ACCURATE BALANCING & COMMISSIONING, INC
1742 E Rd, Loxahatchee, FL 33470
Phone 561-351-0245
Roberta.tabfirm.com
TAB/Cx Supervisor Robert Shorr
NEBB Certification 93429
Expires 3/31/2018
CERTIFIED TEST; ADJUST., BALANCE REPORT
Project: SLC Courthouse Annex AHU Replacement
St Lucie County, Florida
2300 Virginia Ave, Ft Pierce, FL 34982
Contractor: Airstron, Inc.
1559 SW 21 AV
Ft. Lauderdale, FL 33312
(954)923-1654 Main
Engineer: OCI Associates, Inc.
181 Melody Lane
Ft Pierce, FL 34950
Phone: 772-466-1165
Technicians: Robert Shorr & Travis Shorr
Test Dates: 10/11/17 thru 10/21/17
THE DATA PRESENTED IN THIS REPORT IS A RECORD OF SYSTEM MEASUREMENTS AND FINAL
ADJUSTMENTS THAT HAVE BEEN OBTAINED IN ACCORDANCE WITH THE CURRENT EDITION OF THE NEBB
PROCEDURAL STANDARDS FOR TESTING, ADJUSTING AND BALANCING OF ENVIRONMENTAL SYSTEMS.
ANY VARIANCES FROM DESIGN QUANTITIES, WHICH EXCEED NEBB TOLERANCES, -ARE NOTED IN THE
TEST -ADJUST -BALANCE REPORT PROJECT SUMMARY DUCT SMOKE DETECTOR TESTING AND
CERTIFICATION VERIFIES THE DIFFERENTIAL PRESSURE ACROSS THE DETECTOR PICK UP TUBES ONLY
AND DOES NOT TEST ANY ELECTRICAL OR DETECTOR OPERATION.
11111117
Ro ert Shorr, NEBB Certified Professional Date
40
RoeERT D. SHORR
CERTIFICATION
3429
Exp.3131/18 j
HvrfmMe
a
ACCURATE BALANCING & COMMISSIONING, INC
1742 E Rd, Loxahatchee, FL 33470 TAB/Cx Supervisor Robert Shoff
Phone 561-351-0245 NEBB Certification #3429
Roberttabfirm.com Expires 3/31/2018
Equipment Calibration Schedule
Instrument
Serial #
Model
Application
PP
Dates of use
Calibration
Date
Evergreen DP Meter with
E2F5-
PNS-PV
FPM, CFM, DP
10/11/17 thru
5/9/17
8" & 15" Flow Hoods
1400188
10/21/17
Evergreen Hydronic
10/11/17 thru
1/26/17
Manometer
1700103
S-DP-125
H dronic Pressure
10/21/17
10/11/17 thru
5/11/17
Extech Tem /RH Meter
120605431
RH-390
Temperature & Humidity10/21/17
10/11/17 thru
5/8/17
Fluke Electrical Meter
99250029
T5-600
Voltage, Amperage
10/21/17
FPM — feet per minute
RH — Relative Humidity
R/A — Return Air
O/A — Outside Air
GPM — Gallons per minute
AHU — Air Handling Unit
TBD — To Be Determined
FCU — Fan Coil Unit
Definitions
CFM — cubic feet per minute
S/A — Supply Air
E/A — Exhaust Air
FL — Full Load
OAFM -Outside Air Flow Meter
N/A — No Design Value.on Drawings
ft — Feet Head
Project Summary
RTU — Roof Top Unit
Perform test & balance of total supply, outside air and chilled water flow for two new air
handlers on the 2°d and Yd floors.
No deficiencies noted.
Deficiencies
Table of Contents
Description Page Number
AHU Reports 1-2
Chilled Water Coil Reports 3-4
G
ACCURATE BALANCING & COMMISSIONING, INC
Air Handling Unit
PROJECT: SLC Courthouse Annex AHU Replacements
LOCATION: Ft. Pierce, FL
PROJECT A: 120115VB
SYSTEM/UNIT: AHU-02
AREA: 2nd Floor
Unit Data _.
Unit Manufacturer Trans
Unit Model Number CSAA050
Unit Serial Number K17E40082
AHU-021SF Fitter Bank
Filter Type _ 2" Pleated
Filter Quantity - Size 1 12
Filter Dimensions - Size 1 20x25
_ Tes_ tData
O/A Damper Position 40 %
Outside Air Duct Size 17.5 x 57.5 in
AHU-021SuooN Fan
VFD Speed Final 70 Hz
Motor Volts T1-T2 484 Volts
Motor Volts T2-T3 481, Volts
Motor Volts T1-T3 483 Volts
Motor Amps Ti 10.2 Amps
Motor Amps T2 10.3 Amps
Motor Amps T3 10.6 Amps
DATE: 11/2/2017
CONTACT: Robert Shorr
—_.. .. Motor Data.•.. -.. ._
AHU-021Suooly Fan
Motor Frame
254T
Motor HP
2x7.5 HP
Motor RPM
1180 RPM
Motor Rated Volts
460 Volts
Motor Phase
3
Motor Hertz
60 Hz
Motor FL Amps
11 Amps
Motor Service Factor
1.15
�.:_: •'-- -- Sheave Data _
AHU-0215uonly Fan.
Motor Sheave MFG
Direct Drive'
Test Pressures 1
Pre -Filter SP In
-0.24 in. we
Cool. Coil SP In
-0.30 in. we
Total SP Suction
-0.44 in. we
Total SP Discharge
1.62 in. we
- _ Alr Test Data
S/A Scheduled Design
17700 CFM
Total S/A Outlet Actual
17157 CFM
R/A Scheduled Design
14700 CFM
Total R/A Inlet Design
14061 CFM
Outside Air Design Max
3000 CFM
Outside Air Actual Max
3096 CFM
O/A Flow Meter
3032 CFM
OAFM K Factor
0.43
Accurate Balancing and Commissioning Page 1 of 4
G
ACCURATE.BALANCING & COMMISSIONING., INC
Air Handling Unit
PROJECT: SLC Courthouse Annex AHU Replacements
LOCATION: Ft. Pierce, FL
PROJECTM 120115VB
SYSTEM/UNIT: AHU-03
AREA: 3rd Floor
,. ..-.
.'Unit Daf_a. _
Unit Manufacturer
Trans .
Unit Model Number
CSAA050
Unit Serial Number
K17E40089
AHU-031SF Filter Bank
-
Filter Type
2" Pleated
Filter Quantity - Size 1
12
Filter Dimensions - Size 1 20x25
-
'Test Data. _ -
O/A Damper Position
25 %
Outside Air Duct Size
17.5 x 57.51n
AHU-03113uooly Fan
VFD Speed Final
60 Hz
Motor Volts T1-T2
484 Volts
Motor Volts T2-T3
480 Volts
Motor Volts T1-T3
482 Volts
Motor Amps T1
12.9 Amps
Motor Amps T2
12.5 Amps
MotorAmps T3
12.8 Amps
DATE: 11/2/2017
CONTACT: Robert Shorr
_ MotorData
AHU-031Suooly Fan
Motor Frame
256T
Motor HP
2x10 HP
Motor RPM
1180 RPM
Motor Rated Volts
460 Volts
Motor Phase
3
Motor Hertz
60 Hz
Motor FL Amps
14.3 Amps
Motor Service Factor
1.15
- 'Stieave.Data - - - _
AHU-03/3upply Fan
Motor Sheave MFG
Direct Drive
Test Pressures,ilter
SP In
-0.23 in. we
ffTot'oaCoil SP In
-0.271n. we
SP Sucton
-0.40 in. we
SP Discharge
1.44 in. we
*It Test_ Data
S/A Scheduled Design
18500 CFM
Total S/A Outlet Actual
18623 CFM
R/A Scheduled Design
15500 CFM
Total R/A Inlet Design
15658 CFM
Outside Air Design Max
3000 CFM
Outside Air Actual Max
2965 CFM
CIA Flow Meter
3020 CFM
OAFM K Factor
0.64
Accurate Balancing and Commissioning Page 2 of 4
ACCURATE BALANCING & COMMISSIONING, INC
Coil Test
PROJECT: SLC Courthouse Annex AHU Replacements
LOCATION: Ft. Pierce, FL
PROJECTM 120115VB
SYSTEM/UNIT: CHWC-2
-.' - Unit Data
Coil Location AHU-2
Coil Type Chilled Water
DATE:. 11/2/2017
CONTACT: Robert Shorr
AlrTest Data ,'
Airflow Design
17700 CFM
Airflow Actual
17157 CFM
Ent. Air DB Temp Design
78.5 Deg F
Ent. Air DB Temp Actual
76.0 Deg F
Ent. Air WB Temp Design
64.8 Deg F
Ent. Air WB Temp Actual
69.0 Deg F
Leay. Air DB Temp Design
52.0 Deg F
Leay. Air DB Temp Actual
53.8 Deg F
Leay. Air WB Temp Design
51.6 Deg F
Leay. Air WB Temp Actual
50.0 Deg F
Wate-r Test_Data
Water, Flow Design
136.4 GPM
Water Flow Actual
130.0 GPM
Coil Inlet PSI Actual
27.9 PSI
Coil Outlet PSI Actual
27.2 PSI
Press. Drop PSI Actual
1.1 It
Ent. Water Temp Design
45.0 Deg F
Ent. Water Temp Actual
42.0 Deg F
Leay. Water Temp Design
55.0 Deg F
Leay. Water Temp Actual
52.0 Deg F
Water Delta T Design
10.0 Deg F
Water Delta T Actual
10.0 Deg F
Balancing Valve Brand
TA
Balancing Valve Size
4 "
Balancing Valve Setting
7
Accurate Balancing and Commissioning Page 3 of 4
irl
ACCURATE BALANCING & COMMISSIONING, INC
Coil Test
PROJECT: SLC Courthouse Annex AHU Replacements
LOCATION: Ft. Pierce, FL
PROJECT #: 120115VB
SYSTEM/UNIT: CHWCJ
_ Unit'Data 71 x Coil Location y AHU-3
Coil Type Chilled Water
DATE: 11/2/2017
CONTACT: RobertShorr
.- Air Test Data. ._,. .. ..
Airflow Design
18500 CFM
Airflow Actual
18623 CFM
Ent. Air DB Temp Design
78.9 Deg F -
Ent. Air DB Temp Actual
77.0 Deg F
Ent. Air WB Temp Design
65.1 Deg F
Ent. Air WB Temp Actual
68.0 Deg F
Leay. Air DB Temp Design
52.0 Deg F
Leay. Air DB Temp Actual
55.4 Deg F
Leay. Air WB Temp Design
51.6 Deg F
Leay. Air WB Temp Actual
53.4 Deg F
r Water Test,bate
Water Flow Design
146.1 GPM
Water Flow Actual
135.0 GPM
Coil Inlet PSI Actual
19.6 PSI
Coil Outlet PSI Actual
19.0 PSI
Press. Drop PSI Actual
1.2 ft
Ent. Water Temp Design
45.0 Deg F
Ent. Water Temp Actual
42.0 Deg F
Leay. Water Temp Design
55.0 Deg F
Leay. Water Temp Actual
52:0 Deg F
Water Delta T Design
10.0 Deg F
Water Delta T Actual
10.0 Deg F
Balancing Valve Brand
TA
Balancing Valve Size
4"
Balancing Valve Setting
7
Accurate Balancing and Commissioning Page 4 of 4