SAINT LUCIE COUNTY FIRE DISTRICT
PLAN REVIEW FORM
5160 N.W. Milner Drive
Port Saint Lucie, FL 34983
Telephone: 772-621-3322
Fax: 772-621-3604
SCANNED
St. Luce County
Web Address: www.slcfd.com
Buildingpept. SLC FMO Permit# B-16-282
Project Name Sands on the Ocean BLDG Permit# 1610-0349
Address 3100 North At City Ft Pierce
Contractor Grimes AC
Address 3054 North US 1 Hwy City Ft Pierce
State FL Zip 34946 Telephone (772)461-8711
Architect/Engineer Telephone
Occupancy Type Highrise Construction Type Square Feet
Occupant Load Number of Stories Access Box Access Key Switch
AFS Permit FA Permit FFP Permit
General Notes
1. An electronic copy of the construction documents submitted on a CD is required. The file format shall be.pdf only.
2. All revisions, including the electronic copy must be received prior to permitting.
3. The Fire Marshal requires 24 hour notice on all inspections.
4. The respective Building Department shall schedule all final inspections through the Fire Marshal's Office.
5. Failed inspections require payment of fee prior to rescheduling of further inspections.
6. Penetrations through rated assemblies shall be of the proper UL design. Design criteria shall be submitted with the construction plans.
7. Fire alarm panels shall be located Indoors within air conditioned space.
8. Plans and construction are subject to corrections in the field to maintain code compliance.
9. Automatic fan shutdown is required for HIVAC system/s that exceed 2,000 cfm design capacity.
10. The Installation or Alteration of Fire Sprinklers, Fire Alarms, and Fixed Fire Protection Systems require a separate review and permit.
THE FLORIDA FIRE PREVENTION CODE, 2012 EDITION IS CURRENTLY ENFORCED.
BUILDINGS WITH LIGHT -FRAME TRUSS -TYPE CONSTRUCTION SHALL BE MARKED WITH APPROVED FIREFIGHTER SAFETY
WARNING SIGNS IN ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODES 69A-3.012 AND 69A-60.0081 PRIOR TO RECEIVING
A CERTIFICATE OF OCCUPANCY.
See tseneral Notes ADove ano nequireo rsevisions oerow
1.Automatic fan shutdown is required for HVAC system/s that exceed 2,000 cfm design capacity. Provide a remote test and
inspect appliance equipped with an audible/visual indicator for each HVAC duct smoke detector. HVAC duct smoke detector shall
be tied into the fire alarm system.
Page -1 of 1❑ Reviewed by Tony Jerger I Date 11-14-16