August 9, 2018
Mr. Joe Cicio, Plans Examiner
St. Lucie County Building Department
2300 Virginia Avenue
Fort Pierce, FL 34982
SCANNED
i8Y
St. Lucie CountV
Subject: Sands I Condominium — Concrete Restoration
3212 South Lakeview Circle (Building 10)
Permit Number—1704-0525
Fort Pierce, Florida
Engineer's Project Number: 17-0346
Dear Mr. Cicio:
Enclosed you will find two (2) copies of the revised plans, and the requested documentation. This
information has been provided in accordance with your comment letter dated February 6, 2018.
1. Remove Mr. Lestrange from all correspondence and resubmit to this department the letters
dated January 9, 2018 FAC 61 G15-23.002. The letters are attached in this submittal.
2. Submit an up -dated current contract with owner. The contractor can provide this
document in the submittal package.
3. The NOA indicated on sheet S3 has expired. Engineer to state current product approval on
plans. The product approval has been updated on the plans in this submittal. Engineer
to design the soffit framing in accordance with the current NOA Specifications to receive
the hardie soffit panel. Plans revised to incorporate the current Product Approval
Specifications have been attached to this submittal.
4. Are you replacing guardrails? Yes, we propose to replace the guardrails.
5. Are you replacing any sliding glass door units? No, we are not proposing to replace the
sliding glass door units.
6. Are you replacing any hurricane shutters? No, we are not proposing to replace the
hurricane shutters.
7. Submit (2) original, signed, sealed, and dated St. Lucie County Design Load Compliance
sheets completely filled out. The St. Lucie County Design Load Compliance form is
completed and attached to this submittal.
1835 20[h Street 1250 W Eau Gallie Blvd., Suite L 806 Delaware Avenue
Vero Beach, FL 32960 Melbourne, FL 32935 FL Pierce, FL 34950
772.569.0035 321.253.1510 772.468.9055
Fax: 772.778.3617 Fax: 321.253.0911 Fax: 772.778.3617
8. Contractor to submit (8) separate release letters from Michael Luc (1 for each permit) and
(8) letters from MBV Engineering signed, sealed, and dated per FAC 61G15-23. Please
find the letters sent by certified mail to Michael Luc from MBV Engineering dated
per FAC 61G15-27.001 in this submittal.
9. Contractor to adjust the permit application front pages to correspond with the plans / all
units are addressed on plans. The contractor can provide this document in the
submittal package.
10. New plans must be designed including all repair details per the original plans (original
plans are void). Plans have been revised in this submittal.
11. Engineer to show the building elevations on plans as proposed per FBC 107.3.5. Plans
have been revised in this submittal.
Should you have E ttWlogtjq regarding the above subject, please do not hesitate to contact our
office. \\�\\ o NJILLA41
Very ly �o . No g10�� ••
w_
oeov
SI
Rodolfo it
FL P.E. #61
RV/mh
cc: Elliott -Merrill Community Management
'rMM BV
ENGINEERING, INC.
MOIA BOW LES VILLAMIZAR & ASSOCIATES
w .mbveng.conn CA #372B
January 09, 2018
Mr. Joe Cicio, Plans Examiner
St. Lucie County Building Department
2300 Virginia Avenue
Fort Pierce, FL 34982
Subject: Sands I Condominium — Concrete Restoration
3212 S. Lakeview Circle (Building 10)
Permit Number: 1704-0525
St. Lucie County, Florida
Engineer's Project Number: 17-0346
Dear Mr. Cicio:
Per your request we are clarifying the changes in the scope for the subject property based on
estimates from the actual findings in comparison with the project done by M.L. Engineering, Inc.
The main work items with substantial additional quantities in the repair estimates are as follows:
Concrete slab repair: 300 SF.
Concrete/Masonry column repair: 9 CF.
Concrete beam repair: 40 CF.
Guardrails: 50 LF.
Should you have any s// regarding the above subject, please do not hesitate to contact our
�cl�P
lce.
truly o \\\�OO�FO E vL
VesF 9
YY b; -p
No.61000
* * ; Of
TATEOF ;LU�
Rodolfo ill ,P.F
FL P.E. #61000'
RV/mh //// NP' \0����
cc: Elliott -Merrill Community Management
1835 20th Street 1250 W. Eau Gallie Blvd., Suite L 806 Delaware Avenue
Vero Beach, FL 32960 Melbourne, FL 32935 Ft. Pierce, FL 34950
772.569.0035 321.253.1510 772.468.9055
Fax 772.778.3617 Fax: 321.253.091 1 Fax:772.778.3617
IMM M BV
ENGINEERING, INC.
MOIA BOWLESVILLAMIZAR &ASSOCIATES
wwwrnbveng.com CA a3728
August 9, 2018
Mr. Joe Cicio, Plans Examiner
St. Lucie County Building Department
2300 Virginia Avenue
Fort Pierce, FL 34982
Subject: Sands I Condominium — Concrete Restoration
3212 S. Lakeview Circle (Building 10)
Permit Number: 1704-0525
St. Lucie County, Florida
Engineer's Project Number: 17-0346
Dear Mr. Cicio:
This letter shall serve as notification that MBV Engineering has been retained since August 18,
2017 to perform the special inspections for the concrete restoration at the subject project and we
will also prepare the final reports for the subject project.
Should you have ,ilf/7ti ns regarding the above subject, please do not hesitate to contact our
office. v\ -LA
/ q�Q
Very trul}� s'c1` 4
- Q
S�& z\
RoA#6�#
FLo
RV/mh
cc: Elliott -Merrill Community Management
1835 20[h Street 1250 W. Eau Gallie Blvd., Suite L 806 Delaware Avenue
Vero Beach, FL 32960 Melbourne, FL 32935 Ft Pierce, FL 34950
772.569.0035 321.253.1510 772.468,9055
Fax: 772.778.3617 Fax: 321.253.091 1 Fax: 772.778.3617
www.mbveng.com CA #3728
January 04, 2018
Mr. Michael A. Lue, RE
M.L. Engineering, Inc.
2030 37" Avenue,
Vero Beach, FL 32960
Subject: Sands I Condominium — Concrete Restoration
Bldgs. 1,3,5,6,7, 8,10,12
Fort Pierce, Florida
ML Engineering Project Number: 16-158
Engineer's Project Number: 17-0346
Dear Mr. Lue:
We were asked to inspect the work under the project reference created by your office. Given that
the scope had a substantial change, the building department requested a change of EOR.
This letter shall serve as notification that pursuant to Florida State Statues, Chapter 61 G15-27.001,
I am taking full professional and legal responsibility of the referenced project as of December 22,
2017.
For your information, the entire design process has been rethought and reworked and new plans
have been created and issued for permit.
Should you have any questions regarding the above subject, please do not hesitate to contact our
office.
u
Rodolfo Vil)<mi, P.E.
FL P.E. #61000, SI #7021620
RV/jat
cc: Elliott -Merrill Community Management
i zZ)v W. tau Ualhe Blvd., Suite L 806 Delaware Avenue
Vero Beach, FL 32960 Melbourne, FL 39235 Ft Pierce, FL 34950
771569.0035 321.253.1510 771468.9055
Fax:772.778.3617 Fax: 321.253.091 1 Fax 772.778.3617
1':M BV
ENGINEERING, INC.
MOIA BOW LES VILLAMIZAR & ASSOCIATES
www.mbveng.com CA #3728
March 8, 2019
Mr. Carl Peterson, Building Official
St. Lucie County Building Department
2300 Virginia Avenue
Fort Pierce, FL 34982
Subject: Sands I Condominium — Concrete Restoration
3212 S. Lakeview Circle (Building 10)
Fort Pierce, Florida
Permit #SLC 1704-0525
Engineer's Project Number: 17-0346
Dear Mr. Carl Peterson:
In accordance with the threshold plan, special inspection has been provided for the subject project:
Concrete Restoration at Sands I Condominium Building 10, located on 3212 S. Lakeview Circle,
Fort Pierce, FL. Copies of our inspection reports to date are enclosed for your records.
Based upon inspections performed and my substantiating reports, it is my professional judgment
that, to the best of my knowledge, the inspected work was performed in accordance with the
approved plans, specifications and applicable workmanship provisions of the Florida Building
Code.
Should you have an uestions regarding the above subject, please do not hesitate to contact our
office. p FOIi////�///
V
67p00
RodONO } i Br�} ���
ll
FL P.E. # t'1 ��2•Y 1 N
IIEAG\`
cc: Elliott -Merrill Community Management
1835 20th Street 1250 W Eau Gallie Blvd., Suite L 806 Delaware Avenue
Vero Beach, FL 32960 Melbourne, FL 32935 Ft. Pierce, FL 34950
772.569.0035 321.253.1510 772.468.9055
Fax: 772.778.3617 Fax: 321.253.0911 Fax: 772.778.3617
i•= M BV
ENGINEERING, INC.
MOIA BOW LES VILLAMIZAR & ASSOCIATES
www.mbveng.com CA #3728
March 8, 2019
Mr. Carl Peterson, Building Official
St. Lucie County Building Department
2300 Virginia Avenue
Fort Pierce, FL 34982
RECEIVED
MAR 11 2019
ST. Lucle County, Permitting
Subject: Sands I Condominium — Concrete Restoration
3212 S. Lakeview Circle (Building 10)
Fort Pierce, Florida
Permit #SLC 7 4-052-
Engineer's Project Number: 17-0346
Dear Mr. Carl Peterson:
In accordance with the threshold plan, special inspection has been provided for the subject project:
Concrete Restoration at Sands I Condominium Building 10, located on 3212 S. Lakeview Circle,
Fort Pierce, FL. Copies of our inspection reports to date are enclosed for your records.
Based upon inspections performed and my substantiating reports, it is my professional judgment
that, to the best of my knowledge, the inspected work was performed in accordance with the
approved plans, specifications and applicable workmanship provisions of the Florida Building
Code.
Should you have any questions regarding the above subject, please do not hesitate to contact our
office. \\�\\\\I IIIIIII///,
II
Very trul No,,
No. 61000
FL P.E. # P-SF �M2.L6i
iA/A IEIAG
RV/jt
cc: Elliott -Merrill Community Management
1835 20th Street 1250 W. Eau Gallie Blvd., Suite L 806 Delaware Avenue
Vero Beach, FL 32960 Melbourne, FL 32935 Ft Pierce, FL 34950
772.569.0035 321.253.1510 772.468.9055
Fax: 772.778.3617 Fax: 321.253.091 1 Fax: 772.778.3617
i•= M BV
ENGINEERING; INC.
MOIA BOW LES VILLAMIZAR & ASSOCIATES
www.mbveng.com CA #3728
February 27, 2020
Mr. Douglas Harvey, Building Official
St. Lucie County Building Department
2300 Virginia Avenue
Fort Pierce, FL 34982
Subject: Sands I Condominium — Concrete Restoration
Bldg. #1-3206 S. Lakeview Circle — Permit No.: SLC 1704-0509
Bldg. #3-3210 S. Lakeview Circle — Permit No.: SLC 1704-0512
Bldg. #5-3216 S. Lakeview Circle — Permit No.: SLC 1704-0515
Bldg. #6-3207 S. Lakeview Circle — Permit No.: SLC 1704-0517
Bldg. #7-3218 S. Lakeview Circle — Permit No.: SLC 1704-0520
Bldg. #8-3209 S. Lakeview Circle — Permit No.: SLC 1704-0522
Bldg. #10-3212 S. Lakeview Circle — Permit No.: SLC 104-0525
Bldg. #12-3215 S. Lakeview Circle —Permit No.: SLC 1704-0529
Fort Pierce, Florida
Engineer's Project Number: 17-0346
Dear Mr. Harvey:
This letter shall serve as a certification that, I, Rodolfo Villamizar, P.E. with the State of Florida
Registration No. 61000, and State of Florida Threshold Inspector No. 7021620, having been
retained as a Special Inspector for the subject project, located in Fort Pierce, FL, based on
inspections performed to the best of my knowledge, belief and professional judgement, the above
described construction of all structural load -bearing components complies with the permitted
documents submitted to Saint Lucie County.
Final inspections were performed on the concrete restoration items, including concrete beams,
concrete columns, concrete slabs, concrete stairs, storm shutters and the replaced aluminum
railings. \� \\\1III II/////
Should gimsgjis�regarding the above subject, please do not hesitate to contact our
office. lb 000
V 1 o Nc '` F_ s ,'
oz
G,
Ro o / .1P�' �\ FEB 2 7 2020
FL P.E. #
RV/it
iI Ucle lI lY 1:i Y
1835 20th Street 1250 W. Eau Gallie Blvd., Suite L 806 Delaware Avenue
Vero Beach, FL 32960 Melbourne, FL 32935 FL Pierce, FL 34950
772.569.0035 321.253.1510 772.468.9055
Fax: 772.778.3617 Fax: 321.253.091 1 Fax: 772.778.3617
i•:M Bel
ENGINEERING, INC.
MOIA BOWLES VILLAMIZAR & ASSOCIATES
www.mbveng.com CA #3728
February 27, 2020
Mr. Douglas Harvey, Building Official
St. Lucie County Building Department
2300 Virginia Avenue
Fort Pierce, FL 34982
Subject: Sands I Condominium — Concrete Restoration
Bldg. #1-3206 S. Lakeview Circle — Permit No.: SLC 1704-0509
Bldg. #3-3210 S. Lakeview Circle — Permit No.: SLC 1704-0512
Bldg. #5-3216 S. Lakeview Circle — Permit No.: SLC 1704-0515
Bldg. #6-3207 S. Lakeview Circle — Permit No.: SLC 1704-0517
Bldg. #7-3218 S. Lakeview Circle — Permit No.: SLC 1704-0520
Bldg. #8-3209 S. Lakeview Circle — Permit No.: SLC 1704-0522
Bldg. #10-3212 S. Lakeview Circle — Permit No.: SLCNffl 4=G5.2--5ft3
Bldg. #12-3215 S. Lakeview Circle — Permit No.: SLC 1704-0529
Fort Pierce, Florida
Engineer's Project Number: 17-0346
Dear Mr. Harvey:
This letter shall serve as a certification that we have performed all the special inspections to review
the installation of the exterior aluminum railings at the subject project. A final railing inspection
including all the entry and stair railings of each building was completed on February 20, 2020.
To the best of my knowledge and belief, I certify that the installation and connection work
performed co OW WU011Q,p rida Building Code 2017, 6'h Edition. Should you have any questions
regarding t �� t e ase do not hesitate to contact our office.
Ve 610�� flaC r� yam,;
11+ —
�W=
y — FEB 2 7 2020
5(P� Cy�?G,i� �;:r E I.`zitll Bent
R o , �R - a. �� Per, I s;Ltln�7 _.
FL P.E. # �� � 7liB � St. Lucie CountIL-1--i
L
RV/it
cc: Mike G. -Elliott Merrill Community Management
1835 20th Street 1250 W. Eau Gallie Blvd., Suite L 806 Delaware Avenue
Vero Beach, FL 32960 Melbourne, FL 32935 Ft. Pierce, FL 34950
771569.0035 321.253.1510 772.468.9055
Fax: 772.778.3617 Fax: 321.253.091 1 Fax 772.778.3617
i=M BV
ENGINEERING, INC.
MOIA BOWLES VILLAMIZAR &ASSOCIATES
www.mbveng.com CA #3728
January 20, 2020
Mr. Douglas Harvey, Building Official
St. Lucie County Building Department
2300 Virginia Avenue
Fort Pierce, FL 34982
Subject: Sands I Condominium — Concrete Restoration
Bldg. #1-3206 S. Lakeview Circle —Permit No.: SLC 1704-0509
Bldg. #3-3210 S. Lakeview Circle — Permit No.: SLC 17A4-0512
Bldg. #5-3216 S. Lakeview Circle — Permit No.: SLC 1704-0515
Bldg. #6-3207 S. Lakeview Circle — Permit No.: SLC 1704-0517
Bldg. 97-3218 S. Lakeview Circle — Permit No.: SLC 1704-0520
Bldg. #8-3209 S. Lakeview Circle — Permit No.: SLC 1704-0522
Bldg. #10-3212 S. Lakeview Circle — Permit No.: SLC
Bldg. #12-3215 S. Lakeview Circle — Permit No.: SLC 1704-0529
Fort Pierce, Florida
Engineer's Project Number: 17-0346
Dear Mr. Harvey:
This letter shall serve as a certification that we have performed all the special inspections to review
the installation of the exterior hurricane storm shutter structures at the subject project. A final
shutter inspection was completed on December 12, 2019.
To the best of my knowledge and belief, I certify that the connection installation work performed
complies with Florid �niWing Code 2017, 6g' Edition. Should you have any questions regarding
the above subjept�� d616ot hesitate to contact our office.
t't c F,Vs',9s
10.61000
p0p y
q7_P__ _
FL P.E. #
'/// VA I IIFIMI I\N
RV/jt10
cc: Mike G. -Elliott Merrill Community Management
1835 20th Street 1250 W. Eau Gallie Blvd., Suite L 806 Delaware Avenue
Vero Beach, FL 32960 Melbourne, FL 32935 Ft Pierce, FL 34950
772.569.0035 321.253.1510 . 772.468.9055
Fax: 772.778.3617 Fax: 321.253.091 1 Fax 772.778.3617
INDIAN RIVER ELECTRIC, INC.
P. O. Box 2166
Vero Beach, FL 32961
Phone: 772-567-5302
Fax: 772-567-1607
June 7, 2018
Velocity Services Group
2300 Hollowman St., Suite 101
Conroe, Texas 77301
Attn: Mr. David Hyatt
Regarding our conversations about the GFI outlets inside anclon each unit. As you
know, there are in excess of 110 GFI outlets in question. All outlets in question are
currently GF1 protected by a GFI circuit breaker in each electrical panel of each unit.
To change all outlets to GFI receptacles is redundant and unnecessary. Changing to
GFI outlets is aproblem. Most of the outlet boxes in question will not accommodate a
GF1 outlet. Having redundant GFI devices will require access to each unit for at least one
hour to remove GFI breaker and install new non-GFI breaker at cost to owner/
association. This will require a representative for supervision of each unit.
Indian RiverElectric can demons rate -to one and-all-tbat t1woutlets-ingnestim are
GFI Proms by a testing device. Redundant GM devices on any circuit may cause one
or more devices to trip, requiring resetting all GFI devices, producing a nuisance to each
homeowner with no added protection to residence.
In addition, as you know in each unit all bath and outside outlets must be GFI
Protected per national electrical code, as they currently are as wired, originally.
Ifyou have any questions or comments Please contact Judd Barker at Indian River
Electric byway of Velocity Services.
Sincerely,