Loading...
HomeMy WebLinkAboutSUBMITTED PAPPERSFRASER ENGINEERING AND T 3504'VDUSTRIAL 33rd STREET. FORT PIERCE • FLORIDA VERO BEACH(561) 567-6167 FMi{ PIERCE(561) 461-7508 SNART(561)283-771 Report of DENSITY OF SOIL IN PLACE ASTM D29�2 1 CLIENT: Bayview Construction Corporation �\ CONTRACTOR: Client Date: SITE: Twin Oaks - Alzheimers + Daycare Center Foundation Fill - Kitchen Bldg. PERM] DENSITY TEST NO. 112 113 114 115 116 117 118 119 120 DATE TESTED 6/14/99 Copies: Client; M .W. Comer 0 - 1' I - 2' 2-3' enter 0 - 1' 1 - 2' 2-3- I.E. Comer 0 - 1' I - 2' 2-3' ALL ELEVATIONS BELOW SLAB GRADE 101 County IN DRY WT.797.5 YERCE4+1 118.7 Ou �=— \��297.6 ' 95.2 `96.1 97 795.496.5 97.5 Respectfully submitted FRASER kENGRING-AND TESTING INAV,Alexander H. Fraser, P.E: Fla. Reg -No. I6178 FOUNDATION INVESTIGATIONS WNCRETE, SOIL. AND ASPHALT REQUEST FOR 30 DAY TEMPORARY POWER RELEASE - DATE: SL z7 9p PERMIT NUMBER: > PROPERTY AODFF:EESS: Lucie County Comm. Devel. Dept. Code Compliance Division 2300 Virginia Avenue Fort Pierce, FL 34982-5852 Ph. (561) 462- 2165 Fax (561) THE UNDERS113NED HEREBY REQUEST RELEASE OF ELECTRICAL POWER TO THEJABOVE DESCRIBED PROPERTY, FORA PERIOD NOTTO EXCEED THIRTY (30) VAYSf FOR TH H PURPOSE OF TESTWt3 SYSTEMS AND EQUIPMENT IN PREPARA- TION FOR FINAL INSPECTION. IN CONSIDERATION OF APPROVAL OF THIS .. REQUEST WE HEREBY ACKNOWLEDGE AND AGREE AS FOLLOWS: 1. This temporary power release is requested for the above stated purpose only, anc there wi8 be no occupancy of any type, other than that permitted, by constriction during this time period. 2. As wit ness by our signatures, we hereby agree to abide by all terms and conditior s of this agreement, including Building Division Policy, which Is incorponited herein by reference. - 3. All conditions and requirements listed in the attached document entitled "Requirements for 30 Day Power for Testing" have been fulfilled and the premise:I is ready for compliance inspection. We hereby release and agree to hold harmless, St Lucie County, and their employees from all Ilabilitics and claims of any type or nature which may arise now or in the future out of this tra isaction, Including any damages which may -be Incurred due to the disconnection j)f electrical power in the event of violation of this agreement DEC 2 8 1999 8bTTZ9b : '0N 3NOHd T d WdeS:OT 6667'T '00N St. Lucie County RubfimdWrks P.O. BOX 3030 FT. PIERCE FL. 34948-3030 2400 RHODE ISLAND AVE. ? FT. PIERCE FL. 34950 ST. LUCIE COUNTY FIRE DIST91 BUREAU OF FIRE PREVENTION PLAN REVIEW JURISDICTION Saint Lucie County OCCUPANCY: Twin Oaks Complex ADDRESS: 3461-3463-3455 & 3451 Midway Rd. CONTRACTOR: Ronald Ringo CONTRACTORS ADDRESS: 3399 SE Golf Trail ARCHITECTIENGINEER: Ahern and Associates BUILDING OWNER: International Alzheimees Foundation OCCUPANCY TYPE: Assisted Living, Ktithen and Business GROSS SQ FT: Indicated below. OCCUPANT LOAD: Varies CONSTRUCTION TYPE:( NFPA-220) Type :111-(200) New Construction: X Tenant Improvement: Shell Only: Addition: Renovation: Fire Alarm System Fixed Fire Suppression: Hood & Duct System: Fuel Storage: Contractor: Contractor. Contractor. Contractor: TELEPHONE FAX NO. (561)-462-2312 (561)-462-2323 F.P.B. # 1125 BUILDING DEPT. NO: 0234. 0239.0244 & 0249 NUMBER OF STORIES:1 Story & two story PHONE NO: (561)2883592 CITY: Sturt, FL. 34997 PHONE NO: (561)-220-8907 REVIEW DATE: 3.31-99 SP'KLRS: Yes NET SQ FT: BASED ON: SBCCI: Type: V-Unprotected. 1. All revisions must be in compliance before the final inspection, or so noted. 2. The Fire Marshal requires 24 hr. notice on all inspections. 3. The Building Departments schedule all final inspections by the Fire Marshal. 4. A copy of the required revisions has been mailed to the Architect: _ Contractor: _ Yes: _ No: X Required Revisions: This permit is for the construction of two 34 bed Assisted Living Facilities. Main Kitchen and a Administration/assisted living facility Assisted Living Facility Buildings A and B: Large facilities: 12,800 sq ft Gross: 1. With the installation of an automatic sprinkler systm a single attic draftstop will required so no area will exceed 9,000 sq ft. 2. The walls across the corridor separating the main reception area from the living area are not indicated as being a rated wall assembly or a smoke partition. If the doors in this wall are protecting the opening for a smoke wall then an additional detector is required on both sides of the door opening. Not indicated in the right corridor. 3. A Fire Alarm Annunciator panel is indicated at each nurses station. The Fire alarm indicating devices shall be connected to a zoned fire alarm control panel. The annunciator panel is then connected to the fire alarm control panel. 4. Chimes are indicated as audible signaling devices. They are permitted but must be heared above the ambient noise level by a minimum of 15 DbA. with the doors closed. KA J Twin Oaks. March 31, 1999 Page No. 2. 5. The individual sleeping rooms indicate a strobe unit in each of these rooms. Audible indication is also required. A Mini- home -Strobe indicating device is permitted. 6. Provide a 2A-10 BC rated fire extinguisher for each 75 ft of travel distance. Kitchen 1. Provide a 3A-40 BC rated fire extinguisher for each side of the cooking appliances. 2. A separate permit is required for the installation of the required fixed fire protection system Installation shall be by a Fl. Certified Contractor for fixed fire protection systems. Administation - Adult Day Care 1. The stairway enclosure has to be protected with a Class B, 1-hour rated door and jamb assembly equipped with a listed self -closing device. See doors marked F-4 and S-1. 2. The corridor door marked F-4 must also be a Class B, 1-hour rated door and jamb assemble if if the door is installed in a 1-hour rated fire rated assembly, If these walls are smoke partitions the doors need to have a fire resistance rating of 20 minutes. A latching device is not required in a smoke partition door. 3. Provide a 2A-1 OBC rated fire extinguisher for each 75 ft of travel.. Fire Alarm System: 1. Installation of the fire alarm system will require a separate permit from the Fire Marshals office. Installation shall -be by a FL. Certified alarm contractor or electrical contractor (EC). 2. Because the automatic sprinkler system has to be supervised by a central station facility or remote station facility, the fire alarm system is also required to be monitored. See enclosed attachment. Automatic sprinkler system: 1. See attached requirements for the installation of the automatic sprinkler system. 2. Thrust blocks are not permitted for the underground sprinkler piping. Mechanical restraints are required in lieu of thrust blocks. `J Twin Oaks March 31, 1999 Page 3. 3. The assisted living buildings may be protected with a N.F.P.A 13-R system instead of a standard 13 system if you wish. All clients must be capable of fast evacuation (3 minute evacuation) to the building exterior or a 1-hour rated corridor. 4. Fast responce of residential sprinklers are required in all rooms used for sleeping. H V.A.0 System: 1. The H.V.A.0 notes idicating automatic fan shut -down. Note that the listed duct detectors must be installed in the suply air. 2. Duct detectors shall initiate a supervisory and trouble signal in the fire alarm control panel and the fire alarm annunciator panel or initiate a general evacuation signal. 3. All kitchen facilities must be protected with a commercial hood and duct system in accordance with N.F.P.A Standard 96,.if there is cooking that will cause a grease laden vapor. Review ;��Date: March 30 , 1999 Joh�KHayde r V o INTERNATIONAL ALZHEIMER'S FOUNDATION TRUST, INC. 2277 SW OLYMPIC CLUB TERRACE PALM CITY, FLORIDA 34490 March 10, 1999 Department of Community Development Division of Growth Management 2300 Virginia Ave., #201 Gentlemen: Please be advised that we will provide a copy of the HOOK-UP AGREEMENT prior to the issuance of a Certificate of Occupancy. All fees wil have been paid in full by then. Sincerely S COSENTINO PRESIDENT o INTERNATIONAL ALZHEIMER'S FOUNDATION TRUST, INC. 2277 SW OLYMPIC CLUB TERRACE PALM CITY, FLORIDA 34490 March 10, 1999 Department of Community Development Division of Growth Management 2300 Virginia Ave., 4201 Gentlemen: Please be advised that we will provide a copy of the HOOK-UP AGREEMENT prior to the issuance of a Certificate of Occupancy. All fees wil have been paid in full by then. 61 3 COSENTINO IDENT Whole Building Performance Method for Commercial Buildings Form 400A-97 ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION Florida Department of Canwnity Affairs FLA/COM-97 Version 2.2 0= MMF_TWIN OAKS ASSISTED LIVING PERMITTING E OFFICE. AL7 S. , M LUCIE 00 CLnaTE ZONE: _6 .+jOWNER: 'TWIN OAKS PERMIT NO: AGENT: - _. JURISDICTION NO: 661000 BUILDING TYPE: Institutional (Health) CONSTRUCTICN OMMITION:..New construction DESIGN 00MPLETICN: Finished Building CONDITICNED.FLOOR AREA: I2800. NuMBER.OF ZONES: 11 MAX. TONNAGE OF EQUIPMENT PER SYSTEM: _ 5 CaeLIMCE CALCULATION: METHOD A DESIGN CRITERIA A. WHOLE BUILDING 61.94 100.00 PRESCRIPTIVE REQUIF12WnS: LIGHTING EXTERICRt LIGHTING 675.00 1100.00 LIGHTING CONTROL REQUIREMENTS HVAC EQUIPMENT CDOLING EQUIPMENT 1. SEER 10.00 10.00 2. SEER 10.00 10.00 3. SEER 10.00 10.00 4. SEER 10.00 10.00 5. SEER 10.00 10.00 6. SEER 10.00 10.00 7. SEER 10.00 10600 8. SEER 10.00 10.00 9. SEER 10.00 10.00 10. SEER 10.00 10.00 11. SEER 10.00 10.00 HEATING EQUIPMENT 1. Et 1.00 i' 2. Et 1.00 3. Et 1.00 _ 4. Et 1.00 5. Et 1.00. 6. Et 1.00 7. Et 1.00 8. Et 1.00 9. Et 1.00 10. Et 1.00 11. Et 1.00 AIR DISTRIBCPTIOK SYSTEM INSULATION REQUIR[R43VTS 1. Unconditioned Space 4.20 4.20 w RESULT .�,vi,�,4� PASSES PASSES PASSES PASSES PASSES PASSES PASSES PASSES PASSES PASSES PASSES PASSES PASSES N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 2. Unconditioned Space 3. Unconditioned Space 4. Unconditioned Space 5. Unconditioned Space 6. Unconditioned space 7. Unconditioned Space 8. unconditioned Space 9. Unconditioned space lo. Unconditiened space 11. Unconditioned Space REHEAT SYSTEM TYPES USED NO REiIEAT SYSTEM is USED WATER HEATING EQUIPMMT 1. EF 2. EF PIPING INSULATION REQUIREMENTS 1. Non -Circulating ----------------------------------- COMPLIANCE CERTIFICATION: 11 I ,h#g?1?y gertify tat the plans and specificatimns coveted by WS ealcu- °latica'are in conpl the Florid_Ene P1tEPARffi SY DATE:-U_► I hereby certify that this building is in compliance with the Florida Energy Efficiency Code. - OWNER/AGENT: DATE: 4.20 4..20 PASSES 4.20 4.20 PASSES 4.20 4.20 PASSES 4.20 4.20 PASSES 4.20 4.20 PASSES 4.20 4.20 PASSES. 4.20 4.20 PASSES 4.20 4.20 PASSES 4.20 4.20 PASSES 4.20 4.20 PASSES 0.85 0.80 PASSES 0.85 0.80 PASSES 0.00 ------------------------------------ 0.00 PASSES Review of the plans and specifica- tions covered by this calculation indicates compliance with the Florida Energy Efficiency Code. Before construction is completed, this building will be inspected for crnpliance in accordance with Section 553.908, Florida Statutes. BUILDING OFFICIAL: DATE: " I hereby certify(*) that the system design is in compliance with the Florida Energy Efficiency Code. ARCHITECT 10 N-rk A H e""t� C;1 / rc- MECMICAL PRIDING : ELECl'RICAL: LIGHTING : (*) Signature is required where Florida law requires design to be performed by registered design professionals. Typed names and registration numbers may be. used where all relevant information is contained on signed/sealed plans. BUILDING ENVELOPE SYSM45 401. . ..-a MjW--=M 17- Elevation TYpe North Ccnmeraial nth commercial West commercial 401------- GLAZING--ZCNE Elevaticn Type -------- --------- North cwmercial South C=nercial East commercial 401.------GLAZING--ZONE Elevation Type North Commercial 401 ------- GLAZING --ZONE Elevation Type --------- -------- North commercial South commercial U sC VLT 1.09 .8 •9 1.09 .8 .9 1.09 .8 .9 - Total Glass Area in Zone N 1- M 6117ry Area(sgft); ---- ---------- 37; 13; 109 1 = 159; z----- U SC - c Shadings---- Area(Sgft)! ---------- ---- 1.09 -- ------------ -- .8 .9 37; 1 1.09 •8 •9 1131 1.09 Total .8 :9 Glass Area in Zone 2 = 109 --------------------------v- Area(Sgft)l U SC vLT Shading 1.09 ------------------ .8 .9 ----------, 48' 48; Total Glass Area in Zone 3 = ------------------------------------------------V_ Area(Sgft); U SC VLT Shading -------------- --- -----7-i 1.09 .5 •9' 781 561 1.09 Total .0 .9 Glass Area in Zone 4 = 134: 401.------GLAZING--ZONE ----- -------------------- VLT Shading Area(Sgft) ' Elevation Type U SC ------------------ ---------- 1 ..------------------------ South Commercial ---- ---- 1.09 .8 .9 5 = 481 481 Total Glass Area in Zone 401. ----GLAZING--ZONE 6------------ Area(Sgft}; Elevation Type ._. U SC VLT Shading -: --------2 south Commercial ---- 1 - -------------- -- - 6 = 1 Total Glass Area in Zone 401.------GLAZING--ZONE 7------------ Area(Sgft); Elevation Type ' U SC VLT Shading ------------------ ---------- ------------------------ - mme North Corcial ---- ---- 1.09 .8 .9 7 = 481 48i Total Glass Area in Zone - .c 401.------GT.AZINC--ZONE 8-----------------------------------------t-v- (--f ) Elevation Type U ---- ---- SC VLT Shading ------------------ Ar ----------1 ' North Commercial 1•.09 .8 .9 24 241 Total Glass Area in Zone •8 = 401.------GLAZING--ZONE ------------------------------------ 9------------ Area(Sgft)i Elevation Type U Sc VLT Shading - North --- Commercial 1.09 .8 .9 24; 24, Total Glass Area in Zone 9 = 401. - ---•LAZING--ZONE 10------------ ------------------------------------v- Area ft (Sg )l Elevation Type .. - .-_.. U .---- ---- Sc VLT Shading ---- ------r------- ----------i North Commercial 1.09 .8 .9 24: 241 Total Glass Area in Zone 10 = ----------- 401.^^-' MMING--ZCUE 11------------------- Area ft , -. ------- Elevation TYPe U SC VLT Shading - ---- -------------- ----`----- South Commercial -- 1.09 Total Glass Area in Zone 11 = 161 716; Total Glass Area = i-- ------------------- 402.------ 1--------- ---U-- insul-R--Gross(Sgft); _ Elevation Type _ _-----1- -----------i North +"P1Y/ 6'T4tl Std@24"oc/Rl9/+"GYP •10 1701 1701 south +"Ply/6"Mtl Std®24"oo/R19/+"GyA .10 19 10 -442 West +"Ply/6"Xtl.Std@24"oc/R19/+"GYP Total Wall Area in Zone 1 = 782; 402.------WAS--ZONE 2 ------ -------=--------------------------------i--- U Insul R Gross(Sgft)I Elevation TYPe -__ -----19 ----------- North. +"Ply/6"Mtl Std@24"oc/R19/+"Gyp 10 Std@24"oc/R19/+"GYP .10 19 1701 1701 South +"ply/6'44tl +Ply/6""Mtl Std@24"oc/R19/+"GYP .10 19 442 782, East Total Wall Area in Zone 2 = 402.------WALLS--ZONE 3--------------------- ------- U Insul R Gross (Sgft)1 Elevation Type ------------ -----------i ----^---- ------------- North19 +"Ply/6"Mtl ------------------- Std@24"oo/R19/+"Gyp .10 19 161 1681 West +"ply/6"Mtl +"Ply/6"Mtl Std@24"oc/R19/+ Gyp •10 19 Std@24 oc/R19/- Gyp 10 681 , 252' East Total Wall Area in Zone 3 = 402-------WALLS--ZONE 4---------'---'- - U Insul R Gross(Sgft)� Elevation TYPe ------------ -----------1 •----------------------------------------- East +'rely/6"Mtl Std@24"oc/R19/+"Gyp •10 19 19 , 102, 1021 102 West +"Ply/6"Mtl " . + Ply/6'Mtl Std@24"oc/Rl9/+"Gyp .10 " Std@24 oc/Rl9/+'Gyp .10 19 North South +"Ply/6'44t1 Std@24 oc/R19/+ Gyp •10 19 " 4 =� 2351 235i_-- Total Wall Area in Zone 402-------W�+S--ZONE ------------- 5---- U Insul R _-_ Gross(Sgft); Elevation Type ------------ -----------; South +"Ply/6'24t1 Std@24"oc/R19/+"Gyp '10 19 Total Wall Area in Zone 5 = 4601 ------------------ ----1-_- 402-------- WALLS --ZONE 6-------------------------- U Insul R Gross(Sgft); Elevation TYPe ------------ -----------; --------------------- ------------------ South +"ply/6"Mtl Std@24"oc/R19/+"Gyp .10 19 6 = 230: . 230{ Total Wall Area in Zone 402.------WALLs--Z� 7--------- ------------ U Insul R --------- ;--- Gross(Sgft); " Elevation Type ------------ -----------; ___ -------------------------------- North +"Ply/6'Utl Std@24"oc/R19/+"GYP .10 19 7 = 460; 460 Total Wall Area in Zone -------------------�--- 402.-----'ELLS-'ZONE 8-------'--------------------- U Insul R Gross(Sgft); Elevation Type ----- ------- -----------i .- ----- -------------------------------- North +"Ply/6"Mtl Std@24"oc/R19/+"Gyp .10 19 8 = 230, 230, Total Wall Area in Zone ---------------------i--- 402.----- WAI.IS--ZONE 9-------- U Insul R Gross(Sgft); Elevation TYPe --------- ------- -----------; North +"ply/61,Mtl Std@24"oc/R19/+"Gyp .10 19 , 115, East +^ply/6"Mti Std@24" oc/R191'P Gyp .10 oc/R19/- Gyp .10 19 17 West +"ply/6"Mtl Std@24 Total Wall Area in Zone 9-=_____________1___ ------ 117 102.---'-' ,l,g--ZG11E.10--------- U Insul R Gross(SgfQ'I -Elevation Type-------- - -- -----------1 ----------------------------------------- North +"ply/6"Mtl Std@24"oc/R19/+^Gyp 10 19 19 , 1341 yiest +"ply/6'Utl Std@24"oc/R19/+"Gyp .10. 19 17, -- East +"ply/6"Mtl Std@24"oc/R19/+"Gyp •10 Wall Area in Zone 10 = 166; Total -__^_1 ------- 402.-----i4ALLS--ZONE 11-------------------------U Insul R Gross(Sgft); Elevation Type ----- ------- -----------I ---------------1---- South +"ply/6'11tl Std@24"oc/R19/+"GYP .10 19 19 2301 68; West +"Ply/6"Mtl Std@24"oc/R19/+ GYP .10 ••10 19 East +"ply/6"Mtl Std@24"oc/Rl9/+"GYP Total Wall Area in Zone 11 = 3661 4568; Total Gross Wall Area = - __1-__ - -------------------------- 403.------DOC)RS--ZONE 1----------------- - U Area(Sgft)i Elevation Type - ---- ----------' ------------------------------------------------- North 1-3/4 Steel Door-Fiberglass/Mineral woo 0.60 0.60 51 51 South 1-3/4 Steel Door-Fiberglass/Mineral woo 51 West 1-3/4 Steel Door-Fiberglass/Mineral woo 1 1 = 15; Total Door Area in Zane ------- 1--- 403.------DOORS--ZONE 2------'-'------------ -------------- U Area(Sgft) Elevation Type ------------- ----- ----------� ----- ---------------------------- North----- 1-3/4 Steel Door-Fiberglass/Mineral woo 0.60 5 5 South 1-3/4 Steel Door-Fiberglass/Mineral woo 0.60 5: East 1-3/4 Steel Door-Fiberglass/Mineral woo 2 = 15 Total Door Area in Zone _-_-1--_ 403------- DOORS --ZONE 3---------- ---------------------------------- U Area(Sgft), Elevation TYPe ----------' North 1-3/4 Steel Door- 3 60 01 talssDoor Area in Zone 403.- __DOORS--zCNE 4------------------- -------------- ---------------i--- U Area(Sgft)I Elevation TyPe ----- ----------i North 1-3/4 Steel Door-Fiberglass/Mineral woo 0•60 201 East 1-3/4 Steel Door-Fiberglass/Mineral woo 0.0 48 oo West 1-3/4 Steel Dr-Fiberglass/Mineral woo 4 891 Total Door Area in Zane ----------------- - . 403.------DOORS--ZONE 5--------''-'-- U Area(Sgft)i Elevation Type --- ----- ----------; North 1-3/4 Steel Door-Fiberglass/Mineral woo 0.60 5 = 01 Total Door Area in Zane --- ___-_-__1___ 403.------DOORS--ZONE 6--------'---- ------ U Area(Sgft)l Elevation Type ----------' ---------------------- ----- -- -- ------- North 1-3/4 Steel Door-Fiberglass/Mineral woo 0.60 0;. 014 Total Door Area in Zone 6 = 403.------DOORS^-ZCSVE 7----------------------------`- ----- U - Area(Sgft): Elevation Type ------^----- ------- ----- ----------i ?; 03/11/1999 01:46 8003870692 ABBOTT&ASSOCIATES PAGE 06 !torch 1-3/4 Steel Door -Fibs woo 0.60 01 01 Total9lawAUmral Door Area in Zone 7 403.-. .--DOOli3--DOORSZONE 8------------- -------------- U Area(Sgft), Elevation Type -------- ----- ----------1 --------- r------------------------ 1-3/4 Steel Door-Fiberglass/Mineral woo - 0.60 101 North Total Door Area in Zone 8 = -------------------------------1--- 403.------DOORS--ZONE 9---------------7- U Area(Sgft) Elevation Type ----- ---------- ----- ---------- North - 1-3/4 Steel-Door-Fiberglass/Wneral woo 0.60 Oi 01 Total Door Area in Zone 9 = --- 403.----=-DOORS--ZONE 10--------------------------------------------- U A=ea(Sgft)--- Elevation Type --------- ----- ^_-__-----1 1 --'-------------- ------------------------- North 1-3/4 Steel Door-Fiberglass/Mineral woo 0.60 0 Total Door Area in Zone 10 = 403------- DOORS --ZONE 11------------------------------------------------ U 1- -- Area(Sgft); Elevation Type ----- --------------------- ----- - ----------1 1 --------------------- North 1-3/4 Steel Door-Fiberglass/Mineral woo 0.60 0 Total Door Area in Zone 11 = Total Door Area = 1.191 404.------BOGIES--ZGNE 1---------------^------------------------------ --i--- , R Area(Sgft)1 Type Color U Insul -- ------------ ---------- -y-^------^----------- ------- ------ SbWI/l/2'VD DedoM Truss/9 Bm.b Medim 0.0270n6 1157 130 "t to ain 11571, ----}mob's--Zran? 1------------------------------------------- 2�a - --- a ------- - ------------------------ ------ Sltngl/1/2"G7D I]ECk/WD TrUss/919 BMediun 0.027 11571 Total Roof Area inZone 230 11571 404------- RoOFS--ZONE 3------------------------------------ =-----------1--- Insul R Area(Sgft)1 Type Color U ------ ------------ -- --1 ------------------------------------ un 0.02 Shngl/1/2"WD Deck/WD Truss/9" BTotal Roof in Zone .330 2392; 4o4------- ROOFS--ZCNE 4------------------------------------------------ 1--- U Insul R Area(Sgft)1 Type Color ----------; ------------------------------------ ------ ----- ------- Shagl/1/2"WD Deck/WD Truss/9" BTotal 20431 Roof Area0.02in Zone 430 20431 - 404.------Ro0FS--ZONE 5 ------------------------------------------------ Insul R Area(Sgft), Type Color U ------------------------------------ ------ ------------ ----------1 0.02 Shngl/1/2'WD Deck/WD Truss/9" BTotal 1336,1 R�Areaun in Zone 530 13361 404. ROOFS--ZCNE 6------------------------------------------------ i--- Type color U Insul R Area(Sgft)1 ---- ------------- ------ -----• ------- ----------1 M mgl/1/2'WD Deck/WD Truss/9" B Medium 0.027 30 6681 Total Roof Area in Zone 6 = 668: 404------- RCVS--ZOIE 7---------------- -------------------------------- ;--- Type Color U Insul R Area(Sgft), ------------------------------------ ------ ------------ ----------1 Sbngl/1/2"WD Deck/WD Truss/9" B Median 0.027 30 13361 Total Roof Area.in Zane 7 = 13361 03/11/1999 --------------i--- ------------- - 404.------ROOFS--ZONE 8---------------Color U Insul R Area(sgft), Type ----- ------- ------- ------------- ------ -'- 30 •_ Medium 0.027 2.1/1/2"WD >� Truss/9�� B ZoW6681 B ----------, 6681 Total Roof Area -------------1--- -- ---- 404.------ --ZM 9---------------- Color U Insul R Area(Sgft){ Type ------------ ------ 11 -------6� _-e%9„ B ---- '-------- 0.027 30 ----------- M�ium DeOk/WD 9 = 6681, Sla►gl/1/2"WD Total Roof Area in Zone -------------------1--- 404. -----ROOFS--ZONE 10---------------Color -- U Insul R Area(Sgft)i Type------- --------=------------'-- Deck/= Truss/9" B Median 0.027 10 = ----------� 7161 7161 Shngl/1/2"WD Total Roof Area in Zone ---------I--- -Colo------- ----------- ZO'NE 11- Insui R 404.------R�-- -------------- Color U- Area(Sgft)1 Type ---------- ------------------------- Slugl/1/2"WD Deck/WD Truss/9" B Medium 0.027 30 in Zone 11 = 6591 Total Roof Area Total Roof Area = 128001 -- ---------------- ---I--- 405.------FfA0R5-ZCUE 1--------------------------- Insul R Area(Sgft)1 Type------- ----------{ ------------------------------------------------ p 1157, Slab on Grade/Uninsulated Total Floor Area in Zone 1 = 11571 ----------I--- ------------------ 405. •--FIows-ZONE 2-------------------- Insul R Area(Sgft)i Type ------- ------------ ----------i p 11571 Slab on Grade/Uninsulated Total Floor Area in Zone 2 =-------------1--- 11571 ------------ 405.------FLOORS-ZCNE 3----------------------- Insul R' Area(Sgft)I Type ------- ------------ ----------I ---- 0 Slab on Grade/Uninsulated .'' ' Total Floor Area in Zone 3 = 23921 23921 ---�--- , ------------------------------ 405------- ER.00RS-ZGNE 4--------------- Insul R Area(Sgft)1 Type---------------- ----------1 ------------------------------- -------- p 20431 Slab on Grade/Uninsulated Total Floor Area in Zone 4 = 20431 --------------------------�--- 405.------FLOORS-ZONE 5------------------ Insul R Area(Sgft)I T7pe------0 ----------, 1 ----------------------------------------------- slab on Grade/Uni.nsulated = � Total Floor Area in"Zone 5 = 13361 13361 --- ----------------------- 405.------FIAORS-ZONE 6----------------- Insul R --- Area(Sgft)I Type ------- ---------- ----------------------------------- Slab on Grade/Uninsulated . 0 Total Floor Area in Zone 6 = 1 668, 6681 405------- FLOcHs-ZCNE 7-----------` ---- insul R Area(Sq£t)i Type Slab on Grade/Uninsulated 0 7 - 1336, Total F1oor.Area in Zone 405------- FLoCRS-ZONE e^-------------------------- Insul R ----1336,--- Area(Sgft)I ------------- - - - - - - - slab on Grade/Uninsulated 0 8 = ----------� 6681 668; Total Floor Area in Zone 405------- FLOORS -ZONE 9------------------------------- Insul R Area(Sgft), Type ------------------- ---------- _ Slab on Grade/Uninsulated 0 9 =-------------- 668; 6661 Total Floor Area in Zone 405. --FLOORS-ZONE 10------------------------ ---- Insul R =-----1--- Area(Sgft)1 ype ------- T------------------ ----------1 •---------- Slab an Grade/Uninsulated 0 10 7161 7161 Total Floor Area in Zone .= 405.------FLOORS-ZONE 11------------------------------------------------ R 1--- Area(Sgft) Type Insul ----------1 ----------------------------------------- ------- slab on Grade/Uninsulated 0 6591 6591 - Total Floor Area in Zane 11 = Total Floor Area = 128001 406.------INFILTRATION -------------------------------------------------- 1--- :CHECK: Infiltration Criteria in 406.1.ABCD have been met. 1 1 MECHANICAL SYSTEMS -------'-----'--- HVAC load sizing has been performed. (407.1.ABCD) 1 1 407.------COMING SYSTEMS--------------------'-'-" ---------------------- --- Tons) Type No Efficiency IPLV ------ ------------- -------------------1 1. -------------------- Split System 1 10 10 10 10 5.001 5.001 2. Split System 1 2 10 10 3.001 3. Split System 1 10 10 4,001 4. Split System 4 10. 10 1.501 5. Split System 2 10 10 1.50: 6, Split System 4 10 10 1.501 7. Split System 2 10 10. 1.501 S. Split System 2 10 10 1.501 9. 10. Split System Split System 2 10 10 1.501 11. Split System 2 10 10 1.50: 408.------HEATING SYSTEM ---------------------------- ------------------- --- TYBe No Efficiency E;TU/hr1 --------- ----------------------- ---------------------------1 1. Electric Resistance 1 1 250001 2. Electric Resistance 1 1 250001 3. Electric -Resistance 2 1 250001 4. Electric Resistance 1 1 250001 5. Electric Resistance 4 1 100001 6. Electric Resistance 2 1 100001 7. Electric Resistance 4 1 100001 8. Electric Resistance 2 1 100001 9. Electric Resistance 2 1 100001 10, Electric Resistance 2' 1 100001 11. Electric Resistance 2 1 100001 409.------VENTILATION---------------------------------------------------1--- :CHECKI Ventilation Criteria in 409.1.ABCD have been met. 1 1 " ___--__ _______1 410.-----AIR DISTRIBUTION SYSTEM-------- _-_ 1 ------------------------1 ___ _ Duct sizing and design have been Performed. (410.1.ABCD) Duct Location R-value; ARU Type -------i - ----------------- Unconditioned Space 4.2; 1. Air Conditioners Unconditioned Space 4.2; 2. Air Conditioners unconditioned Space 4.21 3. Air Conditioners Unconditioned Space 4.2; 4. Air Conditioners Unconditioned Space 4.21 5. Air Conditioners Unconditioned Space 4.21 6. Air Conditioners Unconditioned Space 4.21 7. Air Conditioners Unconditioned Space 4.21 S. Air Conditioners Unconditioned Space 4.21 9. Air Conditioners unconditioned Space 4.21 10. Air conditioners Unconditioned Space 4.2' U. Air Conditioners Ogm; ----------------------------------------------- Testing and balancing will be performed. (410.1.ABCD) 1 411. -----pITAlPS AND PIPING -ZONE -^----- --------------------- Basic prescriptive requireients in 411.1.ABCD have been met. 1 ' PLUMBING SYSTEMS 411.-----PUMPS AM PIPING -ZONE Type ------------------------ 4b1.-----PUMPS AND PIPING -ZONE Twe ---------------- 411.-----PUMPS AND PIPING -ZONE Type ------------------------ 1. Non -Circulating 411.-----PW S AND PIPING -ZONE. Type ------------------------ ' 411. --PUMPS AND PIPING -ZONE Type 411------ PUMPS AND PIPING -ZONE Type _ ---------------^----- 411------ PUMPS AND PIPING -ZONE Type------------------ - 411------ PUMPS AND PIPING -ZONE Type ---------------------- 411.-----PUMPS AND PIPING -ZONE Type -----.__ R-value/in Diameter Thickness! ---------- -------- ------- 1 -- 2- ^ R-velut/in Diameter- Thickness ------------------------------ ----------- R-value/in Diameter Thickness: -------- -------- 1 0' 1 ----------------i--- R-value/in Diameter Thickness: ---------- -------- -------- 1 --------------------i--- R-value/in Diameter Thickness! ---------- ---- 1 .. R-value/iri Diameter Thickness' ------------------ ------- --------------'--- R-value/in Diameter Thickness! ---------------------------1 --------------'--- R-value/in Diameter Thickness; ---------- -------- ------- { -------------------- --- R-value/in Diameter Thiclmess; -----------------' 411.-----PUMPS AND PIPING -ZONE 10------------------------------ Type R-value/in Diameter Thickness; --- -- ' ------------------------ _ 411.-----PUMPS AND PIPING -ZONE 11------------- ------- --------- ------ ----------------- ------------- - ------------- i(;;bg)saz� s��2M oN Z adfy joa4uo0 oN T addy jo�juoO oN adXI aoedS ---1--------------------------------------- £ 3,zoz-skGISAS ONIIJI'I-----'Sib I LSTT = Z auoz zb; eas,( 1e40s ;o0£Z = Z auoZ.:1o;'s'43eM ie3od, .LSTT 00£Z Y ;;O/uo T ta amstaZ ---------- ------ ----------------- ----------------- --- - :(;;bS)eajy 533e14 ON Z addy 10:14u00 ON T adXl joa-uo0 ON adiCL a0eds _--i--------------------------------------- Z 2NOZ-slmw2LS ONIamI'I- '6(b iLSTT = T auoZ s0; ealv 1e40y D0£Z = T auoZ z0; 944eM jelOL LSTT 00£Z i+ ;30/u0 T TQ amspq (q;bS)l?@xi s3;eM ON Z addy jo-14u00. ON T �dQ j®A;W'J OR edAl 00 S --------------------------------------T 3NOZ-SYSILBAS JNIIMIR---- 'SD, ---�--------3atu uaaq aneg QOHK'T•bT4 ut satouaToi;;a �0-0H '--=`-'-----------------------------------mdoIIJW----.. PTV ---� 4am uaaq eAtIq CD99•T•£T6 ut eta84tz0 Fiut;[a3aX i ----- i-------'---'----------------NOIS(1$I2iSSIQ 2IIMOd 'IEDINISI3"i3------ £T6 )T03I� skmWAS 'lii0I2LI= --------------------------------- ------------------------ --- suoIIeO 04eglndul sso'Idgpuels xauaiot;33 adT4 ----------------------------------TT 3NOZ-SK SAS ONIZiEdfi Ualvbi----- *ZI ------------------------------------------------------�� �ITeO a4eu4ndul ssorlAgpuegS dauaioz;;3 -------------------------------------OT 3NOZ-SK IS.is ONIS'd3FUMV14 ----- •ZTb '------------------- ---------- ------------------------ suojjeO apa4ndul ssoZdgpue}s AouaToT;;3 ad+IS ---i---------------------------------- 6 3NOZ-SKILSAS ONIUM 2gLYM------ ZTY '--------------------------------------- ------------------------ j-O94edqnduj ssojAqptm4g A8�t3 ------ _-----------------------�OZskmSAS ONIdVIIVM--- - ZTb ------------------------ _-- sod -s doua0t;;3 addj;uo-j --at}ndul s i _--_---------------------- - - L 3NOZ-S(•LLIS7S ONIsM 2III,HM-----' ZT6 '------------------------ -- ----- GMjjeO a;eg}ndul ssoZdgpue;S KDuatot;;s ad4l _--i---------------------------------- 9 3NOZ-smusz.s ONIMM 2I3,LM-----'ZTb '------------------------------------------------�------------- ---'suojjI?E) 9;e2j;ndul sso'Idgpue;S dauatot;33 ad4.L ---------=------------S MMZ-SKIWAS ONIJvm MM ------- ZTb„ ------------------------------------ ------------------------ ;suojjeO e4eU4ndul ssoZAgpueag douaiot;;3 addy ------------------------------------b 3NOZ-St•IMAS ONILvm ? lvm-----•ZTb OOT S•b Too,. 98• MK ZT=> Z: i00T S•b T00• S8• M$ ZT=> •T ----------------------------------- --------------------- --- suojjeo a-4eu4ndul ssoZdgpuegs douatot;;3 addy {----------------------------------£ 3N6Z-SKIMM ONIdl�i 2IISi�1-----'ZTb ---------------------------------------- ------------------------ :GmlleO 03eU4ndul ssoZdgpue'4S d0uat0t;;2 ad+GL --;----------------------------------Z 3NOZ-SK SAS.ONI�LM 2£ZLVM-- ZTY i---------- ---------- ---------- ---------- iMMIM 9,4unndul ssoZAgpuegS douatot;;3 addy ---i-----------------r----------------T 3NOZ-skmsxs JNLLVM 2MLVM----- ZTb i--------- -------- ---------- --------------- __ 7caninrnaa antra rrrT/rr/ca 03/11/1999 01:46 8003870692 ABBOTT&ASSOCIATES PAGE 11 Nurse Stat 1 On/Off 8 4700 23921 Total Watts for Zone 3 = 4700: Total Area for Zone 3 = 2392: 41.5------ LICHTING<SYSTEMS-ZONE 4---------------------------------------1--- Space Type No Control Type 1 No Control Type 2 No Watts Area(Sgft)1 ----------- --------------- ----------------- --- --------------- ' Reading, T 1 on/off 6 4100 20431 Total Watts for Zone 4 = 4100: Total Area for Zone 4 = 2043: 415------ LIQUING SYSTEMS -ZONE 5--------------------------------------- 1--- Space Type No Control Type 1 No Control Type 2 No Watts Area(Sgft)1 ----------- ------------------------------- --- ------ ----------' Patient Ro 1 On/off 4 2700 1336: Total Watts for Zone 5 = 27001 Total Area for Zone 5 = 13361 415 ------ LIGHTING SYSTEMS -ZONE 6--------------------------------------- 1--- Space Type No Control Type 1 No Control Type 2 No Watts Area(Sgft) ---__a------ ----------------- ----------------- ----------' Patient Ro 1 On/Off 2 1350 6681 Total Watts for Zone 6-= 13501 Total Area for Zone 6 = 6681 415.-----LIGHTING SYSTEMS -ZONE 7 --------------------------------------- Space Type No Control Type 1 No Control Type 2 No Watts Area(Sgft)1 ---------- ----------------- ----------------- --- ------ -----' Patient Ro 1 On/Off 4 2700 13361 Total Watts for Zone 7 = 27001 Total Area for Zone 7 = 13361 415------ LIGHTING SYSTEMS -ZONE 8-------------------- -------------------:--- Space Type No Control Type 1 No Control Type 2 No Watts Area(Sgft): ---------- ----------------- ----------------- --- ----------------' Patient Ro 1 On/Off 2 1350 668: Total Watts for Zone 8 = 13501 Total Area for Zone 8 = 668: 415.-----LIGHTING SYSTEMS -ZONE 9-------------------------------- =------ :--- Space Type No Control Type 1 .No Control Type 2 No Watts Area(Sgft) ---------- ----------------- --------------- -- --- ----------------1 Patient Ro 1 On/Off 2 800 668: Total Watts for Zone 9 = 800: Total Area for Zone 9 = 6681 415.-----LIGHTING SYSTEMS -ZONE 10---------------------------------------- 1--- Space Type No Control Type 1 No Control Type 2 No Watts Area(Sgft): ---------- ----------------- ----------------- --- ------ ----------' Patient Ro 1 On/Off 2 800 716: Total Watts for Zone 10 = 8001 Total Area for Zone 10 = 7161 415.-----LIGHTING SYSTEMS -ZONE 11--------------------------------------- 1--- .Space Type No Control Type 1 No Control Type 2 No Watts Area(Sgft)1 ---------- ----------------- ----------------- - Patient Ro 1 on/Off 2 1300 659: Total Watts for Zone 11 = 1300: Total Area for Zone 11 = 659: Total Watts = 24400: Total Area = 12800: : CHECK 1 Lighting criteria in 415.1.ABCD have been net. 1 1 ------------------------------------------------------------------'-----'--- 16. Operation/maintenance manual will be provided to owner.(102.1)1 1 -------------------------------------------- ---------- =--------------------- �!� � � w has �• ; iri+kkk$4it kS�kk N Nj W %R "Rx RxxR%%xR xl ttRR xPau �r�rK rrr R, naa nxuPaoorrannarPnPnPe xu nrrn � v n 03/11/1999 01:46 6003870692 ABBOTT&ASSOCIATES PAGE 13 Nln/P91"I "ove G"q 5. INFILTRATION ad romp DMI x,.t . A naa..e x a,... Doti.. XM v V _ —� d y 6. SUBTOTAL COOLING LOAD FOR SPACE 7. SUPPLY DUCT HEAT AIN QE1. �a .. `R Ldr R ■MMb QiY� . � / � J S. ROOM, ZONE OR BLOCK DESIGN LOAD Ago cruel w* m a D.d,dtr xa NM Oft Ima to saw"* ift ow" CPU @. VENTILATION ® h 390 tr,a01WWdb msmdta ,o, �w ss yy . x d i?F3D OMI. . ... x,., . .....x�08I.. isormoir . . - . /�/ %,R.3� ...,xaa, 10. RETURN AIR LOAD FROM LIGHTING AND ROOF MOTE, c3A dp% 0 "m raug" Mov4somm LIGMA n4 . 10.. oaa saa t�Eatd Rtudoe d, • fycr ce m LWWL ... x Xat . mob? r-400 Lem w=: uw u xww 4 ETD ma a,, u Poew F-^• Oda Pool miMl no , N' A A . . % .CUD tanoe d. h=W M Pa 1m94f M10 warm anEomn wq Cc*" good. ro,w to M9 %. DAB Laod Go"" ..... ... 1-i. . 11. RETURN DUCT HEAT GAIN X LIM a sauroo. ad" ............ . 12. TOTAL LOADS ON EOUIPMENT (Bluh) -AxWO 6046 13. DESIGN CONDITIONS (HEATING) wro.a Hff* dawdle oa.. Dpftw . 14. TRANSMISSION LOSSES HEATING LOAD a IAI wms ddmosoun so A. U-Fwar Iftm Da, � A? �.�p ll//��� LOW MGM /¢1 ..�v x ... x .: waft ...... x.......... ..X ........... . ........... ...... ... .. %............ x ............n ..., Doom .�. ��.... X /.6 % . }.....n....... Y. A; • .. .. .0.... ... ..... .apt .. . ...... ... x...... ....x ... ... tr ... 6b11Ri01Ml .... x .. ' .. x ...- xd9l r :���� X x ... . x.,.......::x..... 89y . . . ,a .. x .. x .... 1S. INFILTRATION 1 /��, ,.! O. M,NM.... ...Xtlo AaO DIM..... ... k t.r . 16. SUBTOTAL HEATING LOAD FOR SPMCE / Z 17. SUPPLY DUCT HEAT LOSS Lon pew.x Lxu in w.Iw a.in .. .... � - 1S. VENTILATION moon.. �/V ....x�711Y 01M....��V .... 1.1. Ilk HUMIDIFICATION LOAD wattilptww...... wo...... I "%WM..............- max Imm" ............... low" 90mftr ........ x I" M %prm ..... . - no ......... 20. RETURN DUCT HFxT I I'1SS Lm r.emr .. .. X LIM to Lt ............... . 21. TOTAL HEATING LOAD ON EQUIPMENT (Stuh) 09 /Q Y, S, 3 WAI A. ^ 4" I P ��H jib O :I it T f . ><� m Xs.. 17c�� r. }tkkitkytkft}tWMS+MDsS. nttnoaltwatst KNM% m X if" M MK1 it w M MTS Is tt w34 S3 anq.a�9aa4n9Mca x40a009a tj 9 R r F7 bJ111/LdJ:1 U1.4V Vuuw. uu-j.. Avis r' xeno,El. Ln ., &Iwwpf� 61?49 5. INFILTRATION - Mn.1n ... ... x CID Tpng Dnl .. x,.1 6. SUBTOTAL COOLING LOAD FOR SPACE 7. SUPPLY DUCT HEAT GAIN a" ran .. x L.M 6 so"* own . y - 8. ROOM, ZONE OR BLOCK DESIGN LOAD Agd OM Nn to to @*Moto 04 We Ilns low 10ep11..1. tll...w.g CFM .I -1 a son " Gil" CFM. '. .... ... ... ®. VENTILATION Iron: Fix M" w a"" ab *two," 20 c��1 a�{. / S • ...17 1../'�A F 4GiYn{a .. •��� ::: x 81Cq BIN.... s t.. 6 10. RETURN AIR LOAD FROM LIGHTING AND ROOF NOT* am 40 i of l.o.sv&w Wzwma7. m Lwa .. x3.4 czm for uw" "mwead a. gm"mic m LyMa tolYln.'a.pxlxl. ' "a Lees) NOTE: uwu vm4g & "D Fx pl. M F.nor 1!•^• 1.rmolviMaq 6m . w. .x.. •.Wm It). oo.oeuoa ge.ad on p wm N %wctm.) NOW: 6u'L7ns111u oolong boo. T*W 10 No. 7. Coiling Low C1.011 ..... ... 11. RETURN DUCT HEAT GAIN Gain lam ... . .... x LM. g:.rulao OYn............. 12. TOTAL LOADS ON EQUIPMENT (Bluh) 04, /V 980 13. DESIGN CONDITIONS (HEATING) .1g16. do. H a. d,wo 0.9ob. 6b. 0lfeanne.. .. 14. TRANSMISSION LOSSES HEATING LOAD _W IQ Ill. u-pactor NOICi =gyp/Di : •..' ' • :: V x.. . / :: X ::: �11� Uftftfib ..��... x:q ..x..... x............x ... ...... .......... :.... x............ x ........... ........... y x.....Yy x.......... - Co3r► c�%E*: (/::. a.../�6 x . .. �:..... ... .. ......... z...... ....x .... ... ... F.nxlox. .... x .. •.. .. x ... ... . 111o710Mknp .. .. x .. —x .... .. 15.INFILTRATION fill.... 10. SUBTOTAL HEATING LOAD FOR SPACE 17. SUPPLY DUCT HEAT LOSS Lose hAer .. ...Kum* orll .. • .. • 9_.. 18. VENTILATION aO 18. HUMIDIFICATION LOAD ftwer111Or.d....... wAm...... I fel .............. - ,gg x @..1x .............. . ........x WM e41.I. ..... .-,ee......... 20. RETURN DUCT HFAT I OSS L.r fww .. ' . .. .. x 1 *$ K Low ................" 21. TOTAL HEATING LOAD ON EQUIPMENT (Bluh) 2,d TO4. I 112 v R 1 03/11/1999 01:46 8003870692 /4 wvo 6P44? ABBOTT&ASSOCIATES 5. INFILTRATION "' .... ia of"... 6. SUBTOTAL COOLING LOAD FOR SPACE 7. SUPPLY DUCT HEAT GAIN he w ew .. .. 0 X Law { swaiw Go. . 8. ROOM, ZONE OR BLOCK DESIGN LOAD ileawnSon tobSobe"14 k* me low 10 Gowns 0,'w 0csr •i....54,0001 {...... Tp. c•a•'^0 cw . ' . ... ... ... - Cl I . I 0. VENTILATION t+o1x v.i mem & womp y MWW40 90CF01 04ma podx E,%rm . . /-J� .X nl ...am*a aw- - - r r . it I., 2nm - 10. RETURN AIR LOAD FROM LIGHTING AND ROOF WIN am 40%o/Xxi tea ^�gomm Lwa $*A . 10. con tat Uvft su-j o in a Fftwamnl {1�ltlr • ... . XaI . t? L .. . le PAGE 17 / i.20 A yVo iewm ee, owns pea L020 Imm, um u qqa { XID M A. u Ivoew F^`• ibc F-vt am nD COMMw. . X.. I41 .YXID twentmR 61*0 en plain. Cnl.eiOWMJ plGTl: fuE0rne1 RN a+tin0 b.e. Ma to No .. coump wo cftmt ..... ... t7h . 11. RETURN DUCT HEAT GAIN add %e,oi ... .... X Lbw t x..YON Gain ............ . 12. TOTAL LOADS ON EQUIPMENT (Btuh) 13. DESIGN CONDITIONS (HEATING) Riela.m.Hw.x.uOWtdfaoe. s dMannc.. 14. TRANSMISSION LOSSES P6EA111d0 LOAD $e H. U-P&C of ee 74" Din Lmd I..e �M :. �'1 y' x .., /o .. x :::. 'ryy.. x............ X .. ..... . .......... .(.�+y.�+'.`.. am$ v16► ... ..:�•r•• X ...../ ...... O..: X .... ...... 'a ........... x...�fb x..... ....:. . ... pwtki" I4map•o i,?.�0®X3. .... X.. . . .. X ... .. . :::: .... /�'•yy ixc::.0�2..:: IXc x.ero.. X.. ... x .... 15. INFILTRATION wamn.... O ..... tamp DNf.•..rL.� e� ...a 1.,. IS. SUBTOTAL HEATING LOAD FOR SPACE S(� 17. SUPPLY DUCT HEAT LOSS Lan Nebr .. ..: LMi. w xrai.ln GN... ... - 16 VENTILATION Ilti.ia nn . ,p` F .. X.o wRlo'oal . Oo AP ... ,., 19. HUMIDIFICATION LOAD &r..wlo.r.e.. .... mum ...... 1 RMwin .............. - = x &A*W ............... _ _l..U" DiM9.I........ X WO R MAwM ----- . !......__ 20. RETURN DUCT HFAT I OSS Lau 4tlnr .. .. X Lim N Len .............Aws 21. TOTAL HEATING LOAD ON EQUIPMENT (Stuh) G .nw .ww 1 AM COMOMBICIAL LOAD CALMAT1ONs All d m - ,Ano ? 'J.odc Long UNWROMOMM 7yvo Svori r�are•�u•e� resat •soe • a� FORT/ Pt-1 G,lf a Lis' �IS,f.IC?".Ed G/v1�L�•_ _ ..�. MA 1. DE. M COMDRIOMS�C:oOLMOi �� PYm+wet='—rl� t SO4AR RA®B11Y11fR] 11�eiO' PiA1�1 YEN �.CSS �iDL2el »tasLn 9�R 8111eGFite. ®eaY11a1r. 8.� .,�,¢;�..A ...L.�... sccat:> =�/mod•. .cum .y�. ......��'..... ............... k............ A .......... s .......... ...... ................ X.,.......... x ...... ... o ........ ...... k............k ........... a ..... ..... ...... ................ ..... ................ k........._..x ...... a y1 - It s .... ...... a 0b,.x•mELM l!StyR Yif�ilyyCr FaMtaY / QQ�, a .JI 0l+. ........ X............k ..... v ...... ... ...... OP.oa .... ........ X............k ..'• ..... . .......... .. P111*� .... .. ....... $ ............x . .._.. a .... ..... .....II............k ........ a ....... sYlYotrtt -WII WG•fmi1..1•. •t�.Pd••�•®•xOsflt awulw QR -. INTERNAL HEAT GAIN tu:.1 a Occupw4s sc.Yr talWA 14v Igv.- qq .... ........... a a oars ,q,11 :: yf�0.. Al, L� .1....1..E wrrrwkteA}si .�.�... taw sow IIIIe ............ L... L.... .... ....... .___•. ............ L... L.... ........ ... ...... ...... ............ L... L.... -... ..... .. v� W YID ft*ft� ..... .....L._.. ........... .......... ................. cow ! ....... �.L. 'AbWiaYe1•rM1.�Y�AOP-rr1111 Nr1 3wbwA UO0 . e® uz/11/1"7 ul:40 uuudb(ub7L AbbUI I&HSbUl:1HItb rkuU 1J S ITS 6& 1 .uppr 0� 5. INFILTRATION /� In .. � - I .... yL .. s W Amp Dx/ All . `!lJ —G�.0 . Jmxe S. SUBTOTAL COOLING LOAD FOR SPACE _ / �► 3 �~ 7. SUPPLY DUCT H 29AIN x Lam a 6rnlab Dab .olip - B. ROOM. ZONE OR BLOCK DESIGN LOAD e AN a1R1 pin m to m,"WS 61 um fts by b MINAW aotarbp CFY a •M An1�aeN R.er• iti .. 9. VENTILATION WM: ra1 MOM 6D I w M INIM ao c pm 2 aAw61w71s,ww1 J A� i .. !�1..Ts ... Jl w wwo Don. :: Arc [/ .. p* V ... x als" DNL .. ap,p s [ 0 10. RETURN AIR LOAD FROM LIGHTING AND ROOF tom, am40% o1 IMb1M6M0 ftwWaawd Lw" .. x1.4 _ won 16/ uafft oca6666 in • F16C166ii711 (1DA1p, ... - It . x4.1 a Ii L .. . velum 6trp1Y„y, Nloll.ae6) ron: We u arw a ero Aa n, u F.c1o� r fte 'IE'ID wrnKllmn 6r.e m aA.wn UaiaalraiaJ MOtE 6a011ac1 iM cWip bra, ow to lb & Ce" LWa O.6M ..... 11. RETURN DUCT HEAT GAIN Ualn taw ... .... x LNa a •rulE4 "n ............ e 12. TOTAL LOADS ON EQUIPMENT MIA I I& DESIGN CONDITIONS (HEATING) l awea w H aaMq DuM10� W. r dMNaan . I 14. TRANSMISSION LOSSES HEATING LOAD W sup"m SC p. U•FWW is" Do Loa! waftFray .. ��s x ::, t :: x d 3�� . - x............x .......... r ...... ... .. x.......... 1.x ..... .:... a x .....//.. nn x ..... ..... a x iQ {✓.... ........... ... ...�..... . ...�.... . J. . x ........... . ...... ... x...... x .... ... a ........... ... ft*"W* .... x .. .. x ... .. . paw � .. .. x.. ...x ... .. a .. 15. INFILTRATION It 0 8' , ... ..... x W D>,, ....� ... a 1.1 16. SUBTOTAL HEATING LOAD FOR SPACE 11A U V. SUPPLY DUCT HEAT) LOSS ' • L. %cW .. f .. x Lira lalWalbbDrn .. .. . 1B. VENTILATION "%MIR.. 1/.HUMIDIFtCAT10NLOAD al6nau11m6w.6......law......) ftlaft .............. - 10Dx ww.............. . 20. RETURN DUCT HFAT 1 OSS x Lim 16 La. ............... . 21. TOTAL HEATING LOAD ON EQUIPMENT (Btuh) 3.2 A Pft .wnl PUBLIC WORKS DEPARTMENT MEMORANDUM TO: Debbie Isenhour, Building Division FROM: Charles A. Cangianelli, Building and Zoning Manager l AS.-� DATE: March 29, 2000 RE: International Alzheimer's Foundation Engineering has reviewed the paving and drainage as-builts for this project and are accepting them for completion at this time. A copy of the Engineer's certifications and drawings are attached for your records. If I can be of further assistance to you in this matter, please let me know. -F0r %erMt0-3A2�{triijl r'J�0 3023 bsrm Bldg '5Ld 14-(Nr09 CAG:ewc Attachment as noted cc: Donald West, P.E., County Engineer Velcon Group, Inc. ST. LUCIE COUNTY DEPARTMENT OF COMMUNITY DEVELOPMENT 2300 VIRGINIA AVENUE, ROOM 201 FT. PIERCE, FL 34992-SSM 407-462-1553 DESIGN CERTIFICATION FOR WIND. LOAD COMPLIANCE This Certification is to be completed by the pro)ert design architect or engineer. This Certification must be submitted with all applications for building permit involving the coon of rWw residence (sm9le or mrdti-tamily), residential addition, any accessory structure requiring a building pannit. and any nonreskential structure. This Certi4zlion stwU not apply to interior renovatrons (promed that no snuetural walls, columns or other ie mbl, component is being effected) and certain otrrer minor buildmg p®mnds. For limner assistance. Please contact Me Building Inspection Office at 462-1553 or-462-2172. a C® CERTIFICATION STATEMENT: I CERTIFY THAT, TO THE BEST OF MY KNOWLEDGE AND BELIEF, THESE PLANS AND SPECIFICATIONS HAVE BEEN DESIGNED TO COMPLY WITH THE APPLICABLE STRUCTURAL PORTION OFTHE BUILDING CODES CURRENTLY ADOPTED AND ENFORCED 'BY ST. LUCIE COUNTY. I ALSO CERTIFY THAT STRUCTURAL ELEMENTS DEPICTED ON THESE PLANS PROVIDE ADEQUATE RESISTANCE TO THE WIND LOADS AND FORCES SPECIFIED BY CURRENT CODE PROVISIONS. DESIGN PARAMETERS AND ASSUMPTIONS USED: (meam dvgck or owyiete the appmprote box) 1. BUILDING CODE EDITION USED MArp )SBCCI ASCE 7$8 /}$GE-7. 73 OTHER (SPECIFY) 2: BUILDING DESIGN IS (CHECK oral ENCLOSED PARTIALLY ENCLOSED OPEN BUILDING 9 �r ?. BUILDING HEOGHT: I 1 FT J. WIND SPEED USED IN BUILDING DESIGN: 1 3 d MRt t • a. WIND EXPOSURE CLASSIFICATION (tssM 70 E]mosatE rAeLFs ar ata.>pnc tbLE roExrrFtID W UIE prl: ^C 6. AVERAGE WIND VELOCITY PRESSURE ON EXTERIOR FACES OF STRUCTURE y ,,`}-I� PSF - 7. PEAK WIND VELOCITY PRESSURE ON EXTERIOR FACESOF STRUCTURE: 6 _ PSF a. VAPORTANCEMSE FACTOR roaum RRDu auimmG maEl: I . 0 `y 9 LOADS: FLOOR (-0O PSF ROOF?DEAD. LO PSF ROOFAJVE I Co PSF 110. WERE SHEAR WALLS CONSIDERED FOR STRUCTURE toecK arEl YES NO _ If NO, why? (mach ax%anabon) 11.., IS A CONTINUOUS LOAD PATH PROVIDED Ic Eoc oW YES NO If NO, why? (mach - ,i- (If,`tr 12 ARE COMPONENT AND CLADDING DETAILS PROVIDED lo4em ow) YES NO If, NO. mny?�gabahYh torarhabon) �_ r 13. MINIMUM SOIL BEARING PRESSURE . 2 5O� PSF ' I ^ AS WITNESSED BY MY SEAL, I HEREBY CERTIFY THAT THE INFORMATION I CERTIFICATION IS TRUE AND CORRECT, TO THE BEST OF MY KNOWLEDGE AND BI NAME: Jol�t� rl �Ii�t^i1: CERTIFICATION NO: Ate IZ--) DESIGN FIRM: Ai�EISh� �iSSIsC'G1• DATE: Z 5 K A-f 9 HERE) CDIX Whole Building Performance MBthod far Commercial Buildings r6­rm40_0X_-jt7 MWGY $SFICIENC7C}CODEUILDTN CONST UCTION pO c Florida Depart YAffairs FLA/COM-91 Version 2.2 PROJECT NAME TWIN OAKS ASSISTED qj=PEO:MIRTING 08ffIC$: ADDRESS: ITIWAY RD _ST. LIICIE COUmT " sT LIICIE JT CLIMATE ZONE: OWNER: W; OAKS ASSISTED AGENT. PERMIT 90. JDRISDICTION NO: 66100D BUILDING{ TYPE: Institutional (Health)_ _ CONSTRUCTION CONDITION: New construction DESIGN COMPLSTTON: 8inished Building NUMBER OF ZONES: 1 CONDITIONED FLOOR AREA: 283A MAX. TONNAGE OF EQUIPMENT PER SYSTEM: 4 — COMPLIANCZ CALCULATION: METHOD A DESIGN CRITERIA RESULT -- A. WHOLE BUILDING �'45.0$ -----... 100.00 PASSES PRESCRIPTIVE REQUIREMENTS: LIGHTING SXTRRIOR LIGHTING 150.00 210.00 PASSES LIGHTING CONTROL REQUiR]DEPrTS PASSES RVAC EQUIPMENT COOLING EQUIPMENT 1. SEER 10.20 10.00 PASSES RRATING EQUIPMENT N/A 1_ Et 1.00 AIR DISTRIBUTION SYSTEM INSULATION REQUIREMENTS 1. Unconditioned Space 4.20 4.20 PASSES REHEAT SYSTEM TYPES USED NO REHEAT SYSTEM is USED WATER BEATING EQUIPMENT 1. Et 0.7E ' SL 0.00 0.03 0. PASSES PIPING INSULATION REQUIRV4MTS 1. Non -Circulating 0.00 0.00 PASSES - --------'---------------------------------------------------------- 1, COMPLIANCFi,,CERTIFICATION: I z,hereby specific lation a Fl:br-ida certify::" iri- the plans and by this calcu- ,ae with the �' I hereby certify that this building is in compliance with the Florida Energy Efficiency Code. Review of the plans and specifica- tions covered by this calculation indicates compliance with the Florida Energy Efficiency Code. Before construction is completed, this building will be inspected for compliance in accordance with Section S53.908, Florida Statutes. BUILDING OFFIC2AL : DATE: wM /AGENT DATfi I hereby certify(*) that the system design i6 is compliance with the Florida gnesgy Efficiency Code. nat--T4roATTrK/STATE ARC =C!T : MEC 0XICAL: PLDMING . ELj5 rIUURL • LIGHTING s q „ formed (*) registered �isde required where Florida danames d6rdgistr ties numbers mAY by registered design prote5sionals. Hyped registration be used where all relevant infozmati.on is contained on signed/sealed plans. BIIa+ n;G ENVELOPS SYSTEMS COMPLIMCE CHECK 403.------GLAZING--ZONE I ------------------------------------------------ Elevation Type U SC VLT Shading ---- ---- -------------- Area(Sgft) ---------- --------- --------------- ---- South Commercial 1_09 .8 .9 30 West Commercial 1,09 .8 .9 30 East Commercial 1.09 .8 .9 26 Total Glass Area in Zone I . 86 ' Total Glass Area = 86 402.------WALLS--ZONE 1------------------------------------------------ --- Elevation Type V Tncul R ------ Groes(Set) --y-----552 East ---- - 5/8"StCo/8"CMU/3/4"ISOWM24•0C 0.1494 West 5/8"StOO/8"CMU/3/4"250 STWH2400e 0.149 4 552 Adjacent 5/8"StCo/84CMU/3/4"TSO BTM24"o0 0.149 4 162 North 5/8"Stco/8"CNU/3/4"ISO ETWN24"oc 0.149 4 209 South 5/8"Stco/8"CMU/3/4"3:S0 BTWN24'oc 0.149 4 371 Total Wall Area in Zone 1 = 1846 Total Gross Wall Area ='' 1846 403.------DOORS--ZONE 1---`-------------------------------------------- --- Elevation Type U ----- Area(Sgft) ---------- ---------------------------------`---=------------- West 1-3/4 Steel Daor-Fiberglass/Mineral Woo 0.60 10 South 1-3/4 Steel DOOM-Fiberglass/Mineral woo 0.60 10 North 1-3/4 Steel Door-Fiberglass/Mineral woo 0.60 20 Total Door Area in Zone 1 - 40 Total Door Area = 40 404------- ROOFS --ZONE I------------------------------------------------ --- Type . Color t7 iusul R ------ ----- ------- Area(Sgft) ------- I - ------------------------------------ Shngl/1/2"Wn Deck/WD Truss/9" B Medium 0.027 30 2811 Total Roof Area in Zone 1 . 2811 Total Roof Area = 2011 405.------PLOORS-ZONE 1-=------------ ---------------------------------- --- .Type rnsul R ------- Area(Sgft) ------- --- ----------------`---------`--------------------- Slab on Grade/Uninsulated 0 2611 Total Floor Area in Zone 1 = 2811 Total Floor Area ft 2811 406------- INFILTRATTON-------- ------------------------------------------ G Infiltration Criteria in 406.1.ABCD have been met. MECHANICAL SYSTEMS CHECK --� ----------- --------------------------- _--------------- .----------- MAC load sizing has been performed. (407.1.ABCD) - 407.------COOLING SYSTEMS ------ =---------------------------------------- --- Type No Efficiency IPLV ----^ -------------- Totes ---------------------------- ------------- l. Split System _2 10.2 10.2 4.00 408------- BEATING SYSTEMS----------------------------------------------- --- Type No Efficiency ----------------------------- - BTU/hr - - --- ------------ --- I. Electric Resistance 2 1 17000 ------- ------------^ --- CK ventilation Criteria in 4o9.1.AB= have been met. -------------------------- --- 410------AIR DISTRMUTION SYSTM -------------- CHECK ---------------------------------------- ---- --- Duct sizing and design have been performed. (410.1-ABCD) I - AM Type Duct T er-ation R-value: ------------------------------------------------- 1. Air Conditioners Unconditioned Space 4.2 --------------- -^- Testing and balancing will be performed- (410.1_ABCD) 413..-----PUWS AND-PIPING-ZORR----------------------------------------- --- Basic prescriptive requirements in 411.1.ASED have been.09t- PL[iNl8M SYSTRMS 411------ PUMPS AM PIPING -ZONE 1--------------------------------------- --- Type R-valve/in Diameter Thickness -------- ---------------- -------------- ------ 1. Son -Circulating 0 . 1 o 412------ WATER MATING SYSTSMB-ZONE 1----------- =---------------------- --- Type Efficiency StandbyLoss jvtmtRate Gallons ---------------------------------- ----- ---- -------------------- 1. 575,000 Htuh .76 001 120000 60 ELECTRICAL SYSTEi-L9 CHECK 413.-----ELECTkICAL POWER DISTItIV=ON--------------------------`- ----- --- Metering criteria iu 413.1_ABCD have been Met. 414------ MOTORS --------------------------------------------------- ----- --- Motor efficiencies in 414.1.ASM have been stet_ 415------ LIGHTING SYSTEMS -ZONE I-----------------•---------------------- --- Space Type No Control Type 1 ND Control Type 2 No Matta Area(Sgfr) ---------- ----------------- ----------------- --- ---------------- KitcheA 1 On/Off 6 3200 2811 Total Watts for Zane 1 - 3200 Total Area for Zone 1 - 2811 TM&I Watts = 3200 Total Area � 2811 CHECK Lighting criteria in 415.1.ABco have been met_ --------------•---------------------------------------------------- I-- - 16. Operation/maintenance manual will be provided to owner.(102.1) M COMMERCIAL LOA29ALCULATIONS Aa C9 mks 1712 Nw 1131aPQftAxmla6•NW W&d*l Pk DC 2WW 11101E 2M • 403 0 QM • am 4SAI'WO 62-f FOIi RUM NIP or awom 1. DESIGN! 00OL�I�" �C/ONOMONS fr ma a Da<sLLLJ-� -Vv rI��a4 L ''Al r- �pnKdro entlm�d...Z-- Dataaago� a 11wn.a ean.a�v as t4 rdn bmsaeryal�--=�T.o. 2 SOLAR RADIATION HEAT GAIN THROUGH GLASS. COOLM LOAD 8MdWMMr rao "� 34-K 3dwf�jtw mmr{;w - m- . x . x .. ...... ........ x........ ..__% .__........ 3. TRANSMISSION GAINS cpfvbw& a UPON* ppaa.rl. urraCmr/. *airy M" GI6a t�:. . .. �c ... J�� =!- .... .... }�. _ .. c Q /.! .: • ..6 y /% ... ... _ ..IC ..../.... x .. ..., s ----------- .... J:� : .. A. ... lxl : .... - ....... Q ............ >< .. ."-- F1nya x .... ......----- •......... .. ....----x............ FW o xg::`::::: laWiK...... ........ x............ 9 ........... - uaa DM as N n., M erlase. OwrM:..� & Palw Air 4. INTERNAL HEAT GAIN a Occupants a novae. 1iTAl b_ Lights & Othere WWI �M-nM UWA ul 111Mda CvUUdra %M4 r4a1a M MUM w a%U0. LOPI 1a+4a NJ.N.R Alm Fw W Awhr 1{ot0.1 ---- .. ............. X_..eL___. .__... .._...... .. 1L... IL -'-• ..... ...._. .... ...... _..._. ............ x ... L.... ..........- AWWWM .�JJJ.��F' - - - - • "ivae7 "�" -TVA,# a a-NvWfoaa u=daWMA=WMUWM nodal Edal01M If 1 DWaaa� s 5. INFILTRATION R4.06..... ... A a 74m aw 21.1 e .. I1�.m�e GJ I pR.:. t SUBTOTAL COOLING LOAD FOR SPACE ?.SUPPLY DUCT H T, AW 1.e1a Gr. .. < � e ur 3 �.e�l■ Ow. - . . L ROOM, ZONE OR BLOCK DESIGN LOACI •eapR1 rR mb s.rar m Ha. m. arr w aa.mola lreaaxy CRI _ t VENTILATION an71 ><a a�w..ev cmc.p. m m.a a.r xi r 10_ RETURN AIR LOAD PROM.LIGHTING AND ROOF Nm ONa %alwa. up",. _ M4 + 1*1 .arts far L60l..fau,atl In a Naamead Lipea... - 1, -.se., . (*A.. . iD1mifik a. - /�iaLrA Mf�t•uo Yvskai@TO wnam,WM=W 4& ... _x.. 141. 'RTD tveaalls.hwam+M/a■n faa.3s.uaa, Wm emromCap low saw.o"@ CN<s+o !mr Cwq ..... H. . 11. RETURN DULY MEAT GAIN at% view ... . .... x IUm a s uer a..... . 12. TOTAL LOADS ON EQUIPMENT (®luh) 40 f' 13. DESIGN CONDITIONS (HEATING) ' IMAM® iia&"7V"db.. bc+}w.ca 14, TRANSMISSION LOSSES HEATING LOAD o w ILOO 71�.a ff.:: g6 A y� 70 ..r..... s . .- - - - . ...�.... AM .� .� .� .. x_ 115. INFILTRATION .-..Q .....�.a...sR.. 1E. SUBTOTAL HEATING LOAD FOR SPACE ,o Sg,� 17. SUPPLY DUCT MEAjLLqp 91, Lom laiw' .40 .. X u" 13 pt "b o Doi, .. .. ♦ 10. vENnurloN�� . 19. HUMIDIFICATION LOAD ba+a s. oNmw .. _ . _ . sw...... , f ....... xar,Ri.w. ------ low.._. ... - 20. RETURN DUCT NEaT I W ................ 21. TOTAL HEATING LOAD ON EOUIPMENT (81uh) .nn soft a _ o INTERNATIONAL ALZHEIMER'S FOUNDATION TRUST, INC. 2277 SW OLYMPIC CLUB TERRACE $' PALM CITY, FLORIDA 34490 � y March 10, 1999 Department of Community Development Division of Growth Management 2300 Virginia Ave., #201 Gentlemen: Please be advised that we will provide a copy of the HOOK-UP AGREEMENT prior to the issuance of a Certificate of Occupancy. All fees wil have been paid in full by then. Sincerely S COSENTINO PRESIDENT 6 Whole Building Performance Method for Ca mercial Buildings Form 40OA-97 ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION Florida Department of CmTma ity Affairs r. FLA/COM-97 Version 2.2 SALT NAMFyTWIN OAKS ASSISTED LIVING PERMITTING OFFICE: `AtmESS: J41UM RD -ff. LUCIE 000NTY� 1ST LUCIE OD CLIMATE ZONE: 6 OWNER: !TWIN OAKS PERMIT N0: Pam: - •. JURISDICTION NO:_661000 BUILDING TYPE: Institutional (Health) OONSn;aXTION CONDITION: ..New CCnstructiai DESIGN 06MPLETION: finished Building OONDITICNEO:FLOOR AREA: _.2800. NUMBER .OF ZONES: 11 MAX. TONNAGE OF EWI24MT PER SYSTEM: 5 COMPLIANCE CALCULATION: METHOD A DESIGN CRITERIA- RESULT ---------- ------ -------- A. WHOLE BUILDING 61.94 100.00 PASSES PRESCRIPTIVE REQUIREMENTS: LIGHTING EXTERIOR LIGHTING LIGHTING CONTROL REQUIREMENTS HVAC EQUIPMENT COOLING EQUIPMENT 1. SEER 2. SEER 3. SEER 4. SEER 5. SEER 6. SEER 7. SEER 8. SEER 9. SEER 10. SEER 11. SEER HEATING EQUIPMENT 1. Et 2. Et 3. Et 4. Et 5. Et 6. Et 7. Et 8. Et 9. Et 10. Et 11. Et AIR DISTRIBUTION SYSTEM INSULATION 1. Unconditiamed Space 675.00 1100.00 PASSES PASSES 10.00 10.00 PASSES 10.00 10.00 PASSES 10.00 10.00 PASSES 10.00 10.00 PASSES 10.00 10.00 PASSES 10.00 10.00 PASSES 10.00 10:00 PASSES 10.00 10.00 PASSES 10.00 10.00 PASSES 10.00 10.00 PASSES 10.00 10.00 PASSES 1.00 N/A 1.00 N/A 1.00 N/A 1.00 N/A 1.00 N/A 1.00 N/A 1.00 N/A 1.00 N/A 1.00 N/A 1.00 N/A 1.00 N/A REQUIREMENTS 4.20 4.20 PASSES 2. Unconditioned Space 3. Unconditioned Space 4. unconditioned Space 5. Unconditioned Space 6. Unconditioned Space 7. Unconditioned Space 8. Unconditioned space 9. unconditioned Space 10. Unconditioned Space 11. unconditioned Space pMMT SYSTEM TYPES USED NO REMT SYSTEM is USED WATER HEATING EQUIPMENT 1. EF 2. EF PIPING INSULATION REgUIREKENTS 1. Non -Circulating ------------------------ C24MIANCE CERTIFICATION: lation are ,y Florida Ent PREPAR�9 S9 .MATE:_, .c the plans and by this ealeu- ce with the I hereby certify that this building is in compliance with the Florida Energy Efficiency Code. - CWNER/AGENP: DATE: 4.20 4.20 PASSES 4.20 4.20 PASSES 4.20 4.20 PASSES 4.20 4.20 PASSES 4.20 4.20 PASSES 4.20 4.20 PASSES 4.20 4.20 PASSES 4.20 4.20 PASSES 4.20 4.20 PASSES 4.20 4.20 PASSES 0.85 0.80 PASSES 0.85 0.80 PASSES 0.00 0.00 PASSES -------------------------- --------- ReView of the plans and specifica- tions covered by this calculation indicates compliance with the Florida 'Energy Efficiency Code. Before construction is completed, this building will be inspected for campliance in accordance with section 553.908, Florida Statutes. BUILDING OFFICIAL: DATE: I hereby certify(*) that the system design is in compliance with the Florida Energy Efficiency Code. SYSTEM DESIGNER REGISTRATION/STATE ARCHITECT :�*ti AblFi�r4 .A9_W) S6 [�l� MECHANICAL: PIMING ELECTRICAL: LIGHTING : (*) Signature is required where Florida law requires design to be performed by registered design professionals. Typed names and registration numbers may be used where all relevant information is contained on signed/sealed plans. , BUILDING ENVE[APE SYSTEMS 4011-QLAZlIiG--7.ONE l._------------- ------- Elevation Type U _ SC VLT--Mmd=g ---- -------------- North Camarcial---- 1.09 .8 .9 South Cutmercial 1.09 •8 •9 West Ccmnercial 1.09 Total .8 •9 Glass Area in Zane 1 = 401------- GLAZING--ZOM 2----- ------- ------ ---------------- Shading Elevation Type U ---- -- Sc ---vLT -- --------- North --------------- Camercial 1.09 .8 .9 South Camtercial 1.09 .8 •9 East comaercial 1.09 Total .8 :9 Glass Area in Zone 2 = 401.------GLAZING--ZONE, 3------------"-'------------------- Shading Elevation Type U ---- ---- SC vLT --- --------- North --------------- Comnercial 1 Total Glass Area in Zone 3 = 401.------GLAZING--ZONE Elevation Type --------- --------- North Ccmnercial South ccmmrcial 401------- GLAZING --ZONE Elevation Type --------- -------- South Camtercial 401. -•---GLAZING--ZCNE Elevation Type --------- ------- South . Conmercial U Sc vLT Shading 1.09 .5 .9. 1.09 .8 .9 Total Glass Area in Zone 4 = Area(S4ft).', 371 131 1M 159 Area(Sgft) ----------i 371 131 1091, 159 ------------- v- Area(Sgft)l ----------; 481 ---------48--v Area(Sgft); ----------i 781 56: 1341 U ----- U Sc VLT Shading Area(Sgft)l -------------- ----------{ 1.09 .8 .9 5 = 481 481 Total Glass Area in Zane 6---. -------'Area(Sgft)l-v- ---SC - vLT C Shading ---- ---- 1.09 Total ---- -------------- .8 .9 Glass Area in Zone 6 = ----------; 241 24; 401.------GLAZING--ZONE ----- ------------- ------------ - VLT Shading - Elevation TYPe U Sc ----- ----------i North Co mtercial ---- 1.09 Total ---- .8 .9 Glass Area in Zone 7 = 48i 481 401.------GLAZING--ZONE 8----------------- Area(Sgft) Elevation Type U ---- SC vLT Shading ------------------ _-_--_ 1 North Camtiercial ---- 3.09 Total .8 .9 Glass Area in Zane 8 = 241 241 401------- GLAZING--ZCNE 9------------ Area(S4ft)� Elevation Type U SC VLT Shading -- ----------1 ------------------------ North Cmimccial 1.09 .8 .9 9 = 241, 241 Total Glass Area in Zone 401. ---ZING--ZONE -------------------- -------------------� 10------- Area(Sgft); Shading Elevation Type U SC VLT North Canercial 1.09 Total -------------- .8 .9 Glass Area in Zone 10 = ----------1 241 241 401.------GLAZING -ZONE ----^----------------------------V- 11---------_-_---Area(Sgft)', Elevation Type U SC vLT Shading -- - ---- South Ccamiercial ---- ---- 1.09 •8 •9 Total Glass Area in Zone 11 = 24: Total Glass Area = 7161 r -------------- ---__1_-- • 402------- 1^- --------------------- U --jrsul R Gross(Sgft)1 ,Elevation Type - ----------1- ----------- i North + "ply/6"Mtl Std@24"oc/R19/+"Gyp.10 19• 1701 1701 • South +"ply/6"Mtl +"Ply/6'Tltl.Std@24"oc/R19/edyp Std@24"oc/R19/+"GYP .10 •10 19 442, 7821 West Total Wall Area in Zone 1 = _21--- 402.------ -- ZONE. 2------------------------------------------^ U Insul R 1 Gross(Sgft)1 Elevation TYPe ------------ -----------; North. +"Ply/6"Mtl Std@24"oc/R19/+"Gyp .10 19 19 1701 1701 South +"Ply/6"Mtl Std@24"oc/RJ9/+"Gyp .10 19 442, East +"ply/6"Mtl Std@24"oc/R19/+"GYP .10 Total Wall Area in Zone 2 = 782i 1--- 402.------S--Z �� -------------------------- 3---------------------- U Insul R Gross(Sgft)i Elevation Type ----------19 ----------{ -------------------------------- North --- +"Ply/6'%tl Std@24"oc/R19/+"Gyp .10 19 116; West +"ply/6"Mtl Std@24"oc/R19/+"Gyp .10 10 19 , East +"ply/6"Mtl Std@24"oc/R19/+"Gyp Total Wall Area in Zane 3 = 252; --__1--- 402.------51--ZONE ------------------- 4-------- U Insul R Gross(Sgft)1 Elevation TYpe ------- -----------i -----------^----------------Gyp East +"ply/6"Mtl Std@24"oc/R19/+"Gyp .10 19 19 , 10 1 West +"ply/6"Mtl +"Ply/6"Mtl Std@24"oc/R19/+"Gyp .10 Std@24"oc/R19/+"Gyp 10 19 235� 2351 North ""Mtl South +Ply/6" Std@24 oc/R19/+ Gyp .10 19 4 =* 235: 6741 Total Wall Area in Zone --- ----------=------1--- 402.--= �---S--ZONE 5-------------------------- U--Insul R Grass(Sgft)1 Elevation TYPe ------------ ----------- 1 ------------ --------- South +"Ply/6"Mtl ------------------- "o19 Std@24c/R19/+"GYP .10 5 = 4601 4601 Total Wall Area in Zone 402. •-----WALLS--WALLS ---------- U Insul R --__1--- Gross(Sgft)1 Elevation TYPe ------------ -----------1 --------------------- ------------------ South +"ply/6"Mtl Std@24"oc/R19/+"Gyp .10 19 2301 Total Wall Area in Zane------230i--- 402------- WALLS--Z� ----- 7-------- ---^------------ U Insul R Gross(Sgft)1 Elevation Type ------ ----- ------- -----------1 -------------------------- North +'ply/6'Mtl Std@24"oc/R19/ "GYP •10 19 7 = 4601 4601 Total Wall Area in Zone --------------------1 w 402.------FIIiLIS--ZOt� 8-------------------- ------- U Insul R Gross(Sgft)1 Elevation Type ---- _______ ___________1 ----------------------- North --- +"Ply/6"Mtl Std@24"oc/R19/+"Gyp .10 19 8 = 2301 230: Total Wall Area in Zane ' -- 402.------WAi�--ZONE• -------- --------------- 9--------------- U Insul R Groas(Sgft)1 ' Elevation Type ----------------------------------------- ------------ -----------i I North +"Ply/6"Mtl Std@24"oc/R19/+"Gyp •10 19 19 115; 341 .11 Est +"Ply/6"Mtl Std@24"oc/R19/+"Gyp •10 19 17: West p Ply/6"Mtl Std624"Oc/R19/+"Gyp .10 in Zone 9 ___i--- 1661 Total Wall Area ---------- �402.------�S--ZONE.10-----------"-- U Insul R Gross(Scift); Elevation TYPe-------` -----------i --------------------------------------- - Worth +" NoPly/6"Mtl Std@24"oc/R19/+"GYP 10 19 19 34115;, , West +"Ply/6"Mtl Std@24"oc/R19/+"GYP .10 1 9 171 �t +"Ply/6"Mtl Std@24"oc/R19/+"Gyp Total Wall Area in Zone 10 = 166 . --^--j_-- ------- -------^-------- ZONE 11----------------- - - 402.---'---- U Insul R Gross(Sgft); Elevation Type -------------- --=--------; --------- --- ------------------------=- south +"Ply/61Mtl Std@24"oc/R19/+"Gyp .10 19 19 230, West Ply/6"Mtl Std@24"oc/R19/+"Gyp .10 +" 19 681 East +'°Ply/6'44t1 Std@24" Total/Wa11 Area Zone 1110 366 Total Gross Wall Area = 4568; 403.------DOORS--ZCNE 1---------------^--- --------------- U Area(Sgft); Elevation Type ----- ----------� --------- ------------ ----Fiber---- ---------------- Worth 1-3/4 Steel Door-Fiberglass/Mineral woo 0.60 0.60 5; 5i South 1-3/4 Steel Door-Fiberglass/Mineral woo 0.60 5 West 1-3/4 Steel Door-Fiberglasswoo 1 = 15 Are Total Door Area in Zone oor 403.------DOORS--ZONE 2---------------------- U Area(Sgft); ' Elevation Type ------------ ----- ----------� --- North---- 1-3/4 Steel Door-Fiberglass/Mineral woo 0.60 0.60 51, 5; South 1-3/4 Steel Door-Fiberglass/Mineral woo 0.60 5' 1-3/4 Steel erglass/Mineral woo East Door-Fib 2 = 15 Total Door Area in Zone ----------------- 403------- DOORS --ZONE 3 -------.- U Area(Sgft)i Elevation TYpe ----- -----------; r-------- ----------------------------------------- ` North 1-3/4 Steel Door-Fiberglass/Mineral woo 0.60 0: O1 Total Door Area in Zone- 3---------------;--- -403.- ---DOORS--ZCNE 4--------------------------- U Area(Sgft)1 Elevation Type ----- ----------i � North 1-3/4 Steel Door-Fiberglass/Mineral woo 0.60 0.60 21; East 1-3/4 Steel Door-Fiberglass/Mineral woo 0. 0 48� • - West 1-3/4 Steel Door-Fiberglass/Mineral woo 4 = 69 Total Door Area in Zone _ --- -------------=--- 403.------DOORS--ZONE 5------------ - U Area(Sgft); ;Elevation Type ------ ----- ----------; ' -------------------------'---^ North 1-3/4 Steel Door-FibergTotlass/Minerl al woo 0.60 01, 0i Door i°n°Zone r--'--- -------------- 403.------DOORS--ZONE 6--------------- ----- U --------- Area(Sgft) ' Elevation Type _ ----- ----- ----------{ -----------------------^ ---------- ---------- --- 1-3/4 Steel Door-Fiberglass/Mineral woo NorthTotal 0.60 6 = Oi Door Area in Zone --------------------- ------ ---------- 403.------DOORS--ZONE 7---------------'- U Area(Sgft)i Elevation TYpe---------- --------- ----- ----------; UJ/11/1999 01:46 _8003870692 ABBOTT&ASSOCIATES PAGE 06 Borth 1-3/4 steel Door-pkberylass/Mineral woo 0.60 01 Total Door Area in Zone 7 _____------'--- DOORS--ZONE 8------------------------------------ " 403. �-- �--- U Area(Sgft) 1 Elevation Type ----- ----------1 --------------------------------^-------- eral woo 0.60 1-3/4 Steel Door-Fibeota nArea 01 North is Zane 8 Door Oi 403.------ DOORS --ZONE 9------------------ U Area(Sgft)i ( Elevation Type -- -0.60 ----------' North - 1-3/4 Steel Door-Fiberglass/Mineral-woo 01 Oi Total Door Area in Zone 9 = --- 403.------ODORS--ZONE 10--------------- - -------------------------------- U Ar'ea(sgft)1 Elevation Type ---------------- ----- ---I ----- 1 North 1-3/4 Steel Door-Fiberglass/Mineral woo 0.60 01 01 Total Door Area in Zone 10 = 403------ -DOORS--ZCNE 11------------------------------------------------ U '--- Area(Sgft)1 Elevation Type ---1 -------------- ----- North 1-3/4 Steel Door-Fibuvlass/Mineral woo 0.60 ------- 01 Total Door Area in Zone li = Total Door Area = 1191 40'4------- RDGFS--ZONE 1---------- --------------------------------------i--- Insul R Area(Sgft)1 Color U Type ----- ------ ---^- -- ------------ um1hr0.02 MMI/l/2"WD Deck/WD Truss/9" Bm®i�t 11571 >a in 70ne l30 ------------------------ 19 ------- 1- d ------------------------ ------ um 0.02 Shngl/1/2"WD Deck/WD Truss/9" BTotal 11571 Roof in Zone 230 11571 404.------ROOFS--ZONE 3------------------------------------ =-----------1--- Insul R Area(Sgft)1 Type Color U -i ------------------------ ------ ----- ------- Shngl/l/2"WD Deck/WD Truss/9" BTotal Medium30 0.02Zone - Area 3 23921 r.404.------ROOFS--ZONE 4------------------------------------------------ Insul R 1--- Area(Sgft)1 Type Color U ------ ------------ Shugl/1/2`WD Deck/WD Truss/9 B Medium 0.027 30 ----------1 20431 Total Roof Area in Zone 4 = 20431 - 404.------ ROOR'"'--ZONE 5---------------------------- --------------------1--- Type Color U Insul R Area(sgft)1 -----------------------=-- -----------= ----------1 --------- Shngl/1/2'WD Deck/WD Truss/9" BTotal 0in2Zone 13361 Roof Areaum 530 13361 ' ---------------------------------------1--- 404. -----ROOFS--ZORE 6--------- r Type Color U Insul R Area(Sgft)1 ---- ------------- ------ -----•-------" ----------1 Shngl/l/2"WD Deck/WD Truss/9" B Medium 0.027 30 6681 Total Roof Area in Zone 6 = 6681 ' 404------- ROOFS --ZONE 7------------------------------------------------ --- Insul R Area(Sgft)1 Type Color U '------- ------------------------------------ ------ ----- .0230 Shngl/1/2"WD Deck/WD Truss/9" BMedium .0 ----------1 13361 Total Zone 7 3361 03/11/1999- ----c-----------i--- 'Insu1 --Colo-------U 404.------R�--ZCNE 8----------'-- R , prea(Sgft), Color --------- Truss/9" B ---- ------------ �- Medium 0.027 30 �zlgl/l/2 idA Zone 8 = _-_-, ------668; 6681 Total Roof Area in ------ ----------------{--- 404.------ROOFS--ZCM 9------------- Color U Insul R Area(Sgft)l Type ------ ----- -- ----- -------------------- •----------------�� 0.027 30 g=1/1/2'W Deck%WD Truss/9" B 9 = -------6�; 668; Total Roof Area in Zone ----------- 404. -----ROOFS--ZONE 10----------- - U Insul R - Area(Sgft), Color Tppe - ------- --------------------'- Median 0.027 30 Mmgl/1/2"WD Deck/WD TrusS/9" B 10 = ----------i 7161 716; Total Roof area Zone -- 404------- ROOFS --ZONE 11--------------- ----------------- color U Insul---R --------�--- Area------i TYpe ------ ----- ---------------- --.,�---------- Medium 0.027 30 Sbngl/1/. 'WD Deck/WD Truss/9" B Total Roof Area in Zone 11 = 659; 659; Total Roof Area = 12659; 8001 -------- ----Insul ---__1_-- 405.------F�-ZONE 1---•------ R Area(Sgft); Type------- ------------ ----------; ------------------ ---------------- p 1157 Slab on Grade/Uninsulated Total Floor Area i-Zone 1 = 1157, ----i--- ORS 405. ..--FIO-ZONE 2--------- Insul. R Area(Sq£t)', Type ------- ----------, ------•----- ----- --------------------- p 115 7, Slab on Grade/Uninsulated Total Floor Area in Zone 2 = 11571 -_-____--i--_ ---------------- 405.------F1+-ZONE 3-------'--'- - Insul R Area(Sgft){ Type ------- ---------- ------------ --; --- p 2392, Slab on Grade/Uninsulated Total Floor Area in Zone 3 = 2; 239_1-__ ----------- , ------' ------------=----- 405-------F�-ZONE 4----------- Insul R Area(Sgft) Type ----------' Slab on Grade/Uninsulated Total Floor Area in Zone 4 = 20431 ------ ----- 405------- S-ZONE 5---------------------------- Insul---- R ------ ;___ Area(Sgft) Type ------0 ---------- ------- -------------------------=--- 1336; Slab on Grade/Uninsulated Total Floor Area in'Zone 5 = 1336 405------- FLOORS -ZONE 6---------------------------- Insul R _---___-i_-- Area(Sgft) T------- ----------, --•----------- ----------------------------------- Slab on Grade/Uninsulated . p Total Floor Area in Zone 6 = 668; 668; 405.------FLoCRS-ZONE T---------------------- Insul R Area(Sgft)( Type --------------- ----------i ---- ----------- -----------------------. Slab on Grade/Uninsulated 0 7 = .1336, 13361 Total Floor Area in Zone 405------- FLOURS -ZONE 8----------------------------Insul R Area(Sgft)i 03/11/1999 01:46 8003870692 ABBOTT&ASSOCIATES PAGE 11 Nurse Stat 1 0n/Off 8 4700 23921 Total Watts for Zone 3 = 4700; Total Area for Zone 3 =2392;--- 415,----- LIGHTING, SYSI M-ZONE 4------------------------- --------- Space Type No Control Type 1 No Control Type 2 No Watts Area(Sgft); ---------- ----------------- ----------------- --- ----------------t Reading, T 1 On/Off 6 4100 2043I Total Watts for Zone 4 = 41001 Total Area for Zone 4 =2043I + 415.-----LIGHTING SYSTEMS -ZONE 5---------------------------------_---I --- Space Type No Control Type 1 No Control Type 2 No Watts Area(Sgft); ---------- ----------------- -7----------- Patient Ro 1 On/off 4 2700 1336I Total Watts for Zone 5 = 2700I Total Area for Zone 5 = 1336! 41,5------ LIGHT ING SYSTEMS -ZONE 6--------------------------------------- I --- 'Space Type No Control Type 1 No Control Type 2 No Watts Area(Sgft) •.--•-�"----- ----------------- ----------------- --- ----------------: Patient Ro 1 On/Off 2 1350 668: Total Watts for Zone 6 = 1350I Total Area for Zone 6 = 668; 415 ------ LIGHTING SYSTEMS -ZONE 7 --------------------------------------- Space Type No Control Type 1 No Control Type 2 No Watts Area(Sgft) ---------- ----------------- ----•-------------- ----------1 Patient Ro 1 On/Off 4 2700 13361 Total Watts for Zone 7 = 27001 Total Area for Zone 7 = 1336I 415 ------ LIGHTING SYSTEMS -ZONE 8--------------------- ------------------ I --- Space Type No Control Type 1 No Control Type 2 No Watts Area(Sgft); ---------- ----------------- ----------------- --- ------ ---------- Patient Ro 1 On/Off 2 1350 668; Total Watts for Zone 8 = 1350I Total Area for Zone 8 = 668; 415------ LIGHTING SYSTEMS -ZONE 9--------------------------------------- I --- Space Type No Control Type 1 No Control Type 2 No Watts Area(Sgft); ---------- ----------------- ----------------- --- ------ ----------I Patient Ro 1 On/Off 2 800 668; Total Watts for Zone 9 = 800I Total Area for Zone 9 = 668; .415 ------ LIGHTING SYSTEMS -ZONE 10 ---------------------------------------- Space Type No Control Type 1 No Control Type 2 No Watts Area(Sgft)I ---------- --- -------------- --- ----------=--- --- ------ ------�----i .Patient Ro 1 On/Off 2 800 716; Total Watts for Zone 10 = 800I Total Area for Zone 10 = • 716 ,415 ------ LIGHTING SYSTEMS -ZONE 11--------------------------------------- I --- Space Type No Control Type 1 No Control Type 2 No Watts Area(Sgft) ---------- ----------------- ----------------- --- ------ ----------- Patient Ro 1 On/Off 2 1300 659I Total Watts for Zone 11 = 1300I Total Area for Zone 11 = 659; Total Watts = 24400I Total Area = 12800I CHECK i Lighting criteria in 415.1.ASCD have been met. • ; ------------------------------------------------------------------'-----'--- 16. Operation/maintenance manual will be provided to owner.(102.1)I I --------- ----------------------------------- ---------- =-----------=--------- \' I kkk�kkkkkkk kk�kA 24P, wsa lsxsww�xxxwwxs uxx xxxxwxx rs Y Y Y P P O P a Y Y 0 11 n a 0 If YAL 0 B P n a 0 I 03/11/1999 01:46 8003870692 ABBOTT&ASSOCIATES it n -ejo ,QCn PAGE 13 41nQ^ � 5. INFILTRATION d - --- / A db Tome DXt A fAwn x G•wu ", q. Jrola _ V 8 D~ 6. SUBTOTAL COOLING LOAD FOR SPACE 7. SUPPLY DUCT HEAT tiara twr .. `�AIM . X uy a bnwr 04,n . s — 8. ROOM. ZONE OR BLOCK DESIGN LOAD AMduo "mmtotommR Use tM Ion, to *OWN* tm so"" erm . nM •llMb,ltl LEulw.7p ceo.ro uLt . ..... - tl 1, — — g. VENTILATION MCI �7 i5 e� irar� ... ..F.::: 10. RETURN AIR LOAD FROM LIGHTING AND ROOF W.OYE• 4o,s a,N WAW40 zm Lk" .. n4 . I .. =M ttrr U" n*oecWin a Arzc==m Lvft... K .Xl1 . aveum Cae�S'�9. . etso Logo t or¢: usa u mao a ¢To la Fr. u t+zror r^• mr me VAM n0,sWp4 •IEPO LOn9Ht9n bows en utc;x l X1n pwmk j pOTQ: G' opinel MMl a &Md. Ma W HD 3. Ca" LOW CAGt ..... ... H. . 11. RETURN DUCT NEAT GAIN eeee tsew ... .... X Lbw a E.nmEd Oon ............ a ' 12. TOTAL LOADS ON EOUIPMENT (Bluh) 13. DESIGN CONDITIONS (HEATING) &ratan 14 maws Oatolft ae.. COMM" 14. TRANSMISSION LOSSES HEATING LOAD � dn ,h Ft, U-Focw 73zv 01U Le.O Nobs :. X............X ........... . ........... X............X ........... . ........... ::6::a.::: x .....:::::: a X...... ....x ... ... gnXalta X.. . . .. X ... X..�,, ..x... . 89y :. X.. ... X .... .. tI&INF:ILTRATION' yIu �. ... ...X,., • 16. SUBTOTAL HEATING LOAD FOR SPACE 17. SUPPLY DUCT HEAT LOSS I.M. %cwt .. /O ... ^ /��oi.. 18. VENTILATION ��/7 "%an.. iV ....X!umam....��L7 ....,.,. It HUMIDIFICATION LOAD t..wtwo..wr...... wm ...... I p►w1s ....' ......... - MR wIXY .............. . . .. .....XaMM lwln ..... .- M......... 20. RETURN DUCT HFAT I nSS L.w. rsta ... .. X U" 1a Lw ............... . 21. TOTAL HEATING LOAD ON EQUIPMENT (Btuh) S, 9 nuf 03/11/1999 01:46 8003870692 ABBOTT&ASSOCIATES i 1 SnYMY / V / 5. INFILTRATION — ° nM1,r^n ....g .. A G. a a".. c%i ' :fee e V 6, SUBTOTAL COOLING LOAD FOR SPACE 7. SUPPLY DUCT HEAT GAIN con lea... 0 x wo f Soo" am, S. / S. ROOM, ZONE OR BLOCK DESIGN LOAD W e.n son m to Boot" rt w. thm 19ba to ea2baYW on ed.bM, "m rA •1..1.l E.+rlrl 1ST TN Cee*ep C. • ... ... .. .. U 1 & VENTILATION PR3PQ rw taw mwmmp m 10. RETURN AIR LOAD FROM LIGHTING AND ROOF wm*waa%orxaw,ewa alomomoxl Lw" .. It xlu amfw UDlxlalOxWOa• �trm ew Uytu.... ,xl.l . txpo Dreonw W. 1.0... . 6� l Notre tw u,at.o & ([lD a4 w. u a,no. rI• M mo aft AD OD=4 w. . x.. ••I1TDtxaeoeltab Oaooa oniWbl►l, t�vt,+.• lawar r10Y9:4tAbtsl "new" Ifk COW. 99W to wo 3. Coama tow or"t ..... ... 11. RETURN DUCT HEAT GAIN 12. TOTAL LOADS ON EQUIPMENT (Bluh) `%.1' &CY 13. DESIGN CONDITIONS (HEATING) &%mm ob.H ff*y OMYF ob.- DIt1pY1G.. 14. TRANSMISSION LOSSES H,EATINO LOAD Mom .. / /1 A x .. i c� ... x....f r x y��,/1�O DIM • � L.6t/n0� .. tt::� is ..x ..x .... ::�d�� . x............ x .. ..... ......... .. x............x .......... a ........... x...... ....x ... rawPhD %�,7�a.�4. Y�. x .. •. :: DAB �..::: .. x .. . .. . -• Mel"MIY,O .. .. X.. ...x .... .. - 15.INFILTRATION O all Mom.... .... .. X n■l,D DMI ..:. ,rL.0 ... . 16. SUBTOTAL HEATING LOAD FOR SPACE 17. SUPPLY DUCT HEAT LOSS 11 VENTILATION e�rrn ..pl � nOM. . , x ab u,np � � 19. HUMIDIFICATION LOAD aw.lwq.b.a......xe.......r lava law" .............. - teD x ww .............. ........ xMq UAwq ..... .-lb ......... . 20. RETURN DUCT HFAT I OSS x li" Is Le ............... . 21. TOTAL HEATING LOAD ON EQUIPMENT (Stuh) / S �y • anT, •nw / PAGE 17 I 5.INFILTRATION ///��� ftia.fl .... $ % M Tamp Dn1 �r . 111.1 • 114an Jf Wama Dw.. y.• x01! . ..... . S. SUBTOTAL COOLING LOAD FOR SPACE 7. SUPPLY DUCT H TaQAIN OWN valleff.S. ROOM. ZONE OR BLOCK DESIGN LOAD AM foot for, M b l•awa wl um on low b allnnaa naaca•IM8 CHI .a"a/f.aaw ca"Chl • S. VENTILATION NOTE: Far wxwn w bm"w w.IlabA.a aocpm I :: x 1.1 Irlt IC. NMNb x ola.• • • • Q .. �/ ... o1N... ,Ln.E . 10. RETURN AIR LOAD FROM LIGHTING AND ROOF NOTE• so 40% a em wastem mewed usm .. 30A 0 Rabm LVAL... - x•: w"wl.wft1•cumwaU Wit: skbaxq. i�emlt•abl NOTfl: LNO U 61TD Na h, U /at1.a' C•�• . far foal vAM no aanix i. NOT[ lobllaat tna evAn0 •�D Cola•C11an Daaab,aM Oln.rn Maro•1a.i•! bob. ablaf to No. i. Couma Lana CRAIt ..... 11. RETURN DUCT HEAT GAIN calf Isa w ... .... x Lfaa l lwlt" Gam ........... . 12. TOTAL LOADS ON EQUIPMENT (Bluh) 13. DESIGN CONDITIONS (HEATING) faaM Eb. f4 m•.n O.IWDa cb. 14. TRANSMISSION LOSSES HEATING LOAD m Egfamb lbr�h. •u•Facw Two Date LOCO osuwa TlD/tb Fro.# .. • //s x :: , t b :: x % ...........% ... ...:. .......... x.............x .......... w % ..../. !1 X ..... ..... o DO71 x IR : V.::: :.. ...�::.:: : ...a:.:: . ,. x .. ..... .x ......... . X...... ...:.......:.. FML1101» .... % .. .. % ... .. , a PAMpow Roo V I 15. INFILTRATION Q� 11°anlal.. Q.....%wAn[+ONI.... a0 .. ...r 1.1. 16. SUBTOTAL HEATING LOAD FOR SPACE 17. SUPPLY DUCT HEA! LOSS t•M 1IW1... I& VENTILATION N1f•Yn.. �v...xwTw �.... // // 614b aN....Q 1.1. 10.HUMIDIFICATIONLOAD ...... wa......I Ntew .............. —Too X Eary ..............muder . .......x«mn+.m ..... .- wb........ 0. RETURN DUCT HFAT I I M L•.1 facto .. .. X a n tau ............... . Lna [21. TOTAL HEATING LOAD ON EQUIPMENT (131uh) 3a y •.nan 4nn -.4ie ntuiu uy rerrormance netnoa ror Commercial Buildings Form 40OA-97 y kL-'.R(Gi EFFICIENC! • �' DDE FOR BUILDING CONSTRUCTION . Florida Department of Ccam mitt' Affairs M/CCM-97 Version 2.2 PROJECT NAME_TWIN OAKS ASSISTED LIVING PERMITTING OFFICE: ` - ADDRESS: _PT ST .LUCIE Port St. Lucie CLIMA'T`E ZONE: 6 OWNER: TWIN OARS PERMIT N0: = AGENT: JURISDICTION N0: 661200_.___,- BUILDING TYPP:_fiusiness (Office) CONSTRUCTION CONDITION: New construction -DESIGN CQMPL# ION: Pinished Building CONDITIONED LOOR AREA: 6898 NUMBER OF ZONES: 4 4M. TONNAGE'OF EQUIPMENT PER SYSTEM: 5 I COMPLIANCE CALCULATION: � AtMOD A --- DESIGN ------ I CRITERfA ---- = RESULT ------ ----------- R. WHOLE BUILDING 70.87 100.QO PASSES FR&SCRiIPTIVE'REQUIREMENTS: I LIMING EXTERIOR LIGHTING 900.00 1200,00 PASSES LIGHTING ONTROL RE7QUIR94RUS I PASSES HVAC EWIPMEP COOLING EQ,UI17k= 1, SEER 10.00 10.00 PASSES 2, SEER 10.00 10.Q0 PASSES 3. SEER 10.00 10.d0 PASSES 4. SEER 10.00 10.00 PASSES HEATING EQUIPMENT 1 1. Et 1.00 N/A 2. Et 1.00 i N/A 3. Et 1.00 N/A 4. Et 1.00 N/A AIR DISTRIBUTION SYSTEM INSULATION REQUIREMENTS -1. Unconditioned Space 4.20 4.20 PASSES 2. Unconditioned Space 4.20 4.20 - PASSES .3. Uncon�i.tioned Space 4,20 4.20 PASSES 4. Union itioned Space Union 4.20 4.2;0 PASSES REHEAT TYPES USED NO iEAT SYSTEM is USED WATER HEATING, EQUIPMEN T i 1. EF 0.68 0.88 PASSES ,PIPING INSULATION REQUIREMENTS I 1_ Non -Circulating 0_00-------_-- 0 00 ---- --------------------- --_----- I--------' ---PASSES COMPLIANCE.CmkTIFICATION: I hereby certify that the plans and i Review of 'the plans and specifica- siiedii'icatibri§ Cbvered by this ealdu- Liens Cev@L`M by',this calculation CCHPLIANCE-CERTIFICATION: % h@�:qby ;gecti€y that the plans and specifications .cove ed by tMs ealeu- latiom'Are in capl' ce the Flarida EnIar i i y PREPVM BY DATA;_ =-- -9 I hereby certify that this building is in compliance :with the Florida Energy Efficiency Code. CWNER/AGENT: DATE: Review of the plans and specifica- tions covered by this calculation indicates compliance with the Florida Energy Efficiency Code. Before construction is completed, this building will be inspected for compliance in accordance with Section 553.908, Florida Statutes. BUILDINO OFFICIAL: DATE: I hereby certify(*) that the system design is in coupliance with the Florida Energy Efficiency Code. SYSTEM DESIGNER REGISTRATION/STATE ARCHITECT : MECHANICAL: PUMING : ELECTRICAL: LIGHTING : (*) Signature is required where Florida law requires design to be performed by registered design professionals. Typed names and registration numbers may be used where all relevant information is contained on signed/sealed plans. 5.1(4FILTRATION _ , r' tlxmin .. , ...It •b'romp our x,.r 69 1 Ins B. SUBTOTAL COOLI G LOAD FOR SPACE nIR 3/-3— 7. SUPPLY DUCT IqEIU GAIN Wrn rector X 6 2097 .. LIN Sensible Gain • B. F.-OOM, ZONE OR BLOCK DESIGN LOAD •ad OUCS 9W. m to subtotal (6) Ou IhLL lo04 to 411;vnaie IN cooling CPU any a SfnuWrl t5„pni. ,d• +•� yoormQ Crrn • sees . (f t . Q.1)E LATION NOTE! Far felum sir Wlings 0 bNenince rd� .WdW CM-DMnum dhl //yy r,xmm .. "ry-pU X OD T6mg DIII. I..X1.1 •��3�. /�v�fltanin , ,a: pL/ ... X Grpins 1XN...5.. , J(Dk6 • V•fr"��+ 10. ETURN AIR LOAD FROM LIGHTING AND ROOF WCTf add 40% of IN in61all6O Meatfoosaant Lights.. X].a . laws.I'o. Lights feCCaeed in a Fimumeconl Upbt■.... X4.1 . (t1. mum; ;r Ntling. Cool aacdl WOTE i U rdue 4 M Prt. rl. U Fealpr F•`^' tmtoe4wnnrwwlenp ,,, (�1. .x. IXTD conaction bes" 64 ptonom lemperaiuni.) fwt• Subtwi the ceiling qe4, rlrlor to No o. Colllno LOW Cradll .... 11, $TURN DUCT HEAT GAIN geln rector ... ... X Lim 6 Seruible Cain ............ r 12. iOTAL LOADS ON EQUIPMENT (Btuh) 13, , ESIGN CONDITIONS (HEATING) InPde dD 1.1 minus GVtaide db • Qflvenca 14. iRANSMISSION LOSSES HEATING LOAD iaooaure 24 Flu LJ•Futor 70mo Dllf ,Adnde�.7 x : ' A / • :: x Load Miss Owls c u x::-irq ::x... .gab' x..I....... X ,. ..... .......... X............x .... ..... .......... X. ,.7 sees>< sees sees o X.;6:L/......X .... .... . , %::.. X..... ....X ... Fbfilons :sees. ::: X .. .. X .. , ... . .. . Ogorl'geiunp .. X .. ... X sees .. -• ,. - 13. • NFILTRATION Mnnln ....0 sees . X do Temp Dill. 18..bUBTOTAL HEATING LOAD FOR SPACE 17. SUPPLY DUCT HEA LOSS ��� lde6 4C1or../ .. X LIM M LMetDle Gain. ... • � 18, VENTILATION ^�1 0...- f0hw"..49 X As TMnp an..f�,V ...F,a. „ 19. WMIDIFICATION LOAD sw was mftiw...... Nwesp• ...1 flimin .............. - rob X lNufN .. ........ , ft (0004 alliday ........ x (ai n Itnin .... ..too* . 2O•.RETURN DUCT HFaT I OSS Leas facto'. .. X Lnw 16 tau ....... . ...... . _ 21.'70TAL HEATING LOAD ON EQUIPMENT (Bluh) ACA_464 llr C COMMERCIAL LOAD CALCULATIONS • Aft Cond•Uoning ConlrAelaat(R00ONE r BLOCK LOAD) 3 A'�, _ .`a ' 1712 ew Hampshtre Avenue, NW eshMptoq OC 2g0g9 +E 262.433 • 9376 .. l • MI/ . All! FORM N • 1 ra Nama.L&LA OAKS 67sf/S7/Y d L/!//N Pnane 61414zip�_�_ 6y., c4r4mmr Pnonv... . !tl I YI s! 1. bESIGN CONDITIONS (COOLING) �• (nna=1Day '�1 awlyar,"I/' r Itptllud! 1 S'r bIQWv1��26 a)Insldvdb'"'`�J"''''�� N11 �--_----^ lAIt&ld1ah63P.m. Q(7111trW111mv=IdiyeareclionalinwMsldldryanb�L`_f .KT.D. 2, SOLAR RADIATION HEAT GAIN THROUGH GLASS, COOLING LOAD SAAdmg andmi Ssimba Was EfeeOf``9te }ig. Fl. ,rao�1+//r Favlol Gas•,&Wo I Cpl. X. X. .. ..... ....:,.. ............X ....... o x .. ,.. ............. %x ii// _ ..,.. .......... ....... ...... �... 3.YRANSMISSION GAINS • Equlealsm a Emp=a=11 Fp Ft. u FK10r Two ...X............ cwv .. x......... .x ... ......... x........... % .. ...... _ X ...... /.. •^/n..... .•J,Q....x ....... .........%.. ...........x ...... . .. .. . Flo �C V , x% ..X .. . IbIrCelling .. .. .... ......... . ....... a ....... ... List Table 9■ to dalumine IM Tem9lninre alllvnnce Across I flatwn Alfcoring talent 4.:INTERNAL HEAT GAIN a:Oecupan(s Humber sln,l9ln want x . i gv...090 :.aravx ........... b, LIghts & Others Ntla �y N TdihUav60%of "ifilillLight& :U'I'/�/j %!'1 /•`••'• s•T 1. Wled Mall, for Flounscint Lights • II=tilf In piWn Lod usage an e=Illnp. Faet=r Facl=r. Ny.NP. BIWI flolws ...... ............ x.... Is..... .. , ...... . ...... .... I . . . . . . . X.. .. IL...: ...... .. .. Styli W Used• ..... ..... A"11a ea ... ......... ..... ... .x..... •C��rl iacb�uv: .;rda: otb" wit/!........... ...._r_...,,L.r.,•.a 1=be used whh ACC:, tlandalN Ppll Sublol+l �%. SANFILTRATION 11Imu ... X ae Two Dirl .�� , , X 1.1 $ _ nMinin•S " 2 Grrn/ Dl,r.. , Xoa O Va B. UBTOTAL COOLING LOAD FOR SPACE 7. WPPLY DUCT HEAT GAIN • Wn lector .. X Lira D SlnsiDl► Un (I S. kOOM, ZONE OR BLOCK DESIGN LOAD Add duct pun M to Suolotu f0I ' Usa thIS 9OW Ia asllrnala Ina caannl CFM gL,Nw. IN c,"..19 CPU 0, YENTILATION NOTE: Fa tolvm air fa or" list 1hnlrines / �. a V �7' hulibat tlD •Dbnum 8O1 /� X OD Trno Dnl. x 1., p-� .. X oreins any „ S5 ....XD.DD • I. /Q.� 10, i ETURN AIR LOAD FROM LIGHTING AND ROOF NOTE c0A /0% o1 the initalllE-fhcfsVwjat Lights , -. - LY ? �. Ligma toceoow in • Vtcu a -t Lights . s . #4.1 " tnumAit "I no. . - ND1tI Uoo u va w L ETD sq et. u snetor pF'^• to, (i with no CNiinD. X. •°(ETD eel, OpnOCtbn Dad1A M pgnune lamo/r/lur..l . NOTEI•I SuDlract th► eoillno boo, ri lot to No J. t'AltinO LOW Ctooil . .. .. rl. 11. 6CTUAN DUCT HEAT GAIN Gala fulot . , x Line 0 SonsiOit Gun . ....... 12.1,OTAL LOADS ON EOUIPMENT (Btuh) Q i d 9, f0. 13. 6ESIGN CONDITIONS (HEATING) • Inside OD J.)minus OuNfd 4b R Dirf/usnee 14. iRANSIVIIiiiON LOSSES HEATING LOAD • WDoaura 0V Ft. U•F+ttor Two oil' 1Mnuoivt x ... .. , x ... , .. . It . LW uol// CLyll. c�v�: 7e?.S • • : ; /YY :: x :: : : 36a v ...... . . is ............ is ..... R ..,.�..... ...... .., .. x ,......... x ...... . Dom Y-Jl .. .. O.... x ...Y.O... , . x .. ...... .. x.. ....x .. ... . DY111x�O/ .....,. .-. X., ..x ... o '3v. xy,Ia... x da..'?... x tic ., . IWOt�' nn0 is. I}JFILTRATION tTtlmM .... 0 .... k Yp TOmo do ..... 16. iUSTOTAL HEATING LOAD FOR SPACE 17.. UPPLY DUCT H€ AT LOSS I L.e11 IICiDt . !y . , X LIM 16 i1n1IW1 Dlln .. • • • Gl 7a 18.1�1ENTILATION //, j/1� 6! Ittrmin..;20o .... x I%T►mp Din„a" ..■,., . �i'O 1D.AUMIDIFICAT10NLOAD aniotPAmnind .....pa......I , eNI H ....... — tau x �10W .............. R 1.N.9 rdsT . x Wq h thnin — 1D0 • . 20. AETURN DUCT HFAT I OSS Lou two, . _ • ' ... X LMV t0 Lo" ................ r 21.!'OTAL HEATING LOAD ON E0UIPMENTA1uh) q, -_., - _._ _..,..:.. . _ - . I... yd f6p), r4CCA COMMERCIAL LOAD CALCULATIONS Ab Conthliming Coneaclon o1 America I T00 ON r BLOCK LOAD) 1712 New HatllpsWe Aveips NW yW�u��Nnpldn, DC 20000 'r""ta 202 a 463 , 0370 :FAX 202.234 • 4721 FORM N . i Fur Nam. aYj�!. O&V 9 - d L 1WH F Proof AO*04 — n"_ _._ ..--L[rk' 51111ZIP.r...._.-. et: c ulclor Phone — Amin fYr _ 11 21 1. DESIGN CONDITIONS (COOLING) rn^r• ol0•Y �m I mills RarW F I (LA11 --•_) +S r dh_L._..__++b �a C+^^elntrr it lntlda db RH WOWdda /����• � QWfWt 4b07Pm I.11nxWtlDne ill WyrgRatllont�.,l�l minY7 Mildo dr7bu16�•1yi,,,,�Lc. 2. SOLAR RADIATION HEAT GAIN THROUGH GLASS. COOLING LOAD . Printing aAdtor ¢cnlbi. Nolte Gllbia0 y4 f1. Solve rector Issue P"1W : ✓: :::•:�:�::..... X ..........x ,. 4 ,.x .......... �.. .... •..... •..•.. X........... ........ :. . ... ................ x........ I ... 9 .: ...... . .....I.... ............... Ix...........x ......• .......... x :x 3.' PIANSMISSION GAINS Equlvp10n1W db Evitoauto S6 FI. V Facldt Tamp 0.11 liters pt�} J �j e� X ....I ./ ..... x ... /�.. • /] /) �% :PO4 . , .. /'I��. ..I. ..l �9�.x....� ... ... CA4U ::%::; %i�I. •.gip .... a Was .:f>•ra .: X......... . X .. ..... ......... . .........X .......... X ... _ : : •C7 :: %U :::: z :: ::... ...�.,y.�... . 16 �!.... . Doets ,x x............x .. ..... .......... Pulillona .....?./;. ..... /...j...K............X .,. n.1..,. ..... c FIN+11 :ULf14::K :l:tl •:7Kt:::: : .. .%..... :YY0.... Rost /.0 flooks111.9 . .... ......... X . , .......... % ........... . ...... . RA,e111ng . ...... .........x ........... , x ........... • .:....... . . list Table 94 to dalermine 111f T,mperalvrt 0111etence ActOst A Return At, Grlina 1.iNTERNALHEATGAIN Lalenl ble Galen! a, Occupants Numi,qt.. Q �pl�..... x............ X G .�.�U... Vinod' x ........................ ,��a0 b.l ighls & Others w.u, Haffc. Use W%of Imcandetgnl Utlnla /�j��/j� A34 X a.l In0'elltd M11s fur Pluuftxtel LlgMs ..�{J.4f.r • Ilynrra In rMurn or F.atihrp. Load usage N.P.H.P, ' mlun Factor Fain. ...... ...... r... .. X.... x. ... ........... ...... ..... AL... x..... ............ .� fens Lai uttoa APollanaa ............... (. ..... .......... .......... 'This tormd.slgned lobe usild wlih ACM.Useual N.. Point Rublalal A. M 5.I�FILTRATION �! Gwns Dill. B. S� 13TOTAL COOLING LOAD FOR SPACE 7. S� PPLY DUCT HEAT GAIN ' Gall Iscldr .. A9.X LIM O tisnsim Gwn B. ROOM, ZONE OR BLOCK DESIGN LOAD Add duct Own M ID SOME, (6) Use this loud to w,11mNt Ilia awing CCU , ..t.M l SIn{�tN,l 1'+•�^nl. To. Qaplm4 QIN .•. It I • 9.1�ENTILAT ON NOTE. Fr IWum sit giltnpo Ob ddtW"M ig C $ia tw owob gbnum ch) Y V'-'�/ / %�o.• _ J,SrF l ¢yf nMmhl ....%001"VDill. ...X1., Oro A i; j%I/ PIMtIIn : ... x Grains DIN... ... X0.68 ■ ■ . :, 13 Px� ' 10. RETURN AIR LOAD FROM LIGHTING AND ROOF NOTE pdd 4% of tM WOW Mcw4 w66t Ltont6 . • X3.4 Is It 1. want 4r Whitt rINbYOod In d lvemmoc.st Vole.... x . %1.1 ■ , , Whim rodlllnp. 6R661 Wwdl NOTE,. U Wu6 a LTD kl ot. U reatr tot , with no cotltr.Q, n . . X 1670 tortW"Oac,6 en pl,6um tomparalmi NOTE btfwl the vofilnp low, 1st fo No 7. Curling land Cadil ... 1�1, 11. R URN DUCT HEAT GAIN gain hlclof ... - ... X Line, 6 Sensibit Gs-n ....... • .... ■ 12. TpTAL LOADS ON EQUIPMENT (Btuh) IM r.. P.. V,Koh 13.'D,ESIGN CONDITIONS (HEATING) Insid. db (•1 militia Outside db . Diffewco ' 14. TrANSMISSION LOSSES HEATING LOAD db emposuts 1,1.ruldr Tome Dllf X - ::a.9 LOW Netts It... ■ : vjV1 X.....,.....% ...., ■ .......... If ....t....7..... X _ . ...... .......... (. j/..... Oaa•s off•/ Y.. ..� �.... % . �. f� V.. .. % .. ...... w . ��.0 .... . ...... �. X.. ....X .. ... w .. • Perlilia�ns .. X .. '' .. % ... il• 1. '�!�.2... ;l.i.? �....'. x . w lG30 • pwef Nling .. % . .. X ■ . 15,1, FILTRATION � U .%db Trap Otn... ,T.t V ■ 15. 4610TOTAL HEATING LOAD FOR SPACE 17. UPPLY DUCT HEAT LOSS li Lau Belot .. /,� , , ICU" tE Stnslld, Gain .. ■ (f g_ 18.1,IENTILATION SS 1.f■ t, tl/min,9 .... %de Twmp Diff..� ..., j��] 19. AUMIDIFICATION LOAD &%*a ID..lra .....Inds . I • Harman .............. — 106 % shift........... . .. ■ . MMM f06 .... , , • X Wd h 41n1n . � . � . _ 100 s ........ � 20. 6ETURN DUCT HFpT I nSS , Lou I,elar . . X Line 16 Lost .. . ■ .. 21. TOTAL 14EATING LOAD ON EQUIPMENT MIUW ... 912 e .wn •Aft ACCA COMMERCIAL LOAD CALCULATIONS AD Condflinntng Contractors of Am/rka 0 ONE r DLOCK LOAD) 1712tAE HampstdteAvemie,ton, DC 20009 202 • /D7.937o 2022234 04721 �7 ,r FORM N•1 • For. Narna�I� Q��..,t /7•SS/-•i i��%�� ftane &ddera Ch rE+ stele Pnana... .. ep Atltlrcas rv.. �tatr - Zln _ 1. DESIGN CONDITIONS (COOLING) (Tlim of DAY 1 IDWIYMOOVZ`4__1 tun .�._..�_In �j a.+n. �• yXttldadb_.�[,�.,� f1N��140u1,ld.dp d / a— ���?�• 04ild•db 03 P.m 01.1 mtrrus lima of day cewacllons�l4 minus lnsida drybvtb�.4--.—TA. 2. dOLAR RADIATION HEAT GAIN THROUGH GLASS. COOLING LOAD 6neMnp andgr s.a,lW& tk+&• E?ypiUte 5%Fir So4r Factor Gum Faclm ... .. ......... X............ K .. ...... a . ..'.. ..:...... ..... .. ........ If.......r....z .......... v _I 3.1IRANSMISSION GAINS • EWr db or ae Marl lapo,ure 5a F1. V fFcilar :x TNnp`Onl •� Q (� will" z......... : x ..... . ......... SrC:: :: = :%a::.: t,wrf ,ro::::x ........X............x : ; ::: a .. ...... . ......x ............ x .. ....... _ . , . padijidns Fingers �g+ ...... �36 .. ..x . 0)S7 ..X.0 .P.0 .... .. K x . .. �/.... a ,.... �. .�H / •� . . :. ..... .........x ............ It .. , ........ .....:.. e P,A ...... r ... . . r A ............ . x- ...: ••. .....�• is 4. INTERNAL HEAT GAIN a ccupartts Nuteber Sonslbie X....�9a..:: .3U: x .......... x .::� ;�;. b. Ights & Others WN1, l NInsI,{ tUpitl, t /•�,{ A3.1 x 1.1 • ■ J(� led W113 FaoI Flawlscani ll/hls F/�G�.1� .//�/��. IlpbI s in return W, 5alllnp. load Vs,pa N.t'.N.P. Blurs Facia Fagter YoltX7 .... ,.. ......... x.... X. .:. .......... ...... ............ X.... X. .... .......... F,Yy V1 INN& 11(a•rlarrga . ... .. ..... .. .. x.... ........... •Tale termdaalpnea to be wind wlin ACG.YendJN s_: :P,pll tiAWA S. INFILTRATION / M1mtn •. • �• - ..... A D0 Tamp 011f N4.n,n 8 .X G,rns DILL , . , .10068 • S. SUBTOTAL COOLING LOAD FOR SPACE 7. SUPPLY DUCT HEAT GAIN Gam flow X Line 1 Sensipts 0sin • �� ` A ROOM, ZONE OR BLOCK DESIGN LOAD Add duot Don M to S„«otal 16) • Use this Iaed 1• eellmale the «<Ilng GrM n mT a SenpOul tsnnnl. 7N tAa`,^p Cru .•—' .' rrt'� B. VENT ILAYION. NOTE. far Muth Sit Wilnpe ap D,nD,gnDe s(an&W 0.04inum 0) X (mot DD TWnP Dlff. /�, ` �e hMnin .ef• U . X Owns Vitt... ... X 1.1 10.,RETURN AIR LOAD FROM LIGHTING AND ROOF NOTE Wd e0% of the installed D Awascent Lights orolti tot Lights ryoeeoed In a III DWAIN4nl Lights.... X X4.1 I! 1. . . M,,J, ei, "111.0 . 'pool UNA NOleg: Uea U wow i ETD D4 r,, L1 FWD? F.+h' corn I•IIIlnooplllnD w. .X. NOT' Su01rae1 In* ceiling '(ETO corlet,lon based on plenum, Imps,etunJ I!1 Iwdl hile, to No 3. Calling Load Credit .... ... (-), 11, RETURN DUCT HEAT GAIN Oein rector , . x lino 1 SeroiDle Gain 1 12.50TAL LOADS ON EQUIPMENT (Bluh) IJ91 f e�,/rah 13.IDESIGN CONDITIONS (HEATING) ' Wide 60 1.1 minus Ourylde d0 a 0d4ronce 14. YRANSMISSION LOSSES HEATING LOAD exposure sq Ff. U'F.elpl w Temp Diff Lead Nails x Went X :�9 e i ... x ... X ... . x..... ...X ...... .. ..... ....... ... X . �: �: o::.. x .. .. , ... ::�s: i X . Parlll+orls ... X.. ILtol fi�Sl l./ ..�Q•?.� x !.�b,1.�.... X .. ..X . •, . . '�dl Illnp .. X.. X , e• - , 15. INFILTRATION n p ... p� 16. USTOTAL HEATING LOAD FOR SPACE 17. S'UPPLY DUCT HEAT LOSS x LIM If 8e411ble Olin., .. ■ �/Z 18.�ENTILATIO�In xdeTamoan p� 19. hUMIDI FICATION LOAD /��� Inatds RH (Deprsd , . , ..XMar , .. , ..I WAnin ............. — too X ctumt ............... (rr,sy 9411day....... X (atd if 4min .... }� .... . 20. 6ETURN DUCT HF `r 1 ASS Less factor . , _ ... X Line 15 LOSS .............. 21. TOTAL HEATING LOAD ON EQUIPMENT OLIN (J 3 0U 1 " COARCIAL LOAD CALCULATIONS • ACCK All C°rdllioning Conlraelord of America (R00 ON t BLOCK LOAD} 171r New Hampshire Mantra, NW / • 111140nplon.DC20009 P"uut 202.40319370 Flu 202 a 231 1 4721 FORM N - 1 It Pima ilp_.-._.._.... By; Cemrecl0r Pndne_ 1. DESIGN CONDITIONS (COOLING) 171m/ of boy ) luly PA112e IV • Nall ld/,j �F 1 s)Insided6_ M ll Ir b)0vlsldodb� wb GQ�J� ���r 0ulyldl db 0 3 p.m. 0 Id minus lima of day cd1tK110ns,,..�1•I minus Inside drybulb�-lea•--.LD. 2, SOLAR RADIATION HEAT GAIN THROUGH GLASS, COOLING LOAD 6nsemg anemr similble Hulot • 6posule 3q-LI. gofer Facto. 61us Fodor // .• x ::9:9 :::::: x ... ..... A�Ass : .......... <.:.:.:..... X .. ......... ... ... ............. X............X .. a ... ..:... %...... .....X ........... • .......... ..... ............... X . X 3. TRANSMISSION GAINS fg116310 l nr db l:1po,Vld b0•Ff. UFeclor rump pill class xY,•1..::::x ...... .... ..X............ X .. ..... _ ........ . ::x.. Po tillons ...... .........X ............ X .. .``.:�Q.rr//.... . FI•�on .% . ... .lIQ.V... . ..........% ........... ollcelling ........x .. , se cable 9f to dalermin. the Temperslpre OlNarentt Acroa + n•Imn Al. Ce.nny ' U Ulenl 4. INTERNAL HEAT GAIN L Oc upants Number SmslO! ltlanl // /►3 j •s ,/r id �l►9� V. %.../��... x b. Lights & Others . Watts N T¢t WadO%ol Incmdlscem Lipnu /jos J� : A4.4 " rQ(� Installed watts for "�.•. Floprefeani Lights , . J./lei/• • X 1.1 n - , /.1 ./. /�• . .'.,� Il ts In return U, eellln V/abe N.P.H,P. .,etuh Fatter Feeler Molodi,' ...... ..: ...... X. . X. ... ......... . ....:. X.... X..... .... ...,.: x. AyPlbnQe'. .... ... .:..:.. ... ... Y.. .. ........... ....... .. : �.. o ov raga*X.,/* • .... form 4eslpnee fd bl usA6 whh ACC:.1.1mualN Pa011 guLloUl ... a Type - et" a'ru uu,wa -----•------------------------------------------� 412------W� HEATING SYST WZONE 1----------------------*" -------- Type Efficiency Efficiency StandbyLoss InputRate Gallons; ---------•------------------------- ------------------------------1 1. a12 kW .88 .001 4.5 401 412------ WATE1 HEATING SYSTEMS -ZONE 2--------------- =------------------ ;--- Type Efficiency StandbyLoss InputRate Gallons; ---------•--------------- ---------- -------------------- ----------I 412.-----WATER HEATING SYSTEMS -ZONE 3---------------------------------- ;--- Type Efficiency StandbyLoss InputRate Gallons; ---------•--------------- ---------- ---------- ---------- ---------I 412------ WATER HEATING SYSTEMS -ZONE 4---------------------------------- i--- Type* Efficiency Staii&yLoss InputRate Gallons; ------------ ------------ ----------------------------------------' ELECTRICAL SYSTEMS CHEC ,1 413 ------ ELWMICAL PagER DISTRIBUTION----------------------------I-----I --- Metering +;riteria in 413.1.ABCD have been met. I Motor Off ciencies in 414.1.ABCD have been tact. � .415.-----LT ING SYSTEMS -ZONE 1 --------------------------------------- Space Type Np Control Type 1 No Control Type 2 No Watts Area(5gft)1 •---------- --- --------------- ----------------- --- ------ ----------I multi -fun. 1 on/Off 4 3900 18211 Total Watts for Zone 1 = 39001 Total Area for Zone 1 = 18211 415------ LIGH�ING SYSTEMS -ZONE Space Type Np Control Type 1 Multi -fun. 1 On/Off 415-- ---- LIGEhNG SYSTEMS -ZONE Space Type Nj Control Type 1 Reading, T 1 On/Off -----LIQfr ING SYSTEh1S-ZONE e Type N6 Control Type 1 2--------------------------------------- I --- No Control Type 2 No Watts Area(Sgft)1 ----------------- --- -- --------------' 5 4300 21571 Total Watts for Zone 2 = 4300 Total Area for Zone 2 = 21571 3--------------------------------------- :--- No Control Type 2 No Watts Area(Sgft) ----------------- --- ---------------- 4 3000 14521 Total Watts for Zone 3 = 30001 Total Area for Zone 3 = 14521 4------------------------------------- --;--- No Control Type 2 No Watts Area(Sgft)1 ----------------- --- ----------------! Reading, T 1 On/Off 4 . 3100 14681 Total Watts for Zone 4 = 31001 Total Area for Zone 4 = 1468; Total Watts = 143001 Total Area = 68981 c=; Lighting criteria in 415.1,ABCD have been met- i I ------------- -------------------------------- --------------------- ;-----I--- 16; oper-ationIlaintenance m► mual will be provided to pwnet•.(102-1) ----------------------------=---------------- Slab on Grade/Uninsulated C 14681 Total Floor Area in Zone 4 14681 TotalFloor Area = gggg'--- 406.------INFILTRATION -------------------------------------------------- I CHEM Infiltration Criteria in 406.1,ABCD have been met. ; MECHANICAL SYSTEMS CHECK ------------------------------------------------------------------l-----l--- - HVAC load sizing has been performed. (407.1.ABCD) 407------- COOLING SYSTEMS -------------- ----------------------------------'--- Type No Efficiency IPLV Tons; ----------- ----------------- ------------- ----- --------------1 1. Split Syptem 1 10 10 5.001 2. Split System 1 10 10 5,001 3. Split Sygtem 1 10 10 4.001 4. Split Sy,tem 1 10 10 4_00! 408.------4E ING SYSTEMS--------------------------------1-------- -- TYPe No Efficiency --------•------------------------ BTU/hr; ---------------------------' -1. Electric1esistance 1 1 344121 2. Electric:Resistance 1 1 344121 3. Electric'Resistance 1 1 250001 4. Electric:Resistance 1 1 25000;--- 409------- VE9TILATION--------------------------------------------------- lCHECK Ventilation Criteria in 409.1.ABCD have been met. I 410------ AIR'DISTRIBUTION SYSTEM --------------------- --------------------- 1--- CHECKI -----------------------•-------------------------------------------;-----l--- Duct sizing and design have been performed. (410.1.ABCD) XV Type Duct Location R-value: --------------------------------------------------------- 1. Air Conditioners Unconditioned Space ------- 4.21 2. Air Conditioners Unconditioned Space 4.21 3. Air Conditioners Unconditioned Space 4.21 4. Air conditioners Unconditioned Space 4.21 CHECK! ------------------------------------------------------------------;-----1--- Testing Od balancing will be performed. (410.1,ABCD) 1 , 411,-----PUMP.� AND PIPING -ZONE ---------------------- =------------------1--- Basic pre,:,criptive requiranents in 411.1.ABCD have been met, 1 PLUMBING SYSTEMS �11.-----p W!d AND PIPING-20NE Type - =1. Non-Circu'ating 411.-----PUMP! AND PIPING-20NE Type 411.-----PUMP; AND PIPING -ZONE Type ------------------------ 1- -------------------------------------1--- R-value/in Diameter Thicknessl ---------- -------- ---------; ------ 5---------- R-value/in Diameter Thickness: 3----------------------- ----------------1--- R-value/in D,iam-ter Thickness; ---------- -------- ---------1 1-3/4 Steel Door=Fiberglass/Mineral woo 0.60 LU; 1-3/4 Steel Door `I;erglass/Mineral woo 0.60 411 total Door Area in Zone 1 = 511 i 1403.------DOOPS--ZONE 2------------------------------------------------,--- levation Type U Area(Sgft)1 ----------------------------------------- ----- ----------1 South 1-3/4 Steel Door-Fiberglass/Mineral woo 0.60 101 Total Door Area in Zone. 2 = 101 403------- D00fs--ZONE 3------------------------------------------------i--- levatiori Type U Area(Sgft); ----------------------------------------- ---- ^--------------1 West 1-3/4 Steel Door-Fiberglass/Mineral woo 0.-60 201 Total Door Area in Zone 3 = 201 403------=DOORS--ZONE 4------------------------------------------------ ;--- Elevation Type U Area(Sgft)1 ----- ---------------------------------------------- ----- ----------1 North 1-3/4 Steel Door-Fiberglass/Mineral woo 0.60 101 East 1-'/4 Steel Door-Fiberglass/Mineral woo 0.60 201 ..Total Door Area in Zone 4 = 301 Total Door Area = 1121 404 ------- ROOFS --ZONE 1 ------------------------------------------------ Type Color U Insul R Area(sgft) -__•---------------------------- ------ ----------------------1 Shngl/1/2'WD I)eck/WD Truss/9" B Medium 0,027 30 18211 Total Roof Area in Zone 1 = 18211 404------- ROOFS --ZONE 2------------------------ ---------------------:--- Type Color U Insul R Area(Sgft)1 ------------"---------------------- ------ ---------------- Shngl/1/2'WD Deck/WD Truss/9" 8 Medium 0.027 30 21571 Total Roof Area in Zone 2 = 21571 404------- ROOFS --ZONE 3------------------------------------------------ 1--- Type Color U Insul R Area(Sgft) ------------------------- ------ ----------------------1 Shngl/1/2'WD Deck/WD Truss/9" B Mediun 0.027 30 14521 Total Roof Area in Zone 3 = 14521 1404.------ROO?S--ZONE 4------------------------------------------------ i--- Type Color U Insul R Area(Sgft)1 -------------------------------- ------ ----------------------1 Shngl/1/2'WD Deck/WD True,/9" B Medium 0.027 30. 14681 Total Roof Area in Zone 4 = 14681 Total Roof Area = 68981 .405.- ----FLOORS-ZONE 1---------------------�---------------------------1--- TypeInsul R Area(Sgft)1 i Slab on Grade%Uninsulated 0 18211 Total Floor Area in Zone 1 = ,18211 405------- FLOORS -ZONE 2---------------------------- -------------------;--- •Type Insul R Area(Sgft) ---------------------------------' -------------------- ----------1 Slab on Grade%Uninsulated 0 21571 _ Total Floor Area in Zone 2 = 21571 405.------FL,ORS-ZONE 3-------------------------------- ---------------- ;--- Type Insul R Area(Sgft)1. ---------------------------------------- ------- ----------- Slab on Grade%Uninsulated 0 14521 _ Total Floor Area in Zone 3 = 14521.:, 405------- FLOORS -ZONE 4......... --------------------- r--------------=1--- ✓ 401.---4--GLAZING--ZONE -----------------------------• a1ECK ---------- Elevation type U SC VLT Shading Area(Sgft) --------- --------------- ---- ---- ------------------ ----------' South Cammercial 1.09 .8 .9 54 West Camercial 1.09 .8 .9 156 Total Glass Area in Zane 1-_-- 210 401.------GLAZING--ZONE .Elevation 2---------------------------=--- --------v- Type U SC VLT Shading Area(Sgft) --------- --------------- ---- ---- ------------------ -- ----- -' South Comercial 1.09 .6 .9 941 - East Commercial 1.09 .8 .9 96; Total Glass Area in Zone 2 = 190 401.------MkZING--ZON2 3------------------------------------------------ v- Elevation Type U SC VLT Shading Area(Sgft) --------- --------------- ---- ---- ------------------ ----------' North Commercial 1.09 8 .9 60 West Camlercial 1109 .8 .9 721 « Total Glass Area in Zone 3 = 132� 401.------GLAZING--ZONE 4------------------------------------------------ v- Elevation Type U Sc VLT shading Area(Sgft) --------- --------------- ---- ---- ------------------ ----------' North Cam-orcial 1.09 .8 .9 90 East Commercial 1.09 .8 .9 72 Total Glass Area in Zone 4 = 1621 Total Glass Area = 694 •402.------WMLS--ZONE 1------------------------------------------------ i--- 'Elevation Type U Insul R Gross(Sgft) ------_� -------------------------------- ------------ -----------� x,South 5%8"Stco/8"CMU/3/4"ISO BTNN24"oc 0.149 4.2 162 West 5/8"5tco/8"CMO/3/4"ISO BTWN24"oc 0.149 4.2 6481 Total Wall Area in Zone 1 = 810 '402,------ WALLS --ZONE 2------------------------------------------------- ;--- uElevation Type U Insul R --------- --- Gross(Sgft); -----------; ---__-___ ;South ----------------------------- 5/8"Stco/8"CMU/3/4"ISO BT024"oc 0.149 4.2 36011 West 5/8"Stco/8"CMU/3/4"ISO BZWN24"oc 0.149 4.2 81 East 5/8"Stco/8"CMU/3/4"ISO BTWN24"oc 0,149 4.2 6481 Total Wall Area in Zone 2 = 1089 402.------WAtLS--ZONE 3------------------------------------------------ ;--- Elevation Type U Insul R Gross(Sgft) --------- North ------------------------------- ------------ 5/S"Stco/8"CMJ/3/4"ISO BT'v7N24"0c 0.149 4.2- -----------' .22511 West 5/8"Stco/8"CMU/3/4"ISO B'IWN24"oo 0,149 4.2 468 East 5/8"Stco/8"CMU/3/4"ISO BT024"oc 0.149 •4.2 32 Total' Wall Area in Zone 3 = 7251 402.------WALPS--ZONE 4 ------------------------------------------------ -Elevation Type U Insul R Gross(Sgft); --------- ----------------------- --------- ------------ -----------' iNorth 5/;"Stco/8"CMU/3/4"ISO B7WN24"oc 0.149 4.2 3061 West 5/ ,Stco/8"CM/3/4"ISO BZWN24"oc 0,149 -4.2 32 -East 5/8"Stco/8"(MU/3/4"ISO BTWN24"oc. 0.149 4.2 468: Total Wa11.Area in Zone 4 = 606 'Total Gross Wall Area'= 3430 Slevation Type U m`� Area(54ft); -