTOR FRAME Not Listed Not Listed HORSEPOWER Not Listed Not Listed RPM 700 700 VOLTAGE: RATED VOLTAGE 115 115 ACTUAL VOLTAGE 121 121 AMPERAGE: RATED AMPERAGE 0.19 0.19 ACTUAL AMPERAGE 0.10 0.10 SAFETY FACTOR Not Listed Not Listed OVERLOAD HEATERS: HEATERS None None HEATER RATING Not Applicable Not A licable MOTOR SHEAVE: PULLEY SIZE Direct Drive Direct Drive PITCH Direct Drive Direct Drive MTR. SLED. ADJUSTMENT Direct Drive Direct Drive FAN SHEAVE: PULLEY SIZE Direct Drive Direct Drive RPM Direct Drive Direct Drive BELTS Direct Drive Direct Drive STATIC PRESSURES: SUCTION / DISCHARGE -0.01" / 0.07" -0.01" / 0.07" TOTAL 0.08" 0.08" NOTES: 0 Orlando Test and Balance, Inc.