LOAD CALCULATIONS
N
(Cooling & Heating)
*;
ACCA MANUAL N, Commercial Load Calculation v
'
Address:
UPG FORT PIERCE
Designed by:
KAMAL HALADI, RE, LEED AP �
801-805 S. KINGS HWY
PREMIER CONSULTING ENGI 1.{e(I
FT PIERCE, FLORIDA 34945
2799 NW 2nd Ave, H-202, Boca Raron,!}��+
Tel: (954) 675.62351 Fax: is 1) 892., 00
1.
DESIGN CONDITIONS (COOLING)
ZONE
NETWORK ROOM (MINI-SPLR UNIT)
Time of Day
@3 p.m.
Daily Range
16
Latitude 26
Inside db
75 DEG.
RH
50%
Outside db
91 Coincidentwb 78
D
Grains Diff
56.5
TEMP. DIFF
16
Entering wb 67
2.
SOLAR RADIATION HEAT GAIN THROUGH GLASS.
COOLING LOAD
u nt"'
Exposure
Sq. Ft.
Solar Factor
Shading and/or
Sensible
Notes
glass factor
N
0 x
29
x
1
=
0
NE
0 x
42
x
1
=
0
E
0 x
64
x
1
=
0
SE
0 x
60
x
1
=
0
S
0 x
44
x
1
=
0
SW
0 x
89
x
1
=
0
W
0 x
88
x
1
=
0
NW
0 x
46
x
1
—
0
3.
TRANSMISSION GAINS (ENVELOPE)
Equivalent or db
Exposure
Sq. Ft.
U Factor
Temp Diff
Glass
all
0 x
1.04
x
16
=
0
Walls
N
0 x
0.125
x
15
=
0
NE
0 x
0.125
x
26
0
E
0 x
0.125
x
36
=
0
SE
0 x
0.125
x
34
=
0
S
0 x
0.125
x
23
=
0
SW
0 x
0.125
x
19
=
0
W
85 x
0.125
x
17
=
181
NW
0 x
0.125
x
16
=
0
Doors
0 x
0.56
x
16
=
0
0 x
0
x
16
=
0
Partitions
170 x
0.087
x
16
=
237
Floors
x
x
16
=
0
x
x
16
=
0
Clg/Roof
95 x
0.05
x
35
=
166
RA Ceiling
x
x
=
0
4.
TRANSMISSION GAINS (OCCUPANTS, LIGHTS & OTHERS)
Latent
a.
Occupants
Number
Sensible
Latent
1 x
255
=
255
x
255
=
0
1
x
255
=
255
x
255
=
0
b.
Lights & Others
Wafts
Incandescent Lights
x
3.4
=
0
Flouresoent Lights
100
x
4.1
=
410
Load
Usage
N.P.H.P.
Btuh
Factor
Factor
Motors
x
x
=
x
x
=
Sens
Let
Usage
Appliances
14500
x
100%
=
14,500
0
x
100%
=
0
0
Other
BTUH
x
100%
=
0
page 1 OF 2
15,749
255
63 70
ATE OF
NA%``�c
##fill
LOAD CALCULATIONS
(Cooling & Heating)
Sensible
Latent
continued .............. ZONE NETWORK ROOM (MINI -SPLIT UNIT)
15,749
255
5. INFILITRATION
Hieght= 10 ft Volume =
950
cult
AIR Changes Per Hour = 0.05 CFM =
1
CFM 1 x db Temp Diff 16 x
1.1
=
14
CFM 1 x Grains Diff 56.5 x
0.68
=
30
6. SUBTOTAL COOLING LOAD FOR SPACE
15,762
285
7. SUPPLY DUCT HEAT GAIN
Gain Factor 0.03 x Line 6 Sensible Gain
15,762
=
473
8. ZONE DESIGN LOAD
16,235
285
This load is used to estimate the cooling CFN
Line 8 Sensible Supply Temp. Diff.
Cooling CFM
11 16,235 / ( 1.1 x 18 )
=
820
16,235
285
10. TOTAL LOAD ON EQUIPMENT 16,521 BTUH
TOTAL LOAD ON EQUIPMENT =
1.4
TON
11. DESIGN CONDITIONS (HEATING)
Inside db 72 DEG F. Outside db
45
DEG F.
TEMP. DIFF 27 DEG F.
12. TRANSMISSION LOSSES
HEATING LOAD
Exposure Sq. Ft. U Factor
db Temp Diff
Windows all 0 x 0.29
x
27 =
0
Walls N 0 x 0.125
x
27 =
0
NE 0 x 0.125
x
27 =
0
E 0 x 0.125
x
27 =
0
BE 0 x 0.125
x
27 =
0
S 0 x 0.125
x
27 =
0
SW 0 x 0.125
x
27 =
0
W 85 x 0.125
x
27 =
287
NW 0 x 0.125
x
27 =
0
Doors 0 0 x 0.56
x
27 =
0
0 0 x 0
x
27 =
0
Partitions x
x
27 =
0
Floors x
x
27 =
0
Roof x
x
27 =
0
Roof/Ceiling 95 x 0.05
x
27 =
128
13. INFILITRATION
Hieght= 10 It Volume =
950
cult
AIR Changes Per Hour = 0.05 CFM =
1
CFM 0.79166667 x dbTemp Diff 27 x
1.1
=
24
14. SUBTOTAL COOLING LOAD FOR SPACE
439
15. VENTILATION
INFILTRATION FROM STEP-13 ABOVE = 1 CFM
OAREQ'D=
o CFM
CFM 0 x db Temp Diff 27 x
1.1
=
0
16. SUPPLY DUCT HEAT LOSS
Gain Factor 0.05 x Line 14 Sensible Gain
439
=
22
17. TOTAL HEATING LOAD ON EQUIPMENT
461
page 2 OF 2
APPENDIX C [CE]
FORMS
FLORIDA BUILDING CODE, ENERGY CONSERVATION
CHAPTER C4—COMMERCIAL ENERGY EFFICIENCY
Form C402-2014 ALTERATIONS, RENOVATED BUILDING and BUILDING SYSTEMS
Climate Zone:
2A
Project Name: UPG FORT PIERCE
Occupancy type:
Address, 801-805 S. KINGS HWY
Alteration❑ Renovated Building El Building SystemX
City, zip code: FT PIERCE, FLORIDA 34945
Building Permit No.:
Builder:
Permnfingotfice: FORT PIERCE
Owner.
BUILDING ENVELOPE INFORMATION (Where changed)
Envelope Component
Description
Requirement
Efficiency
Location
Unit
Required
Installed
Rooll o
YP
Existing Roof
Table C402.1.2 or
Table C402.2
SU-factor or
2 R-value
Existing
Roof refleciancelEmiftance
(low slope roofs)
EXISii
Existing ROOF
Table C4022. t.1
2 Solar reflectance,
> Thermal emittance
Existing
Wall type, above grade
Existing WALL
-Table C402. 1.2 or Table C402.2
<_ U-factor or
> R-value
Existing
Existing
Wall, below grade
NIA
Floor type
Existing floor
Vertical fenestrations
Existing fenestration
Table C4023
5 U-factor
Existing.
s sHGc
Existing
skylights
N/A
< U-/actor
< SHGC
BUILDING SYSTEMS INFORMATION [tor HVAC, service hot water or pool heating, lighting systems, and replacement fenestration (Cl01.4.7)]
System
Type (describe system)
Requirement
Efficiency
Location
Unit
Required
Installed
Air-conditionfng system
SPLIT SYSTEM Tables C403.2.3 (1-3, 6-8, 10-11)
SEER orEER, 1EER
13
21
Heating system
HEAT PUMP
Tables C403.2.3(2-6)
HSPF or COP AFUE, E, or E
1
1
Ventilationvair handling system
NA
Tables C403.2.10.1(1-2)
Fan power(cbn).
Ducts
Locaflon:DUCTLESS
FluiddesUNIT
EXISTING ti
Table C403.2.7.1
R-value
6
6
Piping
Table C403.2.8
Inches
Hot water
tA3,4:;A 94411.E
EF, E„COP
Lighting
Space types: (appendf.s1),;�
::y�jr;G1,7�, . ti , ;
•
Lighting power density
EXISTING
Fenestrations: Enter Information in BUILDING ENVELO . i OF5 i o ;(�nroe/ ��
Other. OFFICE : No 63970
COMPLIANCE IS BYANSYASHRAEfIESNA 90.1
(Submit alternate form or append documents as needed)2 '
l hereby certify that the plans and specifications cover L It a 1ajcu/rlirn are In ccmniiaroe.WN ne
Florida Building Code, Energy Conservation. "T • '� p;: _ ��
PREPARED BY._KafTlal Halabi, // S <"° R ]-O • `�%\ ��,
DATE: (, //� ",•S/(�
1 hereby certify that this building is in compliance with t e He �d._Lj-%-+T.:'�Iri*!e ;L�sserval,nn:
OWNER/AGENT. 4�11111111%
DATE:
Review oI plans and specifications covered by this
calculation indicates compliance with the Florida Building
Code. Energy Conservation. Before construction is
completed, this building will be inspected for compliance
in accordance with Section 553.908, F.S.
BUILDING OFFICIAL:
DATE.
FLORIDA BUILDING CODE — ENERGY CONSERVATION, 5lh EDITION (2014) C-C.1