HomeMy WebLinkAboutCOMPRESSIVE STRENGTH TEST;ETC ATC Group Services LLC 9955 N.W.116 Way Suite 1 Miami, FI.33178 TELEPHONE (305) 882.8200, FACSIMILE (305) 882-1200 Compressive Strength Test of Concrete Cylinders Client Name: Wawa Inc. Date Cast: 5/18/2018 Project Name: Wawa Store #5220 Field Mark: EM-1 ProjectlD: 3996000423 Cylinder Set ID: 24227 Project Address: Prima Vista Blvd & Floresta Drive, Port St. Lucie Technician: rr nge Permit No.: Supplier: e ` BY St. Lucie County VE. Sample Location: Building Columns sonotubes (13) AUG 2 7 2018 Remarks: FIELD DATA rcl a ut.uuy vcNu Design Strength (PSI:) 4000 Slump (In.): Mix Description: 1176610 Placement: Direct Ticket Number: 35713641 Weather: Partly Cloudy Truck Number: 4623 Concrete Temp ff): 62 Batch Time: 9.21.00 AM Air Ternp (eF): 72 Time Sampled: 10:10:00 AM Air Content: Elapsed Time (Min): 49 Cubic Yards Sampled: 515 Unit Wt: Number of Cylinders Cast: 5 TEST RESULTS Curing (Days) TestDa a Diameter (in) Area (Sq in TotalLoad (lbs-force) CompressiveStrencith (PSI) Break Type' r 7 5/25/2018 4.01 12.62 42110 3336 2 I1 �p� 28 6/15/2018 4.03 12.75 58740 4607 5 L."_1 0z' 28 6/15/2018 4.01 12.62 52800 4183 5 IS�t 28 6/16/2018 4 12.56 55060 4384 2 { o n 56 7/13/2018 0 C.7 Compressive Strength Average (PSI) of the 28 day Breaks = 4390 PASS No Other Breaks Evaluated C Type 1 Type 2 Type 3 Type 4 Type 5 Type 6 Reasonablywell- Well -formed cone on ColumnerveNcal Diagonal fracture with Side fractures at top or Similar to type 5, but formed canes on both one engvertical cracidng through both no cracking through the bottom (Occurs cylinder is pointed. ends, less than t in. cracks running through ends, no well formed ends; tap wth hammer commonly with (25 film) of cracking caps, no well-defined cones. to distinguish from type unbonded caps.) though caps. cone on other end. t. •• All dimensions and directions are approximate Checked B William Martin Project Manager.y-'��• --�' r ru O2J18 1 jil�Jij�— Aef us Engine I syn.r�giaer Florida baas6482613 As a mutual protection to our client the public and ourselves, all reports are submitted as the confidential property of clients. Autorizathen fdr publication of statements, conclusions, or extracts from our reports Is reserved pendingwdhen approval. Our reports apply only to Me strengths of the test speylmens fin no! tome in -situ strengths of Me members Indentiaed In the "Location' Irdarmatlon. , I" lent! ATC Group Services LLC 9955 N.W.116 Way Suite 1 Miami, FI.33178 Iff'Tc TELEPHONE (305) 882-8200, FACSIMILE (305) 882-1200 Compressive Strength Test of Concrete Cylinders Client Name: Wawa Inc. Date Cast: 7/9/2018 Project Name: Wawa Store #5220 Field Mark: KA-1 ProjectlD: 3996000423 Cylinder Set ID: 2�518 Project Address: Prima Vista Blvd & Floresta Drive, Port St. Lucie Technician: r,C rj Cj Permit No.: Supplier: t'C Sample Location: Building sidewalk line J (10, 15) & A (10,15) AUG 2 Zia Remarks: Set was casted by GC/Mosley & Son Dar-Mitting pepartrnent FIELD DATA cr I tide! I r Design Strength (PSI:) 3500 Slump (In.): L_� Mix Description: 1176610 Placement: Direct Ticket Number: 35711087 Weather: Partly Sunny Truck Number: 10067034 Concrete Temp (aF): Batch Time: 9:30:00 AM Air Temp (eF): Time Sampled: Air Content: Elapsed Time (Min): Cubic Yards Sampled: 20/30 Unit Wt: Number of Cylinders Cast: 5 TEST RESULTS Curing (Days) Tes Da a Diameter (in) Area (Sq in TotalLoad (lbs-force) CompressiveStrentith (PSI) Break Tvoe 7 7/16/2018 4.01 28 8/6/2018 4 28 8/6/2018 4.02 28 8/6/2018 3.99 56 9/3/2018 12.62 38820 12.56 47640 12.69 66420 12.5 49660 3075 5 3793 5 5236 5 3974 2 0 Compressive Strength Average (PSI) of the 28 day Breaks = 4330 PASS No Other Breaks Evaluated Type 1 Type 2 Type 3 Type 4 Type 5 Type 6 Reasonablywell- Well -formed cone on Columnervediczl Diagonal fracture with Side fractures at top or Similar to type 5, but forted cones on both one enc NeNral cracking through both no cracking through the actin (Occurs cylinder is pointed. ends, less than 1 in. tracks conning through ends, no wall formed ends; tap with hammer commonly with (25 mm) of narking caps, no well-defined cones. to distinguish from type unbonded raps.) though caps. cone on other end. 1. " All dimensions and directions are approximate Checked By: William Martin !If:V _ Project Manager. -U/-'�'°','�f As a mutual protection to our client, the public and ourselves, all reports are submitted as the confidential 6mpe,;ty of clients. Autodzaxon for publication of statements, conclusions, or extracts from our reports is reserved pendingwritten approval. Our reports apply only to the strengths of fir test spechmeml and not to the to -situ strengths of the members Indentified In the"Location"Information. - - �' ATC Group Services LLC 9955 N.W.116 Way Suite 1 Miami, FI.33178 ,. TELEPHONE (305) 882.8200, FACSIMILE (305) 882-1200 Compressive Strength Test of Concrete Cylinders Client Name: Wawa Inc. Date Cast: 7/9/2018 Project Name: Wawa Store #5220 Field Mark: KA-2 ProjectlD: 3996000423 Cylinder Set ID: 24519 Project Address: Prima Vista Blvd & Floresta Drive, Port St. Lucie Technician: Khaled Afif( Permit No.: Supplier: Cemex Sample Location: Building sidewalk line J (10,15) Remarks: FIELD DATA Design Strength (PSI:) 4000 Slump (In.): 5.5 Mix Description: 1176610 Placement: Direct Ticket Number: 35711968 Weather: Partly Sunny Truck Number: 10065283 Concrete Temp (OF): 88 Batch Time: 1:25:00 PM Air Temp (OF): 90 Time Sampled: 2:15:00 PM Air Content: Elapsed Time (Min): 50 Cubic Yards Sampled: 4.5/15 Unit Wt: Number of Cylinders Cast: 5 TEST RESULTS Curing (Days) TestDate Diameter (in) Area (Sq in Totall-oad (lbs-force) CompressiveStrength (PSI) Break Type 7 7/16/2018 3.99 12.5 31450 2517 5 28 8/6/2018 4.01 12.62 70080 5552 5 28 8/6/2018 4.02 12.69 70020 5520 5 28 8/6/2018 4.02 12.69 73300 5778 2 56 9/3/2018 0 Compressive Strength Average (PSI) of the 28 day Breaks = 5620 PASS No Other Breaks Evaluated —yt F[ f F. IIIr11r�}fill1I1''/'1'f1n'I1�1tj,\\III'I Type 1 Type 2 Type 3 Type 4 Type 5 Type 6 Reasonablywell- Well -formed cone an Columnerverllon Diagonal facture with Side fractures at top or Similar to type 5, but fomted cones on both one end.Verlical cracking through both no cracking through the bottom(Occurs cylinder is pointed. ends, less than 1 in. cracks running through ends. no well formed ends; tap with hammer commonly w ili (25 rum) of cracking caps, no well-defined cones. to distinguish from type unbendedcaps.) though ceps. cone on other end. 1. "All dimensions and directions are approximate Checked By: William Martin Project Manager. G As a mutual protection to our client, the public and ourselves, all reports are submitted as the confidential property of clients. Aulcfiiation for publication of statements, conclusions, or extracts from our reports Is reserved pendingwdtten approval. Our reports apply only to the strengths of the test specimens and not to I" In -situ strengths of the members Indentined In the "Locatlon"Information. I '- - ff'T ATC Group Services LLC 9955 N.W.116 Way Suite 1 Miami, FI.33178 JRk C TELEPHONE (305) 882-8200, FACSIMILE (305) 882-1200 Compressive Strength Test of Concrete Cylinders Client Name: Wawa Inc. Date Cast: 7/14/2018 Project Name: Wawa Store #5220 Field Mark: NH-1 ProjectlD: 3996000423 Cylinder Set ID: 24526 Project Address: Prima Vista Blvd & Floresta Drive, Port St. Lucie Technician: Norman Hunter Permit No.: Supplier: Centex Sample Location: East Parking South Section Remarks: W/Fiber FIELD DATA Design Strength (PSI:) 4000 Slump (In.): 5.5 Mix Description: 1564868 Placement: Direct Ticket Number: 68393 Weather: Mild Truck Number: 35824016 Concrete Temp (OF): 86 Batch Time: 6:15:00 AM Air Temp (°F): 77 Time Sampled: 7:05:00 AM Air Content: Elapsed Time (Min): 50 Cubic Yards Sampled: 10/90 Unit Wt: Number of Cylinders Cast: 5 TEST RESULTS Curing (Days) Tes Da a Diameter (in) Area (Sq in Totalt-oad (lbs-force) ComoressiveStrenoth (PSI) Break Type 7 7/21/2018 4.01 12.62 50110 3970 5 28 8/11/2018 4.01 12.62 60940 4828 5 28 8/11/2018 4.02 12.69 64950 5120 5 28 8/11/2018 4.03 12.75 61390 4815 5 56 9/10/2018 0 Compressive Strength Average (PSI) of the 28 day Breaks = 4920 PASS No Other Breaks Evaluated Type 1 Type 2 Type 3 Type 4 Type 5 Type 6 Reasonably well- Well -formed cone an Columnervertical Diagonal fracture with Side fractures at tap or Similar to type 5, but formed cones on both one eadyeoical racking through both no cracking through the bottom. (Occurs cylinder is painted. ends, less than 1 in. cracks running though ends, no well formed entls: tap with hammer commonly with (25 ram) of crdeMng caps, no well-defined cones. to distinguish from type unbondedceps.) though caps. cone on other end. 1. •• All dimensions and directions are approximate 1 :'lid Protect Manager. Checked By: William Martin Floro..L(eense#6251g_; 0/0HAIENn;lo" As a mutual protection to our client, the public and ourselves, all reports are submitted as the confidential property of cllea4. ltutodzatlon for pdblicTgon of statements, conclusions, or extracts from our reports is asserted pendingwritten approval. Our reports apply only to the strengths of the test speclmeas and not I. the Ir. sltu strengths of me members Indentili In the Zocatlon" Information. 1' ATC Group Services LLC 9955 N.W,116 Way Suite 1 Miami, FI. 33178 15k C TELEPHONE (305) 882.8200, FACSIMILE (305) 882.1200 'T Compressive Strength Test of Concrete Cylinders Client Name: Wawa Inc. Date Cast: 7/14/2018 Project Name: Wawa Store #5220 Field Mark: NH-2 ProjectlD: 3996000423 Cylinder Set ID: 24527 Project Address: Prima Vista Blvd & Floresta Drive, Port St. Lucie Technician: Norman Hunter Permit No.: Supplier: Centex Sample Location: North Parking West Section Remarks: w/Fiber FIELD DATA Design Strength (PSI:) 4000 Slump (In.): 6 Mix Description: 1564868 Placement: Direct Ticket Number: 69637 Weather: Mild Truck Number: 35824207 Concrete Temp (OF): 87 Batch Time: 7:25:00 AM Air Temp (OF): 80 Time Sampled: 8:25:00 AM Air Content: Elapsed Time (Min): 60 Cubic Yards Sampled: 60/90 Unit Wt: Number of Cylinders Cast: 5 TEST RESULTS Curing (Days) TestDa a Diameter (in) Area S in Totall-oad (lbs-force) CompressiveStrength (PSI) Break Tvoe 7 7/21/2018 4 12.56 45940 3658 5 28 8/11/2018 4.02 12.69 57470 4530 5 28 8/11/2018 3.99 12.5 57240 4580 5 28 8/11/2018 4.03 12.75 55650 4365 2 56 9/10/2018 0 Compressive Strength Average (PSI) of the 28 day Breaks = 4490 PASS No Other Breaks Evaluated Type 1 Type 2 Type 3 Type 4 Type 5 Type 6 Reasonablywell- Well4ormed cone on Columnervertical Diagonal hactum with side fratlures al top or Similar to type S. but formed cones on both one end,Verbcal cracking through both no cackng through the bottom.(Occurs cylinderis pointed. ends, less than 1 in. cracks running through ends, no well formed ends; tap with hemmer commonly with (25 mm)of=clang caps, no well-defined cones. to distinguish from type unbonded caps.) though caps. cane on other end. i. " All dimensions and directions are approximate Checked By: William Martin Project Manager. As a mutual protection to our client, the public and ourselves, all reports are submitted as the confidential propehy of c!lents. Amoriiedop for p`uhlicatlon of statements, conclusions, or extracts from our reports is reserved pendingwdtten approval. Our reports apply only to the strengths of the test specimens erd not:c the In -situ strengths of the members Indentified In the"Location"Information. A TC GIB Services LLC ,' 9955 N.W. Way Suite 1 Miami, FI.33178 - TELEPHONE (305) 882-8200, FACSIMILE (305) 882-1200 Compressive Strenath Test of Concrete Cylinders Client Name: Wawa Inc. Date Cast: 7/18/2018 Project Name: Wawa Store #5220 Field Mark: JP-1 ProjectlD: 3996000423 Cylinder Set ID: 24563 Project Address: Prima Vista Blvd & Floresta Drive, Port St. Lucie Technician: Juan Paniagua Permit No.: Supplier: Cemex Sample Location: Curbs at building islands Remarks: FIELD DATA Design Strength (PSI:) 3500 Slump (In.): 3 Mix Description: 3500 curb blend Placement: Direct Ticket Number: 35832349 Weather: Sunny Truck Number: 4589 Concrete Temp ff): 82 Batch Time: 2:49:00 PM Air Temp ff): 91 Time Sampled: 3:45:00 PM Air Content: Elapsed Time (Min): 56 Cubic Yards Sampled: 8/8 Unit Wt: Number of Cylinders Cast: 5 TEST RESULTS Curing (Days) TestDate Diameter (in) Area S in TotalLoad (lbs-force) CompressiveStrencith (PSI) Break Type 7 7/24/2018 4.02 12.69 65390 5155 5 28 8/14/2018 4.03 12.75 73020 5727 5 28 8/14/2018 3.99 12.5 75570 6047 2 28 8/14/2018 4 12.56 78010 6211 5 56 9/11/2018 0 Compressive Strength Average (PSI) of the 28. day Breaks = 6000 PASS No Other Breaks Evaluated Type 1 Type 2 Type 3 Type 4 Type 5 Type 6 Reasonably well. Well -formed cone on Columner vertical Diagonal fracture with Side fractures at lop or Similar to type 5, but formed cones on both one endYemcel clacking through both no cracking through the bottom. (Occurs cylinder Is pointed. ends, less than 1 in. cracks running through ends, no wellformed ends; tap with hammer commonlywith (25 mm) of craddng caps, no well-defined cones. to distinguish from type unbonded raps.) though raps, cone on other end. 1. " All dimensions and directions are approximate ,...........„„ VS E PA Checked By: William Martin Project Manager.�rT I �' ,�.'�/.>•�,'• �,�CENSF C¢� iy STAEOF '# eAd .Senfot Engineer , ?�F, I.IUP a�4r Florida License #-fi 519- : - /ONALENGo,0 •� - - ....wnn ": Tl' As a mutual protection to our client, the public and ourselves, all reports are submitted as the confidential property of �Hents. Autorization for publicedon of statements, conclusions, or extracts from our reports is reserved pendingwriften approval. Our reports apply only to the strengths of the test specimens and hot to'he In-situ'.6engths of the members indenfified In the "Location" information. _ % ATC Gl�'_ s., Services LLC ,9955 N.W.116 Way Suite 1 Miami, FI.33178 X. O'Tc'TELEPHONE (305) 882-8200, FACSIMILE (305) 882-1200 Compressive Strength Test of Concrete C linderS Client Name: Wawa Inc. Date Cast: 7/26/2018 Project Name: Wawa Store #5220 Field Mark: JP-1 ProjectlD: 3996000423 Cylinder Set ID: 24599 Project Address: Prima Vista Blvd & Floresta Drive, Port St. Lucie Technician: Juan Paniagua Permit No.: Supplier: Adonel Sample Location: Stamped S on G between gridlines 10 & 13 N of gridline B and store NE landscape island Remarks: FIELD DATA Design Strength (PSI:) 4000 Slump (In.): 6 Mix Description! 4k psi & Color Placement: Direct Ticket Number: 13549 Weather: Sunny Truck Number: 7014 Concrete Temp (°F): 80 Batch Time: 10:17:00 AM Air Temp ff ): 92 Time Sampled: 12:00:00 PM Air Content: Elapsed Time (Min): 103 Cubic Yards Sampled: 8/13 Unit Wt: Number of Cylinders Cast: 5 TEST RESULTS Curing (Days) TestDate Diameter (in) Area (Sq in Totall-oad (lbs-force) ComoressiveStrencith (PSII Break Type 7 9/1/2018 4.03 12.75 52100 4087 5 28 8/23/2018 4.01 12.62 62620 4961 5 28 8/23/2018 4.02 12.69 63480 5004 5 28 8/23/2018 4 12.56 63180 5030 2 56 9/20/2018 0 Compressive Strength Average (PSI) of the 28 day Breaks = 5000 PASS No Other Breaks Evaluated Type 1 Type 2 Type 3 Type 4 Type 5 Type 6 Reasonablywell- Weil -formed cone on Columnervertical Diagonal fracture with Side fractures at top or Similar to type 5, but formed cones on both one endNediral cracking through both no cracking through the bottom. (Occurs cylinder is pointed. ends, less than 1 in. cracks running through ends, no wall formed ends; tap with hammer commonly with (25 men) of cracking caps, no wall -defined cones, to distinguish from type unbonded caps.) though caps. cone on other end. 1. , All dimensions and directions are approximate rr Checked By: William Martin Project Manager. am i 9l, STATE OF Ser,.or Engineer_ .. .�H(...... " Florida License ti 62519, . ��RAL ENGnr'�k As a mutual protection to our client thepublic and ourselves, all reports are submitted as the confidential property of dents. Autombration for p0lication of statements, conclusions, or mmmcla from our reports Is resomed pendingwritten approval. Our reports apply only to the strengths of the test specimens and wi to the jm-situ strengths of the members indentified in the "Locatlon" information. n ATC Group Services LLC JO 9955 N.W.116 Way Suite 1 Miami, FI.33178 TELEPHONE (305) 882-8200, FACSIMILE (305) 882-1200 Compressive Strength Test of Concrete Cylinders Client Name: Wawa Inc. Date Cast: 3/30/2018 Project Name: Wawa Store #5220 Field Mark: EM-1 ProjectlD: 3996000423 Cylinder Set ID: 23877 Project Address: Prima Vista Blvd & Floresta Drive, Port St. Lucie Technician: Ahmed Mokhtar Permit No.: Supplier: Cemex Sample Location: Building footers: F8x22 at Al, A3 Remarks: FIELD DATA Design Strength (PSI:) 4000 Slump (In.): 5 Mix Description: 1176610 Placement: Pump Ticket Number: 35616266 Weather: Mostly Cloudy Truck Number: 4589 Concrete Temp (OF): 65 Batch Time: 9:47:00 AM Air Temp (OF): 77 Time Sampled: 10:20:00 AM Air Content: Elapsed Time (Min): 33 Cubic Yards Sampled: 100.5/115.5 Unit Wt: Number of Cylinders Cast: 5 Curing (Days) TestDate Diameter (in) Area (Sq in TotalLoad (lbs-force) ComoressiveStrenath (PSI) BreakTvoe��e �. 7 4/6/2018 4 12.56 58960 4694 5 f r 28 4/27/2018 4.01 12.62 63580 5037 5 I �— 28 4/27/2018 4.03 12.75 61870 4853 2 `- 28 4/27/2018 4.02 12.69 60050 4734 2F 56 5/25/2018 0 Compressive Strength Average (PSI) of the 28 day Breaks = 4870 PASS CD No Other Breaks Evaluated —•t -- Type 1 Type 2 Type 3 Type 4 Type 5 Type 6 Reasonably well. Well4ormed cone on Calumnervertical Diagonal fracture with Side fractures at top or Similar to type 5, but fanned cones an bog, one endNertical craddng through both no cracking through the bon...(Occurs cylinderispointed. ends, less than 1 in. cracks mnning through ends, no well formed ends; tap with hammer commonly with (25 mm)of cradling caps, no well-defined canes. to distinguish from type unbonded caps.) though raps, cone on other end. i. •' All dimensions and directions are approximate �* Checked By: William Martin Project Manager.lf�'-"" As a mutual protection to our client, the public and ourselves, all reports are submltied as the confidential property of clients. Autorizatlon for publication of statemems, conclusions, or extracts from our reports is reserved pendingwritten approval. Our reports apply only to the strengths of the test specimens and not to the In -situ strengths of the members Indengfied In the "Location" Information. NITC i ATC Group Services LLC 9955 N.W.116 Way Suite 1 Miami, FI.33178 k TELEPHONE (305) 882.8200, FACSIMILE (305) 882-1200 Compressive Strength Test of Concrete Cylinders Client Name: Wawa Inc. Date Cast: 3/30/2018 Project Name: Wawa Store #5220 Field Mark: EM-2 ProjectlD: 3996000423 Cylinder Set ID: 23878 Project Address: Prima Vista Blvd & Floresta Drive, Port St. Lucie Technician: Ahmed Mokhtar Permit No.: Supplier: Cemex Sample Location: Building footers: F6x7 By R and F8 at H9 Remarks: FIELD DATA Design Strength (PSI:) 4000 Slump (In.): 5 Mix Description: 1176610 Placement: Pump Ticket Number: 35616700 Weather: Mostly Cloudy Truck Number: 7679 Concrete Temp ff): 65 Batch Time: 11:30:00 AM Air Temp (°F): 77 Time Sampled: 12:10:00 PM Air Content: Elapsed Time (Min): 40 Cubic Yards Sampled: 63/115.5 Unit Will: Number of Cylinders Cast: 5 TEST RESULTS Curing (Days) TestDale Diameter (in) Area (Sq in Totall-oad (lbs-force) CompressiveStrenoth (PSI) Break Type 7 4/6/2018 3.99 12.5 51190 4096 5 28 4/27/2018 4.03 12.75 61320 4810 2 28 4/27/2018 4 12.56 60350 4805 5 28 4/27/2018 4.01 12.62 55880 4427 2 56 5/25/2018 0 Compressive Strength Average (PSI) of the 28 day Breaks = 4680 PASS No Other Breaks Evaluated Type 1 Type 2 Type 3 Type 4 Type 5 Type 6 Reasenablywell- Well -formed cone on Columnervedical Diagonal fracture with Side fractures at top or Similar to type 5, but formed cones on both one end,Vertical aacldng through both no cracking through the bottom. (Occurs cylinder is pointed. ends, less Nan 1 in. cracks running through ends, no well formed ends; tap with hammer commonly with (25 mn) of cracking caps, no welldenned cones. to distinguish from type unbundled caps.) through caps. cone on other end. 1. •` All dimensions and directions are approximate Checked By: William Martin Project Manager::/s'�3�%f{ i As a mutual protection to our cllen%the public and ourselves, all reports are submitted as the confidential property cf cdents. Autorlratlonm publication of statements, conclusions, or extracts from our reports Is reserved pendingwrttien approval. Our reports apply only to the strengths of the test specimens and not to the in -situ strengths of the members indentined In the "Location"Information. ATC Group Services LLC AT 9955 N.W.116 Way Suite 1 Miami, FI.33178 TELEPHONE (305) 882.8200, FACSIMILE (305) 882-1200 Nkc I Compressive Strength Test of Concrete Cylinders Client Name: Wawa Inc. Date Cast: 3/30/2018 Project Name: Wawa Store #5220 Field Mark: EM-3 ProjectlD: 3996000423 Cylinder Set ID: 23879 Project Address: Prima Vista Blvd & Floresta Drive, Port St. Lucie Technician: Emmanuel Monuma Permit No.: Supplier: Cemex Sample Location: Building footers: F8x26 at 1-114, G14 Remarks: FIELD DATA Design Strength (PSI:) 4000 Slump (In.): 5 Mix Description: 1176610 Placement: Pump Ticket Number: 55054863 Weather: Mostly Cloudy Truck Number: 5324 Concrete Temp ff): 65 Batch Time: 1:31:00 PM Air Temp ff): 77 Time Sampled: 2:05:00 PM Air Content: Elapsed Time (Min): 34 Cubic Yards Sampled: 115.5/115.5 Unit Wt: Number of Cylinders Cast: 5 TEST RESULTS 1 Curing (Days) TestDate Diameter (in) Area (Sci in Totall-oad (lbs-force) CompressiveStrength (PSI) Break Tvoe 7 4/6/2018 4.01 12.62 55200 4373 5 28 4/27/2018 4.02 12.69 64450 5080 2 28 4/27/2018 4 12.56 65540 5218 5 28 4/27/2018 4.03 12.75 69530 5454 2 56 5/25/2018 0 Compressive Strength Average (PSI) of the 28 day Breaks = 5250 PASS No Other Breaks Evaluated Type 1 Type 2 Type 3 Type 4 Reasonablywell- Well -formed cone on Columnerwulical Diagonal fracture with formed Cones on both one end,Vertical craclang through both no craclung through the ends, less than 1 in. crocks running through ends, no well formed ends; tap with hammer (25 mm) of cracking caps, no well-defined cones. to distinguish from type thoughcaps. cone on other end. 1. " All dimensions and directions are approximate Checked By: William Martin f 4'% _ Project Manager: / i"tf �, + 1l� Type 5 Side fractures at top or bottom. (Occurs commonly with unbonded caps.) Type 6 Sinular to type 5, but cylinder is painted. rlarpLicense anzolu,-nnCp•„r�- As a mutual protection to our client, the public and ourselves, all reports are submitted as the confidential property of clicrds. Autod:atlon for pabllcatlon of statements, conclusions, or extracts from our reports Is reserved pendingwdtten approval. Our reports apply only to the strengths of the test specimens and not to the In -situ etfangths of the members Indentified In the "Location" Information. " ATC Group Services LLC JIFkTC 9955 N.W.116 Way Suite 1 Miami, FI.33178 TELEPHONE (305) 882.8200, FACSIMILE (305) 882-1200 Compressive Strength Test of Concrete Cylinders Client Name: Wawa Inc. Date Cast: 4/4/2018 Project Name: Wawa Store #5220 Field Mark: EM-1 ProjectlD: 3996000423 Cylinder Set ID: 23922 Project Address: Prima Vista Blvd & Floresta Drive, Port St. Lucie Technician: Emmanuel Monuma Permit No.: Supplier: Centex Sample Location: Building footers: F6@A10, F8x26 F8x26, F4@jl4, F5@K15, F8x25 J10, 12, F8 @ 1-19, F8 @ H4 Remarks: FIELD DATA Design Strength (PSI:) 4000 Slump (In.): 5 Mix Description: 1176610 Placement: Direct Ticket Number: 35625364 Weather: Mostly Cloudy Truck Number: 8036 Concrete Temp (OF): 65 Batch Time: 1:09:00 PM Air Temp (OF): 77 Time Sampled: 2:00:00 PM Air Content: Elapsed Time (Min): 51 Cubic Yards Sampled: 9/9 Unit Wt: Number of Cylinders Cast: 5 TEST RESULTS Curing (Days) TestDate Diameter(in) Area S in Totall-oad (lbs-force) ComoressiveStrength (PSI) BreakTvoe 7 4/11/2018 4.03 12.75 45860 3597 5 28 5/2/2018 4 12.56 64550 5139 5 28 5/2/2018 4.01 12.62 65640 5200 5 28 5/2/2018 4 12.56 63180 5030 5 56 5/30/2018 0 Compressive Strength Average (PSI) of the 28 day Breaks = 5120 PASS No Other Breaks Evaluated Type 1 Type 2 Type 3 Type 4 Type 5 Type 6 Reasonably well. Well-lonned cone on Columnervertical Uagonal fracture with Side fracases at top or Similar to type 5, but fomretl cones on both one endNencal cracking lhmugh both no cracking through the bmtom.(Occurs cylinder is pointed. ends. less than l in. cracks running through ends, no well formed! ends: lap with hammer commonly with (25 mac) of cracking caps, no well-defined cones. to distinguish faces type unbonded caps.) though caps. cone on other end. 1. "All dimensions and directions are approximate Checked By: William Martin Protect Manager: Ff' i Asamutual protectiontoourclient,thepublicandourselves, all reportsaresubmittedas theconfidentialof property eclmans'aAutorlugonforpubllcangt of statements. conclusions, or [nth eta frees our reports Is reserved Dentlingwatten approval. Our reports apply only to the strengths of the test spedmans aril rio: to'Ne Irvsltu strengths of the members Indenggetl In the 'Location' Information. k ATC Group Services LLC jT 9955 N.W.116 Way Suite 1 Miami, FI.33178 A, C TELEPHONE (305) 882-8200, FACSIMILE (305) 882-1200 Compressive Strength Test of Concrete Cylinders Client Name: Wawa Inc. Date Cast: 7/10/2018 Project Name: Wawa Store #5309 Field Mark: AA-1 ProjectlD: 3996000428 Cylinder Set ID: 24499 Project Address: Hiatus Road & Pembroke Road, Pembroke Pines, Technician: t ��Qyl Permit No.: Supplier: ta1e� j Sample Location: Building Slab B-J x 10-15 Remarks: Design Strength (PSI:) 4000 Mix Description: CAJ95R30 Ticket Number: 686611 Truck Number: 15035 Batch Time: 11:22:00 AM Time Sampled: 12:22:00 PM Elapsed Time (Min): 60 Unit Wt: Curing (Days) TestDa e 7 7/17/2018 28 8/7/2018 28 8/7/2018 28 817/2018 56 9/4/2018 Slump (In.): L Placement: Weather: Concrete Temp ('F): Air Temp ff): Air Content: Cubic Yards Sampled: Number of Cylinders Cast: AUG 2 7 2018 tong Depa tYtefl? n 4, Cr i Pump Partly Cloudy 88 93 10/110 5 Diameter (in) Area (So in Totall-oad (lbs-force) CompressiveStrength (PSI) Break T+vppri��e��--- 4.02 12.69 48030 3786 61L�1 3.99 12.5 58410 4674 5 0 4 12.56 58830 4684 5 0 3.99 12.5 58200 4657 2 0 c7 C Compressive Strength Average (PSI) of the 28 day Breaks = 4670 PASS No Other Breaks Evaluated Type 1 Type 2 Type 3 Type 4 Reasonably well- Well -formed cone on Columnervedical Diagonal fracture Win fanned cones an both one endlNertical craclang through win no cracking through the ends, less than 7 In. sacks running through ends, no welt loaned ends; tap with hammer (25 con) of cracking caps, no well-defined canes, to distinguish from type though caps, cone on other end. 1. All dimensions and directions are approximate f _ Checked By: William Martin Project Manager: U E Type 5 Side fractures at top or bottom (Occurs commonly with unbonded raps.) Type 6 Similar to type 5, but cylinder is painted. As a mutual protection to our client, the public and ourselves, all reports are submitted as the confidential property of clldm.. Analfta!ion fa publlcatlon of statements, conclusions, or edracts from our reports is reserved pendingwdtten approval. Our reports apply only to the strengths of the test specimens and not to the Insau sirmlyths of the members indentifned In the 'Location' Information. I, 0 1, ' ff-T ATC Group Services LLlIC JA 9955 N.W.116 Way Suite 1 Miami, FI.33178 k. C TELEPHONE (305) 882-8200, FACSIMILE (305) 882-1200 Compressive Strength Test of Concrete Cylinders Client Name: Wawa Inc. Date Cast: 5/1512018 Project Name: Wawa Store #5220 Field Mark: EM-2 ProjectlD: 3996000423 Cylinder Set ID: 24194 Project Address: Prima Vista Blvd & Floresta Drive, Port St. Lucie Technician: r as r it ^ ` Permit No.: Supplier: F�'ir- x Sample Location: Building Slab:(15, 12.5), (K,F) I AUG 2 7 2918 Remarks: Slump was measured at the pump Design Strength (PSI:) 4000 Slump (In.): — o Mix Description: 1603448 Placement: Pump Ticket Number: 35706556 Weather: Mostly Cloudy Truck Number: 4623 Concrete Temp (OF): 65 Batch Time: 8:03:00 AM Air Temp (OF): 72 Time Sampled: 8:42:00 AM Air Content: Elapsed Time (Min): 39 Cubic Yards Sampled: 60/115 Unit-Wt: Number of Cylinders Cast: 5 TEST RESULTS Curing (Days) TestDate Diameter (in) Area (So in Totall-oad (lbs-force) ComoressiveStrencith (PSI) BreakT 1 7 5/22/2018 4.01 12.62 53980 4276 5 28 6/12/2018 4.03 12.75 70350 5518 2 i a 28 6/12/2018 3.99 12.5 68970 5519 5 28 6/12/2018 4.02 12.69 69200 5455 5 56 7/10/2018 0 N C'J Compressive Strength Average (PSI) of the 28 day Breaks = 5500 PASS i No Other Breaks Evaluated I� Type 1 Type 2 Type 3 Type 4 Reasonably well. Wall -formed cone on Columnervertical Diagonal fracture with formed woos on both me endNeNcal craddng thmugh both no crac mg through the ends, less than 1 in. cracks conning thmugh ends, no well formed entls: tap with hammer (25 no of crdclting ups, no we!I-deened cones. to distinguish from type though ups. cone an other and. 1. •• All dimensions and directions are approximate Checked By: William Martin Project Manager. D E [T Type 5 Type 6 Side fracums at top m Similar to type 5, but bottom(Occurs cylinder is pointed. commonly win unbonded raps.) As a mutual protection to ourclleny the public and ourselves, all reports are Submitted as the confidential prope,ty of talents. Autnr!zaIlon forpub!Icatlon of statements, conclusions, or extracts from our reports is reserved pendingwdtten approval. Our reports apply only to the strengths of the test specimens Ind not to the in-shu strengths of the members Indentined In the "Loudon" Information. - 1 ^ ATC Group Services LLC 9955 N.W.116 Way Suite 1 Miami, FI.33178 TELEPHONE (305) 882-8200, FACSIMILE (305) 882-1200 N AkT' Compressive Strength Test of Concrete Cylinders Client Name: Wawa Inc. Date Cast: 5/15/2018 Project Name: Wawa Store #5220 Field Mark: EM-3 ProjectlD: 3996000423 Cylinder Set ID: 24195 Project Address: Prima Vista Blvd & Floresta Drive, Port St. Lucie Technician: Emmanuel Monuma Permit No.: Supplier: Cemex Sample Location: Building Slab:(15, 12.5), (K,F) Remarks: FIELD DATA Design Strength (PSI:) 4000 Slump (In.): 7.5 Mix Description: 1603448 Placement: Pump Ticket Number: 35707144 Weather: Mostly Cloudy Truck Number: 4924 Concrete Temp (aF): 65 Batch Time: 10:16:00 AM Air Temp (°F): 72 Time Sampled: 10:48:00 AM Air Content: Elapsed Time (Min): 32 Cubic Yards Sampled: 110/115 Unit Wt: Number of Cylinders Cast: 5 TEST RESULTS Curing (Days) TestDate Diameter (in) Area (Sq in Totall-cad (lbs-force) CompressiveStrength (Pall Break Type 7 5/22/2018 4.02 12.69 47930 3778 5 28 6/12/2018 4.01 12.62 70750 5605 5 28 6/12/2018 4.03 12.75 69620 5461 5 28 6/12/2018 3.99 12.5 70410 5634 2 56 7/10/2018 0 Compressive Strength Average (PSI) of the 28 day Breaks = 5570 PASS No Other Breaks Evaluated —H [. '.,. RM Type 1 Type 2 Type 3 Type 4 Reasonably well- Well -formed cone on Columnervertical Diagonal fracture with fomcetl cones on both one end,Vedical uscidng through both no cracking through the ends, less than 1 in. chocks formed through ends, no well fored ends; tap with hummer rm (25 n) of cracking caps, no well-defined wnes. to distinguish from type though caps. cone on other end. 1. •' All dimensions and directions are approximate r .h�i Y.•n. Checked By: William Martin Project Manager., DU R Type 5 Type 6 Side fractures at top or Similar to type 5, but botiom.(Occum cylinder is pointed. commonly with unbundled caps.) As a mutual protection to our client, the public and ourselves, all reports are submitted as the confidential propertys of.;ltmp, Autodmtlon for publication of statements, conclusions, or extracts from our reports Is reserved pendingwdtien approval. Our reports apply only to the strengths of the test specimens and not to the insittt strengths of the members Indentlfied In the "Location"Information. - -. -TC ATC Group Services LLC 9955 N.W.116 Way Suite 1 Miami, FI.33178 iJA ' TELEPHONE (305) 882-8200, FACSIMILE (305) 882-1200 Compressive Strength Test of Concrete Cylinders Client Name: Wawa Inc. Date Cast: 5/16/2018 Project Name: Wawa Store #5220 Field Mark: EM-1 ProjectlD: 3996000423 Cylinder Set ID: 24196 Project Address: Prima Vista Blvd & Floresta Drive, Port St. Lucie Technician: Emmanuel Monuma Permit No.: Supplier: Cemex Sample Location: Building column line 15G & H.1 Electric pannel and dumpster footing Remarks: FIELD DATA Design Strength (PSI:) 4000 Slump (In.): 5 Mix Description: 1176610 Placement: Direct Ticket Number: 35710001 Weather: Partly Cloudy Truck Number: 4589 Concrete Temp ff): 65 Batch Time: 12:30:00 PM Air Temp (eF): 72 Time Sampled: 1:40:00 PM Air Content: Elapsed Time (Min): 70 Cubic Yards Sampled: 10.5/10.5 Unit Wt: Number of Cylinders Cast: 5 Curing (Days) Tes Date Diameter (in) Area (Sq in Totall-oad (lbs-force) CompressiveStrenoth (PSII BreakTvoe 7 5/23/2018 4.02 12.69 44930 3542 2 28 6/13/2018 4.03 12.75 61160 4797 5 28 6/13/2018 4 12.56 60400 4809 5 28 6/13/2018 4.01 12.62 62250 4932 5 56 7/11/2018 0 Compressive Strength Average (PSI) of the 28 day Breaks = 4850 PASS No Other Breaks Evaluated Type 1 Type 2 Type 3 Type 4 Reasonably well- Well -formed cone on Columnervertical Diagonal fracture with formed cones on both one end.Vertical cmciang through both no cracking through the ends, less than 1 in. cracks running through ends, no well formed ends: tap with hammer (25 mil) of cracidng caps, no well-0efined wiles. to distinguish from type though caps. cone on other end. 1. •' All dimensions and directions are approximate Checked By: William Martin Prolect Manager. -^ ✓ "'��r�A -� PU E Type 5 Type 6 Side fractures at top or Similar to type 5, but bottom. (Occurs cylinderis pointed. commonly with unbonded caps.) Fronds t.i zlk' .1162516. b ads/0NAL W ,�ao!'�r As a mutual protectton to our client, the public and ourselves, all reports are submitted as the confidential property. ofcllents: Autcdaation to: publication of statements, conclusions, or motracts fresh our reports is reserved pendingwritten approval. Our reports apply only to the strengths of the test spccim<ns and not to the In-sltu strengths of the members Indernified In the "Location" Information. - - - r