HomeMy WebLinkAboutMISC EMAILPAUL WELCH INC.
Mechanical * Electrical * Civil Engineering
SG BY Ep 1984 S.W. Biltmore St. Suite#114
Port Saint Lucie, FL 34984
SL LUcAe
County Phone (772) 785 - 9888
Email pwelchinc@aol.com !!
June 14, 2017
Re: Door Replacement
3375 Oleander Av.
Fort Pierce, FL
To Whom It May Concern:
Our office has calculated the required design pressure in accordance with ASCE 7-10 and
FBC 2014 for the replacement of the door at the above referenced address.
Wind speed: V a: 160mph, Vad: 124 mph
Exposure: C
Enclosure Type: Enclosed
Door Size: 12'-0" wide X 14'-0" high Roll Up Door
Quantity of Doors: 1
Location: Per Attached Sketch
Required Design Pressure (Zone 5): +31.4/ -40.6 PSF Worst Case
Door to be installed shall be equal to, or exceed the required design pressures as listed
above. All installations shall be in accordance with FBC 2014 and manufacturer's
installation instructions.
Proposed Door: Janus International FL#12765.3 (+36 / -41 PSF).
Thank yc for your attention to this matter.
Submitt
by:
PAUL
LCId INS.
Paul We
h, P.E.
Reg. No
9945 `
Attached: Product Approval Affid.
Area of Work Plan