HomeMy WebLinkAboutPLAN REVIEW FORMSAINT LUCIE COUNTY FIRE DISTRICT
`�Q,OUNTy�,ti PLAN REVIEW FORM
9\, 5160 N.W. Milner Drive
.1 •�� Port Saint Lucie, FL 349
-33283
2 LAMED'
� `Telephone: 772-621-3322 ®®®
�9FDISIQ\�' Fax: 772-621-3604 BY
Web Address: www.slcfd.com St. Lucie County
Building Dept. SLC FMO Permit# B-17-113
Project Name
Address
The Storage Depot Center
BLDG Permit #
1611-0531
5801 South US Hwy 1
City
PSL
Contractor Restar Services Construction
Address 2423 South Orange Avenue City Orlando
State FL Zip 32806 Telephone (407)859-8750
Architect/Engineer ZJS Engineering Services Telephone (909) 823-4150
.Occupancy Type Storage Construction Type 11B Square Feet 9612
Occupant Load 88perplans Numberof Stories Access Box Required Access Key Switch
•AFS Permit Required FA Permit Required FFP Permit
General Notes
1. An electronic copy of the construction documents submitted on a CD Is required. The file format shall be .pdf only.
2. All revisions, Including the electronic copy must be received prior to permitting.
3. The Fire Marshal requires i4 hour notice on all inspections.
4. The respective Building Department shall schedule all final inspections through the Fire Marshal's Office.
S. Failed inspections require payment of fee prior to rescheduling of further Inspections.
6. Penetrations through rated assemblies shall be of the proper UL design. Design criteria shall be submitted with the construction plans.
7. Fire alarm panels shall be located Indoors within air conditioned space.
S. Plans and construction are subject to corrections In the field to maintain code compliance.
9. Automatic fan shutdown is required for HVAC systemis that exceed 2,000 cfm design capacity.
10. The Installation or Alteration of Fire Sprinklers, Fire Alarms, and Fixed Fire Protection Systems require a separate review and permit.
THE FLORIDA FIRE PREVENTION CODE, 2012 EDITION IS CURRENTLY ENFORCED.
BUILDINGS WITH LIGHT -FRAME TRUSS -TYPE CONSTRUCTION SHALL BE MARKED WITH APPROVED FIREFIGHTER SAFETY
WARNING SIGNS IN ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODES 69A-3.012 AND 69A-60.0081 PRIOR TO RECEIVING
A CERTIFICATE OF OCCUPANCY.
bee ttenerai Notes Hoove ana Hequirea Hevisions tselow
1. The Installation or Alteration of Fire Sprinkler, Fire Alarm Systems require a separate review and permit.
* Mechanical plans are missing*
2. Automatic fan shutdown is required for HVAC system/s that exceed 2,000 cfm design capacity. Provide a remote test and
inspect appliance equipped with an audible/visual indicatorfor each HVAC duct smoke detector. HVAC detectors shall be tied
into the fire alarm System.
Page 11 ! of �J Reviewed by Tony Jerger Date 05-18-17