HomeMy WebLinkAboutREVIEW COMMENTSv
Planning 8, Development Services
Building &Code Regulation Division
2300 Virginia Avenue
Fort Pierce, FL. 34982.
Phone:(772)462.2172 Fax:(772)46246443
Address: 8243 Business Park Or
City / State / Zip: Port St Lucie, FI 34952
Parcel#: 3426-702-0004-000/0
Zoning: PNRD
APPLICATION INFORMATION
Permit Number: 1703-0686
Permit Type: COMMERCIAL RENOVATION
CONTRACTOR INFORMATION
Contractor Name:
Raxcie L Ledgister
Business Name:
Dlr General Construction Inc
Business Addr:
134 Ne Jettie Terr
City / State / Zip:
Port St Lucie, Fill 34983
REVIEWS AND COMMENTS
Review Type
DOCUMENTS MISSING
3/31/2017 Comment:
3/31/2017 Comment:
3/3112017 Comment:
i
FIRE DEPARTMENT REVIEW
Comment:
FRONT COUNTER REVIEW
Comment:
PE REVIEW COMMENTS (2)
Comment:
4/4/2017
Comment
4/4/2017
4/13/2017 Comment:
4/13/2017 Comment:
i
1
4/13/2017 Comment:
REVIEW COMMENTS
SCAvlyti_
oUANNED B , B\
RV `S11PLAUP i .r,.
Owner(s):
A Holdings 1000 Llc
Jurisdiction: ST LUCIE COUNTY
Lot#: S 12' 2, Block:
ALL3,4
Stories: Automatic Sprinkler System? No
Fax Number: 772-873-2311
Status Reviewed By Date Started
PENDING Lashahna Ingram
NEEDS NOC
NEEDS SUB FOR PLUMBING
NEEDS SUB FOR ELECTRIC
PENDING Tony Jerger
COMPLETE Lashahna Ingram 3/31/2017
INCOMPLETE Joe Ciclo 511512017
Email: Rledgister2@Gmail.Com
Date Comoleted Date Released
3/3112017 3/3112017
SHOW THE LOCATION ON THE FRONT BUILDING ELEVATION FOR THE MALTESE CROSS PER F.A.C.69A-
60.0081 "THE MALTESE CROSS IS THE FIRE SYMBOL AS STATED FAC 69A-60.0081 ' THIS MUST BE
POSTED ON THE FRONT ELEVATION OF THE SPACE PER DIRECTION OF THIS SECTION
PROVIDE VERTICAL ACCESSIBILITY TO THE STAGE AND CHOIR AREA PER FBC ACCESSIBILITY 206.2.6
SECOND REVIEW "' WE DO NOT GRANT EXCEPTIONS TO THE ACCESSIBILITY CODES I DESIGN
PROFESSIONAL MAY NOTE ON PLANS THE SPECIFIC CODE SECTIONS OR OTHER CRITERIA WHICH
EXEMPTS CHURCHES FROM THIS CODE
ARCHITECT TO INCLUDE AN INTERIOR FINISHES TABLE ON PLANS PER FBC 808.9 "' TABLE 803.9
UPON RE -SUBMITTAL DESIGN PROFESSIONAL TO SUBMIT A BREAKDOWN SHEET ADDRESSING
COMMENTS BY ALL REVIEWERS
COMMENTS E-MAILED AS OF THIS DATE
r
%G• f.laG1G l/Oi.as.�
Planning B Development Services REVIEW COMMENTS
Building& Code Regulation Division
2300 Virginia Avenue
Fort Pierce, FL 34982
Phone:(772)462-2172 Fax:(772)462.6443
3
Comment:
***ARCHITECT TO CALCULATE THE OCCUPANT LOAD FOR ALL AREAS OF THE TENANT SPACE PER FBC
511212017
TABLE 1004.1.2 ON THE NET AREA PER FBC DEFINITIONS IN CHAPTER 2 `SHOW THE SQ.FTG AND
OCCUPANT COUNT BREAKDOWN ON PLANS FOR THE LOBBY[ STANDING SPACE ] , OFFICE, PULPIT AND
STORAGE AREAS • UN -FIXED SEATS ARE 7 S.F. PER PERSON IN THE ASSEMBLY AREAS
5/15/2017 Comment:
SEE FBC 1028.9 FOR ASSEMBLY AISLE WIDTH / 24" WIDTHS DO NOT COMPLY
5/15/2017 Comment:
DESIGN PROFESSIONAL TO SHOW THE REQUIRED CORRIDOR AND OPENING RATING ON PLANS PER FBC
TABLE 1018.1 FOR THE REAR CORRIDOR
5/15/2017 Comment:
SECOND REVIEW COMMENTS E-MAILED AS OF THIS DATE
PLANS EXAMINER ELECTRIC
INCOMPLETE Carl Peterson 411812017
4/18/2017 Comment:
PLEASE FURNISH A PANEL SCHEDULE PER 107.2.1 OF THE FLORIDA BUILDING CODE
PLANS EXAMINER MECHANICAL
COMPLETE Carl Peterson 411712017 411812017 4118/2017
Comment:
PLANS EXAMINER PLUMBING
INCOMPLETE Greg Smyth 4/4/2017
4/4/2017 Comment:
PLEASE SHOW CORRECTED OCCUPANT LOAD PER SECTION 403 FLORIDA PLUMBING CODE 2014
1. 4/4/2017 Comment:
PLEASE SHOW THE REQUIRED TWO WATER CLOSETS FOR THE FEMALE RESTROOM PER TABLE 403.1
FLORIDA PLUMBING CODE
PLANS EXAMINER REVIEW
COMPLETE Joe Cicio 4/312017 511212017 5/12/2017
Comment:
ZONING REVIEW
COMPLETE Lydia Galbraith 3/31/2017 3131/2017 313112017
Comment:
Planning 8 Development Services
Building & Code Regulation Division
2300 Virginia Avenue
Fort Pierce, FL. 34982
Phone:(772)462.2172 Fax:(772)462.6443
PROPERTY INFORMATION
Address: 8243 Business Park Dr
City / State / Zip: Port St Lucie, FI 34952
Parcel#: 3426-702-0004.000/0
Zoning: PNRD
r
i
'APPLICATION INFORMATION
i
f Permit Number: 1703-0686
Permit Type: COMMERCIAL RENOVATION
Contractor Name:
Raxcie L Ledgister
Business Name:
Dlr General Construction Inc
Business Addr:
134 Ne Jettie Terr
City / State / Zip:
Port St Lucie, FI 34983
REVIEW COMMENTS
SCANNED
BY
St. Lucie Countv
1
Owner(s):
FI Holdings 1000 Llc
Jurisdiction: ST LUCIE COUNTY
Lot#: S 12' 2, Block:
ALL3,4
Stories: Automatic Sprinkler System? No
Fax Number: 772-873-2311
Email: Rledgister2@Gmail.Com
REVIEWS AND COMMENTS
Review Tvoe Status Reviewed By Date Started Date Completed Date Released
DOCUMENTS MISSING
PENDING Lashahna Ingram
{ 3/3112017 Comment:
NEEDS NOC
3/31/2017 Comment:
NEEDS SUB FOR PLUMBING
3/31/2017 Comment:
NEEDS SUB FOR ELECTRIC
FIRE DEPARTMENT REVIEW
PENDING Tony Jerger
Comment:
FRONT COUNTER REVIEW
COMPLETE Lashahna Ingram 3/31/2017 313112017 3131/2017
Comment:
PLANS EXAMINER ELECTRIC
INCOMPLETE Carl Peterson 411812017
4118/2017 Comment:
PLEASE FURNISH A PANEL SCHEDULE PER 107.2.1 OF THE FLORIDA BUILDING CODE
PLANS EXAMINER MECHANICAL
COMPLETE Carl Peterson 4117/2017 4118/2017 4/18/2017
Comment:
PLANS EXAMINER PLUMBING
INCOMPLETE Greg Smyth 41412017
4/4/2017 Comment:
PLEASE SHOW HIGH LOW DRINKING FOUNTAIN PER SECTION 211 FLORIDA ACCESSABILITY CODE 2014
4/4/2017 Comment:
PLEASE SHOW HOT WATER TO ALL SINKS PER 607.1 FLORIDA PLUMBING CODE 2014
4/4/2017 Comment:
PLEASE SHOW CORRECTED OCCUPANT LOAD PER SECTION 403 FLORIDA PLUMBING CODE 2014
4/4/2017 Comment:
PLEASE SHOW SERVICE SINK PER TABLE 403.1 FL PLUMBING CODE
I
iti �cfGZG UDx`����ry�
Planning & Development Services
Building & Code Regulation Division
2300 Virginia Avenue
Fort Pierce, FL 34982
Phone:(772)462.2172 Fax:(772)462.6443
REVIEW COMMENTS
Page 2
414/2017
Comment:
PLEASE SHOW THE REQUIRED TWO WATER CLOSETS FOR THE FEMALE RESTROOM PER TABLE 403.1
FLORIDA PLUMBING CODE
PLANS EXAMINER REVIEW
INCOMPLETE Joe Cicio 41312017
Comment:
IS THIS TENANT SPACE SPRINKLED 77 [ ARCHITECT TO NOTE ON PLANS ] / IF NOT [ ARCHITECT TO NOTE
4/3/2017
ON PLANS ] , TENANT SEPARATION WALLS MUST BE DESIGNED AS 2 HOUR RATED PARTITIONS • SHOW
ALL TESTING DETAILS AND TEST NUMBERS ON PLANS " [ SEE FBC TABLE 508.4 ]
4/3/2017
Comment:
ARCHITECT TO STATE THE CONSTRUCTION TYPE ON PLANS • FBC SECTION 602
Comment:
ARCHITECT TO CALCULATE THE CORRECT OCCUPANT LOADS ON PLANS PER FBC TABLE 1004.1.2 / USE
4/3/2017
EITHER 7,5 OR 15 S.F.P.P. PER TABULAR VALUES, UNFIXED SEATS [ MUST HAVE AN OCCUPANT LOAD
BREAKDOWN FOR ALL AREAS
4/3/2017
Comment:
ARCHITECT TO CALCULATE THE MEANS OF EGRESS DOOR SIZING SIZES ON PLANS PER THE
CALCULATED OCCUPANT LOADING' FBC 1005.3.2
4/3/2017
Comment:
SUBMIT LIFE SAFETY PLANS W/ ALL TRAVEL DISTANCES FBC 1014.3
4/4/2017
Comment:
SHOW THE LOCATION ON THE FRONT BUILDING ELEVATION FOR THE MALTESE CROSS PER F.A.C.69A-
60.0081
4/4/2017
Comment:
CHOIR RISER IS NOT PER CODE • SEE FBC 1009.7.2
4/4/2017
Comment:
PROVIDE VERTICAL ACCESSIBILITY TO THE STAGE AND CHOIR AREA PER FBC ACCESSIBILITY 206.2.6
4/4/2017
Comment:
ARCHITECT TO SHOW THE REQUIRED INSIDE MANUEVERING CLEARANCES [ CLEAR FLOOR SPACES ] ON
PLANS FOR THE RESTROOM DOORS AND ALL RESTROOM FIXTURES' SEE FBC ACCESSIBILITY 404.2.4.1
4/4/2017
Comment:
ARCHITECT TO SHOW ALL ACCESSIBLE RESTROOM DETAILS ON PLANS LE: DISPENSOR HEIGHTS, GRAB
BAR HEIGHTS ETC FOR BOTH RESTROOMS
4/4/2017
Comment:
SHOW THE REQUIRED NON-ABSORBANT WALL COVERINGS ON PLANS FOR THE RESTROOMS AND
SERVICE SINK AREAS `SEE FBC 1210.2.1 AND 1210.2.2
4/12/2017
Comment:
SHOW THE TEST STANDARDS ON PLANS FOR THE GYPSUM BOARD WI ACCESORIES' SEE FBC 2506.2
4/1212017
Comment:
ARCHITECT TO SHOW THE MARKING AND IDENTIFICATION ON PLANS FOR THE REQUIRED SIGNS OR
STENCILLING IN THE ABOVE CEILING AREA' SEE FBC 703.7' DESIGN PER CODE
4/1312017
Comment:
ARCHITECT TO INCLUDE THE ACCOUSTICAL CEILING W/ METAL GRID TESTING STANDARDS ON PLANS
PER FBC 808 WI DETAILS FOR INSTALLATION
4/1312017
Comment:
ARCHITECT TO SHOW THE FLAME SPREAD AND SDI FOR THE INSULATION ON PLANS PER FBC 720
4/13/2017
Comment:
ARCHITECT TO INCLUDE AN INTERIOR FINISHES TABLE ON PLANS PER FBC 808.9
4/13/2017
Comment:
DOUBLE 30" DOORS IN THE MEANS OF EGRESS ARE NOT COMPLIANT WITH FBC 1008.1.1 /ARCHITECT TO
CORRECT
4/13/2017
Comment:
UPON RE -SUBMITTAL DESIGN PROFESSIONAL TO SUBMIT A BREAKDOWN SHEET ADDRESSING
COMMENTS BY ALL REVIEWERS
4/1312017
Comment:
COMMENTS E-MAILED AS OF THIS DATE
ZONING REVIEW
COMPLETE Lydia Galbraith 3131/2017 3/31/2017 3/31/2017
Comment:
Planning 8, Development Services
Building & Code Regulation. Division
2300 Virginia Avenue
Fort Pierce, FL 34982
Phone:(772)462-2172 Fax:(772)462-6443
Address: 8243 Business Park Dr
City I State I Zip: Port St Lucie, FI 34952
Parcel#: 3426-702-0004-000/0
Zoning: PNRD
REVIEW COMMENTS
SGANNED
BY
St. Lucie Countv
Owner(s):
FI Holdings 1000 Llc
Jurisdiction: ST LUCIE COUNTY
Lot#: S 12- 2, Block:
ALL3,4
1
APPLICATION INFORMATION
Permit Number: 1703-0686 Stories: Automatic Sprinkler System? No
Permit Type: COMMERCIAL RENOVATION
CONTRACTOR INFORMATION
Contractor Name: Raxcie L Ledgisler Fax Number: 772-873-2311
Business Name: Dlr General Construction Inc
Business Addr: 134 Ne Jettie Terr Email: Rledgistet2@Gmail.Com
City / State / Zip: Port St Lucie, FI 34983
REVIEWS AND COMMENTS
Review Type Status Reviewed By Date Started Date Completed Date Released
DOCUMENTS MISSING PENDING Lashahna Ingram
3/31/2017 Comment: NEEDS NOC
3/31/2017 Comment: NEEDS SUB FOR PLUMBING
3/31/2017 Comment: NEEDS SUB FOR ELECTRIC
FIRE DEPARTMENT REVIEW PENDING Tony Jerger
( Comment:
FRONT COUNTER REVIEW COMPLETE Lashahna Ingram 3/3112017 313112017 3/31/2017
Comment:
PLANS EXAMINER ELECTRIC INCOMPLETE Carl Peterson 4/18/2017
4/18/2017 Comment: PLEASE FURNISH A PANEL SCHEDULE PER 107.2.1 OF THE FLORIDA BUILDING CODE
PLANS EXAMINER MECHANICAL COMPLETE Carl Peterson 4/1712017 4118/2017 4/18/2017
Comment:
PLANS EXAMINER PLUMBING INCOMPLETE Greg Smyth 4/4/2017
4/4/2017 Comment: PLEASE SHOW HIGH LOW DRINKING FOUNTAIN PER SECTION 211 FLORIDA ACCESSABILITY CODE 2014
4/4/2017 Comment: PLEASE SHOW HOT WATER TO ALL SINKS PER 607.1 FLORIDA PLUMBING CODE 2014
4/4/2017 Comment: PLEASE SHOW CORRECTED OCCUPANT LOAD PER SECTION 403 FLORIDA PLUMBING CODE 2014
4/4/2017 Comment: PLEASE SHOW SERVICE SINK PER TABLE 403.1 FL PLUMBING CODE
.a-1 4o0=
Planning & Development Services
Building & Code Regulation Division
2300 Virginia Avenue
Fort Pierce, FL 34982
Phone:.(772)462.2172 Fax:(772)462.6443
REVIEW COMMENTS
4/4/2017 Comment:
PLEASE SHOW THE REQUIRED TWO WATER CLOSETS FOR THE FEMALE RESTROOM PER TABLE 403.1
FLORIDA PLUMBING CODE
PLANS EXAMINER REVIEW
INCOMPLETE Joe Cicio 41312017
Comment:
IS THIS TENANT SPACE SPRINKLED ?? [ ARCHITECT TO NOTE ON PLANS ) / IF NOT [ ARCHITECT TO NOTE
4/3/2017
ON PLANS ) , TENANT SEPARATION WALLS MUST BE DESIGNED AS 2 HOUR RATED PARTITIONS' SHOW
ALL TESTING DETAILS AND TEST NUMBERS ON PLANS •• [ SEE FBC TABLE 508.41
4/3/2017 Comment:
ARCHITECT TO STATE THE CONSTRUCTION TYPE ON PLANS' FBC SECTION 602
Comment:
ARCHITECT TO CALCULATE THE CORRECT OCCUPANT LOADS ON PLANS PER FBC TABLE 1004.1.21 USE
4/3/2017
EITHER 7,5 OR 15 S.F.P.P. PER TABULAR VALUES, UNFIXED SEATS [ MUST HAVE AN OCCUPANT LOAD
BREAKDOWN FOR ALL AREAS
4/3/2017 Comment:
ARCHITECT TO CALCULATE THE MEANS OF EGRESS DOOR SIZING SIZES ON PLANS PER THE
CALCULATED OCCUPANT LOADING • FBC 1005.3.2
4/3/2017 Comment:
SUBMIT LIFE SAFETY PLANS W/ ALL TRAVEL DISTANCES FBC 1014.3
4/4/2017 Comment:
SHOW THE LOCATION ON THE FRONT BUILDING ELEVATION FOR THE MALTESE CROSS PER F.A.C.69A-
60.0081
414/2017 Comment:
CHOIR RISER IS NOT PER CODE • SEE FBC 1009.7.2
4/4/2017 Comment:
PROVIDE VERTICAL ACCESSIBILITY TO THE STAGE AND CHOIR AREA PER FBC ACCESSIBILITY 206.2.6
4/4/2017 Comment:
ARCHITECT TO SHOW THE REQUIRED INSIDE MANUEVERING CLEARANCES [ CLEAR FLOOR SPACES ] ON
PLANS FOR THE RESTROOM DOORS AND ALL RESTROOM FIXTURES • SEE FBC ACCESSIBILITY 404.2.4.1
4/4/2017 Comment:
ARCHITECT TO SHOW ALL ACCESSIBLE RESTROOM DETAILS ON PLANS I.E: DISPENSOR HEIGHTS, GRAB
BAR HEIGHTS ETC FOR BOTH RESTROOMS
4/4/2017 Comment:
SHOW THE REQUIRED NON-ABSORBANT WALL COVERINGS ON PLANS FOR THE RESTROOMS AND
SERVICE SINK AREAS `SEE FBC 1210.2.1 AND 1210.2.2
4/12/2017 Comment:
SHOW THE TEST STANDARDS ON PLANS FOR THE GYPSUM BOARD W/ ACCESORIES • SEE FBC 2506.2
4/1212017 Comment:
ARCHITECT TO SHOW THE MARKING AND IDENTIFICATION ON PLANS FOR THE REQUIRED SIGNS OR
STENCILLING IN THE ABOVE CEILING AREA • SEE FBC 703.7' DESIGN PER CODE
4/13/2017 Comment:
ARCHITECT TO INCLUDE THE ACCOUSTICAL CEILING W/ METAL GRID TESTING STANDARDS ON PLANS
PER FBC 808 W/ DETAILS FOR INSTALLATION
4/13/2017 Comment:
ARCHITECT TO SHOW THE FLAME SPREAD AND SDI FOR THE INSULATION ON PLANS PER FBC 720
4/13/2017 Comment:
ARCHITECT TO INCLUDE AN INTERIOR FINISHES TABLE ON PLANS PER FBC 808.9
4/1312017 Comment:
DOUBLE 30" DOORS IN THE MEANS OF EGRESS ARE NOT COMPLIANT WITH FBC 1008.1.1 /ARCHITECT TO
CORRECT
4/1312017 Comment:
UPON RE -SUBMITTAL DESIGN PROFESSIONAL TO SUBMIT BREAKDOWN SHEET ADDRESSING
COMMENTS BY ALL REVIEWERS
4/13/2017 Comment:
COMMENTS E-MAILED AS OF THIS DATE
ZONING REVIEW
COMPLETE Lydia Galbraith 3/3112017 3/3112017 313112017
Comment:
r
�f.GrG1r✓ UOw�wv�
Planning & Development Services
Building & Code Regulation Division
2300 Virginia Avenue
Fort Pierce, FL. 34982
Phone:V72)462.2172 Fax:(772)462-6443
.PROPERTY INFORMATION
Address: 8243 Business Park Dr
City / State / Zip: Port St Lucie, FI 34952
Parcel#: 3426-702-0004-000/0
Zoning: PNRD
APPLICATION INFORMATION
Permit Number: 1703-0686
REVIEW COMMENTS
SGANNELj
BY
St. Lucie Countv
1
Owner(s):
FI Holdings 1000 Llc
Jurisdiction: ST LUCIE COUNTY
Lot#: S 12' 2, Block:
ALL3,4
Stories: Automatic Sprinkler System? No
Permit Type: COMMERCIAL RENOVATION
CONTRACTOR INFORMATION
I
Contractor Name: Raxcie L Ledgister Fax Number: 772-873-2311
Business Name: Dlr General Construction Inc
Business Addr: 134 Ne Jettie Terr Email: Rledgiste2@Gmail.Com
City / State / Zip: Port St Lucie, FI 34983
REVIEWS AND COMMENTS
Review Type Status Reviewed By Date Started Date Completed Date Released
DOCUMENTS MISSING PENDING Lashahna Ingram
3/31/2017 Comment: NEEDS NOC
3/31/2017 Comment: NEEDS SUB FOR PLUMBING
3/31/2017 Comment: NEEDS SUB FOR ELECTRIC
FIRE DEPARTMENT REVIEW PENDING Tony Jerger
Comment:
FRONT COUNTER REVIEW COMPLETE Lashahna Ingram 3131/2017 313112017 313112017
Comment:
PLANS EXAMINER ELECTRIC PENDING Carl Peterson
Comment:
PLANS EXAMINER MECHANICAL PENDING Carl Peterson
Comment:
PLANS EXAMINER PLUMBING INCOMPLETE Greg Smyth 4/412017
4/4/2017 Comment: PLEASE SHOW HIGH LOW DRINKING FOUNTAIN PER SECTION 211 FLORIDA ACCESSABILITY CODE 2014
4/4/2017 Comment: PLEASE SHOW HOT WATER TO ALL SINKS PER 607.1 FLORIDA PLUMBING CODE 2014
4/4/2017 Comment: PLEASE SHOW CORRECTED OCCUPANT LOAD PER SECTION 403 FLORIDA PLUMBING CODE 2014
4/4/2017 Comment: PLEASE SHOW SERVICE SINK PER TABLE 403.1 FL PLUMBING CODE
Planning & Development Services
Building & Code Regulation Division
2300 Virginia Avenue
Fort Pierce, FL 34982.
Phone:]772)4622172 Fax:[7772]462-6443
REVIEW COMMENTS
2
4/4/2017
Comment:
PLEASE SHOW THE REQUIRED TWO WATER CLOSETS FOR THE FEMALE RESTROOM PER TABLE 403.1
FLORIDA PLUMBING CODE
PLANS EXAMINER REVIEW
INCOMPLETE Joe Cicio 413/2017
Comment:
IS THIS TENANT SPACE SPRINKLED ?? [ ARCHITECT TO NOTE ON PLANS ] I IF NOT [ ARCHITECT TO NOTE
4/3/2017
ON PLANS ] , TENANT SEPARATION WALLS MUST BE DESIGNED AS 2 HOUR RATED PARTITIONS' SHOW
ALL TESTING DETAILS AND TEST NUMBERS ON PLANS ** [ SEE FBC TABLE 508.41
4/3/2017
Comment:
ARCHITECT TO STATE THE CONSTRUCTION TYPE ON PLANS' FBC SECTION 602' "
Comment:
ARCHITECT TO CALCULATE THE CORRECT OCCUPANT LOADS ON PLANS PER FBC TABLE 1004.1.2 / USE
413/2017
EITHER 7,5 OR 15 S.F.P.P. PER TABULAR VALUES, UNFIXED SEATS [ MUST HAVE AN OCCUPANT LOAD
BREAKDOWN FOR ALL AREAS
4/3/2017
Comment:
ARCHITECT TO CALCULATE THE MEANS OF EGRESS DOOR SIZING SIZES ON PLANS PER THE
CALCULATED OCCUPANT LOADING * FBC 1005.3.2
4/3/2017
Comment:
SUBMIT LIFE SAFETY PLANS W/ ALL TRAVEL DISTANCES FBC 1014.3
4/4/2017
Comment:
SHOW THE LOCATION ON THE FRONT BUILDING ELEVATION FOR THE MALTESE CROSS PER F.A.C.69A-
60.0081
4/4/2017
Comment:
CHOIR RISER IS NOT PER CODE' SEE FBC 1009.7.2
4/4/2017
Comment:
PROVIDE VERTICAL ACCESSIBILITY TO THE STAGE AND CHOIR AREA PER FBC ACCESSIBILITY 206.2.6
4/4/2017
Comment:
ARCHITECT TO SHOW THE REQUIRED INSIDE MANUEVERING CLEARANCES [ CLEAR FLOOR SPACES ] ON
PLANS FOR THE RESTROOM DOORS AND ALL RESTROOM FIXTURES' SEE FBC ACCESSIBILITY 404.2.4.1
4/4/2017
Comment:
ARCHITECT TO SHOW ALL ACCESSIBLE RESTROOM DETAILS ON PLANS LE: DISPENSOR HEIGHTS, GRAB
BAR HEIGHTS ETC FOR BOTH RESTROOMS
4/4/2017
Comment:
SHOW THE REQUIRED NON-ABSORBANT WALL COVERINGS ON PLANS FOR THE RESTROOMS AND
SERVICE SINK AREAS * SEE FBC 1210.2.1 AND 1210.2.2
4/1212017
Comment:
SHOW THE TEST STANDARDS ON PLANS FOR THE GYPSUM BOARD W/ ACCESORIES * SEE FBC 2506.2
4/12/2017
Comment:
ARCHITECT TO SHOW THE MARKING AND IDENTIFICATION ON PLANS FOR THE REQUIRED SIGNS OR
STENCILLING IN THE ABOVE CEILING AREA' SEE FBC 703.7 * DESIGN PER CODE
4/13/2017
Comment:
ARCHITECT TO INCLUDE THE ACCOUSTICAL CEILING W/ METAL GRID TESTING STANDARDS ON PLANS
PER FBC 808 W/ DETAILS FOR INSTALLATION
4/13/2017
Comment:
ARCHITECT TO SHOW THE FLAME SPREAD AND SDI FOR THE INSULATION ON PLANS PER FBC 720
4/13/2017
Comment:
ARCHITECT TO INCLUDE AN INTERIOR FINISHES TABLE ON PLANS PER FBC 808.9
4/13/2017
Comment:
DOUBLE 30" DOORS IN THE MEANS OF EGRESS ARE NOT COMPLIANT WITH FBC 1008.1.1 /ARCHITECT TO
CORRECT
4/13/2017
Comment:
UPON RE -SUBMITTAL DESIGN PROFESSIONAL TO SUBMIT BREAKDOWN SHEET ADDRESSING
COMMENTS BY ALL REVIEWERS
4/13/2017
Comment:
COMMENTS E-MAILED AS OF THIS DATE
ZONING REVIEW
COMPLETE Lydia Galbraith 3/31/2017 3131/2017 3131/2017
Comment: