HomeMy WebLinkAboutPRODUCT INFORMATIONSpe.a=%tSt1tLDING DIVISION
REVIEWED FOR CO IJANCE
REVIEWED RY f
D• E MUST BE lal? ON
OR NO ,INSPECTION WILL BE MADE.
generator set
QSB5
series` BY ANNEL)
St. Lucie Count
engine
MINIM; 5111wir"MI-11
Description
Cummins Power Generation commercial
generator sets are fully integrated power
generation systems providing optimum
performance, reliability and versatility for
stationary standby and prime power
applications:
Features
Cummins° heavy-duty engine - Rugged 4-
cycle, industrial diesel delivers reliable power,
low emissions and fast response to load
changes.
LJ�
Power
Generation
Control system - The PowerCommando
electronic control is standard equipment and
provides total genset system integration including_
automatic remote starting/stopping, precise
frequency and voltage regulation. Optional features
include alarm and status message display, output
metering, auto -shutdown at fault detection and
NFPA 110 Level 1 compliance.
Cooling system - Standard integral set -mounted
radiator system, designed and tested for rated
ambient temperatures, simplifies facility design
requirements for rejected heat.
Alternator - Several alternator sizes offer
Fuel Tanks - Dual wall sub -base fuel tanks are
selectable motor starting capability with low
also available.
reactance 2/3 pitch windings, low waveform
distortion with non -linear loads and fault
NFPA - The genset accepts full rated load in a
clearing short-circuit capability.
single step in accordance with NFPA 110 for Level
1 systems.
Permanent magnet generator (PMG) -
Warranty and service -Backed by a
Offers enhanced motor starting and fault
clearing short-circuit capability.
comprehensive warranty and worldwide distributor
network.
Standby rating
Prime rating
Continuous rating
Data sheets
Model
60 Hz
kW MA)
50 Hz
kW (M)
60 Hz
kW kV
50 Hz
kW MA)
60 Hz
kW kV
50 Hz
kW (M)
60 Hz
50 Hz
DSFAA
35 44
32 40
D-3366
DSFAB
40 50
35 44
D-3367
j
DSFAC
50 63
45 56
D-M68
i
DSFAD
60 5
55 69
D-3369
DSFAE
80 100
72 90
D-3370
j
Our energy working for you.'
cumminspower.com
02013 Cummins Power Generation Inc. 167559i (8/13)
Generator set specifications
Governor regulation class
Voltage regulation, no load to full load
m 1 %
Random voltage variation
t 0.5%- 3 phase only, t 1.5% -1 phase only
Frequency regulation
Isochronous
Random frequency variation
x 0.25%
Radio frequency emissions compliance
J
Engine specifications
Bore
107 mm (4.21 in)
Stroke
124.0 min (4.88 in)
Displacement
4.5 litres (272 in)
Configuration
Cast iron, in -line, 4 cylinder
Battery capacity
1000 amps minimum at ambient temperature of -18 °C to 0 °C
0°F to 32°
Battery charging alternator
100 amps
Starting voltage
12 volt, negative ground
Fuel system
Direct injection: number 2 diesel fuel, fuel filter, automatic electric
fuel shutoff
Fuel filter
Single element, 10 micron filtration, spin -on fuel filter with water
separator
Air cleaner type
Dry replaceable element
Lube oil filter type(s)
Spin -on, full flow
Standard cooling system
High ambient radiator
Alternator specifications
Design
Bmshless, 4 pole, drip proof, revolving field
Stator
2/3 pitch
Rotor
Single bearing, flexible discs
Insulation system
Class H
Standard temperature rise
150 °C standby at 40 °C ambient
Exciter type
Torque match (shunt) standard, PMG optional
Phase rotation
A (U), B M, C OM
Altemator cooling
Direct drive centrifugal blower fan
AC waveform total harmonic distortion
< 5% no load to full linear load, <3% for any single harmonic
Telephone influence factor (TIF)
< 50 per NEMA MG1-22.43
Telephone harmonic factor (rHF)
I < 3
Available voltages
60 Hz Three phase line -neutral line -line 160 Hz Single phase line-neutraUline-line
• 120/208 • 139/240 • 240/416 • 277/480 120/240
• 120/240 Delta • 220/380 • 255/440 • 347/600
• 127/220
Note: Consult factory for other voitages.
Generator set options and accessories
Engine
❑ 120 V 150 W lube oil
heater
❑ 120/240 V 1000 W coolant
heater
Fuel system
❑ 24 hour sub -base tank
(dual wall)
❑ 12 hour sub -base tank
(dual walo
Alternator
❑ 105 °C rise
❑ 125 °C rise
❑ 120 V 100 W anti -
condensation heater
❑ PMG excitation
❑ Single phase
Exhaust system
❑ Genset mounted muffler
❑ Heavy duty exhaust elbow
❑ Slip on exhaust connection
Generator set
❑ AC entrance box
❑ Battery
❑ Battery charger
❑ Enclosure: aluminum, steel,
weather protective or sound
attenuated
❑ Export box packaging
❑ Main line circuit breaker
Note: Some options may not be available on all models - consult factory for availability.
❑ PowerCommand Network
Communications Module
(NCM)
❑ Remote annunciator panel
❑ Spring isolators
❑ UL 2200 Listed
❑ 2 year prime power warranty
❑ 2 year standby power warranty
❑ 5 year basic power warranty
Our energy working for you' cumminspower.com
02013 Cummins Power Generation Inc. I S75591(e/13)
Control system PCC 2100
PowerCommand control is an integrated generator
set control system providing governing, voltage
regulation, engine protection and operator interface
functions. Major features include:
• Integral AmpSentry" Protective Relay providing a full
range of alternator protection functions that are
matched to the alternator provided.
• Battery monitoring and testing features and smart
starting control system.
• Three phase sensing, full wave rectified voltage
regulation system, with a PWM output for stable
operation with all load types.
• Standard PCCNet_ and optional Echelon
LONWORKe network interface.
• Control suitable for operation in ambient
temperatures from -40 °C to +70 °C (-40 OF to
+158 OF) and altitudes to 5000 meters (13,000 feet).
• Prototype tested; UL, CSA, and CE compliant.
• InPower PC -based service tool available for
detailed diagnostics.
Operator/display panel
• Off/manual/auto mode switch
• Manual run/stop switch
• Panel lamp test switch
• Emergency stop switch
• Alpha -numeric display with pushbutton access for
viewing engine and alternator data and providing
setup, controls and adjustments
• LED lamps indicating genset running, not in auto,
common warning, common shutdown
• Configurable LED lamps (5)
• Configurable for local language
Engine protection
• Overspeed shut down
• Low oil pressure warning and shut down
• High coolant temperature warning and shut down
• High oil temperature warning (some models)
• Low coolant level warning or shut down
• Low coolant temperature warning
• High and low battery voltage warning
• Weak battery warning
• Dead battery shut down
• Fail to start (overcrank) shut down
• Fail to crank shut down
• Redundant start disconnect
• Cranking lockout
• Sensor failure indication
Engine data
• DC voltage
• Lube oil pressure
• Coolant temperature
• Lube oil temperature (some models)
• Engine speed
AmpSentry AC protection
• Over current and short-circuit shut down
• Over current warning
• Single and three phase fault regulation
• Over and under voltage shut down
• Over and under frequency shut down
• Overload warning with alarm contact
• Reverse power and reverse Var shut down
• Excitation fault
Alternator data
• Line -to -line and line -to -neutral AC volts
• Three phase AC current
• Frequency
• Total and individual phase power factor, kW and WA
Other data
• Genset model data
• Start attempts, starts, running hours
• kW hours (total and since reset)
• Fault history
• Load profile (hours less than 30% and hours more
than 90% load)
• System data display (optional with network and other
PowerCommand gensets or transfer switches)
Governing
• Digital electronic isochronous governor
• Temperature dynamic governing
• Smart idle speed mode
• Glow plug control (some models)
Voltage regulation
• Digital PWM electronic voltage regulation
• Three phase line -to -neutral sensing
• Suitable for PMG or shunt excitation
• Single and three phase fault regulation
• Configurable torque matching
Control functions
• Data logging on faults
• Fault simulation (requires InPower)
• Time delay start and cooldown
• Cycle cranking
• PCCNet interface
• Configurable customer inputs (4)
• Configurable customer outputs (4)
• Configurable network inputs (8) and outputs (16) (with
optional network)
• Remote emergency stop
Options
❑ LED bargraph AC data display
❑ Thermostatically controlled space heater
❑ Key -type mode switch
❑ Ground fault module
❑ Auxiliary relays (3)
❑ Echelon LONWORKs interface
❑ Modion Gateway to convert to Modbus (loose)
❑ PowerCommand iWatch web server for remote
monitoring and alarm notification goose)
❑ Digital input and output module(s) (loose)
❑ Remote annunciator (loose)
For further detail see document S-1409.
Our energy working for you -
®2013 CUm im Power Generation No. 151559i iaM)
cumminspower.com
i
r ,.
Ratings definitions
Emergency standby power (ESP):
Applicable for supplying power to varying electrical
load for the duration of power interruption of a reliable
utility source. Emergency Standby Power (ESP) is in
accordance with ISO 8528. Fuel Stop power in
accordance with ISO 3046, AS 2789, DIN 6271 and BS
5514.
Limited -time running power (LTP):
Applicable for supplying power to a constant electrical
load for limited hours. Limited Time Running Power
(LTP) is in accordance with ISO 8528.
Prime power (PRP):
Applicable for supplying power to varying electrical
load for unlimited hours. Prime Power (PRP) is in
accordance with ISO 8528. Ten percent overload
capability is available in accordance with ISO 3046, AS
2789, DIN 6271 and BS 5514.
Base load (continuous) power (COP):
Applicable for supplying power continuously to a
constant electrical load for unlimited hours. Continuous
Power (COP) in accordance with ISO 8528, ISO 3046,
AS 2789, DIN 6271 and BS 5514.
dill
<.�. IN", 1=1 1�
r�l.l r:: •aid I .
31
This outline drawing is for reference only. See respective model
data sheet for specific model outline drawing number.
Oo not use Am Installation desion
Model
Dim "A"
mm (in.)
Dim °Bra
mm fin.)
Dim -C^
mm (in.)
Set Weight'
dry kg fibs)
Set Weight'
wet lig (Ibs)
DSFAA
2104 82.8
1016 40.0
1255 49.4
1080 2380
DSFAB
2104 82.8
1016 40.0
1255 49.4
1080 2380
DSFAC
2104 82.8
1016 40.0
1255 49.4
1120 2470
DSFAD
2104 82.8
1016 40.0
1255 49.4
1140 2520
DSFAE
2104 82.8
1016 40.0
1255 49.4
1220 2690
' Weights represent a set with standard features. See outline drawings for weights of other configurations.
Codes and standards
Codes or standards compliance may not be available with all model configurations — consult factory for availability.
This generator set is designed in facilities The generator set is available Listed to UL
w!lF.Su.Z7.Rr certified to ISO 9001 and manufactured in U I 2200, Stationary Engine Generator Assemblies
facilities certified to ISO 9001 or ISO 9002. ® L for all 60 Hz low voltage models.
The Prototype Test Support (PTS) program
verifies the performance integrity of the
Engine certified to Stationary Emergency U.S.
�A(~ '�"sa
generator set design. Cummins Power
EPA New Source Performance Standards, 40
�15
a,...
Generation products bearing the PTS
V.S. EPA CFR 60 subpart IIII Tier 3 exhaust emission
-
symbol meet the prototype test
levels. U.S. applications must be applied per
requirements of NFPA 110 for Level 1
this EPA regulation.
1 ne generator set pacxage is availaole certified
CO- All low voltage models are GSA certified to International for seismic application in accordance with the
product class 4215-01. Building following International Building Code:
Code IBC2000, IBC2003, IBC2006, IBC2009 and
Warning: Back feed to a utility system can cause electrocution and/or property
except through an approved device or after building main switch is open.
North America
1400 73rd Avenue N.E.
Minneapolis, MN 55432
USA
Phone 763 574 5000
Fax 763 574 5298
not connect to any building's electrical system
Our energy working for you.
02013 Cummins Power Generation Inc. Ag rights reserved.
Cummins Power Generation and Cummins are registered trademarks of Comics Inc. Powercomrrand, AmpSentry, InPower
and "Our energy working for you.' are trademarks of Cummins Power Generation. otlercomparty, pmduct, or service names
may be trademml¢ or service marks of others. Specifications are subject to change wi0m d notice.
s-15591(eA3)
Power
Generation
s
cumminspower.com
1
Model:
Frequency:
Fuel type:
KIN rating:
Emissions level:
DSFAE
60 SCANNED
Diesel BY
80 standby St. Lucie Count,,
72 prime
EPA NSFIS Stationary Emergency Tier 3
Exhaust emission data sheet: I EDS-1076
Exhaust emission compliance sheet:
EPA-1110
Sound Performance data sheet-
MSP-1051
Cooling erformance data sheet:
MCP-166
Prototype test summary data sheet:
PTS-276
Standard set -mourned radiator cooling outline:
0500-4552
Optional set -mounted radiator cooling outline:
Optional heat exchanger cooling outline:
Optional remote radiator cooling outline:
Fuel consumption
Standby
Prime
Continuous
kW (kvA)
kW (kVA)
kW (kVA)
Ratings
80 (100)
72 (90)
Load
1/4
1/2
3/4
1 Full
1/4 1
1/2
3/4
Full
Full
US gph
2.1
3.8
5.5
6.9
2.0
3.4
5.2
6.3
L/hr
8.0
14.2
21.0
26.1
7.5
13.0
19.5
24.0
Engine
Standby
rating
Prime
ratio
Continuous ratio
Engine manufacturer
Cummins Inc.
-
Engine model
QSB5-G3 NR3
Configuration
Cast iron, in -line, 4 cylinder
Aspiration
Turbocharged and air-to-air aftercooled
Gross engine power output, kWm(bhp)
108 (145)
1 94 (126)
BMEP at set rated load, kPa (psi)
1437 (208)
1308 (190)
Bore, mm (in.)
107 (4.21)
Stroke, mm (in.)
124 (4.88)
Rated speed, rpm
1800
`
Pistonspeed, m/s (tt/min)
7.4(1464)
-
Compression ratio
17.3:1
Lube oil capacity, L (qt)
12.1 (12.8)
Overseed limit, rpm
2100 ± 50
Regenerative power, kW
13
Fuel flow
Maximum fuel Flow with C180, Uhr (US gph)
132 (35)
Maximum fuel Flow with C174, Uhr (US gph)
-
Maximum fuel inlet restriction with clean filter, mm Hg Ch. H)
127 (5)
Maximum return restriction, mm H (in. H)
152 (6)
02011 Cummins Power Generation Ina M rights reserved. Cummins Power Generation and Cummins are registered trademarks of Cummins Inc.
'Our energy working for you.' is a trademark of Cummins Power Generation. Specifications are subject to change without notice.
D-3370c (I Ill 11
- Standby Prime Continuous ratio
Air'
ratio ratio 9
Combustion air, m'/min (scfm) 9.1(320) 8.6(305)
Maximum air cleaner restriction, We fin. H,0) 3.7(15)
37.0
Exhaust i
Exhaust flow at set rated load, m'/min (cfm) 20.8 (736) 19.8 (702)
Exhaust temperature, °C (*F) 1 451 (844) 430 (806)
Standard set -mounted radiator coolie
Ambient design, °C (°F)
54 (129)
Fan load, kW- (HP)
9.3 (12.5)
Coolant capacity (with radiator), L (US Gal.)
17(4.5)
Cooling system air flow, m'/min (scfm)
189 (6675)
Total heat rejection, MJ/min (Btu/min)
3.74 (3550) 3.45 (3271)
Maximum cooling air flow static restriction, kPa (in. H O)
0.12 (0.5)
Optional set -mounted radiator coolie
Ambient design, °C °
Fan load, kWm (HP)
Coolant capacity (with radiator), L (US Gal.)
Cooling system air flow, m'/min (scfm)
i
Total heat rejection, MJ/min (Btu/min)
Maximum cooling air flow static restriction, kPa (in. H O)
Optional heat exchanger coolie
Set coolant capacity, L US Gal.
Heat rejected, jacket water circuit, MJ/min (BW/min)
Heat rejected, aftercooler circuit, MJ/min (Btu/min)
Heat rejected, fuel circuit, MJ/min (Btu/min)
Total heat radiated -to room, MJ/min (Btu/min)
Maximum raw water pressure, jacket water circuit, kPa (psi)
Maximum raw water pressure, aftercooler circuit, kPa (psi)
Maximum raw water pressure, fuel circuit, kPa (psi)
i
Maximum raw water flow, jacket water circuit, Umin (US Gal/min)
-
Maximum raw water flow, aftercooler circuit, Umin (US Gal/min)
Maximum raw water flow, fuel circuit, Umin (US Gallmin)
Minimum raw water flow at 27 °C (80 °F) inlet temp, jacket water
circuit, Umin US Gal/min
Minimum raw water flow at 27 °C (00 °F) inlet temp, aftercooler circuit,
Umin US Gallmin
Minimum raw water flow at 27 °C (80 °F) inlet temp, fuel circuit, Umin
US Gal/min)I
Raw water delta P at min flow, jacket water circuit, kPa (psi)
Raw water delta P at min flow, aftercooler circuit, kPa (psi)
Raw water delta P at min flow, fuel circuit, kPa (psi)
Maximum jacket water outlet temp, °C ('F)
Maximum aftercooler inlet temp, °C (°F)
Maximum aftercooler inlet temp at 25 °C (77 °F) ambient, °C (°F)
Our energy working for you.'"a
www.cummmsoer er.com02011 � Power
'Our energy
Power Generation Inc. arightsununinreserved.Cummrtn Power Generation and Cummtra are hanewahMtrademarks
notice.
of Cummins Inc. Q®nersalon
'Our eriergyworkirg for you.' a a traoemark of Cumm'nis Power Generation. specifications are subject change witlou[ notice. �Y�
0-337DC(11/11)
Optional remote radiator cooling
g
Standby
rating
Prime
rating
Continuous
rating
Set coolant capacity, L (US gal)
j
Max flow rate at max friction head, jacket water circuit, Umin (US
gal/min)I
Max flow rate at max friction head, aftercooler circuit, Umin (US
j
gal/min)I
Heat rejected, jacket water circuit, MJ/min (Btu/min)
- !
Heat rejected, aftercooler circuit, MJ/min (Btu/min)
Heat rejected, fuel circuit, MU/min (Btu/min)
{
Total heat radiated to room, MJ/min (Btu/min)
_ )
Maximum friction head, jacket water circuit, kPa (psi)
_
Maximum friction head, aftercooler circuit, kPa (psi)
Maximum static head, jacket water circuit, in (ft)
}
Maximum static head, aftercooler circuit in (ft)
j
Maximum jacket water outlet temp, °C CF)
j
Maximum aftercooler inlet temp at 25 °C (77 OF) ambient, °C CF)
f
Maximum aftercooler inlet temp, °C CF)
I
Maximum fuel flow, Uhr (US gph)
9
Maximum fuel return line restriction, kPa (in Hg)
{
Weightsz
Unit dry weight kgs pbs.) 11200 (2650)
Unit wet weight kgs (Ibs.) 1220 (2690)
Notes -
'For non-standard remote installations contact your local Cummins Power Generation representative.
'Weights represent a set with standard features. See outline drawing for weights of other configurations.
Derating factors
Engine power available up to 2500 in (8200 ft) at ambient temperatures up to 55 °C (131 'F). Consult your
Standby Cummins Power Generation distributor for temperature and ambient requirements outside these
ammeters.
Engine power available up to 2380 in (7800 ft) at ambient temperatures up to 55 °C (131 oF). Consult your
Prime Cummins Power Generation distributor for temperature and ambient requirements outside these
arameters.
Continuous
Ratings definitions
Applicable for supplying emergency power fa
the duration of normal power interruption. No
sustained overload capability is available for
this rating (equivalent to fuel stop power in
accordance with IS03046, AS2789, DIN6271
and BS5514). Nominally rated.
Our energy working for you.TM
Applicable for supplying power in lieu of
commercially purchased power. Prime
power is the maximum power available at a
variable load for an unlimited number of
hours. A 10% overload capability is available
for limited time (equivalent to prime power in
accordance with IS08528 and overload
power in accordance with IS03046, AS2789,
DIN6271 and BS5514). This rating is not
aoolicable to all aenerator set models.
Applicable for supplying power continuously
to a constant load up to the full output rating
for unlimited hours. No sustained overload
capability is available for this rating. Consult
authorized distributor for rating (equivalent
to continuous power in accordance with
IS08528, IS03046, AS2789, DIN6271 and
BS5514). This rating is not applicable to all
generator set models.
www.cumminspower.com �wer PO
m2011 Cummins Power Generation Inc. All rights reserved. Cummins Power Generation and Cummins are registered trademarks of Cummins Inc. Generation
'Our energy working for you.* is a trademark of Cummins Power Generation. Spe�catrom are subject to change wiNout notice.
M370c(1Ill 1)
Alternator data
Three phase table'
105- C
105' C
I 10S' C
105' C
125- C
125' C
125' C
125' C
150' C
I 150' C
150' C
Feature code
B418
B415
B268
B304
B417
B414
B267
B303
B416
B413
B419
Alternator data sheet
206
207
208
206
205
206
208
205
205
205
205
number
Voltage ranges
110/190
120/208
1201208
3471600
110/190
120/208
120/208
347/600
110/190
120/208
3471600
Thru
Thru
Thru
Thm
Thru
Thm
Thru
Thru
120/208
1391240
139/240
1201208
1391240
1391240
120/208
139/240
220/380
240/416
240/416
2201380
240/416
240/416
220/380
240/416
thm
thru
thru
thru
thru
thru
thru
thru
240/416
277/480
277/480
2401416
2771480
277/480
240/416
277/480
Surge kVV
182
82
83
182
81
81
83
82
81
81
82
Motor starting kVA (at
Shunt
313
360
422
313
260
313
422
260
260
260
260
90% sustained voltage)
PMG
1368
1423
1497
1368
1306
1368
497
1306
1 306
1306
306
Full load current -
120/208 127/220 139/240 2401416 254/440 277/480 347/600
Am sat standby rating
278 262 241 139 131 120 96
Single phase table
105' C
105' C
105' C
105' C
125' C
125' C
125- C
I 12W C
Feature code
B418
B415
B274
B268
B417
B414
B273
B267
Alternator data sheet
Number
206
207
207
208
205
206
206
208
Voltage ranges
120/240'
120/2402
1201240'
1201240'
120/240'
120/240'
1201240'
1201240'
Surge kW
80
81
81
81
79
80
80
81
Motor starting kVA (at
90% sustained voltage)
Shunt
185
215
215
250
155
185
185
250
PMG
220
250
250
290
183
220
220
290
Full load current -
4m s at standby rating
120/24Q' 1201240'
1 222 333
Single phase power can be taken from a three phase generator set at up to 2/3 set rated 3-phase kW at 1.0 power factor. Also see Note 3
below.
' The broad range alternators can supply single phase output up to 2/3 set rated 3-phase kW at 1.0 power factor.
The extended stack (full single phase output) and 4 lead alternators can supply single phase output up to full set rated 3-phase kW at 1.0
power factor. -
Formulas for calculating full load currents:
Three phase output
kW x 1000
Voltage x 1.73 x 0.8
Cummins Power Generation
1400 73' Avenue N.E.
Minneapolis, MN 55432 USA
Phone: 763 574 5000
USA toll -free: 877 769 7669
Fax: 763 574 5298
Single phase output
kW x SinglePhaseFactor x 1000
Voltage
Warning: Back feed to a utility system can cause electrocution and/or property damage. Do not connect to any building's electrical system
except through an approved device or after building main switch is open.
Our energy working for yomm
www.cumminsi2ower.com � Power
02011 Cummins Power Generation Inc. All rights reserved. Cummins Power Generation and Cunonirs are registered trademarks of of Canmins Inc. Generation
'Our energy working furyou.' is a trademark of Cummins Power Generation. Speci icawns are subjectle charge wdhrout notice.
D-3370c(11111)