Loading...
HomeMy WebLinkAboutCERTIFIED TEST REPORTBY Xwf v yr y.St. Lucie AIR PROSERV INC. AABC CERTIFIED TESTING, ADJUSTING AND BALANCING COMPANY 22344 SW 57th Cir. BOCA RATON FL, 33428 Phone: 305-807-0188 /Fax: 561-488 7381 24ckl- CERTIFIED TEST ADJUST AND BALANCE REPORT DATE . 9/27/2017 PROJECT MARCO'S PIZZA 901 EAST PRIMA VISTA BLVD. PORT SAINTLUCIE, FL ARCHITECT GARCIA SEUFERT ARCHITECTS, INC. 121 W.122". AVE. TAMPA, FL DESIGN ENGINEER STE,PANEK—LEWIS & ASSOCIATES 2257 TWELVE OAKS WAY #103 WESLEY CHAPEL, FL MECH.CONTRACTOR N/A ilnnll OCT - 9 RM AIR PROSERV INC. AABC CERTIFIED TESTING, ADJUSTING AND BALANCING COMPANY PROJECT MARCO'S PIZZA 901 EAST PRIMA VISTA BLVD. PORT SAINT LUCIE, FL This is to certify that Air Prosery Inc. has balanced the system to their optimum performance capabilities. The testing and balancing has been performed in accordance with the standards requirements and procedures of the Associated Air Balancing Council and the results of these tests are herein recorded. AABC Certification Number:10-09-52 Date:9/27/2017 Test & Balance Engineer: Zoran Cvetkovie BS. ME, AABC TBE tAec cpF.tifletl: HVAc�TESrING ARID'B..A1 A`NGIN;G _r r r` . " . AABC AIr Prosery Inc., 22344 SW 57x clr, Boca Raton, FL, $3428 / Tel: ,561-208-3882, Cell: 305-807-0188, Fax:561-488-7381 INSTRUMENT CALIBRATION REPORT PROJECT NAME: MARCO'S PIZZA -PORT ST. LUCIE MANUFACTURER MODEL SERIAL APPLZCATZON CALIBRATION DATE Shortrid a Inst ADM-860C M02186 Flowhood 12/05/16 Fluke 971 10510471 Tem .Humid.Meter 04/21/17 Alnor AXD540 56097010 Micromanometer 06/30/17 Alnor 8570 37030 Thermo Anem. 07/01/17 Alnor RVA+ 70608194 Vane Anem. 01/23/17 Klein Tools CL800 0516C-Al Kfamp Meter 01/23/17 Alnor AVM410 AVM411528002 Thermo Anem. 01123/17 DATE: 9/27/2017 Air Prosery Inc, 22344 SW 57c' cir, Boca Raton, FL, 93428 / Tel: REPORT ABBREVIATIONS Abbreviation Definitions Cell:305-807-0188, Fax:561-488-7381 AK Free area times the coefficient of discharge CF DDC flow correction factor CFM Cubic Feet per Minute CHW Chilled Water CR Ceiling Register— supply air CW Condenser Water Cv Flow coefficient DD Direct drive fan, no pulleys involved DDC Direct Digital Control DX Direct Expansion RAT -Entering Air Temperature ESP External Static Pressure EWT Entering Water Temperature FPM Feet Per Minute GPM Gallon Per Minute LAT Leaving Air Temperature LWT Leaving Water Temperature MBH British Thermal Units Expressed in Thousand N/A Not available / Not Applicable N/AC Not accessible O/A Outside Air OBD Opposed Blade Damper P/T Measurement used Pitot Tube Traverse (Velocity Reading ) R/A Return Air RPM Revolutions Per Minute RG Return Grille - Return Air RR Return Register — Return Air S/A Supply Air TSP Total Static Pressure VAV• Terminal Box Defined as Variable Air Volume VD Volume Damper 2 Air Pro5ery Inc., 22344 SW 571h cir, Boca Raton, FL, / Tel:561-208-3882, Cell:305-807-0188, Fax:561-488.7381 AIR APPARATUS TEST REPORT PROJECT: 17114 MARCO'S PIZZA MARCO'S PIZZA UNIT AHU-1 SYSTEM SUPPLY AIR LOCATION CEILING SERVICE KITCHEN UNIT DATA MOTOR DATA MAKE GOODMAN MAKE FRAME N/A N/A MODEL ARUF364216AA POWER BRAKE PWR. 1/2 SERIAL 0611031471 RPM SER. FACTOR N/A N/A TYPE SIZE PC N/A NAMEPLATE VOLTAGE 208 DISCHARGE CLASS HORIZONTAL N/A NAMEPLATE AMPERES 2.95 ARRANGEMENT DT ACTUAL VOLTAGE 211 SHEAVE MAKE DD ACTUAL AMPERES 2.4 SHEAVE DIAMETER DD C.F.L.A OVERLOAD 2.91 SHEAVE BORE DD PHASE HERTZ 1 60 BELT MAKE DD PWR. FACTOR EFFICIENCY N/A N/A N BELTS BELT SIZE DD DD SHEAVE MAKE DD NUMBERS OF FILTERS 1 SHEAVE DIAMETER DD FILTER TYPE T/A SHEAVE BORE DD FILTER SIZE 24X24X1 OPERATING DIAMETER DD TEST DATA CENTER DISTANCE DD TEST DESIGN ACTUAL STATIC PRESSURE PROFILE OUTSIDE AIRFLOW 280 274 DEVICE DESIGN B.P.D. ACTUAL &P.D. ACTUAL ENT. B.P. ACTUAL LVG. &P RETURN AIRFLOW 1070 956 FILTER -.26 TOTAL AIRFLOW 1350 1230 COIL -.26 TOTAL STATIC PRESSURE N/A FAN .19 EXT. STATIC PRESSURE 0.50 0.45 FAN RPM N/A DD VORTEX OR VFD POSITION N/A - STATIC PRESSURE SETPOINT N/A - OUT. AIR DAMPER POSITION N/A - REf. AIR DAMPER POSITION N/A - REMARKS " TEST DATE: 9/27/2017 READINGS BY: ZC PAGE: 3 Air Prosery Inc., 22344 SW 57'h cir, Boca Raton, FL, 33428 J Tel. 561-208-3882, Cell 305-807-0188, Fax 561-488-7382 Alr Prosery Inc., 22344 SW 57'h dr, Boca Ratan, FL, 33428 / Tel: 561-208-3882, Cell: 305-807-0188, Fax: 561-488-7381 AIR APPARATUS TEST REPORT PROJECT: 17114 MARCO'S PIZZA MARCO'S PIZZA UNIT AHU-2 SYSTEM SUPPLY AIR LOCATION CEILING SERVICE DINING UNIT DATA MOTOR DATA MAKE CARRIER MAKE FRAME N/A N/A MODEL FS4CNP060 POWER BRAKE PWR. 3/4 SERIAL 4616AS5566 RPM SER.FACTOR N/A N/A TYPE SIZE PC N/A NAMEPLATE VOLTAGE 208 DISCHARGE I CLASS HORIZONTAL N/A NAMEPLATE AMPERES 6.0 ARRANGEMENT DT ACTUAL VOLTAGE 214 SHEAVE MAKE. DD ACTUAL AMPERES 5.3 SHEAVE DIAMETER DD C.F.L.A. OVERLOAD 5.83 SHEAVE BORE DD PHASE HERTZ 1 60 BELT MAKE DD PWR. FACTOR EFFICIENCY N/A N/A # BELTS BELT SIZE DD DD SHEAVE MAKE DD NUMBERS OF FILTERS 1 SHEAVE DIAMETER DD FILTER TYPE T/A SHEAVE BORE DD FILTER SIZE 24X24X1 OPERATING DIAMETER DD TEST DATA CENTER DISTANCE DD TEST DESIGN ACTUAL STATIC PRESSURE PROFILE OUTSIDE AIRFLOW 400 414 DEVICE DESIGN S.P.D. ACTUAL S.P.D. ACTUAL ENT. S.P. ACTUAL LVG. S.P RETURN AIRFLOW 1550 1376 FILTER -.29 TOTAL AIRFLOW 1950 1790 COIL -,29 TOTAL STATIC PRESSURE N/A FAN .24 EXT. STATIC PRESSURE_ 0.50 0.53 FAN RPM N/A DD VORTEX OR VFD POSITION N/A - STATIC PRESSURE SETPOINT N/A OUT. AIR DAMPER POSITION N/A - RET. AIR DAMPER POSITION N/A - REMARKS: TEST DATE: 9/27/2017 READINGS BY: ZC PAGE: S nu nusery mc., «ava sW sr' cir, Boca Raton, FL, 33428 / Tel: 561-208-3882, Cell: 305-807-0188, Fax: 561-488-7381 REGISTER, GRILLE, DIFFUSER TEST REPORT (Flow Hood) PROJECT: 17114 MARCO'S PIZZA MARCO'S PIZZA UNIT AHU-2 SYSTEM SUPPLY AIR TERMINAL BOX - LOCATION MARCO'S PIZZA MANUFACTURER TEST INSTRUMENT PLOW HOOD LOCATION OR REGISTER, GRILLE, DIFFUSER DESIGN PRELIMINARY FINAL ADDRESS NUMBER TYPE SIZE FLOW FLOW FLOW % DINING 1 A 24X24 925 838 90.6 11 2 " " 925 845 91.4 W REST RM. 3 B " 50 52 104.0 M.REST RM. 4 " 50 55 110.0 TOTAL 1950 0 1790 REMARKS ' TEST DATE: 9/27/2017 READINGS BY: ZC PAGE: (� Air Prosery Inc„ 22344 SW 57N cir, Boca Raton, FL, 33428 / Tel: 561-208-3882, Cell: 305-807-0188, Fax: 561-488-7382 AIR APPARATUS TEST REPORT PROJECT: 17114 MARCO'S PIZZA MARCO'S PIZZA UNIT ARU-3 SYSTEM SUPPLY AIR LOCATION CEILING SERVICE DINING UNIT DATA MOTOR DATA MAKE CARRIER MAKE FRAME N/A N/A MODEL FB4CNP06O POWER BRAKE PWR. 3/4 SERIAL 4561A86350 RPM SER. FACTOR N/A N/A TYPE SIZE PC N/A NAMEPLATE VOLTAGE 208 DISCHARGE CLASS HORIZONTAL N/A NAMEPLATE AMPERES 6.0 ARRANGEMENT DT ACTUAL VOLTAGE 212 SHEAVE MAKE DD ACTUAL AMPERES 5.1 SHEAVE DIAMETER DD C.F.L.A. OVERLOAD 5.89 SHEAVE BORE DO PHASE HERTZ - 1 60 BELT MAKE DD PWR. FACTOR EFFICIENCY N/A N/A N BELTS DELT SIZE DO DO SHEAVE MAKE DD NUMBERS OF FILTERS 1 SHEAVE DIAMETER DO FILTER TYPE T/A SHEAVE BORE DD FILTER SIZE_ 24X24X1 OPERATING DIAMETER DO TEST DATA CENTER DISTANCE DD TEST DRSIGN ACTUAL STATIC PRESSURE PROFILE OUTSIDE AIRFLOW 400 405 DEVICE DESIGN B.P.D. ACTUAL IRS. ACTUAL ENT. B.P. ACTUAL LVG. S.P RETURN AIRFLOW 1550 1372 FILTER -.26 TOTAL AIRFLOW 1950 1777 COIL -,26 TOTAL STATIC PRESSURE N/A - FAN .22 EXT. STATIC PRESSURE 0.50 0.48 FAN RPM N/A DO VORTEX OR VFD POSITION N/A - STATIC PRESSURE SC-TPOINT N/A OUT. AIR DAMPER POSITION N/A RET. AIR DAMPER POSITION N/A - REMARKS: TEST DATE 9/27/2017 READINGS BY: ZC PAGE ... .:- _. .. ... ,... -. .. .. .( -'r••.l Alr Prosery Inc., 22344 SW 57�h clr, Boca Raton, FL, t13428 / Tel 561-208-3882is..- , Cell 305.-807 0188, Fax 561-488-7381 REGISTER, GRILLE, DIFFUSER TEST REPORT (Flow Hood) PROJECT: 17114 MARCO'S PIZZA MARCO'S PIZZA UNIT AHU-3 SYSTEM SUPPLY AIR TERMINAL BOX - LOCATION MARCO'S PIZZA MANUFACTURER TEST INSTRUMENT FLOW HOOD LOCATION OR REGISTER, GRILLE, DIFFUSER DESIGN PRELIMINARY FINAL ADDRESS NUMBER TYPE SIZE FLOW FLOW FLOW % KITCHEN 1 A 24X24 650 604 92.9 2 " 650 588 90.5 3 " 650 585 90.0 TOTAL 1950 0 1777 REMARKS: ' TEST DATE 9/27/2017 READINGS BY: ZC PAGE: 8 Air Prosery Inc., 22344 SW 57'h cir, Boca Raton, FL, 33428 / Tel: 561-208-3882, Cell: 305.807-0188, Fax: 561-488-7381 FAN TEST REPORT PROJECT: 17114 MARCO-S PIZZA MARCO-S PIZZA UNIT Es-1 UNIT SYSTEM EXHAUST AIR SYSTEM LOCATION CEILING LOCATION SERVICE REST ROOM SERVICE UNIT DATA UNIT DATA MAKE NUTONE MAKE MODEL 696N-RO2 MODEL SERIAL N/A SERIAL SHV. MAKE SHV. BORE DD DD SHV. MAKE SHV. BORE SHV. DIAM. CENTER DIST. DD DD SHV. DIAM. CENTER DIST. BELT MAKE --SIZE DD BELT MAKE # BELTS BELT DD DD # BELTS BELT SIZE MOTOR DATA MOTOR DATA MAKE N/A MAKE FRAME POWER N/A N/A FRAME POWER SER. FACTOR I RPM N/A N/A SER. FACTOR RPM NAMEPLATE VOLTAGE 115 NAMEPLATE VOLTAGE NAMEPLATE AMPERES 0.90 NAMEPLATE AMPERES ACTUAL VOLTAGE 115 ACTUAL VOLTAGE ACTUAL AMPERES 0.76 ACTUAL AMPERES PHASE HERTZ 1 60 PHASE HERTZ SHV. MAKE SHV. BORE DD DD SHV. MAKE SHV. BORE SHV. DIAM. OPER. DIAM. DD DD SHV. DIAM. OPER. DIAM. TEST DATA DESIGN ACTUAL TEST DATA DESIGN ACTUAL AIRFLOW 50 53 AIRFLOW ENT. S.P. LVG. S.P. N/A N/A 0 .18 ENT. S.P. LVG. S.P. TOTAL STATIC PRESSURE 0.25 0.18 TOTAL STATIC PRESSURE FAN RPM N/A DD FAN RPM REMARKS: REMARKS READINGS BY: ZC READINGS BY: I TEST DATE: 9/28/2037 TEST DATE: PAGE: 4 Air Prosery Inc., 22344 SW 570i clr, Boca Raton, FL, AABC / Tel:561.208-3882, Cell:305-807-0188, Fax:561-488-7381 FAN TEST REPORT PROJECT: 17114 MARCO'S PIZZA MARCO'S PIZZA UNIT HEF-1 UNIT SYSTEM EXHAUST AIR SYSTEM LOCATION ROOF LOCATION SERVICE HOOD -PIZZA OVEN SERVICE UNIT DATA UNIT DATA MAKE ACCUREX MAKE MODEL XRVD-141-VG-7-G MODEL SERIAL 14915402 SERIAL SHV. MAKE SHV. BORE DD DD SHV. MAKE SHV. BORE SHV. DIAM. CENTER DIST. DD DD SHV. DIAM. CENTER DIST. BELT MAKE DD BELT MAKE # BELTS BELT SIZE DO DO # BELTS BELT SIZE MOTOR DATA MOTOR DATA MAKE VARY GREEN-GREENHECK MAKE FRAME POWER N/A 3/4 FRAME POWER SER. FACTOR RPM N/A 300-1725 SER. FACTOR RPM NAMEPLATE VOLTAGE 115 NAMEPLATE VOLTAGE NAMEPLATE AMPERES 10.1 NAMEPLATE AMPERES ACTUAL VOLTAGE 115 ACTUAL VOLTAGE ACTUAL AMPERES 7.3 ACTUAL AMPERES PHASE HERTZ 1 60 PHASE HERTZ SHV. MAKE SHV. BORE DD DD SHV. MAKE SHV. BORE SHV. DIAM. OPER. DIAM. DD DD SHV. DIAM. OPER. DIAM. TEST DATA DESIGN ACTUAL TEST DATA DESIGN ACTUAL AIRFLOW 875 965 AIRFLOW ENT. S.P. LVG. S.P. N/A N/A -.44 0 ENT. S.P. LVG. S.P. TOTAL STATIC PRESSURE N/A 0.44 TOTAL STATIC PRESSURE FAN RPM N/A DO FAN RPM REMARKS: REMARKS: READINGS BY: ZC IREADINGS BY: TEST DATE: 10/8/2017 TEST DATE: PAGE: 10 Air Prosery Inc., 22344 SW 57'" cir, Boca Ratan, FL, M428 / Tel: 561-208-3882, Cell:305-807-0188, Fax: 561-488-7381 RECTANGULAR DUCT TRAVERSE RFPnRT PROJECT: 17114 MARCO'S PIZZA MARCO-S PIZZA UNIT REF-1 SYSTEM EXHAUST AIR ZONE — SERVICE PIZZA HOOD LOCATION KITCHEN ALTITUDE 0 DUCT DATA TEST DATA DESIGN ACTUAL HEIGHT WIDTH 11.5 44.25 STANDARD AIRFLOW 875 965 DENSITY S.P. 0.075 MEASURED AIRFLOW 965 AIR TEMP. DB AREA 3.53 1 AVERAGE VELOCITY 1247.61 273.00 POSITION 1 2 3 4 5 6 7 8 9 10 11 12 13 1 278 268 2 3 4 6 7 8 9 10 11 12 13 READINGS TAKEN WITH AIR SLOWING TOWARD THE OBSERVER NORIZONrAL NUAVERS ARE LEFT TO RIGIR. VERTICAL NUAWFRS ARE TOP TO SOTTOM REMARKS: ai I I [TEST DATE: 10/7/2017 I READINGS BY: ZC I PAGE: II I f 44ej 140LiT10N NOTES RACTOR TO VERIFY OUSTING 5 OF ALL AREAS OF N PRIOR TO CONSTRUCTION RACTOR .SHALL NOTIFY THE OF ANY DISCREPANCY THE DRAIVINGS AND E%61ING S. DEBRIS SHALL BE REMOVED SITE AND DISPOSED OF PROPER MEANS. RACFOR TO NAWNN A DAILY PROCESS AND TO KEEP DUST TO A WNUAUM. USE Y ENCLOSURES TO LWIT OUST MIGRATON KID EWFIHO E. IV