HomeMy WebLinkAboutMISC EMAILt t Fort Pierce Engineering, Inc. Dependable Mechanical, Electrical & Plumbing Design V4 CA# 28173 February 23, 2017 RE: Sam Snead's Tavern: 8540 Commerce Centre Dr., Port St. Lucie, FL 34986 The purpose of this letter is to address the match -up of the indoor air handling unit with the outdoor condensing unit for the split DX air conditioning system at the above address. The indoor air handling is an existing York model LA12000OA6, rated at 10 tons, and the outdoor condensing unit which is being replaced is a Ruud model RAWL120CAZ rated at 10 tons. This replacement condensing unit is an acceptable match -up for cooling capacity and inter -operability with the existing indoor air handling unit (with proper expansion device). The newer, more efficient condensing unit should provide at a minimum the previous system efficiency, if not exceed the rating as per section 101.4.7 of the 2014, 5th Edition FBC Energy Conservation Code. 31, Svobo$a, PE, Agnic�-ljfTqgieger 6GANNED BY St. Lucie Countv 315 South Th Street ♦ Fort Pierce, FL 34950 ♦ Phone 772-672-4636 ♦ Fax 772-672-4637 www.fp-eng.com Y:\PPicm Fn&m S\I7Pm1a WYACI M\VW241 ACD =-Sam&o ffs TZv WACAPivvov Ldm P'e 1dI A. Fori fierce Engineering, Inc.C, Dependable Mechanical, Electrical &Plumbing Design CA# 28173 ht, February 23, 2017 ®r✓ RE: Sam Snead's Tavern: 8540 Commerce Centre Dr., Port St. Lucie, FL 34986 The purpose of this letter is to address the match -up of the indoor air handling unit with the outdoor condensing unit for the split DX air conditioning system at the above address. The indoor air handling is an existing York model LA12000OA6, rated at 10 tons, and the outdoor condensing unit which is being replaced is a Ruud model RAWL120CAZ rated at 10 tons. This replacement condensing unit is an acceptable match -up for cooling capacity and inter -operability with the existing indoor air handling unit (with proper expansion device). The newer, more efficient condensing unit should provide at a minimum the previous system efficiency, if not exceed the rating as per section 101.4.7 of the 2014, 5th Edition FBC Energy Conservation Code. o�`� G 9' SdGe •��'� 51 �W nfl 0 2 •••:.tea = "EcFic 1, Svoboda, PE1 Ld�fD AP s�®cha"niE�il=Ei4t�'inec��rincip ID oUANNED BY it. Lucie County 315 South 7" Street • Fort Pierce, FL 34950 ♦ Phone 772-6724636 ♦ Fax 772-6724637 www.fp-eng.com Y:YI Piaa:Pnginaain$W PmjeM VAC Lmm\1799241 AC exams- Sun S=&TawWAC AP�Ld¢ Pa..I dI