HomeMy WebLinkAboutCERTIFIED TEST REPORTBY
Xwf v yr y.St. Lucie
AIR PROSERV INC.
AABC CERTIFIED TESTING, ADJUSTING AND BALANCING COMPANY
22344 SW 57th Cir. BOCA RATON FL, 33428
Phone: 305-807-0188 /Fax: 561-488 7381
24ckl-
CERTIFIED TEST ADJUST AND
BALANCE REPORT
DATE .
9/27/2017
PROJECT
MARCO'S PIZZA
901 EAST PRIMA VISTA BLVD.
PORT SAINTLUCIE, FL
ARCHITECT
GARCIA SEUFERT ARCHITECTS, INC.
121 W.122". AVE.
TAMPA, FL
DESIGN ENGINEER
STE,PANEK—LEWIS & ASSOCIATES
2257 TWELVE OAKS WAY #103
WESLEY CHAPEL, FL
MECH.CONTRACTOR
N/A
ilnnll
OCT - 9 RM
AIR PROSERV INC.
AABC CERTIFIED TESTING, ADJUSTING AND BALANCING COMPANY
PROJECT
MARCO'S PIZZA
901 EAST PRIMA VISTA BLVD.
PORT SAINT LUCIE, FL
This is to certify that Air Prosery Inc. has balanced the system to their optimum
performance capabilities. The testing and balancing has been performed in
accordance with the standards requirements and procedures of the Associated
Air Balancing Council and the results of these tests are herein recorded.
AABC Certification Number:10-09-52
Date:9/27/2017
Test & Balance Engineer:
Zoran Cvetkovie BS. ME, AABC TBE
tAec cpF.tifletl: HVAc�TESrING ARID'B..A1 A`NGIN;G _r r r` . " . AABC
AIr Prosery Inc., 22344 SW 57x clr, Boca Raton, FL, $3428 / Tel: ,561-208-3882, Cell: 305-807-0188, Fax:561-488-7381
INSTRUMENT CALIBRATION REPORT
PROJECT NAME:
MARCO'S PIZZA -PORT ST. LUCIE
MANUFACTURER
MODEL
SERIAL
APPLZCATZON
CALIBRATION DATE
Shortrid a Inst
ADM-860C
M02186
Flowhood
12/05/16
Fluke
971
10510471
Tem .Humid.Meter
04/21/17
Alnor
AXD540
56097010
Micromanometer
06/30/17
Alnor
8570
37030
Thermo Anem.
07/01/17
Alnor
RVA+
70608194
Vane Anem.
01/23/17
Klein Tools
CL800
0516C-Al
Kfamp Meter
01/23/17
Alnor
AVM410
AVM411528002
Thermo Anem.
01123/17
DATE:
9/27/2017
Air Prosery Inc, 22344 SW 57c' cir, Boca Raton, FL, 93428 / Tel:
REPORT ABBREVIATIONS
Abbreviation Definitions
Cell:305-807-0188, Fax:561-488-7381
AK
Free area times the coefficient of discharge
CF
DDC flow correction factor
CFM
Cubic Feet per Minute
CHW
Chilled Water
CR
Ceiling Register— supply air
CW
Condenser Water
Cv
Flow coefficient
DD
Direct drive fan, no pulleys involved
DDC
Direct Digital Control
DX
Direct Expansion
RAT
-Entering Air Temperature
ESP
External Static Pressure
EWT
Entering Water Temperature
FPM
Feet Per Minute
GPM
Gallon Per Minute
LAT
Leaving Air Temperature
LWT
Leaving Water Temperature
MBH
British Thermal Units Expressed in Thousand
N/A
Not available / Not Applicable
N/AC
Not accessible
O/A
Outside Air
OBD
Opposed Blade Damper
P/T
Measurement used Pitot Tube Traverse (Velocity Reading )
R/A
Return Air
RPM
Revolutions Per Minute
RG
Return Grille - Return Air
RR
Return Register — Return Air
S/A
Supply Air
TSP
Total Static Pressure
VAV•
Terminal Box Defined as Variable Air Volume
VD
Volume Damper
2
Air Pro5ery Inc., 22344 SW 571h cir, Boca Raton, FL,
/ Tel:561-208-3882, Cell:305-807-0188, Fax:561-488.7381
AIR APPARATUS TEST REPORT
PROJECT: 17114 MARCO'S PIZZA MARCO'S PIZZA
UNIT
AHU-1
SYSTEM
SUPPLY AIR
LOCATION
CEILING
SERVICE
KITCHEN
UNIT DATA
MOTOR DATA
MAKE
GOODMAN
MAKE
FRAME
N/A
N/A
MODEL
ARUF364216AA
POWER
BRAKE PWR.
1/2
SERIAL
0611031471
RPM
SER. FACTOR
N/A
N/A
TYPE
SIZE
PC
N/A
NAMEPLATE VOLTAGE
208
DISCHARGE
CLASS
HORIZONTAL
N/A
NAMEPLATE AMPERES
2.95
ARRANGEMENT
DT
ACTUAL VOLTAGE
211
SHEAVE MAKE
DD
ACTUAL AMPERES
2.4
SHEAVE DIAMETER
DD
C.F.L.A
OVERLOAD
2.91
SHEAVE BORE
DD
PHASE
HERTZ
1
60
BELT MAKE
DD
PWR. FACTOR
EFFICIENCY
N/A
N/A
N BELTS
BELT SIZE
DD
DD
SHEAVE MAKE
DD
NUMBERS OF FILTERS
1
SHEAVE DIAMETER
DD
FILTER TYPE
T/A
SHEAVE BORE
DD
FILTER SIZE
24X24X1
OPERATING DIAMETER
DD
TEST DATA
CENTER DISTANCE
DD
TEST
DESIGN
ACTUAL
STATIC PRESSURE PROFILE
OUTSIDE AIRFLOW
280
274
DEVICE
DESIGN
B.P.D.
ACTUAL
&P.D.
ACTUAL
ENT. B.P.
ACTUAL
LVG. &P
RETURN AIRFLOW
1070
956
FILTER
-.26
TOTAL AIRFLOW
1350
1230
COIL
-.26
TOTAL STATIC PRESSURE
N/A
FAN
.19
EXT. STATIC PRESSURE
0.50
0.45
FAN RPM
N/A
DD
VORTEX OR VFD POSITION
N/A
-
STATIC PRESSURE SETPOINT
N/A
-
OUT. AIR DAMPER POSITION
N/A
-
REf. AIR DAMPER POSITION
N/A
-
REMARKS
"
TEST DATE: 9/27/2017
READINGS BY: ZC
PAGE: 3
Air Prosery Inc., 22344 SW 57'h cir, Boca Raton, FL, 33428 J Tel. 561-208-3882, Cell 305-807-0188, Fax 561-488-7382
Alr Prosery Inc., 22344 SW 57'h dr, Boca Ratan, FL, 33428 / Tel: 561-208-3882, Cell: 305-807-0188, Fax: 561-488-7381
AIR APPARATUS TEST REPORT
PROJECT: 17114 MARCO'S PIZZA MARCO'S PIZZA
UNIT
AHU-2
SYSTEM
SUPPLY AIR
LOCATION
CEILING
SERVICE
DINING
UNIT DATA
MOTOR DATA
MAKE
CARRIER
MAKE
FRAME
N/A
N/A
MODEL
FS4CNP060
POWER
BRAKE PWR.
3/4
SERIAL
4616AS5566
RPM
SER.FACTOR
N/A
N/A
TYPE
SIZE
PC
N/A
NAMEPLATE VOLTAGE
208
DISCHARGE
I CLASS
HORIZONTAL
N/A
NAMEPLATE AMPERES
6.0
ARRANGEMENT
DT
ACTUAL VOLTAGE
214
SHEAVE MAKE.
DD
ACTUAL AMPERES
5.3
SHEAVE DIAMETER
DD
C.F.L.A.
OVERLOAD
5.83
SHEAVE BORE
DD
PHASE
HERTZ
1
60
BELT MAKE
DD
PWR. FACTOR
EFFICIENCY
N/A
N/A
# BELTS
BELT SIZE
DD
DD
SHEAVE MAKE
DD
NUMBERS OF FILTERS
1
SHEAVE DIAMETER
DD
FILTER TYPE
T/A
SHEAVE BORE
DD
FILTER SIZE
24X24X1
OPERATING DIAMETER
DD
TEST DATA
CENTER DISTANCE
DD
TEST
DESIGN
ACTUAL
STATIC PRESSURE PROFILE
OUTSIDE AIRFLOW
400
414
DEVICE
DESIGN
S.P.D.
ACTUAL
S.P.D.
ACTUAL
ENT. S.P.
ACTUAL
LVG. S.P
RETURN AIRFLOW
1550
1376
FILTER
-.29
TOTAL AIRFLOW
1950
1790
COIL
-,29
TOTAL STATIC PRESSURE
N/A
FAN
.24
EXT. STATIC PRESSURE_
0.50
0.53
FAN RPM
N/A
DD
VORTEX OR VFD POSITION
N/A
-
STATIC PRESSURE SETPOINT
N/A
OUT. AIR DAMPER POSITION
N/A
-
RET. AIR DAMPER POSITION
N/A
-
REMARKS:
TEST DATE: 9/27/2017
READINGS BY: ZC
PAGE: S
nu nusery mc., «ava sW sr' cir, Boca Raton, FL, 33428 / Tel: 561-208-3882, Cell: 305-807-0188, Fax: 561-488-7381
REGISTER, GRILLE, DIFFUSER TEST REPORT (Flow Hood)
PROJECT: 17114 MARCO'S PIZZA MARCO'S
PIZZA
UNIT
AHU-2
SYSTEM
SUPPLY AIR
TERMINAL BOX
-
LOCATION
MARCO'S PIZZA
MANUFACTURER
TEST INSTRUMENT
PLOW HOOD
LOCATION
OR
REGISTER, GRILLE, DIFFUSER
DESIGN
PRELIMINARY
FINAL
ADDRESS
NUMBER
TYPE
SIZE
FLOW
FLOW
FLOW
%
DINING
1
A
24X24
925
838
90.6
11
2
"
"
925
845
91.4
W REST RM.
3
B
"
50
52
104.0
M.REST RM.
4
"
50
55
110.0
TOTAL
1950
0 1790
REMARKS
'
TEST DATE:
9/27/2017
READINGS BY: ZC
PAGE: (�
Air Prosery Inc„ 22344 SW 57N cir, Boca Raton, FL, 33428 / Tel: 561-208-3882, Cell: 305-807-0188, Fax: 561-488-7382
AIR APPARATUS TEST REPORT
PROJECT: 17114 MARCO'S PIZZA MARCO'S PIZZA
UNIT
ARU-3
SYSTEM
SUPPLY AIR
LOCATION
CEILING
SERVICE
DINING
UNIT DATA
MOTOR DATA
MAKE
CARRIER
MAKE
FRAME
N/A
N/A
MODEL
FB4CNP06O
POWER
BRAKE PWR.
3/4
SERIAL
4561A86350
RPM
SER. FACTOR
N/A
N/A
TYPE
SIZE
PC
N/A
NAMEPLATE VOLTAGE
208
DISCHARGE
CLASS
HORIZONTAL
N/A
NAMEPLATE AMPERES
6.0
ARRANGEMENT
DT
ACTUAL VOLTAGE
212
SHEAVE MAKE
DD
ACTUAL AMPERES
5.1
SHEAVE DIAMETER
DD
C.F.L.A.
OVERLOAD
5.89
SHEAVE BORE
DO
PHASE
HERTZ -
1
60
BELT MAKE
DD
PWR. FACTOR
EFFICIENCY
N/A
N/A
N BELTS
DELT SIZE
DO
DO
SHEAVE MAKE
DD
NUMBERS OF FILTERS
1
SHEAVE DIAMETER
DO
FILTER TYPE
T/A
SHEAVE BORE
DD
FILTER SIZE_
24X24X1
OPERATING DIAMETER
DO
TEST DATA
CENTER DISTANCE
DD
TEST
DRSIGN
ACTUAL
STATIC PRESSURE PROFILE
OUTSIDE AIRFLOW
400
405
DEVICE
DESIGN
B.P.D.
ACTUAL
IRS.
ACTUAL
ENT. B.P.
ACTUAL
LVG. S.P
RETURN AIRFLOW
1550
1372
FILTER
-.26
TOTAL AIRFLOW
1950
1777
COIL
-,26
TOTAL STATIC PRESSURE
N/A -
FAN
.22
EXT. STATIC PRESSURE
0.50
0.48
FAN RPM
N/A
DO
VORTEX OR VFD POSITION
N/A
-
STATIC PRESSURE SC-TPOINT
N/A
OUT. AIR DAMPER POSITION
N/A
RET. AIR DAMPER POSITION
N/A
-
REMARKS:
TEST DATE 9/27/2017
READINGS BY: ZC
PAGE
... .:- _. .. ... ,... -. .. .. .( -'r••.l
Alr Prosery Inc., 22344 SW 57�h clr, Boca Raton, FL, t13428 / Tel 561-208-3882is..-
, Cell 305.-807 0188, Fax 561-488-7381
REGISTER, GRILLE, DIFFUSER TEST REPORT (Flow Hood)
PROJECT: 17114 MARCO'S PIZZA MARCO'S PIZZA
UNIT
AHU-3
SYSTEM
SUPPLY AIR
TERMINAL BOX
-
LOCATION
MARCO'S PIZZA
MANUFACTURER
TEST INSTRUMENT
FLOW HOOD
LOCATION
OR
REGISTER, GRILLE, DIFFUSER
DESIGN
PRELIMINARY
FINAL
ADDRESS
NUMBER
TYPE
SIZE
FLOW
FLOW
FLOW
%
KITCHEN
1
A
24X24
650
604
92.9
2
"
650
588
90.5
3
"
650
585
90.0
TOTAL 1950 0 1777
REMARKS:
'
TEST DATE 9/27/2017
READINGS BY: ZC
PAGE: 8
Air Prosery Inc., 22344 SW 57'h cir, Boca Raton, FL, 33428 / Tel: 561-208-3882, Cell: 305.807-0188, Fax: 561-488-7381
FAN TEST REPORT
PROJECT: 17114 MARCO-S PIZZA MARCO-S PIZZA
UNIT
Es-1
UNIT
SYSTEM
EXHAUST AIR
SYSTEM
LOCATION
CEILING
LOCATION
SERVICE
REST ROOM
SERVICE
UNIT DATA
UNIT DATA
MAKE
NUTONE
MAKE
MODEL
696N-RO2
MODEL
SERIAL
N/A
SERIAL
SHV. MAKE
SHV. BORE
DD
DD
SHV. MAKE
SHV. BORE
SHV. DIAM.
CENTER DIST.
DD
DD
SHV. DIAM.
CENTER DIST.
BELT MAKE
--SIZE
DD
BELT MAKE
# BELTS
BELT
DD
DD
# BELTS
BELT SIZE
MOTOR DATA
MOTOR DATA
MAKE
N/A
MAKE
FRAME
POWER
N/A
N/A
FRAME
POWER
SER. FACTOR
I RPM
N/A
N/A
SER. FACTOR
RPM
NAMEPLATE VOLTAGE
115
NAMEPLATE VOLTAGE
NAMEPLATE AMPERES
0.90
NAMEPLATE AMPERES
ACTUAL VOLTAGE
115
ACTUAL VOLTAGE
ACTUAL AMPERES
0.76
ACTUAL AMPERES
PHASE
HERTZ
1
60
PHASE
HERTZ
SHV. MAKE
SHV. BORE
DD
DD
SHV. MAKE
SHV. BORE
SHV. DIAM.
OPER. DIAM.
DD
DD
SHV. DIAM.
OPER. DIAM.
TEST DATA
DESIGN
ACTUAL
TEST DATA
DESIGN
ACTUAL
AIRFLOW
50
53
AIRFLOW
ENT. S.P.
LVG. S.P.
N/A
N/A
0
.18
ENT. S.P.
LVG. S.P.
TOTAL STATIC PRESSURE
0.25
0.18
TOTAL STATIC PRESSURE
FAN RPM
N/A
DD
FAN RPM
REMARKS:
REMARKS
READINGS BY: ZC
READINGS BY:
I
TEST DATE: 9/28/2037
TEST DATE:
PAGE: 4
Air Prosery Inc., 22344 SW 570i clr, Boca Raton, FL,
AABC
/ Tel:561.208-3882, Cell:305-807-0188, Fax:561-488-7381
FAN TEST REPORT
PROJECT: 17114 MARCO'S PIZZA MARCO'S PIZZA
UNIT
HEF-1
UNIT
SYSTEM
EXHAUST AIR
SYSTEM
LOCATION
ROOF
LOCATION
SERVICE
HOOD -PIZZA OVEN
SERVICE
UNIT DATA
UNIT DATA
MAKE
ACCUREX
MAKE
MODEL
XRVD-141-VG-7-G
MODEL
SERIAL
14915402
SERIAL
SHV. MAKE
SHV. BORE
DD
DD
SHV. MAKE
SHV. BORE
SHV. DIAM.
CENTER DIST.
DD
DD
SHV. DIAM.
CENTER DIST.
BELT MAKE
DD
BELT MAKE
# BELTS
BELT SIZE
DO
DO
# BELTS
BELT SIZE
MOTOR DATA
MOTOR DATA
MAKE
VARY GREEN-GREENHECK
MAKE
FRAME
POWER
N/A
3/4
FRAME
POWER
SER. FACTOR
RPM
N/A
300-1725
SER. FACTOR
RPM
NAMEPLATE VOLTAGE
115
NAMEPLATE VOLTAGE
NAMEPLATE AMPERES
10.1
NAMEPLATE AMPERES
ACTUAL VOLTAGE
115
ACTUAL VOLTAGE
ACTUAL AMPERES
7.3
ACTUAL AMPERES
PHASE
HERTZ
1
60
PHASE
HERTZ
SHV. MAKE
SHV. BORE
DD
DD
SHV. MAKE
SHV. BORE
SHV. DIAM.
OPER. DIAM.
DD
DD
SHV. DIAM.
OPER. DIAM.
TEST DATA
DESIGN
ACTUAL
TEST DATA
DESIGN
ACTUAL
AIRFLOW
875
965
AIRFLOW
ENT. S.P.
LVG. S.P.
N/A
N/A
-.44
0
ENT. S.P.
LVG. S.P.
TOTAL STATIC PRESSURE
N/A
0.44
TOTAL STATIC PRESSURE
FAN RPM
N/A
DO
FAN RPM
REMARKS:
REMARKS:
READINGS BY: ZC IREADINGS BY:
TEST DATE: 10/8/2017 TEST DATE: PAGE: 10
Air Prosery Inc., 22344 SW 57'" cir, Boca Ratan, FL, M428 / Tel: 561-208-3882, Cell:305-807-0188, Fax: 561-488-7381
RECTANGULAR DUCT TRAVERSE RFPnRT
PROJECT: 17114 MARCO'S PIZZA MARCO-S PIZZA
UNIT
REF-1
SYSTEM
EXHAUST AIR
ZONE
—
SERVICE
PIZZA HOOD
LOCATION
KITCHEN
ALTITUDE
0
DUCT DATA
TEST DATA
DESIGN
ACTUAL
HEIGHT
WIDTH
11.5
44.25
STANDARD AIRFLOW
875
965
DENSITY
S.P.
0.075
MEASURED AIRFLOW
965
AIR TEMP. DB
AREA
3.53
1 AVERAGE VELOCITY
1247.61
273.00
POSITION
1
2
3
4
5
6
7
8
9
10
11
12
13
1
278
268
2
3
4
6
7
8
9
10
11
12
13
READINGS TAKEN WITH AIR SLOWING TOWARD THE OBSERVER NORIZONrAL NUAVERS ARE LEFT TO RIGIR. VERTICAL NUAWFRS ARE TOP TO SOTTOM
REMARKS:
ai
I I [TEST DATE: 10/7/2017 I READINGS BY: ZC I PAGE: II I
f
44ej 140LiT10N NOTES
RACTOR TO VERIFY OUSTING
5 OF ALL AREAS OF
N PRIOR TO CONSTRUCTION
RACTOR .SHALL NOTIFY THE
OF ANY DISCREPANCY
THE DRAIVINGS AND E%61ING
S.
DEBRIS SHALL BE REMOVED
SITE AND DISPOSED OF
PROPER MEANS.
RACFOR TO NAWNN A DAILY
PROCESS AND TO KEEP DUST
TO A WNUAUM. USE
Y ENCLOSURES TO LWIT OUST
MIGRATON KID EWFIHO
E.
IV