PLAN REVIEW FORM
3, y.
5160 N.W. Milner Drive
,�
Port Saint Lucie, FL 34983
scEi N��L
- ' N,
X�'9FDIS`�
Telephone: 772-621-3322
Fax: 772-621-3604
air
Address:
S+
�' LUCIA
Web www.slcfd.com
rnilna
Building Dept. SLC
FMO Permit# B-17-186
Project Name American Freight
BLDG Permit # 1706-0284
Address
7151 South US Hwy 1
City
PSL
Contractor US General Contractors (772) 335-0035
Address 20325E Giffen Avenue City PSL
State FL Zip 34952 Telephone (772)335-0035
Architect/Engineer Michael Anderson Telephone (772) 418-2118
Occupancy Type Mercantile Construction Type IIB Square Feet 20,604
Occupant Load 692 per plans Number of Stories Access Box Required Access Key Switch
AFSPermit Required FA Permit Required FFP Permit
General Notes
1. An electronic copy of the construction documents submitted on a CD is required. The file format shall be .pdf only.
2. All revisions, Including the electronic copy must be received prior to permitting.
3. The Fire Marshal requires 24 hour notice on all Inspections.
4. The respective Building Department shall schedule all final Inspections through the Fire Marshal's Office.
S. Failed inspections require payment of fee priorto rescheduling of further Inspections.
6. Penetrations through rated assemblies shall be of the proper UL design. Design criteria shall be submitted with the construction plans.
7. Fire alarm panels shall be located Indoors within air conditioned space.
B. Plans and construction are subject to corrections In the field to maintain code compliance.
9. Automatic fan shutdown is required for HVAC system/s that exceed 2,000 cfm design capacity.
10. The Installation or Alteration of Fire Sprinklers, Fire Alarms, and Fixed Fire Protection Systems require a separate review and permit.
THE FLORIDA FIRE PREVENTION CODE, 2012 EDITION IS CURRENTLY ENFORCED.
BUILDINGS WITH LIGHT-FRAMETRUSS-TYPE CONSTRUCTION SHALL BE MARKED WITH APPROVED FIREFIGHTER SAFETY
WARNING SIGNS IN ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODES 69A-3.012 AND 69A-60.0081 PRIOR TO RECEIVING
A CERTIFICATE OF OCCUPANCY.
See ueneral Notes Above arm Keauireci Hevisions uetow
1. Automatic fan shutdown is required for HVAC system/s that exceed 2,000 cfm design capacity. Provide a remote test and
inspect appliance equipped with an audible/visual indicator for each HVAC duct smoke detector. HVAC duct detectors shall be
tied into the fire alarm system.
2. The Installation or Alteration of Fire Sprinkler, Fire Alarm Systems require a separate review and permit.
3. Portable fire extinguishers from a licensed contractor are required.
Page —1 of 1❑ Reviewed by Tony Jerger Date 07-28-17