M L Engineering, Inc. Proje:. :o. 17-139A Report No.1
Consulting Engineers cc: Gene Ross Elliott Merrill
2030 37° Avenue /+ p1n1�r� Chris Arias Daniello Const.
Vero Beach, Florida 32960 SCANNED Carl Peterson SLC Bldg Dept
Phone (772) 569-1257 BY File
Fax neeri gine.c 41 St. Lucie Countv
mlengineeringinc.com
BRYN MAWR CONDOMINIUMS - BLDG. A
5061 NORTH HIGHWAY AIA, FT. PIERCE, FLORIDA
THRESHOLD INSPECTION REPORT
SLC BUILDING PERMIT NUMBER: 1706-0046
PROJECT NAME: Bryn Mawr — Bldg. A DATE: July 12, 2017
CLIENT: Elliott Merrill Community Mgt. LOCATION: Ft. Pierce, Florida
CONTRACTOR: Daniello & Assoc. PROJECT MGR: Chris Arias
INSPECTED BY: Mike Luc WEATHER: Sunny
WORK INSPECTED:
In progress concrete repairs at walkways.
OBSERVATIONS:
Unit 402
Demo of all loose concrete is complete for two (2) concrete surface spalls. The existing
reinforcing has minor surface corrosion and will require power tool cleaning and priming.
Estimated total area of repair is five (5) square feet.
Unit 403
The delaminated stucco on the ceiling has been removed. We discovered there are no spalls in
the concrete. The area shall be patched with new stucco and feathered to match the surrounding
areas.
Estimated total area of stucco repair is three (3) square feet.
Units 601, 603 & 604
Demo is complete for five (5) surface spalls and corroded reinforcing exposed. Further
demolition at Unit 603 is required to expose the corrosion and clean the bars.
The other spalled areas' reinforcing have minor surface corrosion and will require power tool
cleaning and priming.
Estimated total area of repairs is ten (10) square feet.
Unit 804
Demo is complete for five (5) surface spalls and corroded reinforcing exposed. The existing
reinforcing top bars have minimal concrete coverage and may be the reason for the spalling. We
_recommend tying the top bar to the bottom bar to provide more clearance from the top of slab.
Estimated total area of repairs is seven and one-half (7.5) square feet.
JUL 1 9 i1ECD
M L Engineering, Inc.
Consulting Engineers
2030 371h Avenue
Vero Beach, Florida 32960
Phone (772) 569-1257
Fax (772)569-4041
mlengineeringine.com
Proje.:. � o. 17-139A Report No. 1
cc: Gene Ross Elliott Merrill
Chris Arias Daniello Const.
Carl Peterson SLC Bldg Dept
File
Re -inspection will be required after all reinforcing have cleaned and coated.
Pic 3 Unit 403 ceiling
2
JUL 1 9 RECD
,;r \
M L Engineering, Inc. Project No. 7-139A Report No. 3
Consulting Engineers
cc: Gene Ross Elliott Merrill
2030 37' Avenue
Chris Arias Daniello Const.
Vero Beach, Florida 32960
Carl Peterson SLC Bldg Dept
Phone (772) 569-1257
File
Fax (772)569-4041
mlengineeringine.com
BRYN MAWR CONDOMINIUMS - BLDG. A
5061 NORTH HIGHWAY AIA, FT. PIERCE, FLORIDA
THRESHOLD INSPECTION REPORT
SLC BUILDING PERMIT NUMBER: 1706-0046
PROJECT NAME:
Bryn Mawr — Bldg. A DATE: July 26, 2017
CLIENT:
Elliott Merrill Community Mgt. LOCATION: Ft. Pierce, Florida
CONTRACTOR:
Daniello & Assoc. PROJECT MGR: Chris Arias
INSPECTED BY:
Mike Luc WEATHER: Sunny
WORK INSPECTED: In progress concrete repairs at balconies.
OBSERVATIONS:
Unit 301— West balcony
Demo of all loose concrete is complete. The reinforcing bars have surface corrosion and will
require power tool cleaning and priming. The top bars were found to have less than 1" of
concrete coverage.
Estimated total area of repair is One (1) square foot.
Unit 302 — East Balcony
Surface spall near the sliding glass door has been chipped. Bars have surface corrosion and
require cleaning and priming.
Estimated total area of repair is three (3) square feet.
Unit 306 — East Balconv
Surface spall near the sliding glass door has been chipped. Bars have surface corrosion and
require cleaning and priming.
Estimated total area of repair is four (4) square feet.
It-2. Lu6,`P:E. T
i'QQ FL C) •�c
:e •'..
M L Engineering, Inc.
Consulting Engineers
2030 37i° Avenue
Vero Beach, Florida 32960
Phone (772) 569-1257
Fax (772) 5694041
mlengineeringinc.com
Pic 1 Unit 302 surface spall
Project No. 17-139A Report No. 3
cc: Gene Ross Elliott Merrill
Chris Arias Daniello Const.
Carl Peterson SLC Bldg Dept
File
2
M L Engineering, Inc.
Consulting Engineers
2030 37' Avenue
Vero Beach, Florida 32960
Phone (772) 569-1257
Fax (772)569-4041
ralengineeringinc.com
Project No..t7-139A Report No. 3
cc: Gene Ross Elliott Merrill
Chris Arias Daniello Const.
Carl Peterson SLC Bldg Dept
File
BRYN MAWR CONDOMINIUMS - BLDG. A
5061 NORTH HIGHWAY AIA, FT. PIERCE, FLORIDA
THRESHOLD INSPECTION REPORT
SLC BUILDING PERMIT NUMBER: 1706-0046
PROJECT NAME: Bryn Mawr — Bldg. A
CLIENT: Elliott Merrill Community Mgt.
CONTRACTOR: Daniello & Assoc.
INSPECTED BY: Mike Lue
DATE: July 26, 2017
LOCATION: Ft. Pierce, Florida
PROJECT MGR: Chris Arias
WEATHER: Sunny
WORK INSPECTED: In progress concrete repairs at balconies.
OBSERVATIONS:
Unit 301— West balconv
Demo of all loose concrete is complete. The reinforcing bars have surface corrosion and will
require power tool cleaning and priming. The top bars were found to have less than 1" of
concrete coverage.
Estimated total area of repair is One (1) square foot.
Unit 302 —East Balconv
Surface spall near the sliding glass door has been chipped. Bars have surface corrosion and
require cleaning and priming.
Estimated total area of repair is three (3) square feet.
Unit 306 — East Balconv
Surface spall near the sliding glass door has been chipped. Bars have surface corrosion and
require cleaning and priming.
Estimated total area of repair is four (4) square feet.
F e
r
M. Lurq
. t •r: �
�G
M L Engineering, Inc.
Consulting Engineers
2030 37' Avenue
Vero Beach, Florida 32960
Phone (772) 569-1257
Fax (772)569-4041
mlengineeringinc.com
Pic 1 Unit 302 surface spall
Project No.17-139A Report No. 3
cc: Gene Ross Elliott Merrill
Chris Arias Daniello Const.
Carl Peterson SLC Bldg Dept
File
Pic 2 Unit 306 surface spall
v M L Engineering, Inc.
Consulting Engineers
2030 371° Avenue
Vero Beach, Florida 32960
Phone (772) 569-1257
Fax (772)569-4041
mlengineeringinc.com
Project No. 17-139A Report No. 2
cc: Gene Ross Elliott Merrill
Chris Arias Daniello Const.
Carl Peterson SLC Bldg Dept
File
BRYN MAWR CONDOMINIUMS - BLDG. A
5061 NORTH HIGHWAY AIA, FT. PIERCE, FLORIDA
THRESHOLD INSPECTION REPORT
SLC BUILDING PERMIT NUMBER: 1706-0046
PROJECT NAME: Bryn Mawr — Bldg. A
CLIENT: Elliott Merrill Community Mgt.
CONTRACTOR: Daniello & Assoc.,
INSPECTED BY: Mike Lue
DATE: July 18, 2017
LOCATION: Ft. Pierce, Florida
PROJECT MGR: Chris Arias
WEATHER: Sunny
WORK INSPECTED: In progress concrete repairs at walkways.
X 1IR MR AWN )1I8)z69I
Unit 301/302
Demo of all loose concrete is complete for two (2) concrete surface spalls. The existing
reinforcing has minor surface corrosion and will require power tool cleaning and priming.
Estimated total area of repair is five (5) square feet.
Column snall A 3rd floor walkway stair door
The loose concrete has been removed and reinforcing exposed. The bars are in serviceable
condition and will require cleaning and priming. The metal doorjamb has some surface
corrosion and shall be cleaned as well. The door frame and opening shall be sealed after repairs
ar
Pic 1 Unit 3 01/3 02 walkway
.•• to
�1(HOlY y ••,
Pic 2 Column spall @ stair door
w M L Engineering, Inc. Project No. 17-139A Report No. 2
Consulting Engineers cc: Gene Ross Elliott Merrill
2030 37 ° Avenue Chris Arias Daniello Const.
Vero Beach, Florida 32960 Cut Peterson SLC Bldg Dept
Phone (772) 569-1257 File
Fax (772) 569-4041
mlengineeringinacom
BRYN MAWR CONDOMINIUMS - BLDG. A
5061 NORTH HIGHWAY AIA, FT. PIERCE, FLORIDA
THRESHOLD INSPECTION REPORT
SLC BUILDING PERMIT NUMBER: 1706-0046
PROJECT NAME: Bryn Mawr — Bldg. A DATE: July 18, 2017
CLIENT: Elliott Merrill Community Mgt. LOCATION: Ft. Pierce, Florida
CONTRACTOR: Daniello & Assoc. PROJECT MGR: Chris Arias
INSPECTED BY: Mike Lue WEATHER: Sunny
WORK INSPECTED: In progress concrete repairs at walkways.
OBSERVATIONS:
Unit 3 01/3 02
Demo of all loose concrete is complete for two (2) concrete surface spalls. The existing
reinforcing has minor surface corrosion and will require power tool cleaning and priming.
Estimated total area of repair is five (5) square feet.
Column spall P. 3`d floor walkway stair door
The loose concrete has been removed and reinforcing exposed. The bars are in serviceable
condition and will require cleaning and priming. The metal doorjamb has some surface
corrosion and shall be cleaned as well. The door frame and opening shall be sealed after repairs
rit
Pic 1 Unit 301/302 walkway
Pic 2 Column spall @ stair door
M L Engineering, Inc.
Consulting Engineers
2030 371h Avenue
Vero Beach, Florida 32960
Phone (772) 569-1257
Fax (772) 569-4041
mlengineeringinc.com
Project No. 17-139A Report No. 3
cc: Gene Ross Elliott Merrill
Chris Arias Daniello Const.
Carl Peterson SLC Bldg Dept
File
BRYN MAWR CONDOMINIUMS - BLDG. A
5061 NORTH HIGHWAY AIA, FT. PIERCE, FLORIDA
THRESHOLD INSPECTION REPORT
SLC BUILDING PERMIT NUMBER: 1706-0046
PROJECT NAME: Bryn Mawr — Bldg. A
CLIENT: Elliott Merrill Community Mgt.
CONTRACTOR: Daniello & Assoc.
INSPECTED BY: Mike Lue
DATE: July 26, 2017
LOCATION: Ft. Pierce, Florida
PROJECT MGR: Chris Arias
WEATHER: Sunny
WORK INSPECTED: In progress concrete repairs at balconies. .
OBSERVATIONS:
Unit 301— West balcony
Demo of all loose concrete is complete. The reinforcing bars have surface corrosion and will
require power tool cleaning and priming. The top bars were found to have less than I" of
concrete coverage.
Estimated total area of repair is One (1) square foot.
Unit 302 — East Balcony
Surface spall near the sliding glass door has been chipped. Bars have surface corrosion and
require cleaning and priming.
Estimated total area of repair is three (3) square feet.
Unit 306 — East Balcony
Surface spall near the sliding glass door has been chipped. Bars have surface corrosion and
require cleaning and priming.
Estimated total area of repair is four (4) square feet.
Y ••
G F
aSy2�..�a
F�.C) fie
SSIOtSP; •``
�nann`�
[ECDIF0VM
OCT - 9 RECD 10
M L Engineering, Inc.
Consulting Engineers
2030 371° Avenue
Vero Beach, Florida 32960
Phone(772) 569-1257
Fax (772)569-4041
mlengineeringinc.com
Project No. 17-139A Report No. 3
cc: Gene Ross Elliott Merrill
Chris Arias Daniello Const.
Carl Peterson SLC Bldg Dept
File
Pic 2 Unit 306 surface spall
OCT - 9 FED
2
M L Engineering, Inc. Project No. 17-139A Report No. 2
Consulting Engineers
cc: Gene Ross Elliott Merrill
2030 371° Avenue
Chris Arias Daniello Coast
Vero Beach, Florida 32960
Carl Peterson SLC Bldg Dept
Phone (772) 569-1257
File
Fax (772) 569-4041
mlengineeringinc.com
BRYN MAWR CONDOMINIUMS - BLDG. A
5061 NORTH HIGHWAY AIA, FT. PIERCE, FLORIDA
THRESHOLD INSPECTION REPORT
SLC BUILDING PERMIT NUMBER: 1706-0046
PROJECT NAME: Bryn Mawr — Bldg. A
CLIENT: Elliott Merrill Community Mgt.
CONTRACTOR: Daniello & Assoc.
INSPECTED BY: Mike Lue
DATE: July 18, 2017
LOCATION: Ft. Pierce, Florida
PROJECT MGR: Chris Arias
WEATHER: Sunny
WORK INSPECTED: In progress concrete repairs at walkways.
OBSERVATIONS:
Unit 301/302
Demo of all loose concrete is complete for two (2) concrete surface spalls. The existing
reinforcing has minor surface corrosion and will require power tool.cleaning and printing.
Estimated total area of repair is five (5) square feet.
Column sDall (a, 3`d floor walkway stair door
The loose concrete has been removed and reinforcing exposed. The bars are in serviceable
condition and will require cleaning and priming. The metal doorjamb has some surface
corrosion and shall be cleaned as well. The door frame and opening shall be sealed after repairs
Fri
Pic 1 Unit 301/302 walkway
F
ia*2.Lu$ E.
.
:,�A,po
Pic 2 Column mall @ stair door
[ECEO E
OCT — 9 REcl)
M L Engineering, Inc. Projr e .do. 17-139A Report No. 1
Consulting Engineers
cc: Gene Ross Elliott Merrill
2030 37a Avenue
Chris Arias Daniello Const.
Vero Beach, Florida 32960
Carl Peterson SLC Bldg Dept
Phone (772) 569-1257
File
Fax (772) 5694041
mlengineeringine.com
BRYN MAWR CONDOMINIUMS - BLDG. A
5061 NORTH HIGHWAY AIA, FT. PIERCE, FLORIDA
THRESHOLD INSPECTION REPORT
SLC BUILDING PERMIT NUMBER: 1706-0046
PROJECT NAME:
Bryn Mawr — Bldg. A DATE: July 12, 2017
CLIENT:
Elliott Merrill Community Mgt. LOCATION: Ft. Pierce, Florida
CONTRACTOR:
Daniello & Assoc. PROJECT MGR: Chris Arias
INSPECTED BY:
Mike Lue WEATHER: Sunny
WORK INSPECTED:
In progress concrete repairs at walkways
OBSERVATIONS:
Unit 402
Demo of all loose concrete is complete for two (2) concrete surface spalls. The existing
reinforcing has minor surface corrosion and will require power tool cleaning and priming.
Estimated total area of repair is five (5) square feet.
Unit 403
The delaminated stucco on the ceiling has been removed. We discovered there are no spalls in
the concrete. The area shall be patched with new stucco and feathered to match the surrounding
areas.
Estimated total area of stucco repair is three (3) square feet.
Units 601. 603 & 604
Demo is complete for five (5) surface spalls and corroded reinforcing exposed. Further
demolition at Unit 603 is required to expose the corrosion and clean the bars.
The other spalled areas' reinforcing have minor surface corrosion and will require power tool
cleaning and priming.
Estimated total area of repairs is ten (10) square feet.
Unit 804
Demo is complete for five (5) surface spalls and corroded reinforcing exposed. The existing
reinforcing top bars have minimal concrete coverage and may be the reason for the spalling. We
recommend tying the top bar to the bottom bar to provide more clearance from the top of slab.
Estimated total area -of repairs_ is. seven -and -one-half (7.5) square feet.
OCT - 9 RFn
r
M L Engineering, Inc.
Consulting Engineers
2030 37i° Avenue
Vero Beach, Florida 32960
Phone (772) 569-1257
Fax (772) 569-4041
nalengineeringinc.corn
Project No.17-139A Report No. 1
cc: Gene Ross Elliott Merrill
Chris Arias Daniello Const.
Carl Peterson SLC Bldg Dept
File
Re -inspection will be required after all reinforcing have cleaned and coated.
Pic 3 Unit 403 ceiling
2
Pic 2 Unit 603 Further demo @ corroded bar
�ECEWE
OCT - 9 RECD
M L Engineering, Inc. Project No. 17-139A Report No. 2
Consulting Engineers
cc: Gene Ross Elliott Merrill
2030 37i6 Avenue
Chris Arias Daniello Const.
Vero Beach, Florida 32960
Carl Peterson SLC Bldg Dept
Phone (772) 569-1257
File
Fax (772)569-4041
mlengineeringine.com
BRYN MAWR CONDOMINIUMS - BLDG. A
5061 NORTH HIGHWAY AIA, FT. PIERCE, FLORIDA
THRESHOLD INSPECTION REPORT
SLC BUILDING PERMIT NUMBER: 1706-0046
PROJECT NAME: Bryn Mawr —Bldg.A
CLIENT: Elliott Merrill Community Mgt.
CONTRACTOR: Daniello & Assoc.
INSPECTED BY: Mike Lue
DATE: July 18, 2017
LOCATION: Ft. Pierce, Florida
PROJECT MGR: Chris Arias
WEATHER: Sunny
WORK INSPECTED: In progress concrete repairs at walkways.
OBSERVATIONS:
Unit 301/302
Demo of all loose concrete is complete for two (2) concrete surface spalls. The existing
reinforcing has minor surface corrosion and will require power tool cleaning and priming.
Estimated total area of repair is five (5) square feet.
Column spall@ 3`d floor walkwav stair door
The loose concrete has been removed and reinforcing exposed. The bars are in serviceable
condition and will require cleaning and priming. The metal doorjamb has some surface
corrosion and shall be cleaned as well. The door frame and opening shall be sealed after repairs
are complete.
Pic 1 Unit 3 01/3 02 walkway
Pic 2 Column spall @ stair door
FOC7::]o
1
M L Engineering, Inc. Project No. 17-139A Report No. 3
Consulting Engineers
cc: Gene Ross Elliott Merrill
2030 37" Avenue
Chris Arias Danielle, Const.
Vero Beach, Florida 32960
Carl Peterson SLC Bldg Dept
Phone (772) 569-1257
File
Fax (772)569-4041
mlengineeringinc.com
BRYN MAWR CONDOMINIUMS - BLDG. A
5061 NORTH HIGHWAY AIA, FT. PIERCE, FLORIDA
THRESHOLD INSPECTION REPORT
SLC BUILDING PERMIT NUMBER: 1706-0046
PROJECT NAME: Bryn Mawr —Bldg. A DATE: July 26, 2017
CLIENT: Elliott Merrill Community Mgt. LOCATION: Ft. Pierce, Florida
CONTRACTOR: Daniello & Assoc. PROJECT MGR: Chris Arias
INSPECTED BY: Mike Luc WEATHER: Sunny
WORK INSPECTED: In progress concrete repairs at balconies.
OBSERVATIONS:
Unit 301 —West balcony
Demo of all loose concrete is complete. The reinforcing bars have surface corrosion and will
require power tool cleaning and priming. The top bars were found to have less than 1" of
concrete coverage.
Estimated total area of repair is One (1) square foot.
Unit 302 — East Balcony
Surface spall near the sliding glass door has been chipped. Bars have surface corrosion and
require cleaning and priming.
Estimated total area of repair is three (3) square feet.
Unit 306 — East Balcony
Surface spall near the sliding glass door has been chipped. Bars have surface corrosion and
require cleaning and priming.
Estimated total area of repair is four (4) square feet.
tc)'P' S•CG�
F•.
rvG , I
OCT 2 3 AECD
'SSIOt`1P;<
M L Engineering, Inc.
Consulting Engineers
2030 37' Avenue
Vero Beach, Florida 32960
Phone (772) 569-1257
Fax (772) 569-4041
mlengineeringine.com
Pic I Unit 302 surface spall
Project No. 17-139A Report No. 3
cc: Gene Ross Elliott Merrill
Chris Arias Daniello Const.
Carl Peterson SLC Bldg Dept
File
2
M L Engineering, Inc.
Consulting Engineers
2030 37' Avenue
Vero Beach, Florida 32960
Phone (772)569-1257
Fax (772)569-4041
mlengineeringinc.com
Project No. 17-139A Report No. 1
cc: Genc Ross Elliott Merrill
Chris Arias Daniello Const.
Carl Peterson SLC Bldg Dept
File
BRYN MAWR CONDOMINIUMS - BLDG. A
5061 NORTH HIGHWAY AIA, FT. PIERCE, FLORIDA
THRESHOLD INSPECTION REPORT
SLC BUILDING PERMIT NUMBER: 1706-0046
PROJECT NAME: Bryn Mawr —
CLIENT: Elliott Merrill Community Mgt.
CONTRACTOR: Daniello & Assoc.
INSPECTED BY: Mike Lue
WORK INSPECTED:
In progress concrete repairs at walkways.
OBSERVATIONS:
DATE: July 12, 2017
LOCATION: Ft. Pierce, Florida
PROJECT MGR: Chris Arias
WEATHER: Sunny
Unit 402
Demo of all loose concrete is complete for two (2) concrete surface spalls. The existing
reinforcing has minor surface corrosion and will require power tool cleaning and priming.
Estimated total area of repair is five (5) square feet.
Unit 403
The delaminated stucco on the ceiling has been removed. We discovered there are no spalls in
the concrete. The area shall be patched with new stucco and feathered to match the surrounding
areas.
Estimated total area of stucco repair is three (3) square feet.
Units 601, 603 & 604
Demo is complete for five (5) surface spalls and corroded reinforcing exposed. Further
demolition at Unit 603 is required to expose the corrosion and clean the bars.
The other spalled areas' reinforcing have minor surface corrosion and will require power tool
cleaning and priming.
Estimated total area of repairs is ten (10) square feet.
Unit 804
Demo is complete for five (5) surface spalls and corroded reinforcing exposed. The existing
reinforcing top bars have minimal concrete coverage and may be the reason for the spalling. We
recommend tying the top bar to the bottom bar to provide more clearance from the top of slab.
Estimated total area of repairs is seven and one-half (7.5) square feet.
�EQ[EOVc
OCT 2 3 AEC'D
M L Engineering, Inc.
Consulting Engineers
2030 37' Avenue
Vero Beach, Florida 32960
Phone (772) 569-1257
Fax (772)5694041
mlengineeringinc.com
Project No. 17-139A Report No. 1
cc: Gene Ross Elliott Merrill
Chris Arias Daniello Const.
Carl Peterson SLC Bldg Dept
File
Re -inspection will be required after all reinforcing have cleaned and coated.
Pic 1 Unit 603 walkway
Pic 3 Unit 403 ceiling
Pic 2 Unit 603 Further demo @ corroded bar
M L Engineering, Inc. Project No. 17-139A Report No. 4
Consulting Engineers cc: Gene Ross Elliott Merrill
2030 37' Avenue Chris Arias Daniello Const.
Vero Beach, Florida 32960 Carl Peterson SLC Bldg Dept
Phone (772) 569-1257 File
Fax (772) 5694041
mlengineeringinc.com
BRYN MAWR CONDOMINIUMS - BLDG. A
5061 NORTH HIGHWAY A FT. PIERCE, FLORIDA
THRESHOLD INSPECTION RE
SLC BUILDING PERMIT NUMBER l 11 '-0046
PROJECTNAME: Bryn Mawr —Bldg. A DATE: October 18, 2017
CLIENT: Elliott Merrill Community Mgt. LOCATION: Ft. Pierce, Florida
CONTRACTOR: Daniello & Assoc. PROJECT MGR: Chris Arias
INSPECTED BY: Mike Lue WEATHER: Sunny
WORK INSPECTED: Final inspection on all repairs
OBSERVATIONS:
The following repairs have been completed and are in accordance with design documents.
Column spall: Walkway stair door
Surface spalls: Balconies @ units 101, 102, 104, 301, 302, 306, 501, 606, 802 & 804
Walkway @ units 301/302, 402, 601, 603, 604 & 804
Ceiling spalls: Walkway @ unit 403 was not a spall and only stucco repair
Slab edge repair: Unit 301 balcony @ north elevation
Deck Coating: Balconies @ units 101, 201 & 204
Walkway @ units 203, 802 & 805