HomeMy WebLinkAboutTEST AND BALANCE REPORTSCANNED BY St. Lucie County TEST & BALANCE REPORT FOR FAMILY DOLLAR STORE #713755 FT. PIERCE, FL MAY - 4 REC'D /7n/- Prepared by PRECISION BRUNCE INC. TESTING, ADJUSTING AND BALANCE PROFESSIONALS AABC National Performance Guaranty Pursuant to the agreement between Precision Balance, Inc., Orlando, Florida AABC Certified Testing & Balancing Agency Celsius Mechanical All systems shall be balanced in accordance with the plans and specifications and to the optimum performance capabilities of the equipment and design. Testing and balancing shall be done in accordance with the standards published by the Associated Air Balance Council. If for any reason, the Agency listed above fails to comply with the specifications, with the exception of termination of business by the Agency, equipment malfunction or inadequacy, or improper design, which prevents proper balancing of the systems, the Associated Air Balance Council will provide supervisory personnel to assist the Agency to perform the work in accordance with AABC Standards. As part of the Performance Guaranty, the engineer or building owner may call upon AABC to assist him with any technical and/or field problems pertaining to the final balanced condition of systems. These services will be made available at no additional charge by the above agency or by AABC National Headquarters. Project Name Family Dollar Store #713755 Address 3214 Ave D Ft. Pierce, FL 34947 Name of Engineer Harold Daniel Hutter III Engineering Firm LIS Address Date 05/02/18 TBE # 06-09-43 FL 33920 By Kyle Stout AABC Certified TBE AABC Associated Air Balance Council Associated Air Balance Council Annual Certificate .1&aiw&' 1to- Kyle Stout Precision Balance, Inc. fivtecoryrzi/iai1.11zm1pa on&a&o 6'eqVt'ed 9esG arzelOalalzce f'ryil�zeeic alwlel- de. r u%m, reFz alatiarbr, aRWI r ct/uz vnezztr, of t/zef ✓lmmocttrtca'.i61-Oalaizc&Ooancd 9/*al6&na,rzedtv1ziz/4 au�/zoiZzed to 16erf rry zocal ins accoiciancu =6111 t1w" searzdaia!, as-1 tlwl-I(/W magi", co mailer- c /Gsmociatedilzi- a&aa-16'ouieciGfo>-tizaJear PF 61 .1/zlm. /'O*&amgo /?&'nGer-MSJMVJQP kx4el1�eco'p&ed. J t/ze. &kw&and c/zar&r assoaizt n. Oer facat m, ir. r c avaG/ aiv aiv aiinaal 6a . v aj& - ez omaza&o2 oo &6 UmJl' r-ccoralf jlwal� 5�61cel�ei zcate ea�/azics� .�ccerrz/icrv /, �0/d' I Q LL4=2;0 r -- Miehael Delcamp, President Kcnneth M. Sufka, Execatipe Hirector Precision Balance, Inc. Telephone: 407-876-4112 Fax: 407-876-4338 Date: 05/02/18 Page: 1 Project: FDS #713755 AIR MOVING EQUIPMENT TEST SHEET SYSTEM AC-1 AC-2 Equipment Location Building Rear Building Rear Area Served Sales/Office Sales/Register Equipment Manufacturer York York Model ZYE12A2131 ZXE14A2C3DA Serial Number N1 B8506771 N1 B8506770 Specified Actual Specified Actual Total CFM-Fan 4000 4262 5000 5467 Total CFM -Outlet 3950 4262 5000 5467 R/A CFM 3350 3621 4400 4841 O/A CFM 600 641 600 626 Total Static Pressure (Total/External) --- /--- .511.47 --- /--- 2.10/1.37 Inlet Pressure --- /--- .24/.20 --- /--- 1.96/1.23 Discharge Pressure --- .27 .14 Fan RPM --- 818 --- 981 Specified Actual Specified Actual Motor Manufacturer --- Marathon --- Baldor Motor HP N/A N/A 5.25 5.25 Phase 3 3 3 3 Voltage 208 211 208 211 Amperage 9.2 8.1 13.5 12.7 Motor RPM 1725 .1725 1750 1750 Motor Service Factor 1.15 1.15 1.15 1.15 Motor Sheave & Bore Size 1 VM50 X .875 1 VP56 X .875 Fan Sheave & Bore Size AK79 X 1.0 BK85 X 1.0 Belts --- Quantity and Size 1 @A50 1 @ BX54 Precision Balance, Inc. Telephone:407-876-4112 Fax: 407-876-4338 Date: 05/02/18 Page: 2 Project: FDS #713755 DUCT TRAVERSE ZONE TOTALS System Zone/Branch Duct Size Area Sq.Ft. Design FPM CFM TEST Test 1 Test 2 Static FPM FPM CFM Press. / Meter AC-1 O/A 22X6 .91 659 600 47 705 641 R/A 30X23 4.79 699 3350 910 756 3621 Vel rid AC-2 O/A 22X6 .91 659 600 56 689 626 R/A 30X23 4.79 919 4400 1040 1010 4841 Vel rid AABC Precision Balance, Inc. Telephone: 407-876.4112 Fax: 407-876-4338 Date: 05/02/18 Page: 3 Project: FDS #713755 DX COOLING COIL DATA System AC-1 AC-2 Location Rear Building Rear Service —Building Sales/Office Sales/Register Manufacturer York York Design Actual Design Actual Design Actual Design Actual CFM 4000 4262 5000 5467 E.A.T., DB OF N/A 73.7 N/A 73.4 E.A.T., WD OF N/A 65.9 N/A 65.8 L.A.T., DB OF N/A 52.9 N/A 53.3 L.A.T., WB OF N/A 52.3 N/A 52.7 O/A., DB F N/A 82.1 N/A 82.1 O/A., WB F N/A 71.7 N/A 71.7 Remarks: AABC Precision Balance, Inc. Telephone:407-876-4112 Fax: 407-876-4338 Date: 05/02/18 Page: 4 Project: FDS #713756 ELECTRICAL DUCT HEATERS No. Area Served Mfg. Design Volts Amps Measured Volts Amps K. W. Des. Meas. 1 AC-1 York 208 33.4 211 31.2 12.0 11.6 2 AC-2 York 208 33.4 211 29.5 12.0 10.6 Precision Balance, Inc. Project: FDS #713755 SMOKE DETECTORS MAKE: AP&C MODEL: SL200N UNITS DESIGN DIFF. PRESSURE AC-1 Supply .01 —1.2 Telephone: 407-876-4112 Fax: 407-876-4338 Date: 05/02/18 Page: 5 ACTUAL DIFF. PRESSURE .23 AC-2 Supply .01 —1.2 .12 H W W N F W Z 0 m ra j AIR DUCT LEAKAGE TEST SUMMARY Project: Air System: Fan CFM (Q) Dollar Store #713755 AC-1 Supply 4000 Precision Balance, Inc. Project Number: Page Leakage Class (CL) Specified Test Pressure (R) Duct Construction Pressure Class (P.) I of 4 C -11 2" DESIGN DATA FIELD TEST DATA RECORD SUBJECT DUCT SURFACE AREA IN FT, ALLOWABLE LEAKAGE DIAMETER PRESSURE "W.G." DATE TECH. WITNESS: ACTUAL CFM FACTOR CFM/100FT. CFM TEST SECT.) ONCE TUBE DUCT ACROSS ORIFICE 24" x 8' 25.12 22" x 10' 26.4 20" x 10' 21.8 18" x 10, 17.7 16" x 14' 19.6 14" x 10' 10.7 12" x 38' 29.64 150.96 1.51 22 3" 5" 2.09 .023 05/01/18 JW MB 22 Precision Balance, Inc. AIR DUCT LEAKAGE TEST SUMMARY Project: Family Dollar Store #713755 Project Number: Page Air System: AC-2 Supply Leakage Class (C,) Fan CFM (Q): 5000 Specified Test Pressure (P) Duct Construction Pressure Class (P.) 2 of 4 C 2" 2" DESIGN DATA FIELD TEST DATA RECORD SUBJECT DUCT SURFACE AREA IN FT, ALLOWABLE LEAKAGE DIAMETER PRESSURE "W.G." DATE TECH. WITNESS: ACTUAL CFM FACTOR CFM/100FT. CFM TEST SECT.) ORIFICE TUBE DUCT ACROSS oRIHCE 26" x 8' 29.50 24" x 10' 31.42 22" x 10' 26.40 20" x 10' 21.82 18" x 16' 28.27 14" x 16' 17.10 154.51 1.55 21 3" 5" 2.12 .021 05/01/18 JW M13 21 Precision Balance, Inc. AIR DUCT LEAKAGE TEST SUMMARY Project: Family Dollar Store #713755 Project Number: Page Air System: AC-1 Return Leakage Class (CL) Fan CFM (Q): 4000 Specified Test Pressure (R) Duct Construction Pressure Class (P.) 3 of 4 C 2" 2" DESIGN DATA FIELD TEST DATA RECORD SUBJECT DUCT SURFACE AREA IN FT, ALLOWABLE LEAKAGE DIAMETER PRESSURE "W.G." DATE TECH. WITNESS: ACTUAL CFM FACTOR CF1vV100 FTC CFM TEST sscr.) OWICE TUBE DUCT ACROSS oWICE 30"x23"x20' 95.83 .96 18 3" 5" 2.14 .018 05/01/18 JW MB 18 Precision Balance, Inc. AIR DUCT LEAKAGE TEST SUMMARY Project: Family Dollar Store #713755 Project Number: Page Air System: AC-2 Return Leakage Class (CL) Fan CFM (Q): 5000 Specified Test Pressure (R) Duct Construction Pressure Class (P.) 4 of 4 U 2" 2" DESIGN DATA FIELD TEST DATA RECORD SUBJECT DUCT SURFACE AREA IN FT, ALLOWABLE LEAKAGE DIAMETER PRESSURE "W.G." DATE TECH. WITNESS: ACTUAL CFM FACTOR CFM/100 FT, CFM TEST sEcr.I ORIFICE TUBE DUCT ACROSS ORIFICE 30"x23"x20' 95.83 .96 15 3" 5" 2.17 .015 05/01/18 JW MB 15 Box 319 usownnuxenuncemuxrn PREC/s/oN BALANCE, ZAfC. 8815 Conroy -Windermere Road TEST AND BA LANCE PROFESSIONALS Orlando, FL 32835 Phone (407) 876-4112 Fax (407) 876-4338 INSTRUMENT LIST Instrument Manufacturer Model Serial No. Required Calibration Calibration Maintained Capture Hood Kit Evergreen Telemetry CH-15D 1700287 24 Months YeAnt Calibration Date: 07/24/2017 Capture Hood Kit Evergreen Telemetry CH-15D 1700353 24 Months Yes/Last Calibration Date: 01129/2017 Water Pressure Sending Evergreen Telemetry S-DP-125 1700120 24 Months Yes/Last Calibration Module Date: 3222017 Pressure Velocity Module Evergreen Telemetry S-PVF-1 1700297 24 Months Yes/Last Calibration Date: 12/042017 Pressure Velocity Module Evergreen Telemetry S-PVF-1 1500321 24 Months Yesn ast Calibration Date: 03/312017 Pressure Velocity Module Evergreen Telemetry S-PVF-1 1600301 24 Months Yes/Last Calibration Date: 05/212016 Certificate ofC�alibration Manufacturer Evergreen Teleme Calibration Environment Product Capture Hood Temperature 91 °F Model CH-15D Rel. Humidity 53 % SN 1700287 Bar. Pressure _ 7A 7 in H 0 As Found As Left � In Tolerance ❑ Out of Tolerance Callbrat ion Data Measurement Variable Test Point Cal Standard Allowable Ran a Test Instrument Min I Max Airflow (CFM) Spec -3%-7 +3%-7 1 2003 2009 2 997 1011 3• 161 164 4 -555 -558 g Indicates out of tolerance condition ' - �T NIST-Traceable Calibration tab Standards Variable _ stem ID Calibration Last Calibration Due Pressure _ 4693940 7/10/2017 7/10/2018 Pressure 1208000080 7/5/2017 7/5/2018 Velocity, 1600344 1/26/2017 1126/2019' Statement of Traceability This Instrument has been checked for accuracy, calibrated: to manufacturer's specifications, and 'found to be within the speed tolerance unless otherwise stated:. It has been -calibrated using measurement standards traceable to the National institue of Standard's and Technology, or accepted intrinsic standards of measurement, or derived by the .ratio type of self calibrated techniques. Calibrated By 624 S. Perry Ln. #102. Temae AZ July 19,.2017 Calibration Date Certificate of Calibration tP/IA;;fAcr.J_f 2A4 A(n,_-- Manufacturer Ever reen Telemetry Calibration Environment Product Humidity Sensor Temperature Model S-H-3-5" Rel. Humidity65 SN 1700245 Bar. Pressure 28:6 in H {J As round Lj As Left ® In Tolerance 0 Out of Tolerance Calibration Data Measurement Variable Test Point Cal Standard Allowable Range Test Instrument Min Max Temperature (°F) Barometric Pressure (in Hg) _ S ec 1 39.6 10 1'0 39,9 2 71-.3 1.0 10 71.8 3 78.7 -1.0 1.0 79.0 4 Spec 130.6 - - -2.0 -2%- -1 2.0 +2%+0.1 131.8 1 28.6 28.6 Humidity %RH 10 to 90% Spec -3% +3% 1 12.0 12 2 2 64.4 62:9 3 68.3 4 87.0 84.9 Indicates out of tolerance condition--t Calibration Standard Variable System ID Calibration Last Calibration Due Tem erature_ 15171149 11-Jan-17 11,1an-18 Pressure 1208000080 5-Jul-17 5-Jul-18 Humidity 20052171 24Jan-17 24-Jan-18 Statement of Traceability This instrument has been checked for accuracy, calibrated to manufacturer's specifications, and found to be within the specified tolerance unless otherwise stated. It been calibrated using measurement standards traceable to the National institue of Standards and Technology, or accepted intrinsic standards of measurement, or derived by -the ratio type of. self calibrated techniques. Temperature accuracy (dry bulb) variesacross the operating range: Temperature over 32.100F +/-1.0 F Temperature over 100-158F +1- 2.0 F Calibrated By 24-Jul-2017 24-Jul-2018 Calibration Date Date Due Ln r Certificate of Calibration Manufacturer Eve reen Telemetry Calibration Environment Temperature Product I Module I Probe ITemperature 75 1 OF Model S-T-1 RM-T-1 PR-T-1 Rel. Humidity 56 % SN 1 1700314 1 1700314 Bar. Pressure 28.7 in H ❑ As Found ® As Left ® In Tolerance ❑ Out of Tolerance Calibration Data Measurement Variable Test Point Cal Standard Allowable'Range Test Instrument Min Max Test Module & Test Probe Temperature (°F) Spec 1 78.8 -0.3 +0.3 78.9 2 241.3 -2.6 +2.6 241,5 3 -43.8 -1.6 +1.6 -44,5 Indicates out of tolerance condition —T Calibration Standard SN & Dates Variable System ID Calibration Last Calibration Due Temperature 15171'149 11-Jan-17 11-Jan-18 Statement of Traceability This. instrument has been checked for accuracy, calibrated to manufacturer's specifications, and found to be within the specified tolerance unless otherwise stated.. It has been calibrated using measurement standards traceable to a National Institueof Standards and Technology, or accepted intrinsic standards of measurement, or'derive¢�fi> t pe of self calibrated techniques. -�y/' 16-Jul-2017 18-Jul-2019 Calibrated By Calibration Date Date Due 92 ■ S. Perry Ln #102, Tempe, AZ 85281 Certificate of Calibration 1�lZCG 15" t v,J t��ita4,(C-r Manufacturer Ever teen Telemet Calibration Environment Temperature Product S-T-1 Module Prdbe Tem erature 78 °F Model RM-T-1 PR-T 4 Rel. Humidi 36 SN 1700156 Sar. Pressure 28:5 in H ❑ As Found ® As Left El In Tolerance Q Out of Tolerance Calibration Data Measurement Variable Test Point Cal Standard Allowable Range Test Instrument Min Max Test Module & Test Probe Temperature (°F) Sec 1 79.0 -0 3 +0.3 79.0 2 242.0 -2:6 +2,6 242.3 3 -43.2 -1.6 +1.6 -43.0 Indicates but of toleranoe'condition —T Calibration Standard SN &Dates Variable -- - System ID. Calibration Last Calibration Due Temperature 15171149 11-Jan-17 1U,Jan=18 Statement of Traceability This instrument has been checked for accuracy, calibrated to manufacturer's specifications, and found to be within the specified tolerance unless othenvise stated,1t has been calibrated using measurement standards traceable to the National Institueof Standards .and Technology, .or accepted intrinsic standards of measurement, -or derived ty,%tt�eiotyp of If calibrated techniques. 28-Jul-2017 28-Jul-2019 Calibrated By Calibration Date Date Due 602.574.6192 ■ 624 S. Perry Ln w Certificate of Calibration POl--7 tC t,I- ( P-Ai .L YA L Manufacturer Evergreen Telemetry Calibration Environment Product Pressure /Velocity Module Temperature 76 OF Model S-PVF-1 Rel. Humidity 57 SN '1700297 Bar. Pressure 28.6 inH 0 As Found As Left ® In Tolerance ❑ Out of Tolerance Calibration Data Measurement Variable Test Point Gal Standard Allowable Range Test Instrument ---M—in---F Max Barometric Pressure (in Hg) Spec -2%-0.1 +2%+0.1 1 24.3 24.3 2 28.6 28.6 3 30.1 30.2 Differental Pressure (in wc) Spec -2%-.001 +2%+.001 1 10.00 9.999 ' 2 2.000 2.005 3 0:5000 0.5020 4 0.0500 0.0500 5 -10.00 =10.05 6 -0.0500 -0.0502 Low Velocity (FPM) Sec -3% - 7 + 3% + 7 1 100 101 2 503 503 Airflow °F 'Spec 3%-T +3%+7 1 100 UPON 2 500 1 REQUEST Indicates out of tolerance condftion °T NIST-Traceable Lab Calibration Standards Variable System ID Calibration Last Calibration Due Pressure 4693940 10-Jul-17 10-Jul-18 Pressure 1208000080 5-Jul-17 5-Jul-18 Veloci 1600344 26-Jan-17 26-Jan-19 Statement of Traceability This instrument has been checked for accuracy, calibrated to manufacturer's specifications, and found to be within the specified tolerance unless otherwise stated. It has been calibrated using measurement standards traceable to the National Institueof Standards and Technology, or accepted intrinsic standards of measurement, or derived �the ratio Wpe ofrself calibrated techniques. 24-Jul-2017 24-Jul-2019 Calibrated By Oalibration Date Date Due 85281 • 602-574.6192 Certificate of Calibration Precision Bal recal Manufacturer Evergreen Telemet Calibration Environment Product Pressure./ Velocity Module Temperature 75 OF Model S-PVF-1 Rel. Humid' 25 % SN 1560321 Bar. Pressure 285 in H I�SI As Found As Leff In Tolerance ❑ Out of Tolerance ( Calibration Data Measurement Variable Test 'Point Cal Standard Aliowable'Range Test` Instrument Min Max Barometric Pressure (in Hg) —Spec -2%-0:1 +2%+0.1 1 2510 26:0 2 28.5, 28.5 3 30.2 30.2 Differental Pressure (in WC) . —Spec -2%-.001 +2%+,001 1 10.00 9.986 2 2.000 2.000 3 U500 0.5008 4 0.0500 0.0501 5 r10.00_— .. ,..,._,, ...;.�... 7-- _10,02' 6 -0.0500 -0.0500 Low Velocity (FPM) Spec -3%-7 +3%+7 1 109 109 . 2 504 502 Airflow (°F) 5 ec -3%-7 +3%+7 1 100 11 - UPON 2 500 t I REQUEST' Indicates out of tolerance condition T NIST-Traceable Lab Calibration Standards Van be System ID. Calibration Last . Calibration Due.. Pressure 4693940 16-Jul-16 16-Jul-17 Pressure 1208000080 15-Se 16 15-Se A7 Velocity 1600344 26Jan-17 26-Jan-19 Statement of Traceability This instrument has been'checked for accuracy, calibrated to manufacturer's specifications, and found to be within the specified tolerance unless otherwise stated. Ithas been calibrated using measurementstandards traceable to the National Institue of Standards and Technology, or accepted intrinsic standards of measurement, or derived t e rahoty a of self calibrated techniques. 31-Mar-2017 31-Mar-2019 Calibrated By Calibration Date Date Due AZ Certificate of Calibration Manufacturer Evergreen Telemetry Calibration Environment Product Capture Hood Temperature 75 of Model CH-15D Rel. Humidity 32 % SN 1700359 Bar, Pressure 28.8 in H ❑ As Found ® As Left ® In Tolerance ❑ out of Tolerance Calibration Data Measurement Variable Test Point Cal Standard Allowable Range Test Instrument Min Max Airflow (CFM) -3% - 7 +3%-7 —Spec 1 2010 - - 2019 2 1005 1000 3 158 158 4 -542 -541 5 Indicates out of tolerance condition T NIST-Traceable Calibration Lab Standards Variable System ID Calibration Last Calibration Due Pressure _ 4693940 7/1012017 7/10/2018 Pressure 1208000080 7/5/2017 7/5/2018 Velocity 1600344 1/26/2017 1/26/2019 Statement of Traceability This instrument has been checked for accuracy, calibrated to manufacturers specifcations, and found to be within the specified tolerance unless otherwise stated. It has beencalibratedusing measurement standards traceable to the National Institue of Standards and Technology, ocaccepted`intrinsic standards of measurement, or derived by the ratio type of self calibrated techniques. �t♦� a�L Calibratii'd S. Perry Ln. #102, Tempe AZ 65261 • 602-574.6192 November 29, 2017 Calibration Date Certificate of Calibration Manufacturer Evergreen Telemetry Calibration Environment Product Humiditv Sensor ITemDerature 1 78 1 OF Model S-H-3-5" Rel.-Humidity 58 SIN 1700347 Bar. Pressure 28.8 in H ❑ As Found ® As Left ® In Tolerance [3 Out of Tolerance Calibration Data Measurement Variable Test Point Cal . Standard Allowable Ran a Test Instrument Mid Max Temperature (°F) Spec 1 39.6 A:0 1.0 39.9 2 78.9 =1.0 1.0 79.0 3 78.6 -1.0 1.0 78.9 4 130.3 -2.0 2.0 -131.1' Barometric Pressure (in Hg) Sec -2% - 0;1 + 2%+ 0:1 1 28.8 28.8 Humidity %RH 10 to 90% Spec 3% +3% 1 7.3 8.7 2 62.7 61.5 3 60.5 60.9 4 81.1 79.4 Indicates out of tolerance condition --t Calibration Standard Variable System ID Calibration Last I Calibration Due Temperature 15171149. 11-Jan-17 11-Jan-18 Pressure 1208000080, 5-Ju1,17 5-Jul-18 Humidity 20052171 24-Jan-17 24-Jan-18 Statement of Traceability This instrument has been checked for accuracy, calibrated to manufacturer's specifications, and found to be within the specified tolerance unless otherwise stated. It has been calibrated using measurement standards traceable to the National Institue of Standards and Technology, or accepted intrinsic standards of measurement, orderived by the ratio type ofself calibrated techniques. Temperature accuracy (dry bulb) varies across the operating range: Temperature over 32-100F +/-1.0 F Temperature over100-158F �1- 2.0 F W�11' I's I L�Imvftzmzw z' I 26-0ec-2017 26-Dec-2018 Calibration Date Date Due 024 S. Perry Ln #1 Certificate of Calibration Manufacturer Evergreen Telemetry Calibration Environment Product Pressure / Velocity,Module Temperature 77 OF Model S7PVF-1 Rel. Humidity 24 % SN 1700414 Bar. Pressure 287 in ❑ As Found ® As Left Im In Tolerance ❑ Out of Tolerance Calibration Data Measurement Variable Test Point Cal Standard Allowable Range Test Instrument Min Max Barometric Pressure (in Hg) Spec -2%-0.1 +2%+0.1 1 24A 24.2 2 28.7 2&8 3 30.3 30.4 Differental Pressure (in wc) Spec -2%-.001 +2%+.001 1 10.00 10.00 2 2.000 1.999 3 0.5000 0.4952 4 0.0500 0.0497 5 -10.00 -10.05 _ 6 -0,0500 -0.0496 Low Velocity (FPM) Sec 3%-7 +3%+7 1 105 106 2 507 509 Airflow °F Spec " -3% - 7 + 3°/a + 7 1 1001 UPON 2 500 1 REQUEST Indicates out of tolerance condition , " T NIST-Traceable Lab Calibration Standards Variable System ID Calibration Last Calibration Due Pressure 4693940 10-Jul-17 10-Jul=18 Pressure 1208000080 5-Jul-17 5-Jul-18 Velocity 1600344 26-Jan-17 26'-Jan-19 Statement of Traceability This instrumenfhasbeen checked for accuracy, calibrated to manufacturer's specifications, and found to be Within the specified tolerance unless otherwise stated. It has been calibrated using measurement standards traceable,to the National Institue of standards and Technology,,or acceptedintrinsic standards of measurement, or derived -by the ratio type of self calibrated techniques. 20-Dec-2017 20-Deo-2019 caudratea fay GanDration Date Date Due 624 S. Perrytn. #102, Tempe AZ Certificate of Calibration j Manufacturer Ever reen Telemetry Calibration Environment Temperature Product Module Probe Temperature 74 1 OF Model RM-T-1 I PR-T-1 Rel. Humiditv I 26 SN 1700432 1 1700422 Bar. Pressure 1 28.7 1 in H U As Found ® As Left- ® In Tolerance ❑ Out of Tolerance Calibration Data Measurement Variable Test Point Cal Standard Allowable Ran a Test Instrument Min Ma_x___1 Test Module & Test Probe Temperature (°F) Spec 1 78.9 -0.3 +0.3 79.1 2 243.1 -2.6 +2.6 243.1 3 -43.4 -1.6 +1.6 44.0 Indicates out of tolerance condition —t Calibration Standard SN &Dates Variable System ID Calibration Last CalibrRonDue Tem erature 15171149 11rJan-17 11-Jan-18 - Statement of Traceability This instrument has been checked for accuracy, calibrated to manufacturer's specifications,.andfound to be within the specified tolerance unless otherwise stated. It has been calibrated using measurement standards traceable to the National Institue of Standards and Technology, or accepted intrinsic standards of measurement, orderive by the ratio type of self calibrated techniques. 21-Dec-2017 21-Dec-2019 Calibrated 13y Calibres}ion Dato Da£e Due ■ 624 S. Perry Ln 4102, Tempe, AZ Certificate of. Calibration Manufacturer Eve reen Telemetry Calibration Environment Temperature Product Module Probe Temperature 77 OF Model PR-T-4-6 Rel. Humidity 36 SN 1700234 Bar, Pressure 28.6 in H ❑ As Found ® As Left ® In Tolerance ❑ Out of Tolerance Calibration Data Measurement Variable Test Point Cal - Standard _ Allowable Range Test Instrument . Min Max Test Module & Test Probe Temperature (°F) Sec 1 79.1 -0.3 +0.3 Y9.0 2 241.1 -2.6 +2.6 241.6 3 -42.9 -1.6 +1.6 -42.5 Indicates out of tolerance condition.—t Calibration Standard SN &Dates Variable 5 stem ID Calibration Last Calibration Due Temperature 15171149 11-Jan-17 11-Jan-18 Statement of Traceability This instrument has been checked for accuracy, calibrated to manufacturer's specifications, and found to be within the specified tolerance unless otherwise stated-111 has been calibrated using measurement standards f�nnnnMln 4n 4k- NJ-,; --- I 1..-a:+.0 �Of J -J J ..-[ or deri edby the ratio type calibrated techniques. � 13-Dec-2017 13-Dec-2019 `CQlGeMad By Calibration Date Dato Due Certificate of Calibration rreasion tialance Manufacturer Evergreen Telemet Calibration Environment Product Pressure I VelocityModule Temperature 74 OF Model S-PVF-1 Rel. Humidity 31 % SN 1700297 Bar. Pressure 28.7 in H 13 As Found As Left Ig In Tolerance ❑ Out of Tolerance Calibration Data Measurement -Variable Test Point Gal Standard Allowable Ran a Test Instrument Min I Max' Barometric Pressure (in Hg) Spec -2%-0.1. +2%+0:1 1 24.9 24,9 2 28.7 28.7 3 30.1 30.1 Differental Pressure (in we) Spec -2%-.001 +2%+,001 - 1 10.00 10.00 2 2.000 2.007 3 0.5000 0.5029 4 0.0500 0.0504 5 -10.00 -10.05 6 -0..0500 0.0502 Low Velocity (FPM) Sec -3% - 7 + 3% +7 1 109 108 2 503 604 Airflow OF S ec -3"/6-.7 +3%+7 1 100 UPON 2 1 500 REQUEST "Indicates out of tolerance condition . - ? NIST-Traceable Lab Calibration Standards Variable System ID. Calibration Last Calibration Due Pressure 4693940 10-Jul-17 10-Jul-18 Pressure 1208000080 5-Jul-17 5-Jul-18 Velocity 1600344 26-Jan-17 26-Jan-19 Statement ofTraceability This instrument has been checked for accuracy, calibrated to manufacturees specifications, and found to be within the specified tolerance unless otherwise stated. It.has been calibrateBusing measurement standards traceable to the National Institue of Standards and Technology, or accepted intrinsic standards of measurement of dnri ;ed by the ratio type of self calibrated techniques.. r 4-Dec-2017 4-Dec-2019 Calibrated By 'Calibration Date Date Due EVERGREEN Certificate of Calibration TELEMETRY Manufacturer Evergreen Telemetry - Calibration Environment Product Pressure I Velocity Module Tem erature 85 Model S-PVF-1 Rel. Humidity26 #.. SN 1600301 Bar. Pressure 28.7 0 As Found As Left l9 In Tolerance ❑ Out of Tolerance Calibration Data Measurement Variable Test Paint Cal Standard - Allowable Range , Test Instrument -Min Max Barometric Pressure (in Hg) Spec -2%-0.1 -2%+_0.1 1 26,2 25.1 2 28.5 28.6 3 30.3 30.4 Differental Pressure (in wc) Spec -2%1001 +2%-.001 1 10.000 9.999 2 2.000 1:998 3 0.5000 0.5016 4 0.0500 0.0502 5 -10.000. if -10.035 6 0.0500 0,0504 Low Velocity (FPM) Sec -3%-7 ♦3%t7 i Soo 502 2 108. 110 Airflow =F Spec -3%-7 -3%+7 1 100 UPON 2 500.. REQUEST mmca¢s out of amn. common -T Calibration Standards Variable System ID Calibration Last I Calibration. Due Pressure - 4593WO 16Ju1-15 I l"u1-15 Pressure 1208000080. 15-Sep-15 15-Se 16 Velcorty, 1 1500301 1 27-Jan-15 27-Jan-17 Statement of Traceability This instrument has been checked for accuracy, calibrated to manufacturers specifications, and found to be within the specified tolerance unless othervnse stated.. 11 has been calibrated using measurement standards traceable to the National Insdlue of Standards and Technology, or accepted Intrinsic standards of measurement, or derived by the ratio type of self calibrated techniques. QRA A0.f 9 ./9_V Z4_t:'I 12-May-2016 12-May-2018 alibrated By Calibration Date Date Due SCANNED BY St. Lucie Countv TEST & BALANCE REPORT FOR FAMILY DOLLAR STORE #713755 FT. PIERCE, FL Prepared by PRECISION BRLRNCE INC. RECEIVED MAY 0 7 2018 ST. Lucie County, Permitting TESTING, ADJUSTING AND RALANCE PROFESSIONALS = L_IAMtNU- SEE CHANGES BEWA' 0 ACCEPTED AS NOTED ❑REJECTED - ❑ RETURNED FOR CORRECTION ACCEPTANCE IS FOR GENERAL COMPLIANCE WITH THE CONTRACT DOCUMENTSONLY, THE CONTRACTCR IS RESPONSIBLE FORCONFIRMINC AND CORRELATING ALL OUMTITIES AND DIMENSIONS; SELECTING FABRICATION PROCESSES AND TECHNIQUES OF CONSTRUCTICN; COORDINATING ITS 'WORK WITH THAT OF ALL OTHER TRADES; AND OPM G ITS ORK I AFE AN SATISFACTORY MANNER Br L!3 1.4, �riL�� f=ram ` JATc�� iII F'n5 - F-r 71 e= a AABC National Performance Guaranty Pursuant to the agreement between Precision Balance, Inc., Orlando, Florida AABC Certified Testing & Balancing Agency Celsius Mechanical All systems shall be balanced in accordance with the plans and specifications and to the optimum performance capabilities of the equipment and design. Testing and balancing shall be done in accordance with the standards published by the Associated Air Balance Council. If for any reason, the Agency listed above fails to comply with the specifications, with the exception of termination of business by the Agency, equipment malfunction or inadequacy, or improper design, which prevents proper balancing of the systems, the Associated Air Balance Council will provide supervisory personnel to assist the Agency to perform the work in accordance with AABC Standards. As part of the Performance Guaranty, the engineer or building owner may call upon AABC to assist him with any technical and/or field problems pertaining to the final balanced condition of systems. These services will be made available at no additional charge by the above agency or by AABC National Headquarters. Project Name Family Dollar Store #713755 Address 3214 Ave D Ft. Pierce, FL 34947 Name of Engineer Harold Daniel Hutter III Engineering Firm LIS Address Alva, FL 33920 Date 05/02/18 TBE # 06-09-43 - By Kyle Stout = AABC Certified TBE AABC Associated Air Balance Council 9 AABC Associated Air Balance Council Annual Certificate ✓Gioa1ykdto- Kyle Stout Precision Balance, Inc. Y,w/-W &O.'Z o� f/m&;7�� a&al Oel�d gZst and a&"ve cooi iizeelC mae e- do ra/el� 1W&k&01?t and /VYZ iWWgt& of t1ze, ✓lssociatca�✓lii� �a/aitcri G'oa�ci./..T/ertzGor��iuroze�i��u/G� aut/ro�Gxed to-/rei�ivro totaG Jstenv Ga/�ueee rm accoidaiu,� wetl&tG.l&alhAztka&mtaGlisW6r,&/e.✓ 06'aizda&m 20AV °T/uv, i,y"w,,onl m-,n er-MSJMVJQP of"(/ 1,"yr.i&a tli6 s, and c/zaitei� o� f dziv�a, sionaLass aw&am 6'er Aa&o 1 a/ lmecoaGkj onv anl a wed Ga ,w glia- ce1&&ze& eal ri,es. -0ecenebla- 31 20AV Michael Delcamp, President Kcn�cth M. Sufka, Executive Strector N Precision Balance, Inc. Telephone: 407-876-4112 Fax: 407-876-4338 Date: 05/02/18 Page: 1 Project: FDS #713755 AIR MOVING EQUIPMENT TEST SHEET SYSTEM AC-1 AC-2 Equipment Location Building Rear Building Rear Area Served Sales/Office Sales/Register Equipment Manufacturer York York Model ZYE12A2B1 ZXE14A2C3DA Serial Number N1 B8506771 N1 B8506770 Specified Actual Specified Actual Total CFM- Fan 4000 4262 5000 5467 Total CFM-Outlet 3950 4262 5000 5467 R/A CFM 3350 3621 4400 4841 O/A CFM 600 641 600 626 Total Static Pressure (Total/External) --- /--- .51/.47 --- /--- 2.10/1.37 Inlet Pressure /--- .24/.20 --- /--- 1.96/1.23 Discharge Pressure --- .27 --- .14 Fan RPM --- 818 --- 981 Specified Actual Specified Actual Motor Manufacturer --- Marathon --- Baldor Motor HP N/A N/A 5.25 5.25 Phase 3 3 3 3 Voltage 208 211 208 211 Amperage 9.2 8.1 13.5 12.7 Motor RPM 1725 1725 1750 1750 Motor Service Factor 1.15 1.15 1.15 1.15 Motor Sheave 8 Bore Size 1 VM50 X .875 1 VP56 X .875 Fan Sheave 8 Bore Size AK79 X 1.0 BK85 X 1.0 Belts -- Quantity and Size 1 @A50 1 @ BX54 IV AGGEPTED ❑ AMEND -SEE CHANT ❑ ACCEPTEDAS NOTED ❑ REJECTED ❑ RETURNED FOR CORRECTION xEPTANCE IS FOR GENERAL COMPLIANCE WITH THE )CUMENTSONLY. THE CONTRACTOR IS RESPONSIBLE FORCI ID CORRELATING ALL QUANTITIES AND DIMENSIONS; t BRICATION PROCESSES AND TECHNIQUES OF CONS? IORDINATING ITS WORK WITH THAT OF ALL OTHER - Pr P/E9CE 5 AABC Precision Balance, Inc. Telephone: 40 7-876-4112 Fax: 407-876-4338 Date: 05/02/18 Page: 2 Project: FDS #713755 DUCT TRAVERSE ZONE TOTALS System Zone/Branch Duct Size Area Sq.Ft. Design FPM CFM TEST Test 1 Test 2 Static FPM FPM CFM Press. / Meter AC-1 O/A 22X6 .91 659 600 47 705 641 R/A 30X23 4.79 699 3350 910 756 3621 Vel rid AC-2 O/A 22X6 .91 659 600 56 689 626 R/A 30X23 4.79 919 4400 1040 1010 4841 Vel rid AABC Precision Balance, Inc. Telephone: 407-876-4112 Fax: 407-876-4338 Date: 05/02/18 Page: 3 Project: FDS #713755 DX COOLING COIL DATA System AC-1 AC-2 Location Building Rear Building Rear Service Sales/Office Sales/Register Manufacturer York York Design Actual Design Actual Design Actual Design Actual CFM 4000 4262 5000 5467 E.A.T., DB T N/A 73.7 N/A 73.4 E.A.T., WD T N/A 65.9 N/A 65.8 L.A.T., DB T N/A 52.9 N/A 53.3 L.A.T., WB T N/A 52.3 N/A 52.7 O/A., DB F N/A 82.1 N/A 82.1 O/A., WB F N/A 71.7 N/A 71.7 Remarks: Precision Balance, Inc. Telephone: 407-876.4112 Fax: 407-876-4338 Date: 05/02/18 Page: 4 Project: FDS #713755 ELECTRICAL DUCT HEATERS No. Area Served Mfg. Design Volts Amps Measured Volts Amps K. W. Des. Meas. 1 AC-1 York 208 33.4 211 31.2 12.0 11.6 2 AC-2 York 208 33.4 211 29.5 12.0 10.6 i 1,v-X-111111 Project: FDS #713755 MAKE: AP$C MODEL: SL200N Precision Balance, Inc. SMOKE DETECTORS UNITS DESIGN DIFF. PRESSURE AC-1 Supply .01 —1.2 Telephone: 407-876-4112 Fax: 407-876-4338 Date: 05/02/18 Page: 5 ACTUAL DIFF. PRESSURE .23 AC-2 Supply .01 —1.2 .12 nNMI EF 0 Z .4 m -1 CO) x m m -1 T 0. m fr v y V W V Ul Ul �D n N y X � 7T m0 .. ID IUOD 'OO 1'1'1 0 v 7 O CIO!? °fo O �NWC, Ci DD OD A K) N _i Precision Balance, Inc. AIR DUCT LEAKAGE TEST SUMMARY Project: Family Dollar Store #713755 Project Number: Page Air System: AC-1 Supply Leakage Class (CL) Fan CFM (Q): 4000 Specified Test Pressure (P) Duct Construction Pressure Class (P.) 1 of 4 C 2" 2" DESIGN DATA FIELD TEST DATA RECORD SUBJECT DUCT SURFACE AREA IN FT, ALLOWABLE LEAKAGE DIAMETER PRESSURE "W.G" DATE TECH. WITNESS: ACTUAL CFM FACTOR CFM/100 FT: CFM TEST SECT.) ORMCE TUBE DUCT ACROSS ORMCE 24" x 8' 25.12 22" x 10' 26.4 20" x 10' 21.8 18" x 10' 17.7 16" x 14' 19.6 14" x 10' 10.7 12" x 38' 29.64 150.96 1.51 22 3" 5" 2.09 .023 05/01/18 JW MB 22 Precision Balance, Inc. AIR DUCT LEAKAGE TEST SUMMARY Project: Family Dollar Store #713755 Project Number: Page Air System: AC-2 Supply Leakage Class (C,) Fan CFM (Q): 5000 Specified Test Pressure (P) Duct Construction Pressure Class (P.) 2 of 4 C 2" 2" DESIGN DATA FIELD TEST DATA RECORD SUBJECT DUCT SURFACE AREA IN FT z ALLOWABLE LEAKAGE DIAMETER PRESSURE `•W.G." DATE TECH. WITNESS: ACTUAL CFM FACTOR CFM/100 FT CFM TEST SECT.) ORQ ICE TUBE DUCT ACROSS OWICE 26" x 8' 29.50 24" x 10' 31.42 22" x 10' 26.40 20" x 10' 21.82 18" x 16' 28.27 14" x 16' 17.10 154.51 1.55 21 3" 5" 2.12 .021 05/01/18 JW MB 21 Precision Balance, Inc. AIR DUCT LEAKAGE TEST SUMMARY Project: Family Dollar Store #713755 Project Number: Page Air System: AC-1 Return Leakage Class (CL) Fan CFM (Q): 4000 Specified Test Pressure (R) Duct Construction Pressure Class (P.) 3 of 4 C 2" 2" DESIGN DATA FIELD TEST DATA RECORD SUBJECT DUCT SURFACE AREA IN FT x ALLOWABLE LEAKAGE DIAMETER PRESSURE "W.G." DATE TECH. WITNESS: ACTUAL CFM FACTOR CFM/100FTx CFM TESTSECTJ OWICE TUBE DUCT ACROSS OWICE 30"x23"x20' 95.83 .96 18 3" 5" 2.14 .018 05/01/18 JW MB 18 J Precision Balance, Inc. AIR DUCT LEAKAGE TEST SUMMARY Project: Family Dollar Store #713755 Project Number: Page Air System: AC-2 Return Leakage Class (C,) Fan CFM (Q): 5000 Specified Test Pressure (P.) Duct Construction Pressure Class (P.) 4 of 4 C 2" 2" DESIGN DATA FIELD TEST DATA RECORD SUBJECT DUCT SURFACE AREA IN FT, ALLOWABLE LEAKAGE DIAMETER PRESSURE "W.G." DATE TECH. WITNESS: ACTUAL CFM FACTOR CFM/100Fr. CFM TEST SECT.) ORRICE TUBE DUCT ACROSS ORMCE 30"x23"x20' 95.83 .96 15 3" 5" 2.17 .015 05/01/18 JW MB 15 M Box 319 cessowrrnuaeu waramnr PRZC/S/ONBALANCE /NC. 8815 Conroy -Windermere Road TEST AND BALANCE PROFESSIONALS Orlando, FL 32835 Phone (407) 876-4112 Fax (407) 876-4338 INSTRUMENT LIST Instrument Manufacturer Model Serial No. Required Calibration Calibration Maintained Capture Hood Kit Evergreen Telemetry CH-15D 1700287 24 Months Yes/last Calibration Date: 0724/2017 Capture Hood Kit Evergreen Telemetry CH-15D 1700353 24 Months Yes/Last Calibration Date: 011292017 Water Pressure Sending Evergreen Telemetry S-DP-125 1700120 24 Months Yes/Last Calibration Module Date: 3/22/2017 Pressure Velocity Module Evergreen Telemetry S-PVF-1 1700297 24 Months Yes/Last Calibration Date: 12/042017 Pressure Velocity Module Evergreen Telemetry S-PVF-1 1500321 24 Months Yes/Last Calibration Date: 03/31/2017 Pressure Velocity Module Evergreen Telemetry S-PVF-1 1600301 24 Months Yes/Last Calibration Date: 05/212016 EVERGREEN TELEMETRY Certificate of Calibration Manufacturer Evergreen Telemetry \l fi\ Vl Calibration Environment Product Capture Hood Temperature 91 or Model CH-15D Rel. Humid 53 % SN 1700287 Bar. Pressure 28.7 in H ❑ As Found As Left 0 In Tolerance ❑ Out of Tolerance Calibration Data Measurement Variable Test Point Cal Standard Allowable Range Test Instrument Min I Max Airflow (CFM) Spec -3% - 7 1 +3%-7 1 2003 2009 2 997 1011 3 161 164 4 -555 -558 5 Indicates out of tolerance condition T NIST-Traceable Calibration Lab Standards Variable System ID Calibration Last Calibration Due Pressure 4693940 7/10/2017 7/10/2018 Pressure 1208000080 7/5/2017 7/5/2018 Velocity 1600344 1/26/2017 V26/2019 Statement of Traceability This instrument has been checked for accuracy, calibrated to manufacturers specifications, and found to be within the specified tolerance unless otherwise stated. It has been calibrated using measurement standards traceable to the National Instnue of Standards and Technology, or accepted intrinsic standards of measurement, or derived by the ratio type of self calibrated techniques. IP229 Calibrated By AZ 86281 • 602-574-6192 July 19, 2017 Calibration Date EVERGREEN TELEMETRY Certificate of Calibration ,I 1A:;-Ta c r ,r_ 12 e., b (� , -- Manufacturer Evergreen Telemetry Calibration Environment Product Humidity Sensor Temperature 74 °F Model S-H35" Rel. Humidi 65 % SN r-2 1700245 �. Bar. Pressure 28.6 in H Lj r,s Found W As Left ® In Tolerance Q Out of Tolerance Calibration Data Measurement Variable Test Point Cal Standard Allowable Range Test Instrument Min Max Temperature ("F) Barometric Pressure (in Hg) S ec 1 39.6 1.0 1.0 39.9 2 71.3 1.0 1.0 71.8 3 78.7 71.0 1.0 4 Sec 130.6 -2.0 -2%-0.1 2.0 +2%+0.1 131.8 1.8 1 28.6 28.6 Humidity %RH 10 to 90% 11 S ec -3% +3% 1 120 12.2 2 64.4 62.9 3 68.3 69.6 _ 4 1 87.0 84.9 Indicates out of tolerance condition -T Calibration Standard Variable System ID Calibration Last Calibration Due Tem erature 15171149 11-Jan-17 11.1an-18 Pressure 1208000080 5:lul-17 5-Jul-18 --Humidity 20052171 24 Jan-17 24-Jan-18 Statement of Traceability This instrument has been checked for accuracy, calibrated to manufacturers specifications, and found to be within the specified tolerance unless otherwise stated. It has been calibrated using measurement standards traceable to the National Institue of Standards and Technology, or accepted intrinsic standards of measurement, or derived by the ratio type of self calibrated techniques. Temperature accuracy (dry bulb) varies across the operating range: Temperature over 32-100F +/_ 1.0 F Temperature over 100.158E +/_ 2.0 F Calibrated By 24-Jul-2017 24-Jul-2018 Calibration Date Date Due Ln EVERGREEN TELEMETRY Certificate of Calibration ML--r t C. % DJ rsA-LA-,S iG- Manufacturer Ever reen Tell etry Calibration Environment Temperature Product Module Probe Temperature 75 OF Model S-T-1 RM-T-1 PR-T-1 Rel. Humidity 56 % SN 1700314 1700314 Bar. Pressure 28.7 in H ❑ As Found ® As Left ® In Tolerance ❑ Out of Tolerance Calibration Data Measurement Variable Test Point Cal Standard Allowable Range Test Instrument Min Max Test Module & Test Probe Temperature (OF) Spec 1 78.8 -0.3 +0.3 78.9 2 241.3 -2.6 +2.6 241.5 3 -43.8 -1.6 +1.6 -44.5 Indicates out of tolerance condition — r Calibration Standard SN &Dates Variable I . System ID Calibration Last Calibration Due Temperature 1 15171149 11Jan-17 11Jan-18 Statement of Traceability This instrument has been checked for accuracy, calibrated to manufacturer's specifications, and found to be within the specified tolerance unless otherwise stated. It has been calibrated using measurement standards traceabpd��Kl National Institue of Standards and Technology, or accepted intrinsic standards of measurement, or derie ratio pe of self calibrated techniques. . 18Jul-2017 16Jul-2019 Calibrated By Calibration Date Date Due 802.574.6192 ■ ■ 624 S. Perry Ln #102, Tempe, AZ 85281 EVERGREEN TELEMETRY Certificate of Calibration PC 15' t O %J P At --A dCr Manufacturer E ergreen Telemetry Calibration Environment Temperature Product S-T-1 Module I Probe ITemperphirp 78 of Model RM-T-1 PR-T-4 lRel. Humidity 36 % SN 11700168 113ar. Pressure 28.5 in H ❑ As Found ® As Left f3 In Tolerance ❑ Out of Tolerance Calibration Data Measurement Variable Test Point Cal Standard Allowable Range Test Instrument Min Max Test Module & Test Probe Temperature (OF) Spec 1 79.0 -0.3 +0.3 79.0 2 242.0 -2.6 +2.6 242.3 3 43.2 -1.6 +1,6 -43.0 Indicates out of tolerance condition —1` Calibration Standard SN & Dates Variable System ID Calibration Last Calibration Due Temperature 15171149 11-Jan-17 11-Jan-18 Statement of Traceabilitv This instrument has been checked for accuracy, calibrated to manufacturers specifications, and found to be within the specified tolerance unless otherwise stated. It has been calibrated using measurement standards traceable to the National Institue of Standards and Technology, or accepted intrinsic standards of measurement, or derived t ratio ty of self calibrated techniques. — 28-Jul-2017 28-Jul-2019 Calibrated By Calibration Date Date Due EVERGREEN TELEMETRY Certificate of Calibration e.- Manufacturer Evergreen Telemetry Calibration Environment Product Pressure / Velocity Module Tem erature 76 OF Model S-PVF-1 Rel. Humidi 57 % SN 1700297 Bar. Pressure 28.6 in H ❑ As Found ® As Left ® In Tolerance ❑ Out of Tolerance Calibration Data Measurement Variable Test Point Cal Standard Allowable Range Test Instrument Min Max Barometric Pressure (in Hg) Spec -2%-0.1 +2%+0.1 1 24.3 24.3 2 28.6 28.6 3 30.1 30.2 Differental Pressure (in wc) Spec -2%-.001 +2%+.001 1 10.00 9.999 2 2.000 2.005 3 0.5000 0.5020 4 0.0500 0.0500 5 -10.00 -10.05 6 40500 -0.0502 Low Velocity (FPM) Sec -3% - 7 + 3% + 7 1 100 101 2 503 1 503 Airflow °F Spec -3%-7 +3%+7 1 100 1 UPON 2 500 1 REQUEST Indicates out of tolerance condition T NIST-Traceable Lab Calibration Standards Variable System ID Calibration Last I Calibration Due Pressure 4693940 10-Jul-17 10-Jul-18 Pressure 1208000080 5-Jul-17 5-Iul-18 Velocity 1600344 26-Jan-17 26-Jan-19 Statement of Traceability This instrument has been checked for accuracy, calibrated to manufacturer's specifications, and found to be within the specified tolerance unless otherwise stated. It has been calibrated using measurement standards traceable to the National Institue of Standards and Technology, or accepted intrinsic standards of measurement, or derived the ratio pe of self calibrated techniques. 24-Jul-2017 24-Jul-2019 Calibrated By Calibration Date Date Due S. Perry Ln. #102, Tempe AZ 85281 • 602-574-6192 EVERGREEN TELEMETRY Certificate of Calibration Precision Bal recal Manufacturer Evergreen Telemetry Calibration Environment Product Pressure /Velocity Module Temperature 75 eF Model S-PVF-1 Rel. Humidity 25 % SN 1500321 Bar. Pressure 28.5 In H ® As Found As Left 4 In Tolerance E3Out of Tolerance Calibration Data Measurement Variable Test Point Cal Standard Allowable Range Test Instrument Min Max Barometric Pressure (in Hg) Spec -2%-0.1 +2'/6+0.1 1 25.0 25.0 2 28.5 28.5 3 30.2 30.2 Differental Pressure (in wc) - E - —Spec -2%-.001 +2%+,001 1 10.00 9.986 2 2.000 2.000 3 0.5000 0.5008 4 U500 0.0501 5 - _ _ 10.00 — r "" - _ - = = --_10.02' 6- -0.0500 -0.0500 Low Velocity (FPM) Spec -3% - 7 + 3% + 7 1 109 109 2 504 502 Airflow OF S ec -3%-7 +3%+7 1 1 100 UPON 2 500 REQUEST Intl!Cates out of tolerance condition T NIST-Traceable Lab Calibration Standards Variable System ID Calibration Last Calibration Due " Pressure 4693940 16-Jul-16 IT 16-Jul-17 Pressure 1208000080 15-Sep-16 15-Se 17 Velocity1600344 26-Jan-17 26-Jan-19 Statement of Traceability This instrument has been checked for accuracy, calibrated to manufacturer's specifications, and found to be within the specified tolerance unless otherwise stated. It has been calibrated using measurement standards traceable to the National Institue of Standards and Technology, or accepted Intrinsic standards of measurement or derived Ae ratio toe of self calibrated techniques. 1 vtr VTL^1' 31-Mar-2017 31-Mar-2019 Calibrated By Calibration Date Date Due 624 S. Perry Ln. #102. Tempe AZ 85281 EVERGREEN TELEMETRY Certificate of Calibration Manufacturer Evergreen Telemetry Calibration Environment Product Capture Hood Temperature 75 of Model CH-15D Rel. Humidity 32 % SN 1700353 Bar. Pressure 28.8 in H 0 As Found ® As Left ® In Tolerance ❑ Out of Tolerance Calibration Data Measurement Variable Test Point Cal Standard Allowable Range Test Instrument Min Max Airflow (CFM) Spec -3% - 7 +3%-7 1 2010 2019 2 1005 1000 3 158 158 4 -542 -541 5 Indicates out of tolerance condition T NIST-Traceable Calibration Lab Standards Variable System ID Calibration Last Calibration Due Pressure 4693940 7/10/2017 7/10/2018 Pressure 1208000080 7/5/2017 7/5/2018 Velocity 1600344 1/26/2017 1/26/2019 Statement of Traceability This instrument has been checked for accuracy, calibrated to manufacturer's specifications, and found to be within the specified tolerance unless otherwise stated. It has been calibrated using measurement standards traceable to the National Institue of Standards and Technology, or accepted intrinsic standards of measurement, or derived by the ratio type of self calibrated techniques. r ��. 10 1W Calibrated By 624 S. Perry Ln. #102, Tempe AZ 85281 November 29, 2017 Calibration Date EVERGREEN TELEMETRY Certificate of Calibration Manufacturer Evergreen Telemetry Calibration Environment Product Humidity Sensor Temperature Model S-H-3-5" Rel. Humidity58 SN 1700347 Bar. Pressure 28.8 in H O As Found As Left 10 In Tnlomnro ❑ Out of Tolerance Calibration Data Measurement Variable Test Point Cal Standard Allowable Range Test Instrument Min I Max Temperature (°F) S ec 1 39.6 -1.0 1.0 _ 39.9 2 78.9 -1.0 1.0 79.0 3 78.6 -1.0 1.0 78.9 4 130.3 -2.0 2.0 131.1 Barometric Pressure (in Hg) Sec 2% - 0.1 + 2%+ 0:1 1 28.8 28.8 Humidity %RH 10 to 90% Spec -3% +3% 1 7.3 8.7 2 62.7 61.5 3 60.5 60.9 4 1 81.1 1 79.4 Indicates out of tolerance condition —t Calibration Standard Variable System ID Calibration Last Calibration Due Temperature 15171149 11-Jan-17 11-Jan-18 Pressure 1208000080 5-Jul-17 5-Jul-18 Humidity 20052171 24-Jan-17 24Jan-18 Statement of Traceabilitv This instrument has been checked for accuracy, calibrated to manufacturer's specifications, and found to be within the specified tolerance unless othenvise stated. It has been calibrated using measurement standards traceable to the National Institue of Standards and Technology, or accepted intrinsic standards of measurement, or derived by the ratio type of self calibrated techniques. Temperature accuracy (dry bulb) varies across the operating range: Temperature over 32-10OF +/_ 1.0 F Temperature over 100-158F +1- 2.0 F 26-13eo-2017 26-Deo-2018 Calibration Date Date Due 602.574.6192 ■ AZ 85261 EVERGREEN TELEMETRY Certificate of Calibration Manufacturer Evergreen Telemetry Calibration Environment Product Pressure/ Velocity Module Temperature 77 °F Model S-PVF-1 Rel. Humidity 24 SN 1700414 Bar, Pressure 28.7 1 in H Q As Found ® As Left IM In Tolerance ❑ Out of Tolerance Calibration Data Measurement Variable Test Point Cal Standard Allowable Range Test Instrument Min Max Barometric Pressure (in Hg) $ ec -2%-0.1 +2%+0.1 1 24.1 24.2 2 28.7 28.8 3 30.3 30.4 Differental Pressure (in wc) S ec -2%-.001 +2%+.001 1 10.00 10.00 2 2.000 1.999 3 0.5000 0.4952 4 0.0500 0.0497 5 -10.00 -10.05 6 -0.0500 -0.0496 Low Velocity (FPM) Sec -3% - 7 + 3% + 7 1 105 106 2 507 509 Airflow °F S c -3%-7 +3%+7 1 1001 1UPON 2 1 500 1 1 REQUEST Indicates out of tolerance condition T NIST-Traceable Lab Calibration Standards Variable System ID Calibration Last Calibration Due Pressure 4693940 10Jul-17 10-Jul-18 Pressure 1208000080 5Jul-17 5Jul-18 Velocity 1600344 26Jan-17 I 26-Jan-19 Statement of Traceabilitv This instrument has been checked for accuracy, calibrated to manufacturer's specifications, and found to be within the specified tolerance unless otherwise stated. It has been calibrated using measurement standards traceable to the National Institue of Standards and Technology, or accepted Intrinsic standards of measurement or derived by the ratio type of self calibrated techniques. 20-Dec-2017 20-Dec-2019 canDra[ed ay callura[lun Dale Ua[e Due 624 S. Perry Ln. 9102, Tempe AZ 85281 • 602-574-6192 EVERGREEN TELEMETRY Certificate of Calibration Manufacturer Evergreen Teleme Calibration Environment Temperature Product Module Probe Temperature 74#inoHo Model RM-T-1 PR-T-1 Rel. Humidi 26SN 1700432 1700422 Bar. Pressure 287 v ns round R9 As Left ® In Tolerance ❑ Out of Tolerance Calibration Data Measurement Variable Test Module & Test Probe Temperature ff) Test Point Sec Cal Standard Allowable Ran a Test Instrument Min i Max 1 78.9 -0.3 1 +0.3 79.1 2 243.1 -2.6 +2.6 243.1 3 -43.4 -1.6 +1,6 -44.0 Indicates out or tolerance condition—T Calibration Standard SN &Dates Variable S stem ID Calibration Last Calibration Due Tem erature 1 15171149 1 11-Jan-17 11Jan-18 Statement of Traceability This instrument has been checked for accuracy, calibrated to manufacturer's specifications, and found to be within the speed tolerance unless otherwise slated. It has been calibrated using measurement standards traceable to the National Institue of Standards and Technology, or accepted intrinsic standards of measurement, or derive by the ratio type rated techniques. � :7 21-Dec-2017 21-Dec-2019 Calibrated By Calibration Da4o Date Dua 602.574.6192 ■ ■ 624 S. Perry Ln #102, Tempe, AZ . , , EVERGREEN TELEMETRY Certificate of Calibration Manufacturer Evergreen Telemetry Calibration Environment Temperature, Product Module Probe Temperature 77 OF Model PR-T4-6 Rel. Humidi 36 % SN 1700234 Bar. Pressure 26.6 in H ❑ As Found ® As Left ® In Tolerance ❑ Out of Tolerance Calibration Data Measurement Variable Test Point Cal Standard Allowable Range Test Instrument Min Max Test Module & Test Probe Temperature (OF) Spec 1 79.1 -0.3 +0.3 79.0 2 241.1 -2.6 +2.6 241.6 3 -42.9 -1.6 +1.6 42.5 Indlcetes out of tolerance condition —t Calibration Standard SN &Dates Variable System ID Calibration Last I Calibration Due Temperature 15171149 11-Jan-17 11-Jan-18 Statement of Traceability This instrument has been checked for accuracy, calibrated to manufacturer's specifications, and found to be within the specified tolerance unless otherwise stated. It has been calibrated using measurement standards 4--m. . ♦- SL- 1..-.A... — Ca.....1.--J...--J —f or deri ed by the ratiolibrated techniques. 13-Dec-2017 13-Dec-2019 alib By Calibration Date Date Due C4�'d?�p1 Certificate of Calibration Precision Balance Manufacturer Evergreen Telemetry Calibration Environment Product Pressure / Velocity Module Temperature 74 OF Model S-PVF-1 Rel. Humidity 31 % SN 1700297 Bar. Pressure 28.7 in H 13 As Found Ej As Left 19 In Tolerance ❑ Out of Tolerance Calibration Data Measurement Variable Test Point Cal Standard Allowable Range Test Instrument Min Max' Barometric Pressure (in Hg) Spec -2%-0.1 +2%+0.1 1 24.9 24.9 2 28.7 28.7 3 30.1 30.1 Differental Pressure (in wc) Spec -2%-.001 +2%+.001 1 1 10.00 10.00 2 2.000 2.007 3 0.5000 0.5029 4 0.0500 0.0504 5 -10.00 -10.05 6 -0.0500 0.0502 Low Velocity (FPM) Sec -3% - 7 + 3% + 7 1 109 108 2 503 504 Airflow OF Spec -3%-7 +3%+7 1 100 UPON 2 500 REQUEST Indicates out of tolerance condition T NIST-Traceable Lab Calibration Standards Variable System ID Calibration Last Calibration Due Pressure 4693940 10-Jul-17 1 10-Jul-18 Pressure 1208000080 5-JUI-17 5-Jul-18, Velocity 1600344 26-Jan-17 26-Jan-19 Statement of Traceability This instrument has been checked for accuracy, calibrated to manufacturers specifications, and found to be within the specified tolerance unless otherwise stated. It has been calibrated using measurement standards traceable to the National Institue of Standards and Technology, or accepted intrinsic standards of measurement, %dtiriied by the ratio type of self calibrated techniques. 4-Dec-2017 4-Dec-2019 Calibrated By Calibration Date Fate Ln. #102. Temoe AZ 85281 EVERGREEN Certificate of Calibration TELEMETRY Manufacturer Evergreen Telemetry Calibration Environment Product Pressure y VelociModule Temperature 85 °F Model S-P, Rel. Humidity 26 % SN 1600301 lBar. Pressure 28.7 in H ❑ As Found is As Left i9 In Tolerance ❑ Out of Tolerance Calibration Data Measurement Variable Test Pant Cal Standard - Allowable Ran a^" Test Instrument Min I Max Barometric Pressure (in H9) S -2%-0.1 1 +2%+0.1 1 25.2 25.1 2 28.5 28.6 3 30.3 30.4 Differental Pressure (in wc) Spec -2%-.001 +2%+.001 1 10.000 9,999 2 2.000 1.998 3 0.6000 0.5016 4 0.0500 0.0502 5 -10.000- _ -10.035 6 1 -U.0500 -Oli504 Low Velouty (FPM) S -3%-7 +3%+7 1 500 502 2 108 110 Airflow °F S -3%-7 1 3%+7 1 100 1 1 UPON 2 500 1 1 REQUEST Indicates outof twemcce mccitl°n- T Calibration Standards Variable System ID I Calibration Last 1 Calibration Due Pressure 459394U 16Jul-15 I 16Jul-16 Pressure 1208000050 lbSe 15 15Se 16 Veloci 1500301 1 27-Jan-15 27-Jan-17 Statement of Traceability This instrument has been checked for aocumcy, calibrated to manufacturer's specifications, and found to be within the specified tolerance unless omerwise stated. It has been calibrated using measurement standards traceable to the National Institue of Standards and Technology. or accepted intrinsic standards of measuremenl, or derived by the ratio type of self calibrated techniques. 4, n P,( 4- / L / 12-May-2016 12-May-2018 alibrated By Calibration Date Date Due