HomeMy WebLinkAboutMISC EMAILPAUL WELCH INC. Mechanical * Electrical * Civil Engineering SG BY Ep 1984 S.W. Biltmore St. Suite#114 Port Saint Lucie, FL 34984 SL LUcAe County Phone (772) 785 - 9888 Email pwelchinc@aol.com !! June 14, 2017 Re: Door Replacement 3375 Oleander Av. Fort Pierce, FL To Whom It May Concern: Our office has calculated the required design pressure in accordance with ASCE 7-10 and FBC 2014 for the replacement of the door at the above referenced address. Wind speed: V a: 160mph, Vad: 124 mph Exposure: C Enclosure Type: Enclosed Door Size: 12'-0" wide X 14'-0" high Roll Up Door Quantity of Doors: 1 Location: Per Attached Sketch Required Design Pressure (Zone 5): +31.4/ -40.6 PSF Worst Case Door to be installed shall be equal to, or exceed the required design pressures as listed above. All installations shall be in accordance with FBC 2014 and manufacturer's installation instructions. Proposed Door: Janus International FL#12765.3 (+36 / -41 PSF). Thank yc for your attention to this matter. Submitt by: PAUL LCId INS. Paul We h, P.E. Reg. No 9945 ` Attached: Product Approval Affid. Area of Work Plan