PAUL WELCH INC.
Mechanical * Electrical * Civil Engineering
1984 S.W. Biltmore St. Suite#114
Port Saint Lucie, FL 34984
Phone (772) 785 - 9888
Email pwelchinc@aol.com
Re: Shutter Installation
10660 South US Highway 1
Port St. Lucie, FL
To Whom It May Concern:
RECrz
MAY 15 2917
PERfNF�TIu
St. Lucie Gouniy, FL
Our office has calculated the required design pressures in accordance with ASCE 7-10
and Florida Building Code 2014 for the installation of accordion shutters di the above
referenced address.
Wind speed: Vwt: 165 mph, V.,a: 128 mph
Exposure: C
Enclosure Type: Enclosed
Shutter Size: 92" Maximum Height for Accordion
116" Maximum Width for Roll Up
Shutter Location: (See Attached Sketch)
Required Design Pressure: +41.2 / -55.2 PSF
Shutters to be installed shall be equal to, or exceed the required design pressures as listed
above "Required Design Pressure".
Shutters shall be installed in accordance with the shutter manufacturer's installation
instructions and Florida Product Approval and Florida Building Code 2014.
Accordion Shutters shall be FL# 1850.3
Roll Up Shutters shall be FL# 5790.1
Thank you for your attention to this matter.
Submitted by:
PAUL WELCH INC.,
Paul Welch, P.E. ,MAY 1 2 7017
Reg. No 29945