HomeMy WebLinkAboutREVIEW COMMENTSPlanning & Development Services
Building S Code Regulation Division
2300 Virginia Avenue
Fort Pierce, FL 34982
Phone;(772)462.2172 •Fax:(772)462.6443
PROPERTY INFORMATION
Address:
3214 Avenue D
City I State I Zip:
Fort Pierce, FI 34947
Parcel#:
2408-211-0001-000/3
Zoning:
IL
APPLICATION INFORMATION
Permit Number:
1701-0326
Permit Type:
BUILDING COMMERCIAL
REVIEW COMMENTS
66ANNLL)
BY
St. Lucie Cour
Owneris):
Angle Properties Llc
Jurisdiction: SAINT LUCIE COUNTY
Lot#: Block:
Stories: Automatic Sprinkler System? No
Contractor Name:
Fax Number:
Business Name:
Email:
Business Addr:
City / State / Zip: ,
REVIEWS AND COMMENTS
Review Type
Status
Reviewed By
Date Started Date Comoleled
pate Released
DOCUMENTS MISSING
PENDING
Angela Huff
1/18/2017
1/18/2017 Comment:
RECORDED NOTICE OF COMMENCEMENT
1/18/2017 Comment:
SUBS FOR MECHANICAL, ELECTRICAL ROOF, PLUMBING
1/18/2017 Comment:
SENT CUSTOMER
TO ERD
ENGINEERING DEPARTMENT
PENDING
Comment:
ENVIRONMENTAL REVIEW
PENDING
Comment:
FIRE DEPARTMENT REVIEW
PENDING
Tony Jerger
Comment:
FRONT COUNTER REVIEW
COMPLETE
Angela Huff
1/1812017 1/1812017
1/1812017
Comment:
PLANS EXAMINER ELECTRIC
COMPLETE
Carl Peterson
31M2017 3/1412017
311412017
Comment:
PLANS EXAMINER MECHANICAL
COMPLETE
Carl Peterson
3/14/2017 3114/2017
3/14/2017
Comment:
��arCao vo
Planning S Development Services
Building & Code Regulation Division
2300 Virginia Avenue
Fort Pierce, FL. 34982
Phone:(772)462-2172 Fax:(772)462.6443
REVIEW COMMENTS
2
PLANS EXAMINER PLUMBING PENDING Greg Smyth
Comment:
PLANS EXAMINER REVIEW INCOMPLETE Joe Cicio 311312017
3/13/2017
Comment:
PLEASE SUBMIT SEPARATE PERMIT FOR THE DUMPSTER ENCLOSURE
Comment:
NEED THE PEMB PLANS W/ ORIGINAL SIGNATURES, DATES AND SEALS FROM THE STEEL BUILDING
DESIGN PROFESSIONAL' PLEASE SUBMIT IN TRIPLICATE WITH [ 21 PDF DISCS' FBC 207.1 "' THESE
3/13/2017
PLANS MUST BE REVIEWED AND APPROVED BY GUY FABER D.P.OF RECORD "' BE SURE TO ADDRESS
ALL STRUCTURAL STEEL FRAMING AND EXTERIOR BUILDING SKIN PACKAGE
3/13/2017
Comment:
CONTRACTOR TO SUBMIT AN ORIGINAL SIGNED, SEALED AND DATED SOIL REPORT # 16-020 FOR
REVIEW
Comment:
ALL EXTERIOR BUILDING WALL SIGNAGE, MONUMENT SIGNS AND YARD DIRECTIONAL SIGNS REQUIRE
3/14/2017
SEPARATE PERMITS
3/1412017
Comment:
ENGINEER TO IDENTIFY THE MULLION ATTACHMENTS AND THE TOP ATTACHMENTS PER THE PRODUCT
APPROVAL ON THE PRODUCT AFFIDAVIT FOR FL# 17688.4 [ RE -SUBMIT IN TRIPLICATE ]
Comment:
ENGINEER TO IDENTIFY THE THRESHOLD ATTACHMENTS PER THE PRODUCT APPROVAL FOR FL#
3/14/2017
17648.1 ON THE ST LUCIE AFFIDAVIT [ RE -SUBMIT IN TRIPLICATE ]
3/14/2017
Comment:
PLEASE SUBMIT A SEPARATE PERMIT FOR THE COMMERCIAL IRRIGATION SYSTEM
3/1412017
Comment:
ARCHITECTURALS ARE SPECIFYING 20 GA: EXTERIOR WALL STUDS AND TRACKS •' FL# 2030-R8 FOR THE
EIFS SYSTEM SPECS 18 GA: STUDS " PLS CORRECT ONE OR THE OTHER
3/1412017
Comment:
DESIGN ENGINEER TO SPECIFY THE ATTACHMENT OF THE DENSGLASS GOLD AND THE 1.5" INSULATION
BOARD TO THE STUDS ON PLANS
3/1412017
Comment:
COMMENTS E-MAILED AS OF THIS DATE
.ZONING REVIEW
PENDING Jeffrey Johnson
Comment:
Joe Cicio
From: Microsoft Outlook
To: 'epalmar@stephensbarrios.com'; 'salikhan@stephensbarrios.com'
Sent: Tuesday, March 14, 2017 2:39 PM
Subject: Undeliverable: Review Comments for Permit Number 1701-0326
Delivery has failed to these recipients or groups:
Iepalmar(alstephensbarrios.com' (eoalmar(alsteohensbarrios.com)
Your message wasn't delivered due to a permission or security issue. It may have been rejected by a moderator, the
address may only accept e-mail from certain senders, or another restriction may be preventing delivery.
'salikhan(alstephensbarrios.com'(salikhan(alstephensbarrios.comj
Your message wasn't delivered due to a permission or security issue. It may have been rejected by a moderator, the
address may only accept e-mail from certain senders, or another restriction may be preventing delivery.
The following organization rejected your message: smtp-relay.gmail.com.
Diagnostic information for administrators:
Generating server: SLCEDGE.Stlucieco.org
epaimar@stephensbarrios.com
smtp-relay.gmail.com #550-5.7.1 Invalid credentials for relay[2001:0:9d38:78cf:3406:2f8:3836:4199]. 550-5.7.1 The IP
address you've registered in your G Suite SMTP Relay service 550-5.7.1 doesn't match domain of the account this email is
being sent from. If 550-5.7.1 you are trying to relay mail from a domain that isn't registered 550-5.7.1 under your G Suite
account or has empty envelope -from, you must 550-5.7.1 configure your mail server either to use SMTP AUTH to identify
the 550-5.7.1 sending domain or to present one of your domain names in the HELD or 550-5.7.1 EHLO command. For
more information, please visit 550 5.7.1 https://support.google.com/a/answer/6140680#invalidcred r15sm719141vke.0 -
gsmtp ##
salikhan@stephensbarrios.com
smtp-relay.gmail.com #550-5.7.1 Invalid credentials for relay[2001:0:9d38:78cf:3406:2f8:3836:4199]. 550-5.7.1 The IP
address you've registered in your G Suite SMTP Relay service 550-5.7.1 doesn't match domain of the account this email is
being sent from. If 550-5.7.1 you are trying to relay mail from a domain that isn't registered 550-5.7.1 under your G Suite
account or has empty envelope -from, you must 550-5.7.1 configure your mail server either to use SMTP AUTH to identify
the 550-5.7.1 sending domain or to present one of your domain names in the HELO or 550-5.7.1 EHLO command. For
more information, please visit 550 5.7.1 https://support.google.com/a/answer/6140680#invalidcred r15sm719141vke.0 -
gsmtp ##
Original message headers:
Received: from SLCCASHUB.stlucieco.org (199.201.190.202) by
SLCEDGE.Stlucieco.org (172.16.0.102) with Microsoft SMTP Server (TLS) id
14.3.301.0; Tue, 14 Mar 2017 14:34:17 -0400
Received: from SLCMAIL.stlucieco.org ([fe80::43c:95bf:882d:c278]) by
Plannin�nt Services
Building & Code Regulation Division
2300 Virginia Avenue
Fort Pierce, FL 34982
Phone:(772)462.2172 Fax:(772)46226443
PROPERTY INFORMATION
' Address:
3214 Avenue D
> .,'.'City / State / Zip:
Fort Pierce, FI 34947
Parcel#:
2408-211-0001-000/3
Zoning:
IL
APPLICATION INFORMATION
Permit Number: 1701-0326
Permit Type: BUILDING COMMERCIAL
CONTRACTOR INFORMATION
Contractor Name:
Business Name:
Business Addr:
'City / State I Zip: ,
0UAIVIVtL)
REVIEW COMMENTS By.
St. Lucie CountV
Page 1
Owner(s):
Angle Properties Llc
Jurisdiction: SAINT LUCIE COUNTY
Lot#: Block:
Stories: Automatic Sprinkler System? No
Fax Number:
Email:
REVIEWS AND COMMENTS
RevleW Tvoe
Status Reviewed By Date Started Date Completed pate Released
DOCUMENTS MISSING
PENDING Angela Huff 1/18/2017
1/18/2017 Comment:
RECORDED NOTICE OF COMMENCEMENT
111812017 Comment:
SUBS FOR MECHANICAL, ELECTRICAL ROOF, PLUMBING
1/18/2017 Comment:
SENT CUSTOMER TO ERD ,
3/21/2017 Comment:
VWG PERMIT IN BIN UNDER "A" ANGLE '
ENGINEERING DEPARTMENT
COMPLETE Jeffrey Johnson 6/1912017 6/19/2017 6119/2017
Comment:
ENVIRONMENTAL REVIEW
COMPLETE Ben Balcer 1/18/2017 3121/2017 3121/2017
Comment:
',FIRE DEPARTMENT REVIEW
PENDING Tony Jerger
Comment:
FRONT COUNTER REVIEW
COMPLETE Angela Huff 111812017 1/1812017 111812017
Comment:
PE REVIEW COMMENTS (2)
INCOMPLETE Joe Cicio 8/7/2017
Comment:
NEED THE PEMB PLANS W/ ORIGINAL SIGNATURES, DATES AND SEALS FROM THE STEEL BUILDING
DESIGN PROFESSIONAL' PLEASE SUBMIT IN TRIPLICATE' FBC 207A "' BE SURE TO ADDRESS ALL
STRUCTURAL STEEL FRAMING AND EXTERIOR BUILDING SKIN PACKAGE, ROOF METAL, AWNINGS AND
3/13/2017
CANOPIES "'"" CHANGED DESIGN PROFESSIONALS "" RE -REVIEW ALL PLANS AND SPECIFICATIONS
PEMB PLANS MUST BE REVIEWED AND APPROVED BY THE NEW DESIGN PROFESSIONAL OF RECORD
FOR CONSTRUCTION * "
.,w...- o~ lnov
Planning & Development Services
Building &-Code Regulation Division
2300 Virginia Avenue
Fort Pierce, FL. 34982
Phone:(772)462.2172 Faz:(7721462-6443
REVIEW COMMENTS
Comment: CONTRACTOR TO SUBMIT AN ORIGINAL SIGNED, SEALED AND DATED SOIL REPORT # 16-020 FOR
3/13/2017 REVIEW " PLEASE SUBMIT AN ORIGINAL SIGNED, SEALED AND DATED SOIL REPORT WITH THE CORRECT
ADDRESS BEING 3214 AVE D
Comment: SUBMIT [ 3 ] ST LUCIE COUNTY "CERTIFICATION FOR DESIGN LOAD COMPLIANCE SHEETS"
8/7/2017 COMPLETELY FILLED OUT BY THE DESIGN PROFESSIONAL OF RECORD' WILL NEED ORIGINALS, SIGNED,
SEALED AND DATED [ NO FAXES, COPIES OR DIGITALS ]
Comment: SUBMIT [ 3 ] ST LUCIE COUNTY "PRODUCT REVIEW AFFIDAVITS COMPLETELY FILLED OUT' MUST
8/7/2017 INCLUDE ALL BUILDING CLADDING' [ ROOF COVERINGS, STOREFRONTS, OVERHEAD DOORS, SWING
DOORS, ETC ] -- SEALS MUST BE ORIGINAL WET OR RAISED SEAL W/ ORIGINAL SIGNATURE AND DATE ""
BE SURE THAT ALL LINES ARE COMPLETELY FILLED OUT W/ METHOD OF ATTACHMENTS FOR EACH ITEM
8/7/2017 Comment: NEW BUILDING AND CONSTRUCTION DATA ` SHEET T-1 • PLEASE ADDRESS TABLES FROM THE FBC NOT
THE IBC
Comment: SHEET A-1 / NOTE REGARDING 1 HOUR WALL" DESIGN PROFESSIONAL OF RECORD TO DETERMINE IF
THIS IS REQUIRED AND DESIGN THE UL DETAILS ON PLANS W/ RATED DOORS "MODIFYTHIS NOTE"
817/2017 SAME REQUIRED FOR THE BOLLARDS PER NOTE ON A-1 " DESIGN PROFESSIONAL TO DETERMINE IF
THESE ARE REQUIRED "SAME WITH NOTE REGARDING THE FIRE RATED PLYWOOD "THIS MUST BE
ACCEPTED BY THE DESIGN PROFESSIONAL OF RECORD AND STATED AS SAME
Comment: SUBMIT [ 3 ] REVISED ENERGY CODES S.S.D. BY THE DESIGN PROFESSIONAL OF RECORD' BE SURE
8/7/2017 THAT SQUARE FOOTAGE IS CORRECT AND ALL REQUIRED CHECK BOXES HAVE BEEN CHECKED' BE
SURE THAT ALL CALC R-FACTORS ARE ON PLAN SHEETS / ALL MUST MATCH -
INSULATION FACTORS AND PLAN NOTES DO NOT MATCH "' CHECK ALL PAGES
8/7/2017 Comment: SHOW THE LOCATION AND DETAILS FOR THE REQUIRED" MALTESE CROSS " FIRE SYMBOL ON THE
FRONT OF THE BUILDING " SEE FAC 69A-60.0081
8/9/2017 Comment: SUBMIT [ 3 ] NEW MANUAL N EQUIPMENT SIZING CALCULATIONS BY ROBERT CASE. MECHANICAL P.E.
8/9/2017 Comment: SUBMIT THE PRODUCT APPROVAL NUMBERS, DETAILS AND METHODS OF ATTACHMENT FOR THE
BAHAMA LOUVERS ON PRODUCT AFFIDAVITS OR PLANS
8/9/2017 Comment: SUBMIT THE DETAILS AND METHODS OF ATTACHMENT FOR THE CANVAS AWNINGS W/ FIRE RATINGS OF
THE CANVAS MATERIALS ON PLANS
8/9/2017 Comment: THE CIVIL ENGINEER MUST DESIGN THE DOWNSPOUT SPACING PER NOTE ON A-2' SUBMIT IN ORIGINAL
FORMAT S.S.D. [ 3 SETS ]
8/9/2017 Comment: CONCRETE PSI ON A-6 IS NOT TO S102 DESIGN NOTES
Comment: GENERAL NOTES S102 CONTAINS 2010 FBC / PLEASE MODIFY TO 2014 FBC / ENGINEER TO IDENTIFY THE
8/9/2017 EXPOSURE ON PLANS PER FBC 1609.4.3 / ENGINEER TO IDENTIFY THE RISK CATEGORY ON PLANS PER
FBC 1604.5
8/9/2017 Comment: SHEET S102 SPECS 5/8" STUCCO / SHEET A-3 SPECS 7/8" ??? PLEASE CORRECT
8/9/2017 Comment: ENGINEERTO DESIGN THE NICHIHA WALL PANEL SYSTEMS ON PLANS W/ PRODUCT APPROVAL.
NUMBERS
8/9/2017 Comment:- ENGINEER TO DESIGN THE ATTACHMENT OF THE SELF -FURRING LATH ON PLANS PER FBC 2507.2 AND
ASTM STANDARD
8/9/2017 Comment: -DESIGN PROFESSIONAL TO INCLUDE THE GYP BOARD SPECS ON PLANS W/ TESTING STANDARDS'
INCLUDE THE METHOD OF ATTACHMENT PER REQUIRED ASTM STANDARD
8/9/2017 Comment: ENGINEER TO DESIGN THE A/C UNIT MOUNTING TO 160 MPH WINDSPEED NOT 140 MPH' SEE FBCM
301.15
8/9/2017 Comment: ENGINEER TO DESIGN THE PARKING LOT LIGHTING ON PLANS W/ FOUNDATIONS AND LIGHT POLES
8/9/2017 Comment: ARCHITECT TO STATE THE CORRECT FBC TABLE FOR THE OCCUPANT LOAD CALCULATIONS' 1004.1.2
ON A-1.1
8/9/2017 Comment: ARCHITECTTO CORRECT THE OCCUPANCY CLASSIFICATIONS ON T-1 TO COINCIDE WITH A-1.1
8/9/2017 Comment: ARCHITECT TO CHANGE THE DVR BOARD NOTE ON A-1 " WE DO NOT ENFORCE THE IBC CODES
Planning& Development Services REVIEW COMMENTS
Building & Code Regulation Division
2300 Virginia Avenue.
Fort Pierce, FL 34982
Phone:(772)462.2172 Fax:(772)462-6443
Page 3
Comment: PLEASE NOTE THAT THE COMMENTS ARE FOR THE CLARIFICATION OR CORRECTION OF THE
SUBMITTED DOCUMENTS. ADDITIONAL REVIEW MAY BE REQUIRED AFTER SUBMITTING CORRECTED
DOCUMENTS
PLEASE NOTE: (1)ALL REVIEW COMMENTS WHEN ANSWERED WILL REQUIRE A COVER LETTER
ADDRESSING WHERE THE CHANGES WERE MADE, (2) ALL CHANGES WILL BE REQUIRED TO BE CLOUDED
ON THE PLANS AND (3) THE CONTRACTOR WHEN RESUBMITTING WILL BE REQUIRED TO INSERT THE
8/15/2017 NEW UPDATED PAGES INTO THE PLANS OR IF THE CONTRACTOR PREFERS, A REVISED COMPLETE SET
OF PLANS CAN BE SUBMITTED
PLEASE NOTE ANY COMMENT NOT ADDRESED MAY BE SUBJECT TO AN ADDITIONAL REVIEW FEE PER ST.
LUCIE COUNTY RESOLUTION #13-196
COMMENTS SENT
PLANS EXAMINER ELECTRIC
COMPLETE
Walter Pride
8/14/2017
811412017
8114/2017
Comment:
PLANS EXAMINER ELECTRIC
COMPLETE
Walter Pride
8/1412017
8/1412017
8114/2017
Comment:
PLANS EXAMINER ELECTRIC
COMPLETE
Walter Pride
8/1412017
811412017
8114/2017
Comment:
I
PLANS EXAMINER MECHANICAL
COMPLETE
Carl Peterson
3/1412017
3114/2017
3114/2017
Comment:
PLANS EXAMINER MECHANICAL
COMPLETE
Carl Peterson
8/812017
8/812017
818/2017
Comment:
PLANS EXAMINER PLUMBING
COMPLETE
Greg Smyth
3/15/2017
311512017
3115/2017
Comment:
PLANS EXAMINER PLUMBING
COMPLETE
Greg Smyth
811012017
8/1012017
Comment:
PLANS EXAMINER REVIEW
COMPLETE
Joe Cicio
311312017
8I712017
8/7/2017
Comment:
ZONING REVIEW
INCOMPLETE
Jeffrey Johnson
611912017
611912017
611912017
Comment:
THE ARCHITECTURE OF THE BUILDING PLAN SET NEEDS TO MATCH THE ARCHITECTURAL
BUILDING
6/19/2017
ELEVATIONS ON
THE APPROVED SITE PLAN.
Planning.& Development Services
Building & Code Regulation Division
2300 Virginia Avenue
Fort Pierce,: FL 34982
Phone:(772)462-2172 Fax:(7721462.6443
�. Page 1
PROPERTY INFORMATION
;Address: 3214 Avenue D
City I State / Zip: Fort Pierce, FI 34947
Parcel M 2408-211-0001-000/3
Zoning: IL
APPLICATION INFORMATION
Permit Number: 1701-0326
Permit Type: BUILDING COMMERCIAL
CONTRACTOR INFORMATION
I
Contractor Name:
I
Business Name:
Business Addr:
City / State / Zip: ,
REVIEW COMMENTS
Owner(s):
Angle Properties Llc
Jurisdiction: SAINT LUCIE COUNTY
Lot#: Block:
Stories: Automatic Sprinkler System? No
Fax Number:
Review Type
Status Reviewed By
Date Started
DOCUMENTS MISSING
PENDING Angela Huff
1/1812017
1/18/2017 Comment:
RECORDED NOTICE OF COMMENCEMENT
1/18/2017 Comment:
SUBS FOR MECHANICAL, ELECTRICAL ROOF,
PLUMBING
1/18/2017 Comment:
SENT CUSTOMER TO ERD
3/21/2017 Comment:
VWG PERMIT IN BIN UNDER "A" ANGLE
ENGINEERING DEPARTMENT
COMPLETE Jeffrey Johnson
611912017
Comment:
ENVIRONMENTAL REVIEW
COMPLETE Ben Balcer
1/1812017
Comment:
FIRE DEPARTMENT REVIEW
PENDING Tony Jerger
Comment:
FRONT COUNTER REVIEW
COMPLETE Angela Huff
1/1812017
Comment:
PE REVIEW COMMENTS (2)
COMPLETE Joe Cicio
81712017
Comment:
Email:
Date Completed Date Released
6/19/2017 6119/2017
3121/2017 3121/2017
1/1812017 1/18/2017
9/19/2017 9/19/2017
JG. �itGlG UOcrot�
Planning & Development Services
Building & Code Regulation Division
2300 Virginia Avenue
Fort Pierce, FL 34982
Phone:(772)462.2172 Faz:(772)462.6443
REVIEW COMMENTS
PE REVIEW COMMENTS (3) INCOMPLETE Joe Cicio 911912017
Comment: CONTRACTOR TO SUBMIT AN ORIGINAL SIGNED, SEALED AND DATED SOIL REPORT # 16-020 FOR
3/13/2017 REVIEW'• PLEASE SUBMIT AN ORIGINAL SIGNED, SEALED AND DATED SOIL REPORT WITH THE CORRECT
ADDRESS BEING 3214 AVE D "' RECEIVED SOIL REPORT "' STILL CONTAINS AN INCORRECT ADDRESS "
PLEASE SUBMIT CORRECT REPORT" FEE DUE
8!7/2017 Comment: NEW BUILDING AND CONSTRUCTION DATA' SHEET T-1 ' PLEASE ADDRESS TABLES FROM THE FBC NOT
THE IBC " THIRD REVIEW " STILL INCORRECT " FEE DUE
Comment: SUBMIT THE PRODUCT APPROVAL NUMBERS, DETAILS AND METHODS OF ATTACHMENT FOR THE
8/9/2017 BAHAMA LOUVERS ON PRODUCT AFFIDAVITS OR PLANS "THIRD REVIEW "DID NOT RECEIVE THE FIRE
RATING MANUFACTURERS SPECS FOR THE CANVAS COVERING " SEE FBC FIRE RATING CRITERIA
REQUIRED' FBC 3105.3.3' SUBMIT IN TRIPLICATE' FEE DUE
8/9/2017 Comment: SUBMIT THE DETAILS AND METHODS OF ATTACHMENT FOR THE CANVAS AWNINGS WI FIRE RATINGS OF
THE CANVAS MATERIALS ON PLANS' FEE DUE
Comment: THE CIVIL ENGINEER MUST DESIGN THE DOWNSPOUT SPACING PER NOTE ON A-2' SUBMIT IN ORIGINAL
8/9/2017
FORMAT S.S.D. [ 3 SETS ) "THIRD REVIEW " COMMENT ADDRESSED ON COVER LETTER" PLEASE
MODIFY THE NOTE ON A-2 WHICH STILL STATES " SPACING DETERMINED BY CIVIL ENGINEER"' FEE DUE
Comment:
ENGINEER TO DESIGN THE NICHIHA WALL PANEL SYSTEMS ON PLANS WI PRODUCT APPROVAL
8/9/2017
NUMBERS' NICHIHA PANELS STILL REFERRED TO ON A-1 FLOORPLAN AND A-3 DETAIL [ 11 • THIRD
REVIEW' DESIGN PROF. STATED" NO NICHIHA THIS BUILDING " IN COVER LETTER AND DID NOT MODIFY
PLAN SHEETS' FEE DUE
Comment:
ENGINEER TO DESIGN THE PARKING LOT LIGHTING ON PLANS W/ FOUNDATIONS AND LIGHT POLES'
8/9/2017
SUBMIT THE MANUFCTURERS SPECIFICATIONS FOR THE LIGHT POLES AND DESIGN THE FOUNDATION
DESIGNS W/ BOLTING' INCOMPLETE COMMENT' FEE DUE
Comment:
PLEASE NOTE THAT THE COMMENTS ARE FOR THE CLARIFICATION OR CORRECTION OF THE
SUBMITTED DOCUMENTS. ADDITIONAL REVIEW MAY BE REQUIRED AFTER SUBMITTING CORRECTED
DOCUMENTS
PLEASE NOTE: (1)ALL REVIEW COMMENTS WHEN ANSWERED WILL REQUIRE A COVER LETTER
ADDRESSING WHERE THE CHANGES WERE MADE, (2) ALL CHANGES WILL BE REQUIRED TO BE CLOUDED
ON THE PLANS AND (3) THE CONTRACTOR WHEN RESUBMITTING WILL BE REQUIRED TO INSERT THE
8/15/2017
NEW UPDATED PAGES INTO THE PLANS OR IF THE CONTRACTOR PREFERS, A REVISED COMPLETE SET
OF PLANS CAN BE SUBMITTED
PLEASE NOTE ANY COMMENT NOT ADDRESED MAY BE SUBJECT TO AN ADDITIONAL REVIEW FEE PER ST.
LUCIE COUNTY RESOLUTION #13-196
COMMENTS SENT
9/19/2017 Comment:
PLEASE CHANGE ALL INSULATION CALL -OUTS ON PLANS TO MATCH THE ENERGY CALCS BEING R-30 IN
WALL CAVITIES AND R-25 CEILING
Comment:
PLEASE RE -SUBMIT ALL REVISED PLANS IN DUPLICATE W/ ORIGINAL SIGNATURES AND PAY THE RE-
9/19/2017
REVIEW FEES UPON RE -SUBMITTAL' YOU WILL NEED TO COME IN WHEN THE PLANS ARE RETURNED
FROM THE FIRE DEPARTMENT AND INSERT THE NEW PAGES INTO THE PLAN PACKAGES.
9/19/2017 Comment:
COMMENTS E-MAILED AS OF THIS DATE
PLANS EXAMINER ELECTRIC
COMPLETE Walter Pride 8114/2017 8114/2017 811412017
Comment:
PLANS EXAMINER ELECTRIC
COMPLETE Waiter Pride 811412017 8/14/2017 8114/2017
Comment:
PLANS EXAMINER ELECTRIC
COMPLETE Walter Pride 811412017 8/14/2017 8114/2017
Comment:
PLANS EXAMINER MECHANICAL
COMPLETE Carl Peterson 311412017 3/1412017 311412017
Comment:
PLANS EXAMINER MECHANICAL
COMPLETE Carl Peterson 0/812017 8/812017 818/2017
Comment:
Planning& Development Services REVIEW COMMENTS
Building & Code Regulation Division
2300 Virginia Avenue.
Fort Pierce, FL. 34982
Phone:(772)462-2172 Fax:(772)462.6443
Page 3
PLANS EXAMINER PLUMBING
COMPLETE
Greg Smyth
311512017
3/1512017
3/15/2017
Comment:
PLANS EXAMINER PLUMBING
COMPLETE
Greg Smyth
8/1012017
8/1012017
Comment:
PLANS EXAMINER REVIEW
COMPLETE
Joe Cicio
3/1312017
BM2017
8/712017
Comment:
ZONING REVIEW
INCOMPLETE
Jeffrey Johnson
611912017
Comment:
1
I
SCANNED
Planning&Development Services REVIEW COMMENTS BY
Building & Code Regulation Division S4. BY
COunty
2300 Virginia Avenue
Fort Pierce; FL 34982
Phone:(772)462.2172 Fax:(772)4624443
Page 1
Address:
3214 Avenue D
4City / State / Zip:
Fort Pierce, FI 34947
•,•Parcel#:
2408-211-0001-000/3
11 Zoning:
IL
APPLICATION INFORMATION
Permit Number:
1701-0326
i
Permit Type:
BUILDING COMMERCIAL
j Contractor Name: Bryan
)
Pagan-Guerero
Business Name: Ap Construction
Contractor Llc
Business Addr: 235 Live Oak Blvd
City / State / Zip: Casselberry, FI 32707
REVIEWS AND COMMENTS
' Review Type
Status
DOCUMENTS MISSING
COMPLETE
Comment:
ENGINEERING DEPARTMENT
COMPLETE
Comment:
ENVIRONMENTAL REVIEW
COMPLETE
Comment:
FIRE DEPARTMENT REVIEW
i
COMPLETE
Comment:
FRONT COUNTER REVIEW
COMPLETE
Comment:
'NOTIFIED FOR PICK UP
COMPLETE
Comment:
NOTIFIED FOR PICKUP -
COMPLETE
REVISIONS
Comment:
PE REVIEW COMMENTS (2)
COMPLETE
Comment:
Owner(s):
Angle Properties Llc
Jurisdiction: SAINT LUCIE COUNTY
Lot#: Block:
Stories: Automatic Sprinkler System? No
Fax Number:
Email: Yazmin@Apcc-FI.Com
Reviewed By
Date Started
Date Completed
Date Released
Angela Huff
111812017
1012312017
10/2312017
Jeffrey Johnson
6119/2017
611912017
6/19/2017
Ben Balcer
1118/2017
3121/2017
31211201T
Tony Jerger
912512017
9126/2017
912612017
Angela Huff
111812017
111812017
111812017
Karen Nielsen
10123/2017
1012312017
10/2312017
Heather Burford
2/1612018
2120/2018
2/2012018
Joe Clelo
81712017
911912017
911912017
Planning S, Development Services REVIEW COMMENTS
Building &'Code Regulation Division
2300 Virginia Avenue.
Fort Pierce, FL.. 34982'
Phone:(772)462.2172 FaX:[772)462-M3
Page 2
PE REVIEW COMMENTS (3)
COMPLETE Joe Cicio 9/19/2017
912912017
9/2912017
Comment:
PLANS EXAMINER ELECTRIC
COMPLETE Walter Pride 8114/2017
8/1412017
8114/2017
Comment:
PLANS EXAMINER ELECTRIC
COMPLETE Walter Pride 8/1412017
811412017
8/14/2017
Comment:
PLANS EXAMINER ELECTRIC
COMPLETE Walter Pride 811412017
8/94/2017
811412017
Comment:
-PLANS EXAMINER MECHANICAL
f
COMPLETE Carl Peterson 3/14/2017
3/1412017
3/1412017
L. Comment:
�. PLANS EXAMINER MECHANICAL
COMPLETE Carl Peterson 818/2017
8/8/2017
81812017
Comment:
PLANS EXAMINER PLUMBING
COMPLETE Greg Smyth 311512017
311512017
3/1512017
Comment:
PLANS EXAMINER PLUMBING
COMPLETE Greg Smyth
811012017
8/1012017
Comment:
PLANS EXAMINER REVIEW
COMPLETE Joe Cicio 3/1312017
8/7/2017
8/712017
Comment:
REVISIONS
COMPLETE Joe Cicio
212012018
212012018
Comment:
REVISIONS
COMPLETE Joe Cicio 2/20/2018
212012018
2120/2018
Comment:
t REVISIONS
I
COMPLETE Joe Cicio 3/1/2018
311/2018
31112018
r
Comment:
REVISIONS
INCOMPLETE Joe Cicio 3/1/2018
Comment:
CONTRACTOR TO SUBMIT THE REVISION FORMS IN DUPLICATE
[ FOR THE DEFERRED SUBMITTAL ] AND
3/1/2018
PAY THE REQUIRED FEE OF $75.00
3/1/2018 Comment:
SEE NOTES ON S1-1.0 ' NEED FULL ENGINEERING FOR THE POLE
LIGHTING SYSTEM
Comment:
THE SEALED CALCULATION FROM P.E. ARLANDSON IS ONLY TO
140 M.P.H. WIND SPEED
AND NEEDS TO
BE 160 M.P.H. AS A RISK II STRUCTURE' THE ANCHOR BOLT DESIGN
IS AN IN- CORRECT WIND SPEED AND
3/1/2018
NEEDS TO BE SIGNED SEALED AND DATED BY THE DESIGN PROFESSIONAL OF RECORD
OR REVIEWED
AND APPROVED BY THE D.P. OF RECORD
3/1/2018 Comment:
COMMENTS E-MAILED AS OF THIS DATE
ZONING REVIEW
COMPLETE Jeffrey Johnson 6/1912017
9/2112017
912112017
Comment: