HomeMy WebLinkAboutTEST REPORT� OMEGA AIR SERVICES L�
DBA OMEGA TEST AND BALL:..ZE
b �.�N-A CERTIFIED INDEPENDENT TESTAND BALANCE COMPANY---
126 WISTERIA AVENUE, FORT PIERCE, FLORIDA 34982
CELL(772)216-7632
TABB CERTIFICATION NO. BB032001C
www.omeaatestandbalance.orq
omeaamaniac5320020vahoo.com
TESTING, AD3USTING, AND BALANCING REPORT
SOUND SOLUTIONS HEARING AID
761 EAST PRIMA VISTA BLVD.
PORT ST. LUCIE, FLORIDA
MECHANICAL
PAUL WELCH EI
1984 SW BILTMORE ST., #114
PORT ST. LUCIE, FLORIDA 34984
GENERAL CONTRACTOR:
SWIEZY CONSTRUCTION COMPANY
825 TILTON ROAD
PORT ST. LUCIE, FLORIDA 34952
MAY 13, 2107
SCANNED
BY
St _Lucie County
spy
--ALL WORKPERFORMED IN ACCORDANCE W17H TABB STANDARDSAND PROCEDURES—
_W
MCUP�
mx� mwa
TA®TEOPQQIIN
BHIQ�61Of ..�+ 1 Ml.
�
.•,.� 19
`n¢rRDFMW0 sdiMCW-
OMEGA AIR SERVICES W,"'t
-" DBA OMEGA TEST AND BALL s;E
...A CERTIFIED INDEPENDENT 7F.STAND BALANCE COMPANY---
126 WISTERIA AVENUE, FORT PIERCE, FLORIDA 34982
CELL (772)216-7632
TABB CERTIFICATION NO. BB032001C/BB032002S/BB1032610T
www.ameaatestandbalance.org
omeaamaniac5320020yahoo.com
SOUND SOLUTIONS HEARING AID
TEST AND BALANCE INSTRUMENTS
SHORTRIDGE SERIES 8400 FLOWHOOD W/ADM860 AIR DATA MULTIMETER
RANGE:
ACCURACY:
CALIBRATION DATE:
0 TO 61 IN H.G
0.05% FS
SEPTEMBER 30, 2016
CHECK -IT DIGITAL PSYCHROMETER —MODEL #622
RANGE:
ACCURACY:
CALIBRATION DATE:
SHORTRIDGE ADT446 TEMPROBE
RANGE:
ACCURACY:
CALIBRATION DATE
FLUKE 322 CLAMP METER
35° TO 20SO F, 5% TO 1000/a RH
t20 *1 DIGIT f30/o
SEPTEMBER 30, 2016
-200 TO 1800 F
t 0.50 FROM 320 TO 1580 F
SEPTEMBER 30, 2016
HUGH A. GRIMES,
CERTIFIED T.A.B.B. CONTRACTOR/SUPERVISOR/TECHNICIAN
--ALL WORK PERFORMED IN ACCORDANCE WITH TABS STANDARDSAND PROCEDURES--
s
NJM GWHES -- —
TAM TEU Uaffl
NilAffiIOf NAROI TI $119
� ew�
- --_ TESMUO, ADJUBMQ AND SAL.ANCUM BURFIW
OMEGA AIR SERVICES Ltu—
DBA OMEGA TEST AND BALL �E
,—^ A CERTIFIED INDEPENDENT TFSTAND BALANCE COMPANY-~N
126 WISTERIA AVENUE, FORT PIERCE, FLORIDA 34982
CELL(772)216-7632
TABB CERTIFICATION NO. B8032001C
www.omenatestandbalance.orcm
omegama niacS32002@vahoo.com
TESTING. ADJUSTING, AND BALANCING WARRANTY
SOUND SOLUTIONS HEARING AID
ALL TESTING, ADJUSTING, AND BALANCING PERFORMED ON THIS PR03ECT BY
OMEGA AIR SERVICES LLC DBA OMEGA TEST AND BALANCE IS UNDER WARRANTY
FOR A PERIOD OF ONE YEAR FROM THE DATE OF COMPLETION OF THE TEST AND
BALANCE UNLESS OTHERWISE NOTED.
WARRANTY PERIOD SHALL BE: MAY 13, 2017 THROUGH MAY 13, 2018
--ALL WORKPERFORMED MACWRDANCE WITH TABB STANDARDSAND PROCEDURES
Hugh Grimes
Omega Air Services, LLC
TABS Supemisor
BB0320M
March 31, 2019
GH A. WUMES,
T.A.B.B. CONTRACTOR/SUPERVISOR/TECHNICIAN
=_�
T� y Caltifk�jfbry
AM
— - mua+am+a
TABB TEUIMQIIN
B81?�610T MARQ� 31. 7019
SOUND SOLUTIONS HEARING AID
AIR HANDLING UNITS
;UNIT
AHU-1
MAKE
GOODMAN
MODEL
ARUF036
SERIAL
NA
SHEAVE
DD
BELTS
DD
FILTERS
1"
;MOTOR
MAKE/FR
DO
HP RPM
1 3 INA
V PH HZ
20811160
FLA/SF
2.15 I NA
SHEAVE
DD
CL
DO
HEAT
ELECTRIC
EVAPORATOR
DESIGN I ACTUAL
S A CFM
1000* I lilt
0 A CFM
120** 1109
R A CFM
NA 902
EXT. SP
NA .33
DISC. SP
NA .17
SUCT. SP
NA 1 -.16
OAT DB WB
NA 84.1 75.7
RAT DB WB
NA 81.1 72.3
LAT DB WB
NA 59.9 58.7
FAN RPM
NA NA
VOLTS
208 209
AMPS
2.15 1.23
CONDENSOR
1
MAKE
GOODMAN
MODEL
CRT036
SERIAL
NA
V PH HZ
20911160
RLA
14.6
LO PRESSURE
70
HIPRESSURE
275
REFRIGERANT
R22
FAN HP RPM
11118 1100
V PH HZ A
208 1 60 1A
CCHEATAMPS
.1
REMARKS: ---*ORIGINAL DESIGN CFM OF 1000 CFM HAS BEEN INCREASED BY ADDING AN ADDITIONAL
OUTLET IN THE FAMILY ROOM ADDITION. NO DESIGN VALUE PROVIDED FOR ADDITIONAL
OUTLET.
---**CHANGED DESIGN OUTSIDE AIR CFM FROM 240 CFM TO 120 CFM IN ORDER TO
ACCOMMODATE ACTUAL OCCUPANCY OF 7 PEOPLE.
Al I WnRK PFRFnRMFn TN Arrf)RndNrF WITH rARR .STANndRM ANn PRnrFn//RF.S
o
MIGH
TA®T®1HIOAN
�3�tlABSYl31.�19
SOUND SOLUTIONS HEARING AID
AIR OUTLETS
AHU
ADDRESS
OUTLET
NUMBER
TYPE
DESIGN
CFM
PRE.
CFM
FINAL
CFM
BEDROOM
1
CD
150
72
138
FAMILY ROOM
2
CD
220
67
203
XITCHEN
3
CD
160
112
146
LIVING ROOM
4
CD
220
119
206
BATHROOM
5
CD
50
111
47
MASTER BEDROOM
6
CD
200
62
183
FAMILY ROOM
7
CD
NA*
188
188
1000*
REMARKS: ---*ADDITIONAL GRILL ADDED TO FAMILY ROOM. NO DESIGN CFM
PROVIDED.
ALL WORK PERFORMED M ACCORDANCE WITH TA BB STANDARDS AND PROCEDURES