HomeMy WebLinkAboutDRAWINGS FROM COMMENTS BY COUNTYIt Advanced Architecture & Planning LLC Architect & Planning 4929 S. Indian River Drive RECU. ED MAY 22 7017 Ft. Pierce, FL 34982 (772)631-5709 Florida License No. AA26002573 Drawings from Comments by County May 19, 2017 at;ANNED St. Lucie County BY ;t I nCia i;0U11tV ®® Plan Review FILEEGOPY Building Department For Pierce, FL Re: Barbell Club Permit #: 1705-0161 PALM PLAZA, 8447 S. US#1, PORT ST. LUICE, FL 34952 The following changes are in response to Plan Review comments and have been clouded and dated. HVAC: See Page Al. Ventilation/Fresh Air adjustment required for Gym use; Plumbing: 1. Occupancy to remain as previous. See Page COV; 2, To have separate gender restrooms would circumvent the ADA Code exception for Disproportionate Costs as identified on Page COV. My professional understanding is that the Accessibility Code always supersedes the other Codes should there be a conflict. (2) restrooms are arovided and must be Unisex to avoid ADA gender discrimination: 3. See Al. Service sink added; 4. See Al. Water heater added; Building: 1. See Page COV: Occupants <50 so changed to Business Occupancy & 1 hr fire walls OK; 2. See Page Al for Cross locations & dimensional requirements; 3. See Page COV. Typo removed, 4. See Page COV. Finishes & Flame Spreads; 5. See Page COV for <50 occupants & panic hardware not required; 6. See Page Al: Door swing reversed in non-ADA restroom; If you have any questions, please contact me at any time. Sincerely, Raymond Chladny, B.arch.Sc., March, AIA MAAA, MFAID, NCARB, Florida License No. AR-0017475