HomeMy WebLinkAboutLOAD CALCULATIONS..... ....... SCANNE BY St. Lucie Cc LOAD CALCULATIONS N (Cooling & Heating) *; ACCA MANUAL N, Commercial Load Calculation v ' Address: UPG FORT PIERCE Designed by: KAMAL HALADI, RE, LEED AP � 801-805 S. KINGS HWY PREMIER CONSULTING ENGI 1.{e(I FT PIERCE, FLORIDA 34945 2799 NW 2nd Ave, H-202, Boca Raron,!}��+ Tel: (954) 675.62351 Fax: is 1) 892., 00 1. DESIGN CONDITIONS (COOLING) ZONE NETWORK ROOM (MINI-SPLR UNIT) Time of Day @3 p.m. Daily Range 16 Latitude 26 Inside db 75 DEG. RH 50% Outside db 91 Coincidentwb 78 D Grains Diff 56.5 TEMP. DIFF 16 Entering wb 67 2. SOLAR RADIATION HEAT GAIN THROUGH GLASS. COOLING LOAD u nt"' Exposure Sq. Ft. Solar Factor Shading and/or Sensible Notes glass factor N 0 x 29 x 1 = 0 NE 0 x 42 x 1 = 0 E 0 x 64 x 1 = 0 SE 0 x 60 x 1 = 0 S 0 x 44 x 1 = 0 SW 0 x 89 x 1 = 0 W 0 x 88 x 1 = 0 NW 0 x 46 x 1 — 0 3. TRANSMISSION GAINS (ENVELOPE) Equivalent or db Exposure Sq. Ft. U Factor Temp Diff Glass all 0 x 1.04 x 16 = 0 Walls N 0 x 0.125 x 15 = 0 NE 0 x 0.125 x 26 0 E 0 x 0.125 x 36 = 0 SE 0 x 0.125 x 34 = 0 S 0 x 0.125 x 23 = 0 SW 0 x 0.125 x 19 = 0 W 85 x 0.125 x 17 = 181 NW 0 x 0.125 x 16 = 0 Doors 0 x 0.56 x 16 = 0 0 x 0 x 16 = 0 Partitions 170 x 0.087 x 16 = 237 Floors x x 16 = 0 x x 16 = 0 Clg/Roof 95 x 0.05 x 35 = 166 RA Ceiling x x = 0 4. TRANSMISSION GAINS (OCCUPANTS, LIGHTS & OTHERS) Latent a. Occupants Number Sensible Latent 1 x 255 = 255 x 255 = 0 1 x 255 = 255 x 255 = 0 b. Lights & Others Wafts Incandescent Lights x 3.4 = 0 Flouresoent Lights 100 x 4.1 = 410 Load Usage N.P.H.P. Btuh Factor Factor Motors x x = x x = Sens Let Usage Appliances 14500 x 100% = 14,500 0 x 100% = 0 0 Other BTUH x 100% = 0 page 1 OF 2 15,749 255 63 70 ATE OF NA%``�c ##fill LOAD CALCULATIONS (Cooling & Heating) Sensible Latent continued .............. ZONE NETWORK ROOM (MINI -SPLIT UNIT) 15,749 255 5. INFILITRATION Hieght= 10 ft Volume = 950 cult AIR Changes Per Hour = 0.05 CFM = 1 CFM 1 x db Temp Diff 16 x 1.1 = 14 CFM 1 x Grains Diff 56.5 x 0.68 = 30 6. SUBTOTAL COOLING LOAD FOR SPACE 15,762 285 7. SUPPLY DUCT HEAT GAIN Gain Factor 0.03 x Line 6 Sensible Gain 15,762 = 473 8. ZONE DESIGN LOAD 16,235 285 This load is used to estimate the cooling CFN Line 8 Sensible Supply Temp. Diff. Cooling CFM 11 16,235 / ( 1.1 x 18 ) = 820 16,235 285 10. TOTAL LOAD ON EQUIPMENT 16,521 BTUH TOTAL LOAD ON EQUIPMENT = 1.4 TON 11. DESIGN CONDITIONS (HEATING) Inside db 72 DEG F. Outside db 45 DEG F. TEMP. DIFF 27 DEG F. 12. TRANSMISSION LOSSES HEATING LOAD Exposure Sq. Ft. U Factor db Temp Diff Windows all 0 x 0.29 x 27 = 0 Walls N 0 x 0.125 x 27 = 0 NE 0 x 0.125 x 27 = 0 E 0 x 0.125 x 27 = 0 BE 0 x 0.125 x 27 = 0 S 0 x 0.125 x 27 = 0 SW 0 x 0.125 x 27 = 0 W 85 x 0.125 x 27 = 287 NW 0 x 0.125 x 27 = 0 Doors 0 0 x 0.56 x 27 = 0 0 0 x 0 x 27 = 0 Partitions x x 27 = 0 Floors x x 27 = 0 Roof x x 27 = 0 Roof/Ceiling 95 x 0.05 x 27 = 128 13. INFILITRATION Hieght= 10 It Volume = 950 cult AIR Changes Per Hour = 0.05 CFM = 1 CFM 0.79166667 x dbTemp Diff 27 x 1.1 = 24 14. SUBTOTAL COOLING LOAD FOR SPACE 439 15. VENTILATION INFILTRATION FROM STEP-13 ABOVE = 1 CFM OAREQ'D= o CFM CFM 0 x db Temp Diff 27 x 1.1 = 0 16. SUPPLY DUCT HEAT LOSS Gain Factor 0.05 x Line 14 Sensible Gain 439 = 22 17. TOTAL HEATING LOAD ON EQUIPMENT 461 page 2 OF 2 APPENDIX C [CE] FORMS FLORIDA BUILDING CODE, ENERGY CONSERVATION CHAPTER C4—COMMERCIAL ENERGY EFFICIENCY Form C402-2014 ALTERATIONS, RENOVATED BUILDING and BUILDING SYSTEMS Climate Zone: 2A Project Name: UPG FORT PIERCE Occupancy type: Address, 801-805 S. KINGS HWY Alteration❑ Renovated Building El Building SystemX City, zip code: FT PIERCE, FLORIDA 34945 Building Permit No.: Builder: Permnfingotfice: FORT PIERCE Owner. BUILDING ENVELOPE INFORMATION (Where changed) Envelope Component Description Requirement Efficiency Location Unit Required Installed Rooll o YP Existing Roof Table C402.1.2 or Table C402.2 SU-factor or 2 R-value Existing Roof refleciancelEmiftance (low slope roofs) EXISii Existing ROOF Table C4022. t.1 2 Solar reflectance, > Thermal emittance Existing Wall type, above grade Existing WALL -Table C402. 1.2 or Table C402.2 <_ U-factor or > R-value Existing Existing Wall, below grade NIA Floor type Existing floor Vertical fenestrations Existing fenestration Table C4023 5 U-factor Existing. s sHGc Existing skylights N/A < U-/actor < SHGC BUILDING SYSTEMS INFORMATION [tor HVAC, service hot water or pool heating, lighting systems, and replacement fenestration (Cl01.4.7)] System Type (describe system) Requirement Efficiency Location Unit Required Installed Air-conditionfng system SPLIT SYSTEM Tables C403.2.3 (1-3, 6-8, 10-11) SEER orEER, 1EER 13 21 Heating system HEAT PUMP Tables C403.2.3(2-6) HSPF or COP AFUE, E, or E 1 1 Ventilationvair handling system NA Tables C403.2.10.1(1-2) Fan power(cbn). Ducts Locaflon:DUCTLESS FluiddesUNIT EXISTING ti Table C403.2.7.1 R-value 6 6 Piping Table C403.2.8 Inches Hot water tA3,4:;A 94411.E EF, E„COP Lighting Space types: (appendf.s1),;� ::y�jr;G1,7�, . ti , ; • Lighting power density EXISTING Fenestrations: Enter Information in BUILDING ENVELO . i OF5 i o ;(�nroe/ �� Other. OFFICE : No 63970 COMPLIANCE IS BYANSYASHRAEfIESNA 90.1 (Submit alternate form or append documents as needed)2 ' l hereby certify that the plans and specifications cover L It a 1ajcu/rlirn are In ccmniiaroe.WN ne Florida Building Code, Energy Conservation. "T • '� p;: _ �� PREPARED BY._KafTlal Halabi, // S <"° R ]-O • `�%\ ��, DATE: (, //� ",•S/(� 1 hereby certify that this building is in compliance with t e He �d._Lj-%-+T.:'�Iri*!e ;L�sserval,nn: OWNER/AGENT. 4�11111111% DATE: Review oI plans and specifications covered by this calculation indicates compliance with the Florida Building Code. Energy Conservation. Before construction is completed, this building will be inspected for compliance in accordance with Section 553.908, F.S. BUILDING OFFICIAL: DATE. FLORIDA BUILDING CODE — ENERGY CONSERVATION, 5lh EDITION (2014) C-C.1