HomeMy WebLinkAboutTEST RESULTSTESTING APPLICATION STANDARD (TAS) 105 NOV 2 i 2018
APPENDIX TAS 105-A oua�y, P�ffA�
FIELD WITHDRAWAL RESISTANCE TEST RESULTS
GENERAL INFORMATION: SCANNED
Job Name: Hartman Apartments AN
Job Address: 1215 Hartman Road St.Lucie CoUntY
Fort Pierce, FL
Job Site Contact: JA Taylor. Inc. (772) 466-4040
TESTING AGENCY/EQUIPMENT INFORMATION:
Note: The undersigned acknowledges that all testing has been conducted and
results have been reported in compliance with TAS 105 Appendix T105-A
Testing Agency: Cleary Inspection Services, Inc.
Address: 1017 North "H" Street
Lake Worth, FL 33460
Telephone: (561) 722 - 9881
Fax: (561) 582 - 8039
Email: clearyinspections@kcwand.com
Representative Name: Katherine I. Cleary
Title: Inspector
Test Apparatus: COMTEN MODEL # DFG2W2000, SERIAL # 20606019
BU1LDING/ROOF SYSTEM INFORMATION: Roof "A"
Approx.
Roof Area Height: Height: =
10 ft.
Roof Area Dimensions: Length: =
66 ft.
Second largest dim.: =
45 ft.
Total roof area: =
2187 ft z
Perimeter width: =
4 ft.
Perimeter area: =
420 ft.'
Comer area: =
428 ft.'
Parapet Height: =
N/A ft.
BUILDING/ROOF SYSTEM INFORMATION: Roof "B" .
Approx.
Roof Area Height: Height: =
10 ft.
Roof Area Dimensions: Length: =
28 ft.
Second largest dim.: =
14 ft.
Total roof area: =
392 ft.,
Perimeter width: =
3 ft.
-- - — Perimeter area: =
180 ft 2
Comer area: =
96 ft.2
Parapet Height: =
N/A ft.
i
Hartman Apartments Cleary Inspection Service, Inc.
1215 Hartman Road Tel. (561) 722-9881, Fax (561) 582-8039
Fort Pierce, FL Email: clearyinspections@kcwand.com
FASTENER INSTALLATION INFORMATION: Roofs "A" & "B"
Is the fastener a self driller? Yes
Tool: Rigid 18v 0-1800 rpm's
Fastener type: #14
Fastener Manufacturer: OMG
TEST INFORMATION: AREA "A"
Test Date:
Number of Test Conducted
"Note the Location of all tests on 'Building Information', attached.
11/5/2013
13
FIELD WITHDRAWAL RESISTANCE TEST RECORDING SHEET
Deck:* See TAS 105-11 to determine number of tests Wood
AREA "A"
SAMPLE NO.
PLAN IDENTIFIER
INITIAL FAILURE
LOAD
FIELD
PERIMETER
CORNER
1
Tl
300
X
2
T2
330
,y
3
T3
330
X
4
T4
320
X
5
T5
350
X
6
T6
265
X
7
T7
305
X
8
T8
315
X
9
T9
350
X
10
T10 _
330
X
11
T11
315
X
12
T12
330
X
13
TO
275
X
STATISTICAL ANALYSIS: AREA "A"
No. of Tests
T Estimator
Mean Failure Load:
Sample Standard Deviation:
Minimum -Characteristic Resistance Force:
n=
13
t' =
2.179
F=
316.5 lbf
SF=
24.5lbf
F'=
301.6lbf
E
Hartman Apartments
1215 Hartman Road
Fort Pierce, FL
Cleary Inspection Senice, Inc -
Tel. (561) 722-9881, Fax (561) 582-8039
Email: clearyinspections@kcwand.com
kcwand.com
TEST INFORMATION: AREA "B"
Test Date: 11/5/2013
Number of Test Conducted 4
*Note the Location of all tests on 'Building Information', attached.
FIELD WITHDRAWAL RESISTANCE TEST RECORDING SHEET
Deck:- See TAS 105-11 to determine number of tests Wood
AREA "B"
SAMPLE NO.
PLAN IDENTIFIER
INITIAL FAILURE
LOAD
FIELD
PERIMETER
CORNER
1
Tl
280
X
2
T2
250
X
3
T3
300
X
4
T4
360
X
STATISTICAL ANALYSIS: AREA "B"
No. of Tests
T Estimator
Mean Failure Load:
Sample Standard Deviation:
Minimum -Characteristic Resistance Force:
Sincerely,
Cleary Inspections Service, Inc.
Katherine I. eary
Miami -Dade Lab Certification No. 16.0211.02
n=
4
t' =
3.182
F=
297.5lbf
SF=
403lbf
F'=
233.31bf
R.N. Sailappan, P.E. �l!
Florida Registration No. 46696
3
Cleary Inspection Service, Inc.
Telephone (561) 722-9881
Fax (561) 582-8039
Email: kc@kcwand.com
Notes:
1. Use of the results herein to determine the required number of
fasteners for insulation attachment or an acceptable anchor or base
sheet fastener spacing, as outlined in TAS 117, shall utilize the
minimum characteristic resistance for (F') determined in compliance
with Section 9 of TAS 105. No margin of safety shall be applied to
field withdrawal resistance test results determined in compliance with
TAS 105.
2. A safety factor of 2 to 1 shall be applied to all results of laboratory
testing.
3. The following pages shall be completed for each roof area and
included with all Field Withdrawal Resistance Test Recording Sheets.
Hartman Apartments — Roof Areas "A" & °B"
1215 Hartman Road
Fort Pierce, FL
Test Date: 11/5/2018
Roof Area Building and Parapet Heights
(If no parapet exists. "N/A")
Roofs "A" & "B"
NIA
10,
Ground
Level
Page 4
Cleary Inspection Service, Inc.
Tel. (561) 722-988, Fax (661) 582-8039
Email: clearyinspections@kcwand.com
Hartman Apartments — Roof "A" & "B"
1215 Hartman Road
Fort Pierce, FL
Test Date: 11/5/2018
Tt
28'
T2
T3
6'
Shingle Roof
T4
Not in test
12'
Shingle Roo
Not in test
16'
Shingle Roo
Not In test
26' T1
9'
18'
T2
TG T7
T5 T8
T10 T11
f3'
T13 3' I
34'
9'
T9
Not in test
Shingle Roof
Not in test
Shingle Roof
Not in test
Shingle Roof
Not in test
Shingle Roof
Not in test
Shingle Roof
Not in test
S41
NOT DRAWN TO SCALE
Drawings & measurements are approximate representation of field layout
Page 5
CERTIFICATE_OF CALIBRATION
TRACEABLE TO THE UNITED STATES NATIONAL INSTITUTE OF STANDARDS AND TECHNOLOGY
AND PERFORMED IN ACCORDANCE WITH IS010012-2003
THIS DEVICE IS CERTIFIED TO BE WITHIN +/- 0.5% OF FULL SCALE READING AT EACH TEST POINT AT
THE TIME OF SHIPMENT
CERTIFICATE NUMBER: 25521 CALIBRATION DATE: 10/8/2018
�rrt� .%��� w� rumtft IrvrCKlvw,lluN
I
MODEL #: DFG2W2000
CUSTOMER: CLEARY INSPECTION SERVICE INC.
CALIBRATION DATA
APPLIED EXPECTED
VALUE VALUE
RUN
(LB) (LB)
(LB)
0.00 0.00
0.000
100.00
400.00 400.00
398.000
600.00
j 800.00 800.00
798.000
1000.00
i
1200.00 1200.00
1199.000
1400.00
i 1600.00 1600.00
1603.000
1800.00
2000.00 2000.00
2005.000
i CALIBRATION EQUIPMENT USED �-
SERIAL#1:
11706016 SERiALa2:
i CAL EQUIP:
COMTEN INDUSTRIES load cell CNR EA, SIN
CNR EA
11706016 was calibrated at ComTen Industries
following to ASTM E-74. The uncertainty is 2
CAL DATE:
Lbf. Report No: 20300
6/122017
i
;
SERIAL #: 20606019
CUSTOMER#: CLE33460
FULL
AVERAGE
SCALE
(LB)
ERROR
0.000
0.000%
398.000
-0.100%
798.000
•0.100% '
1199.000
-0.D50%
1603.000
0.150%
2006.D00
0.300%
I
I THIS EQUIPMENT IS CERTIFIED TRACEABLE TO THE UNITED STATES NATIONAL INSTITUTE OF STANDARDS AND TECHNOLOGY. '
CONDITIONS ---.--"--"— VALIDATION � -- —
TEMPERATURE 69.5T r
RELATIVEHUMIDITYc- -32% - - - CALIBR.",71 10N. _ -
PERFORMED-m==z'^"-'�
AS FOUND NOTES: (' Indicates that the part was out of tolerance) BY: MG 7 -
Calibration not valid without CERTIFIED stamp and initials
6405-49th Street North, Pinellas Park, FL 33781-5724 * 727-520-1200 F FAX 727-520-0299
E-Mail: sales@com-ten.com ' Web: www.com-ten.com
SC 0011
St \'uc\eC
RECEIVED
NOV 2 7 2018
TESTING APPLICATION STANDARD (TAS) No. 10LLucie County, Pertnittlng
APPENDIX TAS 105-A
FIELD WITHDRAWAL RESISTANCE TEST RESULTS
GENERAL INFORMATION:
Job Name:
Job Address:
Job Site Contact:
Hartman Apartments
1215 Hartman Road
Fort Pierce, FL
JA Taylor, Inc. (772) 466-4040
TESTING AGENCY/EQUIPMENT INFORMATION:
Note: The undersigned acknowledges that all testing has been conducted and
results have been reported in compliance with TAS 105 Appendix T105-A
Testing Agency:
Address:
Telephone:
Fax:
Email:
Representative Name:
Title:
Cleary Inspection Services, Inc.
1017 North "H" Street
Lake Worth, FL 33460
(561) 722 - 9881
(561) 582 - 8039
clearyinspections@kcwand.com
Katherine I. Cleary
Inspector
Test Apparatus: COMTEN MODEL # DFG2W2000, SERIAL # 20606019
BUILDING/ROOF SYSTEM INFORMATION: Roof "A"
Approx.
Roof Area Height:
Height: =
10 ft.
Roof Area Dimensions:
Length: =
66 ft.
Second largest dim.: =
45 ft.
Total roof area: =
2187 R°
Perimeter width: =
4 ft.
Perimeter area: =
420 ft 2
Corner area: =
428 ft.'
Parapet Height: =
N/A ft.
BUILDING/ROOF SYSTEM INFORMATION: Roof'B"
Approx.
Roof Area Height:
Height: =
10 ft.
Roof Area Dimensions:
Length: =
28 ft.
Second largest dim.: =
14 ft.
Total roof area: =
392 R.'
Perimeter width: =
3 ft.
Perimeter area: =
180 ft.'
Comer area: =
36 ft'
Parapet Height: =
N/A ft.
Hartman Apartments
1215 Hartman Road
Fort Pierce, FL
Cleary Inspection Service, Inc.
Tel. (561) 722-9881, Fax (561) 582-8039
Email: clearyinspections@kcwand.com
FASTENER INSTALLATION INFORMATION: Roofs "A" & "B"
Is the fastener a self driller? Yes
Tool: Rigid 18v 0-1800 rpm's
Fastener type: 414
Fastener Manufacturer: OMG
TEST INFORMATION: AREA "A"
Test Date: 11/5/2013
Number of Test Conducted 13
*Note the Location of all tests on 'Building Information', attached.
FIELD WITHDRAWAL RESISTANCE TEST RECORDING SHEET
Deck:* See TAS 105-11 to determine number of tests Wood
AREA "A"
SAMPLE NO.
PLAN IDENTIFIER
INITIAL FAILURE
LOAD
FIELD
PERIMETER
CORNER
1
Tl
300
X
2
T2
330
X
3
T3
330
X
4
T4
320
X
5
T5
350
X
6
T6
265
X
7
T7
305
X
8
T8
315
X
9
T9
350
X
10
T10
330
X
11
T11
315
X
12
T12
330
X
13�71
T13
275
X
STATISTICAL ANALYSIS: AREA "A"
No. of Tests n = 13
it Estimator t' = 2.179
Mean Failure Load: F= 316.5 lbf
Sample Standard Deviation: SF= 24.5 lbf
Minimum -Characteristic Resistance Force: F'= 301.6 lbf
2
Hartman Apartments
1215 Hartman Road
Fort Pierce, FL
Cleary Inspection Service, Inc.
Tel. (561) 722-9881, Fax (561) 582-8039
Email: clearyinspections@kcwand.com
TEST INFORMATION: AREA "B"
Test Date: 11/5/2013
Number of Test Conducted 4
*Note the Location of all tests on 'Building Information', attached.
FIELD WITHDRAWAL RESISTANCE TEST RECORDING SHEET
Deck:* See TAS 105-11 to determine number of tests Wood
AREA "B"
SAMPLE NO.
PLAN IDENTIFIER
INITIAL FAILURE
LOAD
FIELD
PERIMETER
CORNER
1
TI
280
X
2
T2
250
X
3
T3
300
X
4
T4
360
X
STATISTICAL ANALYSIS: AREA "B"
No. of Tests
T Estimator
Mean Failure Load:
Sample Standard Deviation:
Minimum -Characteristic Resistance Force:
Sincerely,
Cleary Inspections Service, Inc.
Katherine I. eary
Miami -Dade Lab Certification No. 16.0211.02
n=
4
t' =
3.182
F=
297.5lbf
SF=
4031bf
F'=
233.3lbf
eu nfarg
R.N. Sailappan,
Florida Registration No. 46696
3
Cleary Inspection Service, Inc.
Telephone (561) 722-9881
Fax (561) 582-8039
Email: kc@kcwand.com
Notes:
1. Use of the results herein to determine the required number of
fasteners for insulation attachment or an acceptable anchor or base
sheet fastener spacing, as outlined in TAS 117, shall utilize the
minimum characteristic resistance for (F') determined in compliance
with Section 9 of TAS 105. No margin of safety shall be applied to
field withdrawal resistance test results determined in compliance with
TAS 105.
2. A safety factor of 2 to 1 shall be applied to all results of laboratory
testing.
3. The following pages shall be completed for each roof area and
included with all Field Withdrawal Resistance Test Recording Sheets.
Hartman Apartments — Roof Areas "A" & "B"
1215 Hartman Road
Fort Pierce, FL
Test Date: 11/5/2018
Roof Area Building and Parapet Heights.
(If no parapet exists, "N/A")
Roofs "A" & "B"
N/A
10,
Ground
Level
Page 4
Cleary Inspection Service, Inc.
Tel. (561) 722-988, Fax (561) 582-8039
Email: clearyinspections@kcwand.com
Hartman Apartments — Roof "A" & "B"
1215 Hartman Road
Fort Pierce, FL
Test Date: 11/5/2018
Ti
Shingle Roof
Not in test
28' T2
T3
Shingle Roof
Not in test
Shingle Roof
T4
Nal in test
12'
Shingle Roof
IS' 40'
Not in test
Shingle Raaf
16'Shingle Roof Jn
Not In test
No[ in test
401
26' T1
9'
Shingle Roof
18,
' 2'
Not in test
1
T2
T3
28,
10'
i0�
T7
T9
Shingle Roof
TO
Not in test
10'
14' T4
T5
T8
40'
17'
17'
T10
T11
T12 Not in test
10'
3'
10'
T13
3'
3' 22'
34'
9'
28'
NOT DRAWN TO SCALE
Drawings & measurements are approximate representation of field layout
Page 5
CERTIFICATE OF CALIBRATION
TRACEABLE TO THE UNITED STATES NATIONAL INSTITUTE OF STANDARDS AND TECHNOLOGY
AND PERFORMED IN ACCORDANCE WITH IS010012-2003
THIS DEVICE IS CERTIFIED TO BE WITHIN +/- 0.5% OF FULL SCALE READING AT EACH TEST POINT AT
THE TIME OF SHIPMENT
CERTIFICATE NUMBER: 25521 CALIBRATION DATE: 10/812018
PART AND CUSTOMER INFORMATION
MODEL#: DFG2W2000
CUSTOMER: CLEARY INSPECTION SERVICE INC.
SERIALM 20606019 i
CUSTOMER#: CLE33460
! CALIBRATION DATA
I APPLIED EXPECTED
VALUE VALUE
(LB) (LB)
RUN1
(LB)
AVERAGE
(LB)
FULL
SCALE
ERROR
0.00 0.00
0.000
O.00D
0.000 %
100.00
(
400.00 400.00
398.000
398.000
-0.100%
600.00
800.00 800.00
798.000
798,000
-0.100
1000.OD
! 1200.00 1200.00
1199.000
1199.000
-0.0500/.
1400.00 !
i 1600.00 1600.00
1603.000
1603.000
0.150%
1800.00
2000.00 2000.00
2006.000
2006.00
0.300%
CALIBRATION EQUIPMENT USED
'
SERIAL#1: 11706016
SERIAL#2:
CAL EQUIP: COMTEN INDUSTRIES load cell CNR EA, SIN
1 CNR EA 11706016 was calibrated at ComTan Industries
following to ASTM E-74. The uncertainty is 2
i
CAL DATE: Lbf. Report No: 20300
( 611212017
-
f THIS EQUIPMENT IS CERTIFIED TRACEABLE TO THE UNITED STATES NATIONAL INSTITUTE OF STANDARDS AND TECHNOLOGY
CONDII TIONS
VALIDATION
69.5'F
_TTEMPERATURE
CALIBRATIONPERFORMED
RELATIVE HUMIDITY: 32 %
AS FOUND NOTES: (' Indicates that the part was out of tolerance)
BY: MG
1
Calibration not
valid without CERTIFIED stamp and initials
6405-49th Street North, Pinellas Park, FL 33781-5724 " 727-520-1200 " FAX 727-520-0299
E-Mail: sales@com-ten.com , Web: www.com-ten.com
r
TESTING APPLICATION STANDARD (TAS) No. 105-11
APPENDIX TAS 105-A
FIELD WITHDRAWAL RESISTANCE TEST RESULTS
GENERAL INFORMATION:
Job Name:
Job Address:
Job Site Contact:
Hartman Apartments
1215 Hartman Road
Fort Pierce, FL
JA Taylor Roofin¢, Inc. (772) 466-4040
TESTING AGENCY/EQUIPMENT INFORMATION:
Note: The undersigned acknowledges that all testing has been conducted and
results have been reported in compliance with TAS 105 Appendix T105-A
Testing Agency:
Cleary Inspection Services, Inc.
Address:
1017 North "H" Street
Lake Worth, FL 33460
Telephone:
(561) 722 - 9881
Fax:
(561) 582 - 8039
Email:
clearyinspections@kcwand.com
Representative Name:
Katherine I. Cleary
Title:
Inspector
Test Apparatus: COMTEN MODEL # DFG2W2000, SERIAL # 20606019
BUILDING/ROOF SYSTEM INFORMATION: Roof "A"
Roof Area Height: Height:
Roof Area Dimensions: Length:
Second largest dim.:
Total roof area:
Perimeter width:
Perimeter area:
Corner area:
Parapet Height:
BUILDING/ROOF SYSTEM INFORMATION: Roof "B"
Roof Area Height: Height:
Roof Area Dimensions: Length:
Second largest dim.: '
Total roof area:
Perimeter width:,,.,
Perimeter area: '
Corner area:
Parapet Height: .
SCgNNS
St tu /ern 0
Approx.
10 ft.
66 ft.
= 45 ft.
2187 ft2
4 ft.
420 ft 2
428 ft.2
i Approx.
10 ft.
' 28 ft.
-14 ft.
_ + t392 ft.�
180-tR.=
36'ff.2 '
. 1 •1
_ i •
SHOP DRAWING / SUBMITTAL RE'
It APPROVED ❑ APPROVED AS NOTED
❑ REVISE AND RESUBMIT ❑ REJECTED
SUBMITTAL WAS REVIEWED FOR DESIGN CONFORMI
GENERAL CONFORMANCE TO CONTRACT DOCU
ONLY. THE CONTRACTOR IS RESPONSIBLI
CONFIRMING AND CORRELATING DIMENSIONS AT J
FOR TOLERANCE. CLEARANCE. QUANTITIES, FABRI
Architectonic Inc.
Fort Pierce, FL 34950
Hartman Apartments
1215 Hartman Road
Fort Pierce, FL
Cleary Inspection Service, Inc.
Tel. (561) 722-9881, Fax (561) 582-8039
Email: clearyinspections@kcwand.com
FASTENER INSTALLATION INFORMATION: Roofs "A" & "B"
Is the fastener a self driller? Yes
Tool: Rigid 18v 0-1800 rpm's
Fastener type: #14
Fastener Manufacturer: OMG
TEST INFORMATION: AREA "A"
Test Date:
Number of Test Conducted
*Note the Location of all tests on 'Building Information', attached.
11/5/2018
13
FIELD WITHDRAWAL RESISTANCE TEST RECORDING SHEET
Deck:* See TAS 105-11 to determine number of tests Wood
AREA "A"
SAMPLE NO.
I
PLAN IDENTIFIER
INITIAL FAILURE
LOAD
FIELD
PERIMETER
CORNER
1
Tl
300
X
2
T2
330
X
3
T3
330
X
4
T4
320
X
5
T5
350
X
6
T6
265
X
7
T7
305
X
8
T8
315
X
9
T9
350
X
10
T10
330
X
11
T11
315
X
12
T12
330
X
13
T13
275
X
STATISTICAL ANALYSIS: AREA "A"
No. of Tests
T Estimator
Mean Failure Load:
Sample Standard Deviation:
Minimum -Characteristic Resistance Force:
n=
13
t' =
2.179
F=
316.5 lbf
SF=
24.51bf
F'=
301.6 lbf
K
Hartman Apartments
1215 Hartman Road
Fort Pierce, FL
Cleary Inspection Service, Inc.
Tel. (561) 722-9881, Fax (561) 582-8039
Email: clearyinspections@kcwand.com
TEST INFORMATION: AREA "B"
Test Date:
Number of Test Conducted
*Note the Location of all tests on 'Building Information', attached.
11/5/2018
4
FIELD WITHDRAWAL RESISTANCE TEST RECORDING SHEET
Deck:* See TAS 105-11 to determine number of tests Wood
AREA "B"
SAMPLE NO.
PLAN IDENTIFIER
INITIAL FAILURE
LOAD
FIELD
PERIMETER
CORNER
1
Tl
280
X
2
T2
250
X
3
T3
300
X
4
T4
360
X
STATISTICAL ANALYSIS: AREA "B"
No. of Tests
T Estimator
Mean Failure Load:
Sample Standard Deviation:
Minimum -Characteristic Resistance Force:
Sincerely,
Cleary Inspections Service, Inc.
atherine eary
Miami -Dade Lab Certification No. 16.0211.02
n=
4
t' =
3.182
F=
297.5lbf
SF=
40.3lbf
F'=
233.3 lbf
vlN r1111;R.N. Sailappan, P.E.
Florida Registration No: 46696
3
Cleary Inspection Service, Inc.
Telephone (561) 722-9881
Fax (561) 582-8039
Email: kc@kcwand.com
Notes:
1. Use of the results herein to determine the required number of
fasteners for insulation attachment or an acceptable anchor or base
sheet fastener spacing, as outlined in TAS 117, shall utilize the
minimum characteristic resistance for (F') determined in compliance
with Section 9 of TAS 105. No margin of safety shall be applied to
field withdrawal resistance test results determined in compliance with
TAS 105.
2. A safety factor of 2 to 1 shall be applied to all results of laboratory
testing.
3. The following pages shall be completed for each roof area and
included with all Field Withdrawal Resistance Test Recording Sheets.
Hartman Apartments — Roof Areas "A" & "B"
1215 Hartman Road
Fort Pierce, FL
Test Date: 11/5/2018
Roof Area Building and Parapet Heights.
(If no parapet exists, "N/A")
Roofs "A" & "B'
N/A
10,
Ground
Level
Page 4
T
Cleary Inspection Service, Inc.
Tel. (561) 722-988, Fax (561) 582-8039
Email: clearyinspections@kcwand.com
Hartman Apartments — Roof "A" & "B"
1215 Hartman Road
Fort Pierce, FL
Test Date: 11/5/2018
14'
T1
28' T2
T3
T4
Shingle Root
Not in lest
16' Shingle Rool
Not in test
26' T1
T3 28' —
10' T9
10' T6 T7
10'
14' T4 T5 T8
17' 11
T10 T11 T12 Not in test
10' 3,
10' T13 3' 3 22'
34' 9'
Shingle Roof
Not In test
1
J
T2
40'
Shingle Roof
Not in test
Shingle Roof
Not in test
40'
eRoof
Not in test
Shingle Roof
Not in test
Shingle Roof
Not in test
40'
28'
NOT DRAWN TO SCALE
Drawings & measurements are approximate representation of field layout
Page 5
CERTIFICATE OF CALIBRATION
TRACEABLE TO THE UNITED STATES NATIONAL INSTITUTE OF STANDARDS AND TECHNOLOGY
AND PERFORMED IN ACCORDANCE WITH ISOID012-2003
THIS DEVICE IS CERTIFIED TO BE WITHIN +1- 0.5% OF FULL SCALE READING AT EACH TEST POINT AT
THE TIME OF SHIPMENT
CERTIFICATE NUMBER: 25521 CALIBRATION DATE: 10/8/2018
iPART
AND CUSTOMER INFORMATION
I
MODEL# DFG2W2000 SERIAL 20606019
CUSTOMER: CLEARY INSPECTION SERVICE INC. CUSTOMER#: CLE33460
CALIBRATION DATA
APPLIED EXPECTED FULL
VALUE VALUE } RUN AVERAGE SCALE
(LB) (LB) (LB) (LB) ERROR
i0.00
0.0o" I 0.000 0.000 0.000%
100.00
400.00 400.00 398.000 39B.000-0.100%
600.00
I
800.00 800.00 798.000 798.000 -0.100%
1000.00 I
1200.00 1200.00 1 1199.000 1199.000-0.0500/.
� 1400.00 1
1600.00 1600.00 ! 1603.000 1603.000 0.150%
1800.00
2000.00 2000.00 2008.000 2006.000 0.300%
i
CALIBRATION EQUIPMENT USED
i SERIAL#1: 11706016 SERIAL#2:
CAL EQUIP:
COWEN INDUSTRIES load cell CNR EA, SIN
CNR EA
11706016 was calibrated at ComTen Industries
following to ASTM E-74. The uncertainty is 2 ;
CAL DATE:
Lbf. Report No: 20300
611212017
i
THIS EQUIPMENT IS CERTIFIED TRACEABLE TO THE UNITED STATES NATIONAL INSTITUTE OF STANDARDS AND TECHNOLOGY.
CONDITIONS I VALIDATION ,
TEMPERATURE-69:52F
RELATIVE HUMIDITY: 32% CALIBRATION
PERFORMED
AS FOUND NOTES: (` Indicates that the part was out of tolerance) BY: MG
Calibration not valid without CERTIFIED stamp and initials
I _
6405-49th Street North, Pinellas Park, FL 33781-5724 ` 727-520-1200 ' FAX 727-520-0299
E-Mail: sales@com-ten.com ' Web: www.com-ten.com