ST. LUCIE COUNTY
_ DEPARTMENT OF COMMUNITY DEVELOPMENT
2300 VIRGINIA AVENUE
reference All American FT. PIERCE, FL. 34982.5652 SCANNED
561462-1553 BY
Job #181684 St. Lucie County
DESIGN CERTIFICATION FOR WIND LOAD COMPLIANCE
for the metal bldq. structure only.
This Certification is to be Completed by the design engineer This Certification must be submitted with all applications
fur building permit involving the construction of new residence (single or multl4arnly), residential addition. any accessory structure requiring
a building permit, and any nonresidential structure. This Certification shag not apply to interior renovations (provided that no structural
walls. columns or other similar component is being effected) and certain other minor building permits. For further assistance, please contact
the Building InspeCBDn Office at 462.1553 or 462-2172.
PROJECT NAME
rl
O"lar Use ONLY
STREETADDRESS
/QQ AveoF r<)4M % n5
PR NUMBER
%1 .s
PERMIT NUMBER
33y/0
OCCP, TYPE
CST. TYPE
CERTIFICATION STATEMENT:
CERTIFY THAT, TO THE BEST OF MY KNOWLEDGE AND BELIEF, plans for fne metal bldg_. S�VE
BEEN DESIGNED TO COMPLY WITH THE APPLICABLE STRUCTURAL PORTION OF THE BUILDING"CODES
CURRENTLY ADOPTED AND ENFORCED 13Y ST. LUCIE COUNTY. I ALSO CERTIFY THAT STRUCTURAL ELEMENTS
DEPICTED ON THESE PLANS PROVIDE ADEQUATE RESISTANCE TO THE WIND LOADS AND FORCES SPECIFIED
BY CURRENT CODE PROVISIONS.
DESIGN PARAMETERS AND ASSUMPTIONS USED'(pleaspchedtorcompletethe vocropritebox)
1. STANDARD BUILDING CODE 1997 EDITION XX ASCE 7.95 OTHER (SPECIFY)
BUILDING DESIGN IS (CHECK ONE) ENCLOSED 22 PARTIALLY ENCLOSED _ OPEN BUILDING
BUILDING HEIGHT: 12 FT 4, WIND SPEED USED IN BUILDING DESIGN: 110 MPH
WIND EXPOSURE CLASSIFICATION IREFER TO EXPOSURE TABLES IN ayIIDNO CODA IDENTIFIED IN LING art:
AVERAGE WIND VELOCITY PRESSURE ON £XTER)OR FACES OF STRUCTURE:
PEAK WIND VELOCITY PRESSURE ON EXTERIOR FACES OF STRUCTURE:
IMPORTANCE(USE FACTOR (OBTAIN FROM BUILDING CDOE). 1.0
N/A
q=25.4131PSF
N/A PSI,
9. LOADS: FLOOR N/A PSF ROOFIDFAD: 4 PSF ROOF/LrVE: 20 PSF
1D. WERE SHEAR WALLS CONSIDERED FOR STRUCTURE (CHECK ONE) YES NO XXIi NO, why? (attach
explalnatlon)
braced frames were provided
11 IS A CONTINUOUS LOAD PATH PROVIDED (CHeCK ONJ YES _Xx NO ^ If NO, why? (attach explainetion)
12. ARE COMPONENT AND CLADDING DETAILS PROVIDED (CHECK ONE) YES ?
axplaination)
13. MINIMUM SOIL BEARING PRESSURE: N/A PSF
NO_ If NO, why? (attach
AS VVITNESSED BY MY SEAL, I HEREBY CERTIFY THAT THE INFORMATION INCLUDED
IS TRUE AND CORRECT, TO THE BEST OF MY KNOWLEDGE AND BELIEF.
NAME: Eric E. Masterson CERTIFICATION NO: 33579
DATE: 9-3-99
� MAR-21-00 TUE 04:50 PM DqV LD MILLER & ASSOC. 5616974105 P. 03
David MY111er and Associates, P.A
David Millcr, A.I.A., NCARB
February 29, 2000
St. Lucie County
Dept. of Community Development
2300 Virginia Avenue
Ft. Pierce, FL 34982
RE: PGA Golf Club
Maintenance Facility Addition
LZPeCt , fi#19_2=0904_.50 1
Foundation Modification
To Whom It May Concern:
The footings for the above referenced project have been modified to correspond with field
conditions and coordination with the pre-engineered structure. Specifically, the spread footings
have been modified to monolithic type and the structure was rotated to accommodate fabrication
inconsistencies. A copy of the plan indicating the extent of the foundation modification is
attached. The revised pre-engineered building plans have been submitted under separate cover
by the General Contractor. The footings and slab as installed are acceptable.
Please notify me if you have any questions or concerns. Thank you,
Sincerely,
11 , I.A.
''l�.ti►'�rm
attachment
cc: Phil Morgan
A,rcbitecture • Engineering • Planning • Construction Management • Interior Design
2090 Palm Beach Lakes Blvd., Suite 205 West Palm Beach, Florida 33409
(561) 697-4700 • (561) 697-4105 Fax
�. . •..... ++ u AA LGAGJ 1]Ayll., ouice :uo west Falm Beach, Florida 33409
(561) 697-4700 • (561) 697-4105 Fax
DRM/sjh
attachment
cc: Phil Morgan
Architecture • ingineerlug • Planning • Construction Management • Interior Design
2090 Palin Beach Lakes Blvd., Suite 205 West Palm Beach, Florida 33409
(561)697-4700•(561)697-4105 Fax
I
ST.IUCIE COUNTY FIRE DISTRICT
BUREAU OF FIRE PREVENTION
PLAN REVIEW
2400 Rhode Island Ave Telephone (561)-462-2312
Fort Pierce, Florida 34950 Fax:: (561)-462-2323
TYPE OF PERMIT
( ) New Construction ( ) Tenant Improvement ( X ) Addition ( ) Renovation/alteration ( ) Shell Only
Jurisdiction:
St Lucie County
Occupancy:
PGA North Maintenance Office
Address:
8100 Plantation Lakes Dr
Contractor:
Mosley & Son Construction
Contractors address: 1400 SE Monterey
Architect/Engineer: David Miller & Associates
Building owner:
PGA Reserve Inc
Occupancy type: Business
Gross sq. ft. 1500 sq fl
Occupant load:
Construction type (NFPA-220) Type:
F.P.B. B-99-140
Building Dept. 99090450
Number of stories: 1
Phone # 561-287-6962
City: Stuart, FL Zip: 34994
Phone #: 561-655-1775
Review date: 9-28-99
Automatic sprinklers:
Net sq. ft.
Based on:
SBCCI: Type:
NOTE
1. All revisions must be in compliance before the final inspection, or so noted.
2. The Fire Marshal requires 24 hr. notice on all inspections.
3. The respective Building Department shall schedule all final inspections through the Fire Marshal's office.
4. Failed inspections require payment of fee prior to scheduling of any further inspections.
5. Permit fees are required to be paid in full prior to any inspections.
6. A copy of the required revision/s have been transmitted to the Architect O Contractor O Yes O No ( )
Revisions Required
1. Provide a 2A-1 OBC rated fire extinguisher for every 75' of travel distance.
Reviewed By: Date: September 28, 1999 /
Tony Liento
0
DE&T
DUNK;LDERGER ENGINEERING & TESTING, INC.
Project Name: Golf Club At The Reserve Report Date: 10-29-99
Office Addition to the Maintenance Building
Client Name: Robert F. Fromm & Associates, Inc. /0elrA/ j 1t 9Yo 90,�KJ-0
590 NW Peacock Loop, Suite 9 Project No.: 99-10-663
Port St. Lucie, FI 34986 Date Tested: 10-25-99
Technician Initials: SM
Attn: Mr. Robert F. Fromm Progress Report No.: 5 (Sheet I of 3)
IAborato `.Proctor.;
, Eie1d
Tests, ` ` v
Test
No.
Probe
Depth
in
Maximum
Dry Density
c
Optimum
Moisture
%
Dry
Density
c
Cone
Resistance'
is
Moisture
%
Minimum
Required
Compaction
%
Percent
Maximum
Density
Test
Result
1
12
109.0
12.0
108.4
- - -
6.3
95
99.4
Pass
2
12
109.0
12.0
109.7
- - -
7.1
95
100+
Pass
3
12
109.0
12.0
107.7
- - -
7.5
95
98.8
Pass
Type of Field Density Test: (X) ASTM D 2922 ( ) ASTM D 2937
Minimum Required Compaction Based on: (X) AASHTO T-180 (ASTM D 1557) ( ) AASHTO T-99 (ASTM D 698)
Compaction percent estimated from cone penetrometer reading obtained with a Brainard-Kilman Model S-214 hand-held cone penetrometer.
Test
No.
s6il
T e
Elevation
c _
- r �- -Test location..Oftce`Aiidttionlo'1VIaintim it Buildi'--
1
1
0-12
20' south of northwest corner
2
1
0-12
35' east and 20' south of northwest corner
3
1
0-12
20' south of northeast comer
Elevation Referenced to: () NGVD
1
Structural Fill
2
Final Grading Fill
3
Mass Grading Fill
4
Utility Backfill - Sanitary
5 -
-Utility Backfill - Water
6
Utility Backfill - Storm
7
Roadway Subgrade
8
Stabilized Subgrade
9
Base Course
10
Other:
cc:
( ) MSL QEA1 Other
Client ... (1) e4;
NOV 0 2 1999
St. Lucie County Public Works
Inches below top of final
I
-' 14 David Miller and Associates, P.A
e
February 29, 2000
St. Lucie County
Dept. of Community Development
2300 Virginia Avenue
Ft. Pierce, FL 34982
RE: PGA Golf Club
Maintenance-Eacility Addition
Permit! _1069045q ram,.
Foundation Modification
To Whom It May Concern:
David Miller, A.I.A., NCARB
The footings for the above referenced project have been modified to correspond with field
conditions and coordination with the pre-engineered structure. Specifically, the spread footings
have been modified to monolithic type and the structure was rotated to accommodate fabrication
inconsistencies. A copy of the plan indicating the extent of the foundation modification is
attached. The revised pre-engineered building plans have been submitted under separate cover
by the General Contractor. The. footings and slab as installed are acceptable.
Please notify me if you have any questions or concerns. Thank you.
Sincerely,
i
D Il , A.I.A.
DRM/sjh
attachment
cc: Phil Morgan
Architecture • Engineering • Planning • Construction Management • Interior Design
2090 Palm Beach Lakes Blvd., Suite 205 West Palm Beach, Florida 33409
(561) 697-4700 • (561) 697-4105 Fax
I
a
David Miller and Associates, P.A
David Miller, A.I.A., NCARB
April 10, 2000
St. Lucie County
Dept. of Community Development
2300 Virginia Avenue
Ft. Pierce, FL 34982
RE: PGA Golf Club
Maintenance Facility Addition
Permit # 99-090450
Insulation
To Whom It May Concern:
The insulation provided by the metal building fabricator (R-11) and installed by the contractor is
acceptable. The insulation is vinyl faced insulation typically used for pre-engineered metal
buildings. I have reviewed the installation and have found this to be acceptable.
Please notify me if you have any questions or concerns. Thank you.
Sincerely
avid R. Miller, A.I.A.
DRM/sjh
Architecture • Engineering •Planning • Construction Management • Interior Design
2090 Palm Beach Lakes Blvd., Suite 205 West Palm Beach, Florida 33409
(561)697-4700•(561)697-4105 Fax
i
`Whole Building Performance Method for Commercial Buildings
ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION
Florida Department of Community Affairs
FLA/COM-97 Version 2.2
PROJECT NAME —PGA RESERVE FACILITY
ADDRESS: PORT ST. LUCIE, FL.
OWNER:
,AGENT:
PGA
BUILDING TYPE: _Service Establishments
.CONSTRUCTION CONDITION: Existing Building
DESIGN COMPLETION: _Addition
CONDITIONED FLOOR AREA: 1340
MAX. TONNAGE OF EQUIPMENT PER SYSTEM:
COMPLIANCE CALCULATION:
METHOD A
-----------------
A. WHOLE BUILDING
PRESCRIPTIVE REQUIREMENTS:
LIGHTING
15"
Form 400A-97
PERMITTING OFFICE:
Stuart
CLIMATE ZONE: 8
PERMIT NO:
JURISDICTION NO: 531400
NUMBER OF ZONES: 1
5
DESIGN CRITERIA
35.08 100.00
RESULT
PASSES
LIGHTING CONTROL REQUIREMENTS PASSES
HVAC EQUIPMENT
COOLING EQUIPMENT
1. SEER 12.00 10.00 PASSES
HEATING EQUIPMENT
1. Et 12.00 N/A
AIR DISTRIBUTION SYSTEM INSULATION REQUIREMENTS
1. Conditioned Space 6.00 0.00 N/A
REHEAT SYSTEM TYPES USED
NO REHEAT SYSTEM is USED
WATER HEATING EQUIPMENT
PIPING INSULATION REQUIREMENTS
----------------------------------------------------------------------------
COMPLIANCE CERTIFICATION:
I hereby certify that the plans and
specifications covered by is calcu-
lation are in'complian ith the
Florida Energy E c ode.
PREPARED Y:
DATE: AU�G 2
I hereby certify that this building is
in compliance with the Florida Energy
Efficiency Code.
OWNER/AGENT:
DATE:
Review of the plans and specifica-
tions covered by this calculation
indicates compliance with the
Florida Energy Efficiency Code.
Before construction is completed,
this building will be inspected
for compliance in accordance with
Section 553.908, Florida Statutes.
BUILDING OFFICIAL:
DATE:
I hereby certify(*) that the system design is in compliance with the Florida
Energy Efficiency Code.
` SYSTEM DESIGNER
ARCHITECT :
MECHANICAL:
REGISTRATION/STATE
PLUMBING
ELECTRICAL:
LIGHTING
(*) Signature is required where Florida law requires design to be performed
by registered design professionals. Typed names and registration numbers may
be used where all relevant information is contained on signed/sealed plans.
BUILDING ENVELOPE SYSTEMS
COMPLIANCE
CHECK
401------- GLAZING --ZONE 1------------------------------------------------
v-
•Elevation Type U SC VLT Shading
Area(Sgft)
----------
------------------------ ---- ---- ---- --------------
North Commercial 1.26 .80 .20 None
64
'East Commercial 1.26 .80 .20 None
32
Total Glass Area in Zone 1 =
96
Total Glass Area =
96
402.------WALLS--ZONE 1------------------------------------------------
---
Elevation Type U Insul R
Gross(Sgft)
----------------------------------------- ----- -------
-----------
North Mtl Bldg wall/R-11 Batt .084 it
670
East Mtl Bldg wall/R-11 Batt .084 it
200
West Mtl Bldg wall/R-11 Batt .084 11
200
Total Wall Area in Zone 1 =
1070
Total Gross Wall Area =
1070
403.------DOORS--ZONE 1------------------------------------------------
---
Elevation Type U
-----
Area(Sgft)
----------
---------------------------------------------------
North 1-3/4 Steel Door -Solid Urethane foam cc 0.40
21
Total Door Area in Zone 1 =
21
Total Door Area =
21
404.------ROOFS--ZONE 1------------------------------------------------
---
Type Color U Insul R
------ ------------
Area(Sgft)
----------
------------------------------------
Sngl Ply/2"Iso/2" Conc/Mtl Deck Medium .065 14
1340
Total Roof Area in Zone 1 =
1340
Total Roof Area =
1340
405------- FLOORS -ZONE 1------------------------------------------------
---
Type Insul R
-------
Area(Sgft)
----------
------------------------------------------------
Slab on Grade/Insulated 10
1340
Total Floor Area in Zone 1 =
1340
Total Floor Area =
1340
406.------INFILTRATION --------------------------------------------------
---
CHECK
Infiltration Criteria in 406.1.ABCD have been met.
MECHANICAL SYSTEMS
CHECK
------------------------------------------------------------ -----
HVAC load sizing has been performed. (407.1.ABCD)
407------- COOLING SYSTEMS----------------------------------------------- ---
Type No Efficiency IPLV Tons
---------------------------- ------------- -------------------
1. Split System 1 12 12 5.00
408.------HEATING SYSTEMS----------------------------------------------- ---
Type No Efficiency BTU/hr
-------------------------------- ---------------------------
1. Electric Resistance 1 12 7500
409------- VENTILATION --------------------------------------------------- ---
CHECK
Ventilation Criteria in 409.1.ABCD have been met.
410.-----AIR DISTRIBUTION SYSTEM---------------------------------------- ---
CHECK
------------------------------------------------------------------I----- ---
Duct sizing and design have been performed. (410.1.ABCD)
AHU Type Duct Location R-value
----------------------------------------------------------------
1. Air Conditioners Conditioned Space 6
CHECK
------------------------------------------------------------- ----
Testing and balancing will be•performed. (410.1.ABCD)
411.-----PUMPS AND PIPING -ZONE -----------------------------------------
Basic prescriptive requirements in 411.1.ABCD have been met.
PLUMBING SYSTEMS
-411.-----PUMPS AND PIPING -ZONE 1
Type R-value/in Diameter Thickness
---------------------------------------------------
1. Circulating 4 .75 2
412------ WATER HEATING SYSTEMS -ZONE 1---------------------------------- ---
Type Efficiency StandbyLoss InputRate Gallons
ELECTRICAL SYSTEMS
CHECK
413------ ELECTRICAL POWER DISTRIBUTION---------------------------- ----- ---
Metering criteria in 413.1.ABCD have been met.
414.-----MOTORS --------------------------------------------------- ----- ---
Motor efficiencies in 414.1.ABCD have been met.
415.-----LIGHTING SYSTEMS -ZONE 1--------------------------------------- ---
Space Type No Control Type 1 No Control Type 2 No Watts Area(Sgft)
---------- ----------------- ----------------- --- ------ ----------
Conference 1 On/Off 2 None 0 500 1340
Total Watts for Zone 1 = 500
Total Area for Zone 1 = 1340
Total Watts = 500
Total Area = 1340
CHECK
Lighting criteria in 415.1.ABCD have been met.
------------------------------------------------------------------ -
16. Operation/maintenance manual will be provided to owner.(102.1)
----------------------------------------------------------------------------