DESIGN CALCULATIONS
FOR
FLORIDA COAST EQUIPMENT
Sign Type: Main Letters & Logo
6000 Orange Ave — Ft Pierce
OLMNED
BY
-3t. Lucie County
will 2
GENERAL NOTES: 0
1. Design is in accordance with the Florida Building Code Sth Edition (2014) LE
for use within and outside the High Velocity Hurricane Zone (HVHZ).
2. Wind loads have been calculated per the requirements of ASCE 7-10 as
shown herein.
3. These engineering calculations pertain only to the structural integrity of
those systems, components, and/or other construction explicitly
specified herein and/or in accompanying engineering drawings. The
existing host structure (if any) is assumed to be in good condition,
capable of supporting the loaded system, subject to building department
approval. No warranty, either expressed or implied, is contained herein.
4. System components shall be as noted herein. All references to named
components and installation shall conform to manufacturer's or industry
specifications as summarized herein.
S. Where site conditions deviate from those noted herein, revisions may be
required or a separate site -specific engineering evaluation performed.
6. Aluminum components in contact with steel or embedded in concrete
shall be protected as prescribed in the 2010 Aluminum Design Manual,
Part 1. Steel components in contact with, but not encased in, concrete
shall be coated, painted, or otherwise protected against corrosion.
7. Engineer seal affixed hereto validates structural design as shown only.
Use of this specification by contractor, et. AI, indemnifies and saves
harmless this engineer for all costs & damages including legal fees &
anallata faac racnitina frnm ripviatinn frnm this riacion
Index:
Pg 1 Cover
Pg 2 Wind Loads
Pg 3 Anchor Design
.mrnu,
lgirteELsunsignature 3%d seal valid
No. 73
�q•• S ATE OF •��,
Easy
# 67382
# 31124
Federal Hwy, 11200 Seals .com Page 1
BocaRaton,
ton, FL Ear 33432 �1
S) EdsySeQLS
r ¢arysezizcvm
ASCE 7-10 Design Wind Loads
WALL -MOUNTED SIGNS
Building Specs
V = 160 mph Basic wind speed
Exposure C
Calculations
a = 9.5 3-sec gust speed power low exponent
zg = 900, Nominal ht. of atmos. boundary layer
Gcpi = 0 Internal pressure coeff
Low mull - GAN
a
WALL -MOUNTED SIGNS
ASD WIND PRESSURES
SIGN
CENTER
CORNER
]EIGHT
(Zone 4) :
(Zone 5)
15 ft
31.2 psf
39.7 psf
20 ft
33.2 psf
42.2 psf
25 ft
34.8 psf
44.2 psf
30 ft
36.1 psf
46.0 psf
35 ft
37.3 psf
47.5 psf
40 ft
38.4 psf
48.8 psf
45 ft
39.3 psf
50.1 psf
soft
40.2 psf 7
51.2 psf
55 ft
41.0 psf
52.2 psf
60 ft
41.8 psf
53.2 psf
70 ft
35.3 psf
70.6 psf
80 ft
36.3 psf
72.6 psf
90 ft
37.2 psf
74.5 psf
100 ft
38.1 psf
76.1 psf
110 ft
38.8 psf
77.7 psf
120ft
39.6 psf
-79.1 psf
130 ft
40.2 psf
80.5 psf
140 ft
40.9 psf
81.7 psf
150 ft
41.5 psf
82.9 psf
175 ft
42.8 psf
85.7 psf
200 ft
44.1 psf
88.1 psf
250 ft
46.2 psf
92.3 psf
.CALCULATION FOR WALL -MOUNTED SIGNS
ASD Load Combo Coeff: 0.6
Kd = 0.85 Directionality factor
Kzt= 1.0 Topographicfactor
A = 10 sq ft Tributary area
0.85
47.3
-1.10
-1.40
0.90
50.2
-1.10
-1.40
0.95
52.7
-1.10
-1.40
0.98
54.7
-1.10
-1.40
1.01
56.5
-1.10
-1.40
1.04
58.1
-1.10
-1.40
1.07
59.6
-1.10
-1.40
1.09
60.9
-1.10
-1.40
1.12
62.2
-1.10
-1.40
1.14
63.3
-1.10
-1.40
1.17
65.4
-0.90
-1.80
1.21
67.3
-0.90
-1.80
1.24
69.0
-0.90
-1.80
1.27
70.5
-0.90
-1.80
1.29
71.9
-0.90
-1.80
1.32
73.3
-0.90
-1.80
1.34
74.5
-0.90
-1.80
1.36
75.7
-0.90
-1.80
1.38
76.8
-0.90
-1.80
1.42
79.3
-0.90
-1.80
1.46
81.6
-0.90
-1.80
1.53
85.5
-0.90
-1.80
� ru
Page 2
?� ����SeC,ilS -CALCULATION :ORWALL-MOUNTED SIGNS
earysealzmm _ • _
Wall Sign Anchor Design
Structure Dimensions & Loading
Design wind pressure: P = 46.0 psf
Sign type: Channel Letter
Sign size: A= 4.4 sgft (per letter, critical)
Wall material: Wood CDX or equiv, thickness to match Min Embed
Anchor type/size: #14 SMS
Ref: APA E830E Fastener Loads for Plywood
Min Embedment: 0.5"
Min edge dist: 2" Min Spacing: 2"
Anchor tensile capacity: Tcap = 112.0 lb (per anchor)
Check Anchors for Pullout
Total Reaction: Rt= 204 lb ... =P*A (per letter)
No. of anchors req'd: n = 1.8 anchors per letter ...= Rt/cap
Total anchors required: 2 anchors per letter
OK, critical anchor option & logo size shown. min (3) per Itr/logo.
Limit to -min (3)-per Itr/logo, min (8) at "EQUIPMENT" capsule. Ref anchor schedule for other anchor options. -
I
fMA
K ",Ixk5�
5
e
Page 3
.� Easy easyseals.com
DESIGN CALCULATIONS
FOR SCANNED
BY
St. Lucie County
FLORIDA COAST EQUIPMENT
Sign Type: Yx& Cabinets
6000 Orange Ave — Ft Pierce
GENERAL NOTES:
1. Design is in accordance with the Florida Building Code 5th Edition (2014)
for use within and outside the High Velocity Hurricane Zone (HVHZ).
2, Wind -loads -have been calculated per the requirements of ASCE 7-10 as
shown herein.. --
-
3. These engineering calculations pertain only to the structural integrity of
those systems, components, and/or other construction explicitly
Index:
specified herein and/or in accompanying engineering drawings. The
existing host structure (if any) is assumed to be in good condition,
Pg i cover
capable of supporting the loaded system, subject to building department
Pg 2 Wind Loads
approval. No warranty, either expressed or implied, is contained herein.
Pg 3 Anchor Design
4. System components shall be as noted herein. All references to named
components and installation shall conform to manufacturer's or industry
specifications as summarized herein.
5. Where site conditions deviate from those noted herein, revisions may be
required or a separate site -specific engineering evaluation performed.
�uunrm„
Eng lle \ tq fih4 seal valid
�.Ppt�7 e`�}1S
6. Aluminum components in contact with steel or embedded in concrete
;� (�``CC•• •••:�.L?
shall be protected as prescribed in the 2010 Aluminum Design Manual,
No. 673
Part 1. Steel components in contact with, but not encased in, concrete
_
* * t*
shall be coated, painted, or otherwise protected against corrosion.
.p �• •�
<!/�
7. Engineer seal affixed hereto validates structural design as shown only.
S TE O •
'�0� ,o� r 0 7' (,4-f:
Use of this specification by contractor, et. Al, indemnifies and saves
Ems# 67382
Chli Ta
harmless this engineer for all costs & damages including legal fees &
'y
y1-t `.0
Easy Se319�r,,,,.re Auth # 31124
nnollato foac rocrdtinn frnm rloviatinn frnm Chic riocion
1200 N Federal Hwy, #200
Boca Raton, FL33432 Easy Sealts.com Page 1
OEq-SySeals CALCULATION `OR WALL -MOUNTED SIGNS
ASCE 7-10 Design Wind Loads
WALL -MOUNTED SIGNS
Building Specs
V = 160 mph Basic wind speed
Exposure C
Calculations
a= 9.5 3-sec gust speed power law exponent
zg = 900' Nominal ht. of otmos. boundary layer
Gcpi = 0 Internal pressure coeff
160 mph - Exp
"C'
WALL -MOUNTED SIGNS
ASD WIND PRESSURES
SIGN
CENTER
CORNER
HEIGHT
(Zone 4)
(Zone 5)
15 ft
31.2 psf
39.7 psf '
20 ft
33.2 psf
42.2 psf
25 ft
34.8 psf
44.2 psf
30 ft
36.1 psf ;
_46.0 psf
35 ft
37.3 psf
47.5 psf
40 ft
38.4 psf
48.8 psf
45 ft
39.3 psf
50.1 psf
50 ft
40.2 psf
51.2 psf
55 ft
41.0 psf
52.2 psf
60 ft
41.8 psf
53.2 psf
70 ft
35.3 psf
70.6 psf
80 ft
36.3 psf
72.6 psf
90 ft
37.2 psf
74.5 psf
100 ft
38.1 psf
76.1 psf
110 ft
38.8 psf
77.7 psf
120 ft
39.6 psf
79.1 psf
130 ft
40.2 psf
80.5 psf
140 ft
40.9 psf
81.7 psf
150 ft
41.5 psf
82.9 psf
175 ft
42.8 psf
85.7 psf
200 ft
44.1 psf
88.1 psf
250 ft
46.2 psf
92.3 psf
ASD Load Combo Coeff: 0.6
Kd = 0.85 Directionality factor
Kzt = 1.0 Topographic factor
A = 10 sq ft Tributary area
Y
qE
a
U d'
a
U "1
Y
0.85
47.3
-1.10
-1.40
0.90
50.2
-1.10
-1.40
0.95
52.7
-1.10
-1.40
0.98
54.7
-1.10
-1.40
1.01
56.5
-1.10
-1.40
1.04
58.1
-1.10
-1.40
1.07
59.6
-1.10
-1.40
1.09
60.9
-1.10
_ -1.40
1.12
62.2
-1.10
-1.40
1.14
63.3
-1.10
-1.40
1.17
65.4
-0.90
-1.80
1.21
67.3
-0.90
-1.80
1.24
69.0
-0.90
-1.80
1.27
70.5
-0.90
-1.80
1.29
71.9
-0.90
-1.80
1.32
73.3
-0.90
-1.80
1.34
74.5
-0.90
-1.80
1.36
75.7
-0.90
-1.80
1.38
76.8
-0.90
-1.80
1.42
79.3
-0.90
-1.80
1.46
81.6
-0.90
-1.80
1.53
85.5
-0.90
-1.80
Page 2
EgssySeals -
4
'Wall Sign Anchor Design
Structure Dimensions & Loading
Design wind pressure:
Sign type:
Sign size:
Wall material:
Anchor type/size:
Anchor tensile capacity:
Check Anchors for Pullout
.CALCULATION OR WALL -MOUNTED SIGNS
P = 46.0 psf
Cabinet
A= 18.0 sgft (entire cabinet)
Masonry (ASTM C90, 1,500 psi min)
1/4" Tapcon
Ref: ITW Tapcon, NOA 07-1126.10
Min Embedment: 1.25"
Min edge dist: 2.5" Min Spacing: 3"
Tcap = 195.0 lb (per anchor)
Total Reaction: Rt = 827 lb ... = P'A (entire cabinet)
No. of anchors req'd: n = 4.2 total anchors ... = Rt/cap
Total anchors required: 5 total anchors balanced over cabinet
OK, typical anchor option shown.
- — - - - — - - - Ref -anchor schedule for other anchor options.
"01:101
51-01*01-10121fNiN
Page 3
Seals
easyseals.com
DESIGN CALCULATIONS
FOR
FLORIDA COAST EQUIPMENT
SignType: Yx& Cabinets
6000 Orange Ave — Ft Pierce
GENERAL NOTES:
1. Design is in accordance with the Florida Building Code 5th Edition (2014)
for use within and outside the High Velocity Hurricane Zone (HVHZ).
2. Wind loads have been calculated per the requirements of ASCE 7-10 as
shown herein.
3. These engineering calculations pertain only to the structural integrity of
those systems, components, and/or other construction explicitly
specified herein and/or in accompanying engineering drawings. The
existing host structure (if any) is assumed to be in good condition,
capable of supporting the loaded system, subject to building department
approval. No warranty, either expressed or implied, is contained herein.
4. System components shall be as noted herein. All references to named
components and installation shall conform to manufacturer's or industry
specifications as summarized herein.
5. Where site conditions deviate from those noted herein, revisions may be
required or a separate site -specific engineering evaluation performed.
6. Aluminum components in contact with steel or embedded in concrete
-shall be protected as prescribed in the 2010 Aluminum Design Manual,
Part 1. Steel components in contact with, but not encased in, concrete
shall be coated, painted, or otherwise protected against corrosion.
7. Engineer seal affixed hereto validates structural design as shown only.
Use of this specification by contractor, et. Al, indemnifies and saves
harmless this engineer for all costs & damages including legal fees &
anonatn fooc roc,dtina from riovivtinn frnm thic Iad.n
Index:
Pg 1 Cover
Pg 2 Wind Loads
Pg 3 Anchor Design
Engine � T" fift s al valid
�i
Mo.673 2
• ST TE OF13
Easy
# 67382
# 31124
Federal Hwy, N200 Ear Seeps .com Page 1
Bocaoca Raton,
tan, FL 33432 1
O'EsSeaLs
/SCE 7-10 Design Wind Loads
WALL -MOUNTED SIGNS
Building Specs
V = 160 mph Basic wind speed
Exposure C
Calculations
a = 9.5 3-sec gust speed power law exponent
zg = 900, Nominal ht. of atmos. boundary layer
Gcpi = 0 Internal pressure coeff
160 mph - Exp
"C"
WALL -MOUNTED SIGNS
ASD WIND PRESSURES
SIGN
CENTER
CORNER
HEIGHT
(Zone 4)
(Zone 5)
15 ft
31.2 psf
39.7 psf
20 ft
33.2 psf
42.2 psf
25 ft
34.8 psf
44.2 psf
30 ft
36.1 psf i
46.0 psf
35 ft
37.3 psf
47.5 psf
40 ft
38.4 psf
48.8 psf
45 ft
39.3 psf
50.1 psf
50 ft
40.2 psf
51.2 psf
55 ft
41.0 psf _ ;
52.2 psf
60 ft
41.8 psf
53.2 psf
70 ft
35.3 psf
70.6 psf
80 ft
36.3 psf
72.6 psf
90 ft
37.2 psf
74.5 psf
100 ft
38.1 psf
76.1 psf
110 ft
38.8 psf
77.7 psf
120 ft
39.6 psf
79.1 psf
130 ft
40.2 psf
80.5 psf
140 ft
40.9 psf
81.7 psf
150 ft
41.5 psf
82.9 psf
175 ft
42.8 psf
85.7 psf
- 200-ft
44.1 psf 7
88.1 psf
250 ft
46.2 psf
92.3 psf
CALCULATION. OR WALL -MOUNTED SIGNS
CONTRACTOR OR COP
ASO Load Combo Coeff: 0.6
Kd= 0.85 Directionalityfactor
Kzt = 1.0 Topographic factor
A = 10 sq ft Tributary area
Y Y
qi
�
� V
0.85
47.3
-1.10
-1.40
0.90
50.2
-1.10
-1.40
0.95
52.7
-1.10
-1.40
0.98
54.7
-1.10
-1.40
1.01
56.5
-1.10
-1.40
1.04
58.1
-1.10
-1.40
1.07
59.6
-1.10
-1.40
1.09
60.9
-1.10
-1.40
1.12
62.2
-1.10
-1.40
1.14
63.3
-1.10
-1.40
1.17
65.4
-0.90
-1.80
1.21
67.3
-0.90
-1.80
1.24
69.0
-0.90
-1.80
1.27
70.5
-0.90
-1.80
1.29
71.9
-0.90
-1.80
1.32
73.3
-0.90
-1.80
1.34
74.5
-0.90
-1.80
1.36
75.7
-0.90
-1.80
1.38
76.8
-0.90
-1.80
1.42
79.3
-0.90
-1.80
1.46
81.6
-0.90
-1.80
1.53
85.5
-0.90
-1.80
Page 2
EasySealts
Wall Sign Anchor Design
Structure Dimensions & Loading
Design wind pressure:
Sign type:
Sign size:
Wall material:
Anchor type/size:
CALCULATION', 'OR WALL -MOUNTED SIGNS
CONTRACTOR COPY'
P = 46.0 psf
Cabinet
A= 18.0 sgft (entire cabinet)
Masonry (ASTM C90, 1,500 psi min)
1/4" Tapcon
Ref: ITW Tapcon, NOA 07-1126.10
Min Embedment: 1.25"
Min edge dist: 2.5" Min Spacing: 3"
Anchor tensile capacity: Tcap = 195.0 lb (per anchor)
Check Anchors for Pullout
Total Reaction: Rt= 827 lb ... =P*A (entire cabinet)
No. of anchors req'd: n = 4.2 total anchors ... = Rt/cap
Total anchors required: 5 total anchors balanced over cabinet
OK, typical anchor option shown.
Ref anchor schedule for other anchor options.
Page 3
Seals
�0000.ra
easyseals.com
C(N_ RN' C 9 4ARY��iT' P
DESIGN CALCULATIONS
FOR
FLORIDA COAST EQUIPMENT
Sian Type: Main Letters & Logo
6000 Orange Ave — Ft Pierce
GENERAL NOTES:
1. Design is in accordance with the Florida Building Code 5th Edition (2014)
for use within and outside the High Velocity Hurricane Zone (HVHZ).
2. Wind loads have been calculated per the requirements of ASCE 7-10 as
shown herein.
3. 'These engineering calculations pertain only to the structural integrity of
those systems, components, and/or other construction explicitly Index:
specified herein and/or in accompanying engineering drawings. The
existing host structure (if any) is assumed to be in good condition, Pg 1 Cover
capable of supporting the loaded system, subject to building department Pg 2 Wind Loads
approval. No warranty, either expressed or implied, is contained herein. Pg 3 Anchor Design
4. System components shall be as noted herein. All references to named
components and installation shall conform to manufacturer's or industry
specifications as summarized herein.
`tquu1rrryr
5. Where site conditions deviate from those noted herein, revisions maybe Engi 'EA
` , `alrtj.seal valid
'.
required or a separate site -specific engineering evaluation performed. utrro . r
r F '•,
6. Aluminum components in contact with steel or embedded in concrete (�.� •�,G
shall be protected as prescribed in the 2010 Aluminum Design Manual, No. 67 8
Part 1. Steel components in contact with, but not encased in, concrete 1
shall be coated, painted, or otherwise protected against corrosion. .01• ,
ST TE OF • •�<4;
7. Engineer seal affixed hereto validates structural design as shown only. �'.�01;.• AllM 1 c1
Use of this specification by contractor, et. Al, indemnifies and saves Chrf a R£�# 67382
harmless this engineer for all costs & damages including legal fees & Easy Sea19��r�rrrGCia th # 31124
anpnatp fppc rnadtino frnm ripvintinn from this rlpOan r,. Boca
Raton,
3432Hwy, g200 Ean Seals.com Page 1
Boca Raton, FL33432 1
�FasySeals
ASCE 7-10 Design Wind Loads
WALL -MOUNTED SIGNS
Building Specs
V = 160 mph Basic wind speed
Exposure C
Calculations
a= 9.5 3-sec gust speed power law exponent
Zg = 900' Nominal ht. of atmos. boundary layer
Gcpi = 0 Internal pressure coeff
CALCULATION,'OR WALL -MOUNTED SIGNS
ASD Load Combo Coeff: 0.6
Kd = 0.85 Directionalityfactor
Kzt= 1.0 Topographicfactor
A = 10 sq ft Tributary area
160 mph - Exp "C"
WALL -MOUNTED SIGNS
ASD WIND PRESSURES
SIGN
CENTER
CORNER
IEIGHT
(Zone 4)
(Zone 5)
Y Y
q=
UU'
_
U '^
15 ft
31.2 psf
39.7 psf
0.85
47.3
-1.10
-1.40
20 ft
33.2 psf
42.2 psf
0.90
50.2
-1.10
-1.40
25 ft
34.8 psf
44.2 psf
0.95
52.7
-1.10
-1.40
30 ft
36.1 psf
46.0 psf
0.98
54.7
-1.10
-1.40
35 ft
37.3 psf
47.5 psf
1.01
56.5
-1.10
-1.40
40 ft
38.4 psf
48.8 psf
1.04
58.1
-1.10
-1.40
45 ft
39.3 psf
50.1 psf
1.07
59.6
-1.10
-1.40
50 ft
40.2 psf
51.2 psf
1.09
60.9
-1.10
-1.40
55 ft
4.1.0 psf
52.2 psf
1.12
62.2
_ -1.10
-1.40
60 ft
41.8 psf
53.2 psf
1.14
63.3
-1.10
-1.40
70 ft
35.3 psf
70.6 psf
1.17
65.4
-0.90
-1.80
80 ft
36.3 psf
72.6 psf
1.21
67.3
-0.90
-1.80
90 ft
37.2 psf
74.5 psf
1.24
69.0
-0.90
-1.80
100 ft
38.1 psf
76.1 psf
1.27
70.5
-0.90
-1.80
110 ft
38.8 psf
77.7 psf
1.29
71.9
-0.90
-1.80
120 ft
39.6 psf
79.1 psf
1.32
73.3
-0.90
-1.80
130 ft
40.2 psf
80.5 psf
1.34
74.5
-0.90
-1.80
140 ft
40.9 psf
81.7 psf
1.36
75.7
-0.90
-1.80
150 ft
41.S psf
82.9 psf
1.38
76.8
-0.90
-1.80
175 ft
42.8 psf
85.7 psf
1.42
79.3
-0.90
-1.80
200 ft
44.1 psf
88.1 psf
1.46
81.6
-0.90
-1.80
250 ft
46.2 psf
92.3 psf
1.53
85.5
-0.90
-1.80
Page 2
1�p�ySeals
resysralscom
Wall Sign Anchor Design
Structure Dimensions & Loading
Design wind pressure:
Sign type:
Sign size:
Wall material:
Anchor type/size:
Anchor tensile capacity:
Check Anchors for Pullout
CALCULATION, ORWALL-MOUNTED SIGNS
P = 46.0 psf
Channel Letter
A = 4.4 sqft (per letter, critical)
Wood CDX or equiv, thickness to match Min Embed
#14 SMS
Ref: APA E830E Fastener Loads for Plywood
Min Embedment: 0.5"
Min edge dist: 2" Min Spacing: 2"
Tcap= 112.0 lb (peranchor)
Total Reaction: Rt = 204 lb ... = P•A (per letter)
No. of anchors req'd: n = 1.8 anchors per letter ... = Rt/cap
Total anchors required: 2 anchors per letter
OK, critical anchor option & logo size shown. min (3) per Itr/logo.
Limit to min (3) per Itr/logo, min (8) at "EQUIPMENT" capsule. Ref anchor schedule for other anchor options.