HomeMy WebLinkAboutREVIEW COMMENTS 2V
w ECTOR
E fl G I fl E E R S
Project Number: U1382-508-171
July 18, 2017
Planning & Development Services 7t
Building & Code Regulation Division
2300 Virginia Avenue
Fort Pierce, FL 34982
ATTENTION: Joe Cicio
1 7;--Blow
j
6UANNED THREES %e%Ng AND ALL RRO,QOS�-D W0N'?{t
BY ARE SUUMTTOANY COP ECiiONS
I_I Irlo rminty `RiQUIRED BY FIELD 114SPECTORS TRT
~. F.4.AY BE NECESSt:f?Y lk# OnDCiwit T O
C�'41 ! y WITH ALL 11 jpL ,-A1L: CC�ra.
REFERENCE: 3207 Industrial 29's St., Fort Pierce, FL 34946 (Permit Number: 1705-0124)
ClearSpan # 7259847
Dear Joe Cicio:
The following is written in response to the plans check letter with review dated June 21, 2017 for the above
referenced project. Our responses are limited to structural concerns only.
GENERAL STRUCTURAL REVIEW COMMENTS ONLY
COMMENT 1: MICHAEL LUE OR ROGER ALWORTH WILL BE THE DESIGN PROFESSIONAL
OF RECORD * IF MICHAEL LUE IS THE D.P. OF RECORD HE MUST REVIEW
AND APPROVE THE PLANS FROM VECTOR ENGINEERING * SEE FAC 61G15-31
FOR GENERAL RESPONSIBILITY AND SEE NOTE 2 BY MICHAEL LUE
REGARDING SHOP DRAWINGS SUBMITTED FOR APPROVAL **** SECOND
REVIEW **** YOU NOW HAVE A NEW ENGINEER FROM VECTOR
ENGINEERING BEING JACOB S. PROCTOR / MR.PROCTOR IS NOT PART OF
THE CERTIFICATE OF AUTHORIZATION FOR VECTOR ENGINEERING AS
DESCRIBED IN F.S. 471.023 AS MR. ALWORTH WAS / IDENTIFY WHO WILL BE
THE DESIGN PROFESSIONAL OF RECORD * MIKE LUE TO MODIFY THE NOTE
ON S-1 TO COMPLY WITH NEW VECTOR ENGINEERING DATE OF 6/12/2017
NOT FEB 15
Response: Jacob Proctor of Vector Structural Engineering will be the E.O.R. for this project.
Jacob is employed by Vector Structural Engineering and is thus covered by Vector's
Certificate of Authorization.
COMMENT 2: THE DESIGN PROFESSIONAL OF RECORD MUST ADDRESS THE FABRIC
COVERING W/ ATTACHMENT TO THE BUILDING FRAMEWORK * NEED THE
FIRE RATING OF THE MATERIAL PER FBC 3102 AND NFPA 701 ****SECOND
REVIEW **** DID NOT ADDRESS **** SUMBIT THE MANUFACTURES
ti SPECIFICATIONS FOR THE MEMBRANE COVERING AS PART OF THE
PACKAGE
/ Response: See attached fabric specifications. In addition, see added sheet K1 & K2 for fabric
connection details.
j
651 W. Galena Park Blvd. / Draper, UT 84040 / T (801) 990-1775 / F (801) 990-1776 / www.vectorse.com
Project Number: U1382-508-171
Date: July 18, 2017
COMMENT 3: VECTOR HAS CLASSIFIED THIS AS A TYPE IIB STRUCTURE AND MIKE LUE
HAS CLASSIFIED TIES AS A TYPE III B STRUCTURE * [PLEASE CLARIFY] FBC
3102.3 DISCUSSES THIS AS A NON COMBUSTIBLE TYPE IIB STRUCTURE ****
SECOND REVIEW / ITEM NOT ADDRESSED ****
Response: See revised drawings by Michael Lue submitted separately.
COMMENT 4: S-1 / NOTE 7 UNDER HELICAL PILES STATES THAT INSTALLER TO REVIEW
THE SOIL TEST AND DETERMINE THE REQUIRED DEPTH AND CAPACITY OF
THE HELICAL PILES * THIS NEEDS TO BE GENERATED BY MIKE LUE WITH
THE PILE SPECS NECESSARY TO ACHIEVE THE REQUIRED LOADS
INCLUDING SHAFT LENGTH AND DISC SIZES **** SECOND REVIEW ****
ITEM NOT ADDRESSED
Response: Addressed by others.
COMMENT 5: ENGINEER TO STATE THE OCCUPANT LOAD ON PLANS OF THE STRUCTURE
FOR A GROUP B AS STATED BY MIKE LUE **** SECOND REVIEW / ITEM NOT
ADDRESSED ****
Response: See revised sheet Bl. The structure has been classified with an S-1 use group.
We hope this meets your needs. If you have any questions or require additional information, please contact us at
your convenience.
Sincerely,
VECTOR STRUCTURAL ENGINEERS
Jacob S. Proctor, P.E.
Project Engineer
JSP/der
Firm License: 26626
OF
18, 2017
FRU88N-6 400
MEMBRANE STRUCTURE
FABRIC WITH ARMORKOTE a
INTERTAPE POLYMER GROUP®
TECHNICAL DATA SHEET
DESCRIPTION PERFORMANCE PROPERTIES
NovaShield® brand FRU88X-6 400 is a flame- The following data are typical values based on ASTM standard tests.
retardant, heavyweight fabric for applications This data should not be considered specification.
requiring UV stability, such as membrane
structures and alternate daily landfill covers. OrahTensile Warp 375 lb 1665 N / Weft 340 Ib 1510 N
The scrim is produced in a special weaving ASTM D5034
pattern to enhance thickness, flatness, Strip Tensile (N/5cm) Warp 2601bAn (2310)NVeft 240lbrin (2131)
abrasion resistance, and tear properties. The ASTM D5035
flame-retardant proprietary coating is used to
enhance abrasion resistance, flex resistance, Tongueiear Warp 120 lb 533 N / Weft 110 lb 489 N
seam strength, UV resistance and longevity. ASTM D2261
FABRIC SPECIFICATIONS ASTM
Tear Warp 110 lb 488 N / Weft 90 lb 400 N
ASTM D4533
Weave: Woven clear HDPE scrim using Mullen Burst 665 psi /4581 kPa
natural FR/UV tapes ASTM D3786
Coating: LDPE, 4 mil average each side
(95 g/m2/side) Accelerated DII >90 % strength retention after 2000 hrs
Color: White, blue, green, grey, Weathering' exposure @ 0.77 W/m2/nm, or 1200 hrs
sandstone and other colors ASTM G154 exposure @ 1.35 W/m21nm
available upon request
Weight: 12.4 oz/yd2 (407g/m2) +/- 5 % Accelerated Natural >80 % strength retention after 5 Florida
Thickness: 23 mil (0.59 mm) ASTM D1777 Weathering Standard YearS2
ASTM G90
ROLL SPECIFICATIONS LowTemperahtre0end -600C
Cares: 4 inch I.D. or 5 inch I.D. available ASTM D2136
Width: Up to 144 inches (-0, +0.5) as
ordered
Length: Minimum 250 yds/roll; Q.U.V [A-340 Lamps]; 8 hrs UV @ 60°C; 4hrs condensation
up to 1000 yds/roll @ 50*C 2 1333 MJ
These values are typical data and are not FR PERFORMANCE
intended as limiting specifications. This product meets the requirements of NFPA 701 — 2015 (Method 1
and Method 2), 2010 (Method 1 and Method 2), 2004 (Method 1 and
Method 2), 1989 (large and small scale) and 1996 (tests 1 and 2),
CAN/ULC S109-M87 (small and large scale), CAN/ULC S102-03,
CAN/ULC S102.2-03, ASTM E84-15a (Class 1), California Fire
Marshal (F-51405).
.. a intertape polymer groups Cu Paramount Drive, Suite 3001 Sarasota, FL 34232 1 USAL `r. 'COPY
Customer Service: 8o0.565.2000 FLL��JJyyCCgq��.��
w Jtape.com I Info@itape.com
— -
-While wr believe them to be guidancthee
statements arniant information
herein are only roc general guidance and are not warrants ort, /
guarantees far ecoumry and completeness. The user must, o test R C
or otherwise, dessfor a suitability purpose.
.ourpuribose.standard
There is m
warranty of fitness fora particular purpose. Our standaN term and cooLrzoOF
conditions of sate apply exclusively to all orders, and all liability far eermc mu.rn
damages of any kind, including consequential, exceeding purchase
pdco is excluded. No one is authorized by us to make oral
wanationI Wereserve theproducsandputomake tions. ngeswlthoutnoticoor NovaShield*
obligation i. our products and publications.
EFFECTIVE: 3/16 1
)vECTOR
E n O I E E R 9
Project Number. U1382-508-171
July 18, 2017
C1earSpan Fabric Structures
1395 John Fitch Blvd
South Windsor, CT 06074
REFERENCE: ClearSpan Building (Order Number: 7259847)
Foundation Review
To Whom It May Concern,
Per your request, we have reviewed the foundation design for above referenced project and found they conform to
the design concept of the project. The foundation plans where completed by ML Engineering, Inc. and sealed by
Michael A. Lue, P.E. with a revision 2 date of 07/18/17.
Please note that our general review was done solely as an aid to the contractor and that we claim no liability for the
correctness of the foundation calculations themselves.
The contractor is responsible for: dimensions to be confirmed and correlated at the jobsite; information that pertains
solely to the means, methods, techniques, sequences and procedures of construction; and for performing all work in
a safe and satisfactory manner.
We hope this meets your needs. If you have any further questions regarding this matter, please call this office at
your convenience.
Very truly yours,
VECTOR STRUCTURAL ENGINEERING, LLC
Jacob S. Proctor, P.E.
Project Engineer
Jul 18, 2017
JSP/kgs
Firm License: COA 26626
651 W. Galena Park Blvd, Ste 1011 Draper, UT 840201 T (801) 990-1775 I F (801) 990-1776 1 www.vectorse.com