TEST & BALANCE REPORT FOR
FAMILY DOLLAR STORE #713755
FT. PIERCE, FL
MAY - 4 REC'D
/7n/-
Prepared by
PRECISION
BRUNCE
INC.
TESTING, ADJUSTING AND BALANCE PROFESSIONALS
AABC National
Performance Guaranty
Pursuant to the agreement between
Precision Balance, Inc., Orlando, Florida
AABC Certified Testing & Balancing Agency
Celsius Mechanical
All systems shall be balanced in accordance with the plans and specifications and to the optimum performance
capabilities of the equipment and design. Testing and balancing shall be done in accordance with the standards
published by the Associated Air Balance Council.
If for any reason, the Agency listed above fails to comply with the specifications, with the exception of termination
of business by the Agency, equipment malfunction or inadequacy, or improper design, which prevents proper
balancing of the systems, the Associated Air Balance Council will provide supervisory personnel to assist the Agency
to perform the work in accordance with AABC Standards.
As part of the Performance Guaranty, the engineer or building owner may call upon AABC to assist him with any
technical and/or field problems pertaining to the final balanced condition of systems. These services will be made
available at no additional charge by the above agency or by AABC National Headquarters.
Project Name Family Dollar Store #713755
Address 3214 Ave D
Ft. Pierce, FL 34947
Name of Engineer Harold Daniel Hutter III
Engineering Firm LIS
Address
Date 05/02/18
TBE # 06-09-43
FL 33920
By Kyle Stout
AABC Certified TBE
AABC
Associated Air
Balance Council
Associated Air Balance Council
Annual Certificate
.1&aiw&' 1to-
Kyle Stout
Precision Balance, Inc.
fivtecoryrzi/iai1.11zm1pa on&a&o
6'eqVt'ed 9esG arzelOalalzce f'ryil�zeeic
alwlel- de. r u%m, reFz alatiarbr, aRWI r ct/uz vnezztr, of t/zef
✓lmmocttrtca'.i61-Oalaizc&Ooancd 9/*al6&na,rzedtv1ziz/4
au�/zoiZzed to 16erf rry zocal ins accoiciancu
=6111 t1w" searzdaia!, as-1 tlwl-I(/W magi", co
mailer- c /Gsmociatedilzi- a&aa-16'ouieciGfo>-tizaJear
PF 61
.1/zlm. /'O*&amgo /?&'nGer-MSJMVJQP kx4el1�eco'p&ed.
J t/ze. &kw&and c/zar&r assoaizt n.
Oer facat m, ir. r c avaG/ aiv aiv aiinaal 6a . v aj& -
ez omaza&o2 oo &6 UmJl' r-ccoralf
jlwal� 5�61cel�ei zcate ea�/azics� .�ccerrz/icrv /, �0/d'
I Q LL4=2;0
r --
Miehael Delcamp, President
Kcnneth M. Sufka, Execatipe Hirector
Precision Balance, Inc.
Telephone: 407-876-4112
Fax: 407-876-4338
Date: 05/02/18
Page: 1
Project: FDS #713755
AIR MOVING EQUIPMENT TEST SHEET
SYSTEM
AC-1
AC-2
Equipment Location
Building Rear
Building Rear
Area Served
Sales/Office
Sales/Register
Equipment Manufacturer
York
York
Model
ZYE12A2131
ZXE14A2C3DA
Serial Number
N1 B8506771
N1 B8506770
Specified
Actual
Specified
Actual
Total CFM-Fan
4000
4262
5000
5467
Total CFM -Outlet
3950
4262
5000
5467
R/A CFM
3350
3621
4400
4841
O/A CFM
600
641
600
626
Total Static Pressure (Total/External)
--- /---
.511.47
--- /---
2.10/1.37
Inlet Pressure
--- /---
.24/.20
--- /---
1.96/1.23
Discharge Pressure
---
.27
.14
Fan RPM
---
818
---
981
Specified
Actual
Specified
Actual
Motor Manufacturer
---
Marathon
---
Baldor
Motor HP
N/A
N/A
5.25
5.25
Phase
3
3
3
3
Voltage
208
211
208
211
Amperage
9.2
8.1
13.5
12.7
Motor RPM
1725
.1725
1750
1750
Motor Service Factor
1.15
1.15
1.15
1.15
Motor Sheave & Bore Size
1 VM50 X .875
1 VP56 X .875
Fan Sheave & Bore Size
AK79 X 1.0
BK85 X 1.0
Belts --- Quantity and Size
1 @A50
1 @ BX54
Precision Balance, Inc.
Telephone:407-876-4112
Fax: 407-876-4338
Date: 05/02/18
Page: 2
Project: FDS #713755
DUCT TRAVERSE ZONE TOTALS
System
Zone/Branch
Duct
Size
Area
Sq.Ft.
Design
FPM CFM
TEST
Test 1 Test 2 Static
FPM FPM CFM Press. /
Meter
AC-1
O/A
22X6
.91
659
600
47
705
641
R/A
30X23
4.79
699
3350
910
756
3621
Vel rid
AC-2
O/A
22X6
.91
659
600
56
689
626
R/A
30X23
4.79
919
4400
1040
1010
4841
Vel rid
AABC Precision Balance, Inc.
Telephone: 407-876.4112
Fax: 407-876-4338
Date: 05/02/18
Page: 3
Project: FDS #713755
DX COOLING COIL DATA
System
AC-1
AC-2
Location
Rear
Building Rear
Service
—Building
Sales/Office
Sales/Register
Manufacturer
York
York
Design
Actual
Design
Actual
Design
Actual
Design
Actual
CFM
4000
4262
5000
5467
E.A.T., DB OF
N/A
73.7
N/A
73.4
E.A.T., WD OF
N/A
65.9
N/A
65.8
L.A.T., DB OF
N/A
52.9
N/A
53.3
L.A.T., WB OF
N/A
52.3
N/A
52.7
O/A., DB F
N/A
82.1
N/A
82.1
O/A., WB F
N/A
71.7
N/A
71.7
Remarks:
AABC Precision Balance, Inc.
Telephone:407-876-4112
Fax: 407-876-4338
Date: 05/02/18
Page: 4
Project: FDS #713756
ELECTRICAL DUCT HEATERS
No.
Area
Served
Mfg.
Design
Volts Amps
Measured
Volts Amps
K. W.
Des. Meas.
1
AC-1
York
208
33.4
211
31.2
12.0
11.6
2
AC-2
York
208
33.4
211
29.5
12.0
10.6
Precision Balance, Inc.
Project: FDS #713755
SMOKE DETECTORS
MAKE: AP&C
MODEL: SL200N
UNITS DESIGN
DIFF. PRESSURE
AC-1 Supply .01 —1.2
Telephone: 407-876-4112
Fax: 407-876-4338
Date: 05/02/18
Page: 5
ACTUAL
DIFF. PRESSURE
.23
AC-2 Supply .01 —1.2 .12
H
W
W
N
F
W
Z
0
m
ra
j
AIR DUCT LEAKAGE TEST SUMMARY
Project:
Air System:
Fan CFM (Q)
Dollar Store #713755
AC-1 Supply
4000
Precision Balance, Inc.
Project Number: Page
Leakage Class (CL)
Specified Test Pressure (R)
Duct Construction Pressure Class (P.)
I of 4
C
-11
2"
DESIGN DATA
FIELD TEST DATA RECORD
SUBJECT DUCT
SURFACE
AREA IN
FT,
ALLOWABLE LEAKAGE
DIAMETER
PRESSURE
"W.G."
DATE
TECH.
WITNESS:
ACTUAL
CFM
FACTOR
CFM/100FT.
CFM
TEST SECT.)
ONCE
TUBE
DUCT
ACROSS
ORIFICE
24" x 8'
25.12
22" x 10'
26.4
20" x 10'
21.8
18" x 10,
17.7
16" x 14'
19.6
14" x 10'
10.7
12" x 38'
29.64
150.96
1.51
22
3"
5"
2.09
.023
05/01/18
JW
MB
22
Precision Balance, Inc.
AIR DUCT LEAKAGE TEST SUMMARY
Project: Family Dollar Store #713755 Project Number: Page
Air System: AC-2 Supply Leakage Class (C,)
Fan CFM (Q): 5000 Specified Test Pressure (P)
Duct Construction Pressure Class (P.)
2 of 4
C
2"
2"
DESIGN DATA
FIELD TEST DATA RECORD
SUBJECT DUCT
SURFACE
AREA IN
FT,
ALLOWABLE LEAKAGE
DIAMETER
PRESSURE
"W.G."
DATE
TECH.
WITNESS:
ACTUAL
CFM
FACTOR
CFM/100FT.
CFM
TEST SECT.)
ORIFICE
TUBE
DUCT
ACROSS
oRIHCE
26" x 8'
29.50
24" x 10'
31.42
22" x 10'
26.40
20" x 10'
21.82
18" x 16'
28.27
14" x 16'
17.10
154.51
1.55
21
3"
5"
2.12
.021
05/01/18
JW
M13
21
Precision Balance, Inc.
AIR DUCT LEAKAGE TEST SUMMARY
Project: Family Dollar Store #713755 Project Number: Page
Air System: AC-1 Return Leakage Class (CL)
Fan CFM (Q): 4000 Specified Test Pressure (R)
Duct Construction Pressure Class (P.)
3 of
4
C
2"
2"
DESIGN DATA
FIELD TEST DATA RECORD
SUBJECT DUCT
SURFACE
AREA IN
FT,
ALLOWABLE LEAKAGE
DIAMETER
PRESSURE
"W.G."
DATE
TECH.
WITNESS:
ACTUAL
CFM
FACTOR
CF1vV100 FTC
CFM
TEST sscr.)
OWICE
TUBE
DUCT
ACROSS
oWICE
30"x23"x20'
95.83
.96
18
3"
5"
2.14
.018
05/01/18
JW
MB
18
Precision Balance, Inc.
AIR DUCT LEAKAGE TEST SUMMARY
Project: Family Dollar Store #713755 Project Number: Page
Air System: AC-2 Return Leakage Class (CL)
Fan CFM (Q): 5000 Specified Test Pressure (R)
Duct Construction Pressure Class (P.)
4 of 4
U
2"
2"
DESIGN DATA
FIELD TEST DATA RECORD
SUBJECT DUCT
SURFACE
AREA IN
FT,
ALLOWABLE LEAKAGE
DIAMETER
PRESSURE
"W.G."
DATE
TECH.
WITNESS:
ACTUAL
CFM
FACTOR
CFM/100 FT,
CFM
TEST sEcr.I
ORIFICE
TUBE
DUCT
ACROSS
ORIFICE
30"x23"x20'
95.83
.96
15
3"
5"
2.17
.015
05/01/18
JW
MB
15
Box 319 usownnuxenuncemuxrn PREC/s/oN BALANCE, ZAfC.
8815 Conroy -Windermere Road TEST AND BA LANCE PROFESSIONALS
Orlando, FL 32835 Phone (407) 876-4112 Fax (407) 876-4338
INSTRUMENT LIST
Instrument
Manufacturer
Model
Serial No.
Required
Calibration
Calibration
Maintained
Capture Hood Kit
Evergreen Telemetry
CH-15D
1700287
24 Months
YeAnt Calibration
Date: 07/24/2017
Capture Hood Kit
Evergreen Telemetry
CH-15D
1700353
24 Months
Yes/Last Calibration
Date: 01129/2017
Water Pressure Sending
Evergreen Telemetry
S-DP-125
1700120
24 Months
Yes/Last Calibration
Module
Date: 3222017
Pressure Velocity Module
Evergreen Telemetry
S-PVF-1
1700297
24 Months
Yes/Last Calibration
Date: 12/042017
Pressure Velocity Module
Evergreen Telemetry
S-PVF-1
1500321
24 Months
Yesn ast Calibration
Date: 03/312017
Pressure Velocity Module
Evergreen Telemetry
S-PVF-1
1600301
24 Months
Yes/Last Calibration
Date: 05/212016
Certificate ofC�alibration
Manufacturer
Evergreen Teleme
Calibration Environment
Product
Capture Hood
Temperature
91
°F
Model
CH-15D
Rel. Humidity
53
%
SN
1700287
Bar. Pressure
_
7A 7
in H
0 As Found As Left � In Tolerance ❑ Out of Tolerance
Callbrat ion Data
Measurement
Variable
Test
Point
Cal
Standard
Allowable
Ran a
Test
Instrument
Min
I Max
Airflow (CFM)
Spec
-3%-7
+3%-7
1
2003
2009
2
997
1011
3•
161
164
4
-555
-558
g
Indicates out of tolerance condition ' - �T
NIST-Traceable Calibration tab Standards
Variable _
stem ID
Calibration Last
Calibration Due
Pressure _
4693940
7/10/2017
7/10/2018
Pressure
1208000080
7/5/2017
7/5/2018
Velocity,
1600344
1/26/2017
1126/2019'
Statement of Traceability
This Instrument has been checked for accuracy, calibrated: to manufacturer's specifications, and 'found to be
within the speed tolerance unless otherwise stated:. It has been -calibrated using measurement standards
traceable to the National institue of Standard's and Technology, or accepted intrinsic standards of measurement,
or derived by the .ratio type of self calibrated techniques.
Calibrated By
624 S. Perry Ln. #102. Temae AZ
July 19,.2017
Calibration Date
Certificate of Calibration
tP/IA;;fAcr.J_f 2A4 A(n,_--
Manufacturer
Ever reen Telemetry
Calibration Environment
Product
Humidity Sensor
Temperature
Model
S-H-3-5"
Rel. Humidity65
SN
1700245
Bar. Pressure
28:6
in H
{J As round Lj As Left
® In Tolerance 0 Out of Tolerance
Calibration Data
Measurement
Variable
Test
Point
Cal
Standard
Allowable Range
Test
Instrument
Min
Max
Temperature (°F)
Barometric
Pressure (in Hg)
_
S ec
1
39.6
10
1'0
39,9
2
71-.3
1.0
10
71.8
3
78.7
-1.0
1.0
79.0
4
Spec
130.6
- -
-2.0
-2%- -1
2.0
+2%+0.1
131.8
1
28.6
28.6
Humidity %RH
10 to 90%
Spec
-3%
+3%
1
12.0
12 2
2
64.4
62:9
3
68.3
4
87.0
84.9
Indicates out of tolerance condition--t
Calibration Standard
Variable
System ID
Calibration Last
Calibration Due
Tem erature_
15171149
11-Jan-17
11,1an-18
Pressure
1208000080
5-Jul-17
5-Jul-18
Humidity
20052171
24Jan-17
24-Jan-18
Statement of Traceability
This instrument has been checked for accuracy, calibrated to manufacturer's specifications, and found to be
within the specified tolerance unless otherwise stated. It been calibrated using measurement standards
traceable to the National institue of Standards and Technology, or accepted intrinsic standards of measurement,
or derived by -the ratio type of. self calibrated techniques.
Temperature accuracy (dry bulb) variesacross the operating range:
Temperature over 32.100F +/-1.0 F
Temperature over 100-158F +1- 2.0 F
Calibrated By
24-Jul-2017 24-Jul-2018
Calibration Date Date Due
Ln
r
Certificate of Calibration
Manufacturer
Eve reen Telemetry
Calibration Environment
Temperature Product
I Module
I Probe
ITemperature
75
1 OF
Model
S-T-1
RM-T-1
PR-T-1
Rel. Humidity
56
%
SN
1 1700314
1 1700314
Bar. Pressure
28.7
in H
❑ As Found
® As Left
® In Tolerance ❑ Out of Tolerance
Calibration Data
Measurement
Variable
Test
Point
Cal
Standard
Allowable'Range
Test
Instrument
Min
Max
Test Module & Test Probe
Temperature (°F)
Spec
1
78.8
-0.3
+0.3
78.9
2
241.3
-2.6
+2.6
241,5
3
-43.8
-1.6
+1.6
-44,5
Indicates out of tolerance condition —T
Calibration Standard SN & Dates
Variable
System ID
Calibration Last
Calibration Due
Temperature
15171'149
11-Jan-17
11-Jan-18
Statement of Traceability
This. instrument has been checked for accuracy, calibrated to manufacturer's specifications, and found to be
within the specified tolerance unless otherwise stated.. It has been calibrated using measurement standards
traceable to a National Institueof Standards and Technology, or accepted intrinsic standards of measurement,
or'derive¢�fi> t pe of self calibrated techniques.
-�y/' 16-Jul-2017 18-Jul-2019
Calibrated By Calibration Date Date Due
92 ■
S. Perry Ln #102, Tempe, AZ 85281
Certificate of Calibration
1�lZCG 15" t v,J t��ita4,(C-r
Manufacturer
Ever teen Telemet
Calibration Environment
Temperature Product
S-T-1
Module
Prdbe
Tem erature
78
°F
Model
RM-T-1
PR-T 4
Rel. Humidi
36
SN
1700156
Sar. Pressure
28:5
in H
❑ As Found
® As Left
El In Tolerance Q Out of Tolerance
Calibration Data
Measurement
Variable
Test
Point
Cal
Standard
Allowable
Range
Test
Instrument
Min
Max
Test Module & Test Probe
Temperature (°F)
Sec
1
79.0
-0 3
+0.3
79.0
2
242.0
-2:6
+2,6
242.3
3
-43.2
-1.6
+1.6
-43.0
Indicates but of toleranoe'condition —T
Calibration Standard SN &Dates
Variable -- -
System ID.
Calibration Last
Calibration Due
Temperature
15171149
11-Jan-17
1U,Jan=18
Statement of Traceability
This instrument has been checked for accuracy, calibrated to manufacturer's specifications, and found to be
within the specified tolerance unless othenvise stated,1t has been calibrated using measurement standards
traceable to the National Institueof Standards .and Technology, .or accepted intrinsic standards of measurement,
-or derived ty,%tt�eiotyp of If calibrated techniques.
28-Jul-2017 28-Jul-2019
Calibrated By Calibration Date Date Due
602.574.6192
■ 624 S. Perry Ln
w
Certificate of Calibration
POl--7 tC t,I- ( P-Ai .L YA L
Manufacturer
Evergreen Telemetry
Calibration Environment
Product
Pressure /Velocity Module
Temperature
76
OF
Model
S-PVF-1
Rel. Humidity
57
SN
'1700297
Bar. Pressure
28.6
inH
0 As Found As Left ® In Tolerance ❑ Out of Tolerance
Calibration Data
Measurement
Variable
Test
Point
Gal
Standard
Allowable
Range
Test
Instrument
---M—in---F
Max
Barometric
Pressure (in Hg)
Spec
-2%-0.1
+2%+0.1
1
24.3
24.3
2
28.6
28.6
3
30.1
30.2
Differental
Pressure
(in wc)
Spec
-2%-.001
+2%+.001
1
10.00
9.999 '
2
2.000
2.005
3
0:5000
0.5020
4
0.0500
0.0500
5
-10.00
=10.05
6
-0.0500
-0.0502
Low Velocity
(FPM)
Sec
-3% - 7
+ 3% + 7
1
100
101
2
503
503
Airflow
°F
'Spec
3%-T
+3%+7
1
100
UPON
2
500
1
REQUEST
Indicates out of tolerance condftion °T
NIST-Traceable Lab Calibration Standards
Variable
System ID
Calibration Last
Calibration Due
Pressure
4693940
10-Jul-17
10-Jul-18
Pressure
1208000080
5-Jul-17
5-Jul-18
Veloci
1600344
26-Jan-17
26-Jan-19
Statement of Traceability
This instrument has been checked for accuracy, calibrated to manufacturer's specifications, and found to be
within the specified tolerance unless otherwise stated. It has been calibrated using measurement standards
traceable to the National Institueof Standards and Technology, or accepted intrinsic standards of measurement,
or derived �the ratio Wpe ofrself calibrated techniques.
24-Jul-2017 24-Jul-2019
Calibrated By Oalibration Date Date Due
85281 • 602-574.6192
Certificate of Calibration
Precision Bal recal
Manufacturer
Evergreen Telemet
Calibration Environment
Product
Pressure./ Velocity Module
Temperature
75
OF
Model
S-PVF-1
Rel. Humid'
25
%
SN
1560321
Bar. Pressure
285
in H
I�SI As Found As Leff In Tolerance ❑ Out of Tolerance
( Calibration Data
Measurement
Variable
Test
'Point
Cal
Standard
Aliowable'Range
Test`
Instrument
Min
Max
Barometric
Pressure (in Hg)
—Spec
-2%-0:1
+2%+0.1
1
2510
26:0
2
28.5,
28.5
3
30.2
30.2
Differental
Pressure
(in WC)
. —Spec
-2%-.001
+2%+,001
1
10.00
9.986
2
2.000
2.000
3
U500
0.5008
4
0.0500
0.0501
5
r10.00_—
.. ,..,._,,
...;.�...
7-- _10,02'
6
-0.0500
-0.0500
Low Velocity
(FPM)
Spec
-3%-7
+3%+7
1
109
109 .
2
504
502
Airflow
(°F)
5 ec
-3%-7
+3%+7
1
100
11
- UPON
2
500
t I
REQUEST'
Indicates out of tolerance condition T
NIST-Traceable Lab Calibration Standards
Van be
System ID.
Calibration Last .
Calibration Due..
Pressure
4693940
16-Jul-16
16-Jul-17
Pressure
1208000080
15-Se 16
15-Se A7
Velocity
1600344
26Jan-17
26-Jan-19
Statement of Traceability
This instrument has been'checked for accuracy, calibrated to manufacturer's specifications, and found to be
within the specified tolerance unless otherwise stated. Ithas been calibrated using measurementstandards
traceable to the National Institue of Standards and Technology, or accepted intrinsic standards of measurement,
or derived t e rahoty a of self calibrated techniques.
31-Mar-2017 31-Mar-2019
Calibrated By Calibration Date Date Due
AZ
Certificate of Calibration
Manufacturer
Evergreen Telemetry
Calibration Environment
Product
Capture Hood
Temperature
75
of
Model
CH-15D
Rel. Humidity
32
%
SN
1700359
Bar, Pressure
28.8
in H
❑ As Found ® As Left ® In Tolerance ❑ out of Tolerance
Calibration Data
Measurement
Variable
Test
Point
Cal
Standard
Allowable
Range
Test
Instrument
Min
Max
Airflow (CFM)
-3% - 7
+3%-7
—Spec
1
2010 -
-
2019
2
1005
1000
3
158
158
4
-542
-541
5
Indicates out of tolerance condition T
NIST-Traceable Calibration Lab Standards
Variable
System ID
Calibration Last
Calibration Due
Pressure _
4693940
7/1012017
7/10/2018
Pressure
1208000080
7/5/2017
7/5/2018
Velocity
1600344
1/26/2017
1/26/2019
Statement of Traceability
This instrument has been checked for accuracy, calibrated to manufacturers specifcations, and found to be
within the specified tolerance unless otherwise stated. It has beencalibratedusing measurement standards
traceable to the National Institue of Standards and Technology, ocaccepted`intrinsic standards of measurement,
or derived by the ratio type of self calibrated techniques.
�t♦� a�L
Calibratii'd
S. Perry Ln. #102, Tempe AZ 65261 • 602-574.6192
November 29, 2017
Calibration Date
Certificate of Calibration
Manufacturer
Evergreen Telemetry
Calibration Environment
Product
Humiditv Sensor
ITemDerature
1 78
1 OF
Model
S-H-3-5"
Rel.-Humidity
58
SIN
1700347
Bar. Pressure
28.8
in H
❑ As Found ® As Left
® In Tolerance [3 Out of Tolerance
Calibration Data
Measurement
Variable
Test
Point
Cal
. Standard
Allowable Ran a
Test
Instrument
Mid
Max
Temperature (°F)
Spec
1
39.6
A:0
1.0
39.9
2
78.9
=1.0
1.0
79.0
3
78.6
-1.0
1.0
78.9
4
130.3
-2.0
2.0
-131.1'
Barometric
Pressure (in Hg)
Sec
-2% - 0;1
+ 2%+ 0:1
1
28.8
28.8
Humidity %RH
10 to 90%
Spec
3%
+3%
1
7.3
8.7
2
62.7
61.5
3
60.5
60.9
4
81.1
79.4
Indicates out of tolerance condition --t
Calibration Standard
Variable
System ID
Calibration Last
I Calibration Due
Temperature
15171149.
11-Jan-17
11-Jan-18
Pressure
1208000080,
5-Ju1,17
5-Jul-18
Humidity
20052171
24-Jan-17
24-Jan-18
Statement of Traceability
This instrument has been checked for accuracy, calibrated to manufacturer's specifications, and found to be
within the specified tolerance unless otherwise stated. It has been calibrated using measurement standards
traceable to the National Institue of Standards and Technology, or accepted intrinsic standards of measurement,
orderived by the ratio type ofself calibrated techniques.
Temperature accuracy (dry bulb) varies across the operating range:
Temperature over 32-100F +/-1.0 F
Temperature over100-158F �1- 2.0 F
W�11' I's I L�Imvftzmzw z' I
26-0ec-2017 26-Dec-2018
Calibration Date Date Due
024 S. Perry Ln #1
Certificate of Calibration
Manufacturer Evergreen Telemetry
Calibration Environment
Product Pressure / Velocity,Module
Temperature
77
OF
Model S7PVF-1
Rel. Humidity
24
%
SN 1700414
Bar. Pressure
287
in
❑ As Found ® As Left
Im In Tolerance ❑ Out of Tolerance
Calibration Data
Measurement
Variable
Test
Point
Cal
Standard
Allowable
Range
Test
Instrument
Min
Max
Barometric
Pressure (in Hg)
Spec
-2%-0.1
+2%+0.1
1
24A
24.2
2
28.7
2&8
3
30.3
30.4
Differental
Pressure
(in wc)
Spec
-2%-.001
+2%+.001
1
10.00
10.00
2
2.000
1.999
3
0.5000
0.4952
4
0.0500
0.0497
5
-10.00
-10.05 _
6
-0,0500
-0.0496
Low Velocity
(FPM)
Sec
3%-7
+3%+7
1
105
106
2
507
509
Airflow
°F
Spec
" -3% - 7
+ 3°/a + 7
1
1001
UPON
2
500
1 REQUEST
Indicates out of tolerance condition , " T
NIST-Traceable Lab Calibration Standards
Variable
System ID
Calibration Last
Calibration Due
Pressure
4693940
10-Jul-17
10-Jul=18
Pressure
1208000080
5-Jul-17
5-Jul-18
Velocity
1600344
26-Jan-17
26'-Jan-19
Statement of Traceability
This instrumenfhasbeen checked for accuracy, calibrated to manufacturer's specifications, and found to be
Within the specified tolerance unless otherwise stated. It has been calibrated using measurement standards
traceable,to the National Institue of standards and Technology,,or acceptedintrinsic standards of measurement,
or derived -by the ratio type of self calibrated techniques.
20-Dec-2017 20-Deo-2019
caudratea fay GanDration Date Date Due
624 S. Perrytn. #102, Tempe AZ
Certificate of Calibration j
Manufacturer
Ever reen Telemetry
Calibration Environment
Temperature Product
Module
Probe
Temperature
74
1 OF
Model
RM-T-1
I PR-T-1
Rel. Humiditv
I 26
SN
1700432
1 1700422
Bar. Pressure
1 28.7
1 in H
U As Found
® As Left-
® In Tolerance ❑ Out of Tolerance
Calibration Data
Measurement
Variable
Test
Point
Cal
Standard
Allowable Ran a
Test
Instrument
Min
Ma_x___1
Test Module & Test Probe
Temperature (°F)
Spec
1
78.9
-0.3
+0.3
79.1
2
243.1
-2.6
+2.6
243.1
3
-43.4
-1.6
+1.6
44.0
Indicates out of tolerance condition —t
Calibration Standard SN &Dates
Variable
System ID
Calibration Last
CalibrRonDue
Tem erature
15171149
11rJan-17
11-Jan-18 -
Statement of Traceability
This instrument has been checked for accuracy, calibrated to manufacturer's specifications,.andfound to be
within the specified tolerance unless otherwise stated. It has been calibrated using measurement standards
traceable to the National Institue of Standards and Technology, or accepted intrinsic standards of measurement,
orderive by the ratio type of self calibrated techniques.
21-Dec-2017 21-Dec-2019
Calibrated 13y Calibres}ion Dato Da£e Due
■ 624 S. Perry Ln 4102, Tempe, AZ
Certificate of. Calibration
Manufacturer
Eve reen Telemetry
Calibration Environment
Temperature Product
Module
Probe
Temperature
77
OF
Model
PR-T-4-6
Rel. Humidity
36
SN
1700234
Bar, Pressure
28.6
in H
❑ As Found
® As Left
® In Tolerance ❑ Out of Tolerance
Calibration Data
Measurement
Variable
Test
Point
Cal
- Standard _
Allowable Range
Test
Instrument
. Min
Max
Test Module & Test Probe
Temperature (°F)
Sec
1
79.1
-0.3
+0.3
Y9.0
2
241.1
-2.6
+2.6
241.6
3
-42.9
-1.6
+1.6
-42.5
Indicates out of tolerance condition.—t
Calibration Standard SN &Dates
Variable
5 stem ID
Calibration Last
Calibration Due
Temperature
15171149
11-Jan-17
11-Jan-18
Statement of Traceability
This instrument has been checked for accuracy, calibrated to manufacturer's specifications, and found to be
within the specified tolerance unless otherwise stated-111 has been calibrated using measurement standards
f�nnnnMln 4n 4k- NJ-,; --- I 1..-a:+.0 �Of J -J J ..-[
or deri edby the ratio type calibrated techniques.
� 13-Dec-2017 13-Dec-2019
`CQlGeMad By Calibration Date Dato Due
Certificate of Calibration
rreasion tialance
Manufacturer
Evergreen Telemet
Calibration Environment
Product
Pressure I VelocityModule
Temperature
74
OF
Model
S-PVF-1
Rel. Humidity
31
%
SN
1700297
Bar. Pressure
28.7
in H
13 As Found As Left Ig In Tolerance ❑ Out of Tolerance
Calibration Data
Measurement
-Variable
Test
Point
Gal
Standard
Allowable
Ran a
Test
Instrument
Min
I Max'
Barometric
Pressure (in Hg)
Spec
-2%-0.1.
+2%+0:1
1
24.9
24,9
2
28.7
28.7
3
30.1
30.1
Differental
Pressure
(in we)
Spec
-2%-.001
+2%+,001
-
1
10.00
10.00
2
2.000
2.007
3
0.5000
0.5029
4
0.0500
0.0504
5
-10.00
-10.05
6
-0..0500
0.0502
Low Velocity
(FPM)
Sec
-3% - 7
+ 3% +7
1
109
108
2
503
604
Airflow
OF
S ec
-3"/6-.7
+3%+7
1
100
UPON
2
1 500
REQUEST
"Indicates out of tolerance condition . - ?
NIST-Traceable Lab Calibration Standards
Variable
System ID.
Calibration Last
Calibration Due
Pressure
4693940
10-Jul-17
10-Jul-18
Pressure
1208000080
5-Jul-17
5-Jul-18
Velocity
1600344
26-Jan-17
26-Jan-19
Statement ofTraceability
This instrument has been checked for accuracy, calibrated to manufacturees specifications, and found to be
within the specified tolerance unless otherwise stated. It.has been calibrateBusing measurement standards
traceable to the National Institue of Standards and Technology, or accepted intrinsic standards of measurement
of dnri ;ed by the ratio type of self calibrated techniques..
r 4-Dec-2017 4-Dec-2019
Calibrated By 'Calibration Date Date Due
EVERGREEN Certificate of Calibration
TELEMETRY
Manufacturer
Evergreen Telemetry
- Calibration Environment
Product
Pressure I Velocity Module
Tem erature
85
Model
S-PVF-1
Rel. Humidity26
#..
SN
1600301
Bar. Pressure
28.7
0 As Found As Left l9 In Tolerance ❑ Out of Tolerance
Calibration Data
Measurement
Variable
Test
Paint
Cal
Standard -
Allowable
Range ,
Test
Instrument
-Min
Max
Barometric
Pressure (in Hg)
Spec
-2%-0.1
-2%+_0.1
1
26,2
25.1
2
28.5
28.6
3
30.3
30.4
Differental
Pressure
(in wc)
Spec
-2%1001
+2%-.001
1
10.000
9.999
2
2.000
1:998
3
0.5000
0.5016
4
0.0500
0.0502
5
-10.000.
if
-10.035
6
0.0500
0,0504
Low Velocity
(FPM)
Sec
-3%-7
♦3%t7
i
Soo
502
2
108.
110
Airflow
=F
Spec
-3%-7
-3%+7
1
100
UPON
2
500..
REQUEST
mmca¢s out of amn. common -T
Calibration Standards
Variable
System ID
Calibration Last
I Calibration. Due
Pressure
- 4593WO
16Ju1-15
I l"u1-15
Pressure
1208000080.
15-Sep-15
15-Se 16
Velcorty,
1 1500301
1 27-Jan-15
27-Jan-17
Statement of Traceability
This instrument has been checked for accuracy, calibrated to manufacturers specifications, and found to be
within the specified tolerance unless othervnse stated.. 11 has been calibrated using measurement standards
traceable to the National Insdlue of Standards and Technology, or accepted Intrinsic standards of measurement,
or derived by the ratio type of self calibrated techniques.
QRA A0.f 9 ./9_V Z4_t:'I 12-May-2016 12-May-2018
alibrated By Calibration Date Date Due
SCANNED
BY
St. Lucie Countv
TEST & BALANCE REPORT FOR
FAMILY DOLLAR STORE #713755
FT. PIERCE, FL
Prepared by
PRECISION
BRLRNCE
INC.
RECEIVED
MAY 0 7 2018
ST. Lucie County, Permitting
TESTING, ADJUSTING AND RALANCE PROFESSIONALS
= L_IAMtNU- SEE CHANGES BEWA'
0 ACCEPTED AS NOTED ❑REJECTED -
❑ RETURNED FOR CORRECTION
ACCEPTANCE IS FOR GENERAL COMPLIANCE WITH THE CONTRACT
DOCUMENTSONLY, THE CONTRACTCR IS RESPONSIBLE FORCONFIRMINC
AND CORRELATING ALL OUMTITIES AND DIMENSIONS; SELECTING
FABRICATION PROCESSES AND TECHNIQUES OF CONSTRUCTICN;
COORDINATING ITS 'WORK WITH THAT OF ALL OTHER TRADES;
AND OPM G ITS ORK I AFE AN SATISFACTORY MANNER
Br L!3 1.4, �riL�� f=ram `
JATc�� iII
F'n5 - F-r 71 e= a
AABC National
Performance Guaranty
Pursuant to the agreement between
Precision Balance, Inc., Orlando, Florida
AABC Certified Testing & Balancing Agency
Celsius Mechanical
All systems shall be balanced in accordance with the plans and specifications and to the optimum performance
capabilities of the equipment and design. Testing and balancing shall be done in accordance with the standards
published by the Associated Air Balance Council.
If for any reason, the Agency listed above fails to comply with the specifications, with the exception of termination
of business by the Agency, equipment malfunction or inadequacy, or improper design, which prevents proper
balancing of the systems, the Associated Air Balance Council will provide supervisory personnel to assist the Agency
to perform the work in accordance with AABC Standards.
As part of the Performance Guaranty, the engineer or building owner may call upon AABC to assist him with any
technical and/or field problems pertaining to the final balanced condition of systems. These services will be made
available at no additional charge by the above agency or by AABC National Headquarters.
Project Name Family Dollar Store #713755
Address 3214 Ave D
Ft. Pierce, FL 34947
Name of Engineer Harold Daniel Hutter III
Engineering Firm LIS
Address Alva, FL 33920
Date 05/02/18
TBE # 06-09-43 -
By Kyle Stout =
AABC Certified TBE AABC
Associated Air
Balance Council
9
AABC
Associated Air Balance Council
Annual Certificate
✓Gioa1ykdto-
Kyle Stout
Precision Balance, Inc.
Y,w/-W &O.'Z o� f/m&;7�� a&al
Oel�d gZst and a&"ve cooi iizeelC
mae e- do ra/el� 1W&k&01?t and /VYZ iWWgt& of t1ze,
✓lssociatca�✓lii� �a/aitcri G'oa�ci./..T/ertzGor��iuroze�i��u/G�
aut/ro�Gxed to-/rei�ivro totaG Jstenv Ga/�ueee rm accoidaiu,�
wetl&tG.l&alhAztka&mtaGlisW6r,&/e.✓ 06'aizda&m
20AV
°T/uv, i,y"w,,onl m-,n er-MSJMVJQP of"(/ 1,"yr.i&a
tli6 s, and c/zaitei� o� f dziv�a, sionaLass aw&am
6'er Aa&o 1 a/ lmecoaGkj onv anl a wed Ga ,w glia-
ce1&&ze& eal ri,es. -0ecenebla- 31 20AV
Michael Delcamp, President
Kcn�cth M. Sufka, Executive Strector
N
Precision Balance, Inc.
Telephone: 407-876-4112
Fax: 407-876-4338
Date: 05/02/18
Page: 1
Project: FDS #713755
AIR MOVING EQUIPMENT TEST SHEET
SYSTEM
AC-1
AC-2
Equipment Location
Building Rear
Building Rear
Area Served
Sales/Office
Sales/Register
Equipment Manufacturer
York
York
Model
ZYE12A2B1
ZXE14A2C3DA
Serial Number
N1 B8506771
N1 B8506770
Specified
Actual
Specified
Actual
Total CFM- Fan
4000
4262
5000
5467
Total CFM-Outlet
3950
4262
5000
5467
R/A CFM
3350
3621
4400
4841
O/A CFM
600
641
600
626
Total Static Pressure (Total/External)
--- /---
.51/.47
--- /---
2.10/1.37
Inlet Pressure
/---
.24/.20
--- /---
1.96/1.23
Discharge Pressure
---
.27
---
.14
Fan RPM
---
818
---
981
Specified
Actual
Specified
Actual
Motor Manufacturer
---
Marathon
---
Baldor
Motor HP
N/A
N/A
5.25
5.25
Phase
3
3
3
3
Voltage
208
211
208
211
Amperage
9.2
8.1
13.5
12.7
Motor RPM
1725
1725
1750
1750
Motor Service Factor
1.15
1.15
1.15
1.15
Motor Sheave 8 Bore Size
1 VM50 X .875
1 VP56 X .875
Fan Sheave 8 Bore Size
AK79 X 1.0
BK85 X 1.0
Belts -- Quantity and Size
1 @A50
1 @ BX54
IV AGGEPTED ❑ AMEND -SEE CHANT
❑ ACCEPTEDAS NOTED ❑ REJECTED
❑ RETURNED FOR CORRECTION
xEPTANCE IS FOR GENERAL COMPLIANCE WITH THE
)CUMENTSONLY. THE CONTRACTOR IS RESPONSIBLE FORCI
ID CORRELATING ALL QUANTITIES AND DIMENSIONS; t
BRICATION PROCESSES AND TECHNIQUES OF CONS?
IORDINATING ITS WORK WITH THAT OF ALL OTHER
- Pr P/E9CE
5
AABC Precision Balance, Inc.
Telephone: 40 7-876-4112
Fax: 407-876-4338
Date: 05/02/18
Page: 2
Project: FDS #713755
DUCT TRAVERSE ZONE TOTALS
System
Zone/Branch
Duct
Size
Area
Sq.Ft.
Design
FPM CFM
TEST
Test 1 Test 2 Static
FPM FPM CFM Press. /
Meter
AC-1
O/A
22X6
.91
659
600
47
705
641
R/A
30X23
4.79
699
3350
910
756
3621
Vel rid
AC-2
O/A
22X6
.91
659
600
56
689
626
R/A
30X23
4.79
919
4400
1040
1010
4841
Vel rid
AABC Precision Balance, Inc.
Telephone: 407-876-4112
Fax: 407-876-4338
Date: 05/02/18
Page: 3
Project: FDS #713755
DX COOLING COIL DATA
System
AC-1
AC-2
Location
Building Rear
Building Rear
Service
Sales/Office
Sales/Register
Manufacturer
York
York
Design
Actual
Design
Actual
Design
Actual
Design
Actual
CFM
4000
4262
5000
5467
E.A.T., DB T
N/A
73.7
N/A
73.4
E.A.T., WD T
N/A
65.9
N/A
65.8
L.A.T., DB T
N/A
52.9
N/A
53.3
L.A.T., WB T
N/A
52.3
N/A
52.7
O/A., DB F
N/A
82.1
N/A
82.1
O/A., WB F
N/A
71.7
N/A
71.7
Remarks:
Precision Balance, Inc.
Telephone: 407-876.4112
Fax: 407-876-4338
Date: 05/02/18
Page: 4
Project: FDS #713755
ELECTRICAL DUCT HEATERS
No.
Area
Served
Mfg.
Design
Volts Amps
Measured
Volts Amps
K. W.
Des. Meas.
1
AC-1
York
208
33.4
211
31.2
12.0
11.6
2
AC-2
York
208
33.4
211
29.5
12.0
10.6
i
1,v-X-111111
Project: FDS #713755
MAKE: AP$C
MODEL: SL200N
Precision Balance, Inc.
SMOKE DETECTORS
UNITS DESIGN
DIFF. PRESSURE
AC-1 Supply .01 —1.2
Telephone: 407-876-4112
Fax: 407-876-4338
Date: 05/02/18
Page: 5
ACTUAL
DIFF. PRESSURE
.23
AC-2 Supply .01 —1.2 .12
nNMI
EF
0
Z
.4
m
-1
CO)
x
m
m
-1
T
0.
m
fr
v
y
V
W
V
Ul
Ul
�D
n
N
y X �
7T
m0
..
ID IUOD 'OO
1'1'1
0
v 7
O CIO!?
°fo
O
�NWC,
Ci
DD
OD
A
K)
N
_i
Precision Balance, Inc.
AIR DUCT LEAKAGE TEST SUMMARY
Project: Family Dollar Store #713755 Project Number: Page
Air System: AC-1 Supply Leakage Class (CL)
Fan CFM (Q): 4000 Specified Test Pressure (P)
Duct Construction Pressure Class (P.)
1 of
4
C
2"
2"
DESIGN DATA
FIELD TEST DATA RECORD
SUBJECT DUCT
SURFACE
AREA IN
FT,
ALLOWABLE LEAKAGE
DIAMETER
PRESSURE
"W.G"
DATE
TECH.
WITNESS:
ACTUAL
CFM
FACTOR
CFM/100 FT:
CFM
TEST SECT.)
ORMCE
TUBE
DUCT
ACROSS
ORMCE
24" x 8'
25.12
22" x 10'
26.4
20" x 10'
21.8
18" x 10'
17.7
16" x 14'
19.6
14" x 10'
10.7
12" x 38'
29.64
150.96
1.51
22
3"
5"
2.09
.023
05/01/18
JW
MB
22
Precision Balance, Inc.
AIR DUCT LEAKAGE TEST SUMMARY
Project: Family Dollar Store #713755 Project Number: Page
Air System: AC-2 Supply Leakage Class (C,)
Fan CFM (Q): 5000 Specified Test Pressure (P)
Duct Construction Pressure Class (P.)
2 of 4
C
2"
2"
DESIGN DATA
FIELD TEST DATA RECORD
SUBJECT DUCT
SURFACE
AREA IN
FT z
ALLOWABLE LEAKAGE
DIAMETER
PRESSURE
`•W.G."
DATE
TECH.
WITNESS:
ACTUAL
CFM
FACTOR
CFM/100 FT
CFM
TEST SECT.)
ORQ ICE
TUBE
DUCT
ACROSS
OWICE
26" x 8'
29.50
24" x 10'
31.42
22" x 10'
26.40
20" x 10'
21.82
18" x 16'
28.27
14" x 16'
17.10
154.51
1.55
21
3"
5"
2.12
.021
05/01/18
JW
MB
21
Precision Balance, Inc.
AIR DUCT LEAKAGE TEST SUMMARY
Project: Family Dollar Store #713755 Project Number: Page
Air System: AC-1 Return Leakage Class (CL)
Fan CFM (Q): 4000 Specified Test Pressure (R)
Duct Construction Pressure Class (P.)
3 of
4
C
2"
2"
DESIGN DATA
FIELD TEST DATA RECORD
SUBJECT DUCT
SURFACE
AREA IN
FT x
ALLOWABLE LEAKAGE
DIAMETER
PRESSURE
"W.G."
DATE
TECH.
WITNESS:
ACTUAL
CFM
FACTOR
CFM/100FTx
CFM
TESTSECTJ
OWICE
TUBE
DUCT
ACROSS
OWICE
30"x23"x20'
95.83
.96
18
3"
5"
2.14
.018
05/01/18
JW
MB
18
J
Precision Balance, Inc.
AIR DUCT LEAKAGE TEST SUMMARY
Project: Family Dollar Store #713755 Project Number: Page
Air System: AC-2 Return Leakage Class (C,)
Fan CFM (Q): 5000 Specified Test Pressure (P.)
Duct Construction Pressure Class (P.)
4 of
4
C
2"
2"
DESIGN DATA
FIELD TEST DATA RECORD
SUBJECT DUCT
SURFACE
AREA IN
FT,
ALLOWABLE LEAKAGE
DIAMETER
PRESSURE
"W.G."
DATE
TECH.
WITNESS:
ACTUAL
CFM
FACTOR
CFM/100Fr.
CFM
TEST SECT.)
ORRICE
TUBE
DUCT
ACROSS
ORMCE
30"x23"x20'
95.83
.96
15
3"
5"
2.17
.015
05/01/18
JW
MB
15
M
Box 319 cessowrrnuaeu waramnr PRZC/S/ONBALANCE /NC.
8815 Conroy -Windermere Road TEST AND BALANCE PROFESSIONALS
Orlando, FL 32835 Phone (407) 876-4112 Fax (407) 876-4338
INSTRUMENT LIST
Instrument
Manufacturer
Model
Serial No.
Required
Calibration
Calibration
Maintained
Capture Hood Kit
Evergreen Telemetry
CH-15D
1700287
24 Months
Yes/last Calibration
Date: 0724/2017
Capture Hood Kit
Evergreen Telemetry
CH-15D
1700353
24 Months
Yes/Last Calibration
Date: 011292017
Water Pressure Sending
Evergreen Telemetry
S-DP-125
1700120
24 Months
Yes/Last Calibration
Module
Date: 3/22/2017
Pressure Velocity Module
Evergreen Telemetry
S-PVF-1
1700297
24 Months
Yes/Last Calibration
Date: 12/042017
Pressure Velocity Module
Evergreen Telemetry
S-PVF-1
1500321
24 Months
Yes/Last Calibration
Date: 03/31/2017
Pressure Velocity Module
Evergreen Telemetry
S-PVF-1
1600301
24 Months
Yes/Last Calibration
Date: 05/212016
EVERGREEN
TELEMETRY
Certificate of Calibration
Manufacturer
Evergreen Telemetry
\l fi\ Vl
Calibration Environment
Product
Capture Hood
Temperature
91
or
Model
CH-15D
Rel. Humid
53
%
SN
1700287
Bar. Pressure
28.7
in H
❑ As Found As Left 0 In Tolerance ❑ Out of Tolerance
Calibration Data
Measurement
Variable
Test
Point
Cal
Standard
Allowable
Range
Test
Instrument
Min
I Max
Airflow (CFM)
Spec
-3% - 7
1 +3%-7
1
2003
2009
2
997
1011
3
161
164
4
-555
-558
5
Indicates out of tolerance condition T
NIST-Traceable Calibration Lab Standards
Variable
System ID
Calibration Last
Calibration Due
Pressure
4693940
7/10/2017
7/10/2018
Pressure
1208000080
7/5/2017
7/5/2018
Velocity
1600344
1/26/2017
V26/2019
Statement of Traceability
This instrument has been checked for accuracy, calibrated to manufacturers specifications, and found to be
within the specified tolerance unless otherwise stated. It has been calibrated using measurement standards
traceable to the National Instnue of Standards and Technology, or accepted intrinsic standards of measurement,
or derived by the ratio type of self calibrated techniques.
IP229
Calibrated By
AZ 86281 • 602-574-6192
July 19, 2017
Calibration Date
EVERGREEN
TELEMETRY
Certificate of Calibration
,I 1A:;-Ta c r ,r_ 12 e., b (� , --
Manufacturer
Evergreen Telemetry
Calibration Environment
Product
Humidity Sensor
Temperature
74
°F
Model
S-H35"
Rel. Humidi
65
%
SN
r-2
1700245
�.
Bar. Pressure
28.6
in H
Lj r,s Found W As Left
® In Tolerance Q Out of Tolerance
Calibration Data
Measurement
Variable
Test
Point
Cal
Standard
Allowable Range
Test
Instrument
Min
Max
Temperature ("F)
Barometric
Pressure (in Hg)
S ec
1
39.6
1.0
1.0
39.9
2
71.3
1.0
1.0
71.8
3
78.7
71.0
1.0
4
Sec
130.6
-2.0
-2%-0.1
2.0
+2%+0.1
131.8
1.8
1
28.6
28.6
Humidity %RH
10 to 90%
11
S ec
-3%
+3%
1
120
12.2
2
64.4
62.9
3
68.3
69.6 _
4 1
87.0
84.9
Indicates out of tolerance condition -T
Calibration Standard
Variable
System ID
Calibration Last
Calibration Due
Tem erature
15171149
11-Jan-17
11.1an-18
Pressure
1208000080
5:lul-17
5-Jul-18
--Humidity
20052171
24 Jan-17
24-Jan-18
Statement of Traceability
This instrument has been checked for accuracy, calibrated to manufacturers specifications, and found to be
within the specified tolerance unless otherwise stated. It has been calibrated using measurement standards
traceable to the National Institue of Standards and Technology, or accepted intrinsic standards of measurement,
or derived by the ratio type of self calibrated techniques.
Temperature accuracy (dry bulb) varies across the operating range:
Temperature over 32-100F +/_ 1.0 F
Temperature over 100.158E +/_ 2.0 F
Calibrated By
24-Jul-2017 24-Jul-2018
Calibration Date Date Due
Ln
EVERGREEN
TELEMETRY
Certificate of Calibration
ML--r t C. % DJ rsA-LA-,S iG-
Manufacturer
Ever reen Tell etry
Calibration Environment
Temperature Product
Module
Probe
Temperature
75
OF
Model
S-T-1
RM-T-1
PR-T-1
Rel. Humidity
56
%
SN
1700314
1700314
Bar. Pressure
28.7
in H
❑ As Found
® As Left
® In Tolerance ❑ Out of Tolerance
Calibration Data
Measurement
Variable
Test
Point
Cal
Standard
Allowable
Range
Test
Instrument
Min
Max
Test Module & Test Probe
Temperature (OF)
Spec
1
78.8
-0.3
+0.3
78.9
2
241.3
-2.6
+2.6
241.5
3
-43.8
-1.6
+1.6
-44.5
Indicates out of tolerance condition — r
Calibration Standard SN &Dates
Variable
I . System ID
Calibration Last
Calibration Due
Temperature
1 15171149
11Jan-17
11Jan-18
Statement of Traceability
This instrument has been checked for accuracy, calibrated to manufacturer's specifications, and found to be
within the specified tolerance unless otherwise stated. It has been calibrated using measurement standards
traceabpd��Kl
National Institue of Standards and Technology, or accepted intrinsic standards of measurement,
or derie ratio pe of self calibrated techniques.
. 18Jul-2017 16Jul-2019
Calibrated By Calibration Date Date Due
802.574.6192 ■
■ 624 S. Perry Ln #102, Tempe, AZ 85281
EVERGREEN
TELEMETRY
Certificate of Calibration
PC 15' t O %J P At --A dCr
Manufacturer
E ergreen Telemetry
Calibration Environment
Temperature Product
S-T-1
Module
I Probe
ITemperphirp
78
of
Model
RM-T-1
PR-T-4
lRel. Humidity
36
%
SN
11700168
113ar. Pressure
28.5
in H
❑ As Found
® As Left
f3 In Tolerance ❑ Out of Tolerance
Calibration Data
Measurement
Variable
Test
Point
Cal
Standard
Allowable
Range
Test
Instrument
Min
Max
Test Module & Test Probe
Temperature (OF)
Spec
1
79.0
-0.3
+0.3
79.0
2
242.0
-2.6
+2.6
242.3
3
43.2
-1.6
+1,6
-43.0
Indicates out of tolerance condition —1`
Calibration Standard SN & Dates
Variable
System ID
Calibration Last
Calibration Due
Temperature
15171149
11-Jan-17
11-Jan-18
Statement of Traceabilitv
This instrument has been checked for accuracy, calibrated to manufacturers specifications, and found to be
within the specified tolerance unless otherwise stated. It has been calibrated using measurement standards
traceable to the National Institue of Standards and Technology, or accepted intrinsic standards of measurement,
or derived t ratio ty of self calibrated techniques.
— 28-Jul-2017 28-Jul-2019
Calibrated By Calibration Date Date Due
EVERGREEN
TELEMETRY
Certificate of Calibration
e.-
Manufacturer
Evergreen Telemetry
Calibration Environment
Product
Pressure / Velocity Module
Tem erature
76
OF
Model
S-PVF-1
Rel. Humidi
57
%
SN
1700297
Bar. Pressure
28.6
in H
❑ As Found ® As Left
® In Tolerance ❑ Out of Tolerance
Calibration Data
Measurement
Variable
Test
Point
Cal
Standard
Allowable
Range
Test
Instrument
Min
Max
Barometric
Pressure (in Hg)
Spec
-2%-0.1
+2%+0.1
1
24.3
24.3
2
28.6
28.6
3
30.1
30.2
Differental
Pressure
(in wc)
Spec
-2%-.001
+2%+.001
1
10.00
9.999
2
2.000
2.005
3
0.5000
0.5020
4
0.0500
0.0500
5
-10.00
-10.05
6
40500
-0.0502
Low Velocity
(FPM)
Sec
-3% - 7
+ 3% + 7
1
100
101
2
503
1 503
Airflow
°F
Spec
-3%-7
+3%+7
1
100
1 UPON
2
500
1
REQUEST
Indicates out of tolerance condition T
NIST-Traceable Lab Calibration Standards
Variable
System ID
Calibration Last
I Calibration Due
Pressure
4693940
10-Jul-17
10-Jul-18
Pressure
1208000080
5-Jul-17
5-Iul-18
Velocity
1600344
26-Jan-17
26-Jan-19
Statement of Traceability
This instrument has been checked for accuracy, calibrated to manufacturer's specifications, and found to be
within the specified tolerance unless otherwise stated. It has been calibrated using measurement standards
traceable to the National Institue of Standards and Technology, or accepted intrinsic standards of measurement,
or derived the ratio pe of self calibrated techniques.
24-Jul-2017 24-Jul-2019
Calibrated By Calibration Date Date Due
S. Perry Ln. #102, Tempe AZ 85281 • 602-574-6192
EVERGREEN
TELEMETRY
Certificate of Calibration
Precision Bal recal
Manufacturer
Evergreen Telemetry
Calibration Environment
Product
Pressure /Velocity Module
Temperature
75
eF
Model
S-PVF-1
Rel. Humidity
25
%
SN
1500321
Bar. Pressure
28.5
In H
® As Found As Left 4 In Tolerance E3Out of Tolerance
Calibration Data
Measurement
Variable
Test
Point
Cal
Standard
Allowable
Range
Test
Instrument
Min
Max
Barometric
Pressure (in Hg)
Spec
-2%-0.1
+2'/6+0.1
1
25.0
25.0
2
28.5
28.5
3
30.2
30.2
Differental
Pressure
(in wc)
- E -
—Spec
-2%-.001
+2%+,001
1
10.00
9.986
2
2.000
2.000
3
0.5000
0.5008
4
U500
0.0501
5 -
_ _ 10.00 —
r "" -
_ - =
= --_10.02'
6-
-0.0500
-0.0500
Low Velocity
(FPM)
Spec
-3% - 7
+ 3% + 7
1
109
109
2
504
502
Airflow
OF
S ec
-3%-7
+3%+7
1 1
100
UPON
2
500
REQUEST
Intl!Cates out of tolerance condition T
NIST-Traceable Lab Calibration Standards
Variable
System ID
Calibration Last
Calibration Due "
Pressure
4693940
16-Jul-16
IT 16-Jul-17
Pressure
1208000080
15-Sep-16
15-Se 17
Velocity1600344
26-Jan-17
26-Jan-19
Statement of Traceability
This instrument has been checked for accuracy, calibrated to manufacturer's specifications, and found to be
within the specified tolerance unless otherwise stated. It has been calibrated using measurement standards
traceable to the National Institue of Standards and Technology, or accepted Intrinsic standards of measurement
or derived Ae ratio toe of self calibrated techniques.
1 vtr VTL^1' 31-Mar-2017 31-Mar-2019
Calibrated By Calibration Date Date Due
624 S. Perry Ln. #102. Tempe AZ 85281
EVERGREEN
TELEMETRY
Certificate of Calibration
Manufacturer
Evergreen Telemetry
Calibration Environment
Product
Capture Hood
Temperature
75
of
Model
CH-15D
Rel. Humidity
32
%
SN
1700353
Bar. Pressure
28.8
in H
0 As Found ® As Left
® In Tolerance ❑ Out of Tolerance
Calibration Data
Measurement
Variable
Test
Point
Cal
Standard
Allowable
Range
Test
Instrument
Min
Max
Airflow (CFM)
Spec
-3% - 7
+3%-7
1
2010
2019
2
1005
1000
3
158
158
4
-542
-541
5
Indicates out of tolerance condition T
NIST-Traceable Calibration Lab Standards
Variable
System ID
Calibration Last
Calibration Due
Pressure
4693940
7/10/2017
7/10/2018
Pressure
1208000080
7/5/2017
7/5/2018
Velocity
1600344
1/26/2017
1/26/2019
Statement of Traceability
This instrument has been checked for accuracy, calibrated to manufacturer's specifications, and found to be
within the specified tolerance unless otherwise stated. It has been calibrated using measurement standards
traceable to the National Institue of Standards and Technology, or accepted intrinsic standards of measurement,
or derived by the ratio type of self calibrated techniques.
r
��. 10 1W
Calibrated By
624 S. Perry Ln. #102, Tempe AZ 85281
November 29, 2017
Calibration Date
EVERGREEN
TELEMETRY
Certificate of Calibration
Manufacturer
Evergreen Telemetry
Calibration Environment
Product
Humidity Sensor
Temperature
Model
S-H-3-5"
Rel. Humidity58
SN
1700347
Bar. Pressure
28.8
in H
O As Found
As Left 10 In Tnlomnro
❑ Out of Tolerance
Calibration Data
Measurement
Variable
Test
Point
Cal
Standard
Allowable Range
Test
Instrument
Min
I Max
Temperature (°F)
S ec
1
39.6
-1.0
1.0 _
39.9
2
78.9
-1.0
1.0
79.0
3
78.6
-1.0
1.0
78.9
4
130.3
-2.0
2.0
131.1
Barometric
Pressure (in Hg)
Sec
2% - 0.1
+ 2%+ 0:1
1
28.8
28.8
Humidity %RH
10 to 90%
Spec
-3%
+3%
1
7.3
8.7
2
62.7
61.5
3
60.5
60.9
4
1 81.1
1
79.4
Indicates out of tolerance condition —t
Calibration Standard
Variable
System ID
Calibration Last
Calibration Due
Temperature
15171149
11-Jan-17
11-Jan-18
Pressure
1208000080
5-Jul-17
5-Jul-18
Humidity
20052171
24-Jan-17
24Jan-18
Statement of Traceabilitv
This instrument has been checked for accuracy, calibrated to manufacturer's specifications, and found to be
within the specified tolerance unless othenvise stated. It has been calibrated using measurement standards
traceable to the National Institue of Standards and Technology, or accepted intrinsic standards of measurement,
or derived by the ratio type of self calibrated techniques.
Temperature accuracy (dry bulb) varies across the operating range:
Temperature over 32-10OF +/_ 1.0 F
Temperature over 100-158F +1- 2.0 F
26-13eo-2017 26-Deo-2018
Calibration Date Date Due
602.574.6192 ■
AZ 85261
EVERGREEN
TELEMETRY
Certificate of Calibration
Manufacturer
Evergreen Telemetry
Calibration Environment
Product
Pressure/ Velocity Module
Temperature
77
°F
Model
S-PVF-1
Rel. Humidity
24
SN
1700414
Bar, Pressure
28.7
1 in H
Q As Found ® As Left
IM In Tolerance ❑ Out of Tolerance
Calibration Data
Measurement
Variable
Test
Point
Cal
Standard
Allowable
Range
Test
Instrument
Min
Max
Barometric
Pressure (in Hg)
$ ec
-2%-0.1
+2%+0.1
1
24.1
24.2
2
28.7
28.8
3
30.3
30.4
Differental
Pressure
(in wc)
S ec
-2%-.001
+2%+.001
1
10.00
10.00
2
2.000
1.999
3
0.5000
0.4952
4
0.0500
0.0497
5
-10.00
-10.05
6
-0.0500
-0.0496
Low Velocity
(FPM)
Sec
-3% - 7
+ 3% + 7
1
105
106
2
507
509
Airflow
°F
S c
-3%-7
+3%+7
1
1001
1UPON
2
1 500
1
1 REQUEST
Indicates out of tolerance condition T
NIST-Traceable Lab Calibration Standards
Variable
System ID
Calibration Last
Calibration Due
Pressure
4693940
10Jul-17
10-Jul-18
Pressure
1208000080
5Jul-17
5Jul-18
Velocity
1600344
26Jan-17
I 26-Jan-19
Statement of Traceabilitv
This instrument has been checked for accuracy, calibrated to manufacturer's specifications, and found to be
within the specified tolerance unless otherwise stated. It has been calibrated using measurement standards
traceable to the National Institue of Standards and Technology, or accepted Intrinsic standards of measurement
or derived by the ratio type of self calibrated techniques.
20-Dec-2017 20-Dec-2019
canDra[ed ay callura[lun Dale Ua[e Due
624 S. Perry Ln. 9102, Tempe AZ 85281 • 602-574-6192
EVERGREEN
TELEMETRY
Certificate of Calibration
Manufacturer
Evergreen Teleme
Calibration Environment
Temperature Product
Module
Probe
Temperature
74#inoHo
Model
RM-T-1
PR-T-1
Rel. Humidi
26SN
1700432
1700422
Bar. Pressure
287
v ns round
R9 As Left
® In Tolerance ❑ Out of Tolerance
Calibration Data
Measurement
Variable
Test Module & Test Probe
Temperature ff)
Test
Point
Sec
Cal
Standard
Allowable
Ran a
Test
Instrument
Min
i Max
1
78.9
-0.3
1 +0.3
79.1
2
243.1
-2.6
+2.6
243.1
3
-43.4
-1.6
+1,6
-44.0
Indicates out or tolerance condition—T
Calibration Standard SN &Dates
Variable
S stem ID
Calibration Last
Calibration Due
Tem erature
1 15171149
1 11-Jan-17
11Jan-18
Statement of Traceability
This instrument has been checked for accuracy, calibrated to manufacturer's specifications, and found to be
within the speed tolerance unless otherwise slated. It has been calibrated using measurement standards
traceable to the National Institue of Standards and Technology, or accepted intrinsic standards of measurement,
or derive by the ratio type rated techniques.
� :7 21-Dec-2017 21-Dec-2019
Calibrated By Calibration Da4o Date Dua
602.574.6192 ■
■ 624 S. Perry Ln #102, Tempe, AZ
. , ,
EVERGREEN
TELEMETRY
Certificate of Calibration
Manufacturer
Evergreen Telemetry
Calibration Environment
Temperature, Product
Module
Probe
Temperature
77
OF
Model
PR-T4-6
Rel. Humidi
36
%
SN
1700234
Bar. Pressure
26.6
in H
❑ As Found
® As Left
® In Tolerance ❑ Out of Tolerance
Calibration Data
Measurement
Variable
Test
Point
Cal
Standard
Allowable
Range
Test
Instrument
Min
Max
Test Module & Test Probe
Temperature (OF)
Spec
1
79.1
-0.3
+0.3
79.0
2
241.1
-2.6
+2.6
241.6
3
-42.9
-1.6
+1.6
42.5
Indlcetes out of tolerance condition —t
Calibration Standard SN &Dates
Variable
System ID
Calibration Last
I Calibration Due
Temperature
15171149
11-Jan-17
11-Jan-18
Statement of Traceability
This instrument has been checked for accuracy, calibrated to manufacturer's specifications, and found to be
within the specified tolerance unless otherwise stated. It has been calibrated using measurement standards
4--m. . ♦- SL- 1..-.A... — Ca.....1.--J...--J —f
or deri ed by the ratiolibrated techniques.
13-Dec-2017 13-Dec-2019
alib By Calibration Date Date Due
C4�'d?�p1
Certificate of Calibration
Precision Balance
Manufacturer
Evergreen Telemetry
Calibration Environment
Product
Pressure / Velocity Module
Temperature
74
OF
Model
S-PVF-1
Rel. Humidity
31
%
SN
1700297
Bar. Pressure
28.7
in H
13 As Found Ej As Left
19 In Tolerance ❑ Out of Tolerance
Calibration Data
Measurement
Variable
Test
Point
Cal
Standard
Allowable
Range
Test
Instrument
Min
Max'
Barometric
Pressure (in Hg)
Spec
-2%-0.1
+2%+0.1
1
24.9
24.9
2
28.7
28.7
3
30.1
30.1
Differental
Pressure
(in wc)
Spec
-2%-.001
+2%+.001
1
1 10.00
10.00
2
2.000
2.007
3
0.5000
0.5029
4
0.0500
0.0504
5
-10.00
-10.05
6
-0.0500
0.0502
Low Velocity
(FPM)
Sec
-3% - 7
+ 3% + 7
1
109
108
2
503
504
Airflow
OF
Spec
-3%-7
+3%+7
1
100
UPON
2
500
REQUEST
Indicates out of tolerance condition T
NIST-Traceable Lab Calibration Standards
Variable
System ID
Calibration Last
Calibration Due
Pressure
4693940
10-Jul-17
1
10-Jul-18
Pressure
1208000080
5-JUI-17
5-Jul-18,
Velocity
1600344
26-Jan-17
26-Jan-19
Statement of Traceability
This instrument has been checked for accuracy, calibrated to manufacturers specifications, and found to be
within the specified tolerance unless otherwise stated. It has been calibrated using measurement standards
traceable to the National Institue of Standards and Technology, or accepted intrinsic standards of measurement,
%dtiriied by the ratio type of self calibrated techniques.
4-Dec-2017 4-Dec-2019
Calibrated By Calibration Date Fate
Ln. #102. Temoe AZ 85281
EVERGREEN Certificate of Calibration
TELEMETRY
Manufacturer
Evergreen Telemetry
Calibration Environment
Product
Pressure y VelociModule
Temperature
85
°F
Model
S-P,
Rel. Humidity
26
%
SN
1600301
lBar. Pressure
28.7
in H
❑ As Found is As Left i9 In Tolerance ❑ Out of Tolerance
Calibration Data
Measurement
Variable
Test
Pant
Cal
Standard -
Allowable
Ran a^"
Test
Instrument
Min
I Max
Barometric
Pressure (in H9)
S
-2%-0.1
1 +2%+0.1
1
25.2
25.1
2
28.5
28.6
3
30.3
30.4
Differental
Pressure
(in wc)
Spec
-2%-.001
+2%+.001
1
10.000
9,999
2
2.000
1.998
3
0.6000
0.5016
4
0.0500
0.0502
5
-10.000-
_
-10.035
6
1 -U.0500
-Oli504
Low Velouty
(FPM)
S
-3%-7
+3%+7
1
500
502
2
108
110
Airflow
°F
S
-3%-7
1 3%+7
1
100
1
1
UPON
2
500
1
1
REQUEST
Indicates outof twemcce mccitl°n- T
Calibration Standards
Variable
System ID
I Calibration Last
1 Calibration Due
Pressure
459394U
16Jul-15
I 16Jul-16
Pressure
1208000050
lbSe 15
15Se 16
Veloci
1500301
1 27-Jan-15
27-Jan-17
Statement of Traceability
This instrument has been checked for aocumcy, calibrated to manufacturer's specifications, and found to be
within the specified tolerance unless omerwise stated. It has been calibrated using measurement standards
traceable to the National Institue of Standards and Technology. or accepted intrinsic standards of measuremenl,
or derived by the ratio type of self calibrated techniques.
4, n P,( 4- / L / 12-May-2016 12-May-2018
alibrated By Calibration Date Date Due