Loading...
HomeMy WebLinkAboutPRODUCT INFORMATIONGE Energy Digital Energy F WMINK 1; 1 SCANNED BY St. Lucie County Low -Voltage Automatic Transfer Switches C GE's Zenith ZTG Series switches are built for standard applications requiring the dependability and ease of operation found in a power itactor switch. Ratings 40 to 3000 amps (2, 3 or 4 poles) UL 1008 listed at 480 VAC • CSA certified at 600 VAC (200-260 amps - 480V) • NFPA 70, 99, 101 and 110 • IEEE 446 and 241 • NEC 517. 700, 701 and 702 • NEMA ICS2-447 • UL 508 and 50 •. ANSI C33.76 • ICS 6 • NEMA 250 • Equipment (Controls and Power Section) Seismic Test Qualified to: ✓ IBC-2006 ✓ IEEE-693-2005 • Double throw, mechanically interlocked contactor mechanism • Electrically operated, mechanically held C�esigned for emergency and .,mndby applications • Available in standard (ZTG) or delayed transition (ZTGD) models Fully Approved • UL and CSA listed • NFPA 70. 99 101 and 110 • IEEE 446 and 241 • NEC 517. 700.701 and 702 • NEMA ICS2-447 • UL 508 and 50 • ANSI C33.76 • ICS 6 • NEMA 250 • IBC-2006 • IEEE-693-2005 • Ringing wave immunity per IEEE 472 (ANSI C37.90A) ZTG switches are equipped with GE's Zenith MX150 microprocessor panel, which controls the operation and displays the status of the transferswitch's position, timers and available sources. As an embedded digital controller, the MX150 offers high reliability and ease of unattended operation across a range of applications. The MX150 features include: • Timer and voltage/frequency settings adjustable without disconnection from the power section • Built-in diagnostics with an LCD display for immediate troubleshooting • LED/LCD indicators for ease of viewing and long life • Nonvolatile memory —clock battery backup not required for standard switch operation • Processor and digital circuitry isolated from line voltage • Inputs optoisolated for high electrical immunity to transients and noise • Communications network interface • Conducted and Radiated Emissions per EN55022 Class B (CISPR 22) (Exceeds EN55011 & MILSTD 461 Class 3) • ESD immunity test per EN61000-4-2 Class B (Level 4) • Radiated RF, electromagnetic field immunity test per EN61000-4-3 (ENV50140) 10v/m • Electrical fast transient/burst immunity test per EN61000-4-4 • Surge immunity test per EN61000-4-5 IEEE C62.41(1.2 X 50ps, 0.5 & 4 kV) • Conducted immunity test per EN61000-4-6IENV50141) • Voltage dips and interruption immunity EN61000-4-11 Design and Construction Features • Close differential 3 phase under -voltage sensing of Source 1(normal)—factory standard setting 90% pickup, 80% dropout (adjustable): under -frequency sensing of Source 1 factory setting 95% pickup (adjustable) • Voltage and frequency sensing of the Source 2 (emergency) —factory standard setting 90% pickup voltage, 95% pickup frequency (adjustable) • Test switch (fast test/lood/no load) to simulate Source 1 [normal) failure — automatically bypassed should the Source 2 (emergency) fail • NEMA Type 1 enclosure is standard — also available in open style or NEMA . Types 3R, 4, 4X or 12 PS-1201 • Page 2 MX150 Control Panel F tNON 1 a,. pP�R 2va 1(a i e nln�nin, Front View C Standard Features (MSTDG Option Pkg.) 6/P Test Switch, Momentary A3 Auxiliary Contact Closed when the switch Is in the Source 2 position (S2) A4 Auxiliary Contact Closed when the switch is in the Source 1 position IS1) CALIBRATE Capabilities are available for Frequency and AS, BC, CA Phase to Phase voltage for both Sources CDT Daily 7.14, 28 timed exercise (CDT memory backup battery included), pushbutton/timer operation E Engine Start Contact EL/P Event Log of 16 Events that track date, time, reason and action taken .11E Adjustable under frequency sensor for S2 KIP Voltage and Frequency Indication for Sl and S2 L Indicating LED Pilot Lights: Ll Indicates switch in S2 position L2 Indicates switch in Sl position L3 Indicates Sl source available L4 Indicates S2 source available P3 Time Delay to Engine Start Q2 Peak Shave / Remote Load Test RSO In -Phase Monitor, self-adjusting T Time Delay on Retransfer to Normal: To delay retransfer to Sl (immediate retransfer on S2 failure) R2E Under voltage sensing of S2 S13 Microprocessor activated commit / no commit on tronferring to S2 U Time Delay for Engine Cool Down: Allows engine to run unloaded after switch retransfer to Sl W Time Delay onTransfertoEmergency.Todelay transfer toS2after availability YEN Pushbutton Bypass of T & W Timers When specified for use with a ZTGD Series delayed transition switch, the control panel also includes the following: DT Time Delay from Neutral Switch Position to Sl on Retransfer DW Time Delay from Neutral Switch Position to S2 LN/P Center -Off position/Off Delay Timing indicating lights Additional Standard Features WEXEG Option Pkg.) CDP Clock Exerciser Load/No Load (Replaces CDT Exerciser Option) VI Voltage Imbalance Monitor (Three Phase) Page 3 . PS-1201 Zenith ZTG Series Ordering Information I`I JI I AO ❑ �— ZEC ZVC ('EL/IY9E CONTROL APPLICATION AMPERESIZE SWITCHEDENCLOSURET'PE OPERATIONAL VOLTAGE ACCESSORIES PANEL POLES Z IT, G, 16.1 01: _6 SwMa (Open Tmm oN Z T G D 0 F01 DdryeETra t. Switch Types A. 0' K GUif 3wnsh 130 U64y-Gmerotas Mia4pmcess4r ca�trdud2 U ❑ uany-uu4y M❑ Monad Tmmfer • Standard: Unless otherwise noted, the standard switch with quick transfer will be supplied. • Delayed Transition: When ordered as the ZTGD, the delayed transition switch offers time delay during transfer from one position to the other. This is primarily for transfer of large motor or inductive loads. The operation of the delayed transition switch Is totally independent the synchronism of the power sources. _,Im noting the need for in -phase monitors or extensive motor -disconnect control wiring between the transfer switch and motor control centers. Example ZTGO00A00040E-ZECOMC4014STD This number string shows the correct format for a ZTG Series Automatic Transfer Switch with an MX150 microprocessor control unit, Utility - Generator, 400 amps, 4 pole, NEMA Type 1 enclosure,120/208V 3�, 4 wire, 60 Hz system with the standard group of accessories. UL 1008 Withstand and Closing Ratings Please refer to GE Publication TB-1102. A,. 0, 4 El 40mnps 2M. mks 3N. 30 ., Opole: sso mws zoo amps ti3 amps 2E0mnps Oro amps 6 6' O' 600 amps 84p mops loon mope Szao mop: 1 § 70 1604 m1ip5 12 Q ,0 zaoopmn Z400 amps 34oa amps M Type 3 End.. Type 12 eWosme 3 R Type 3R Endosme 4 0 Toe4Endo m 4 X Type4%e m. 0 0 opmsveum A B cmwnraei4 edon M E X E M A N O 0 120 1 2 wire 60 0 120/240 1 3 wire 60 2 110/220 1 3 wire 50 0 240 3 3 wire 60 1 208 3 3 Wire 60 2 220 3 3 wire 50 5 139/240 3 4 wire 60 0 120/208 3 4 wire 60 1 127/220 ;3 4 wire 60 2 127/220 3 4 wire 50 0 480 3 3 wire 60 1 440 3 3 Wire 60 2 440 3 3 Wire 50 5 460 1 3 wire 50 7 480 1 2 wire 60 8 254/440 3 4 wire 60 0 575 3 3 wire 60 1 347/600 3 4 Wire 60 3 575 1 2 Wire 60 0 277/480 3 4 Wire 60 1 277 1 2 Wire 60 4 266/460 3 4 wire 60 5 460 3 3 wire 60 2 380 1 2 wire 50 0 240/416 3 4 wire 60 1 2201380 3 4 Wire 60 2 220/380 3 4 wire 50 3 240/416 3 4 wire 50 7 380 3 3 wire 60 Note Operating voltage must bespecified attime of order. Only the most common voltages are shown above. Then dcose ad&fiwW as<ecwdes 6A 6AP Al AlE A3 A4 A62 ATGEW-X CTAP DS LCM M90 M90A M908 M91 M91A M91B MCM OCVR-15G OCVR-15S T3/1N3; UMD� >�VI None PS-1201 • Page 4 Options 6A Test Switch, Maintained 6AP Test Switch, Maintained Programmable Al Auxiliary Contact, operates on Source 1 line failure A3E Auxiliary Contact, operates on Source 2 line failure A3 Auxiliary Contacts: Closed when the transfer switch is in Source 2 position A4 Auxiliary Contacts: Closed when the transfer switch is in Source 1 position A62 Sequential Universal Motor Load Disconnect Circuit. Normally closed Auxiliary contacts for Motor Loads. Open 0-60 seconds plor to transfer, after transfer, or both in either direction then reclose in timed sequence after transfer. ATGEW-X[Extended annual parts and labor warranty (1-4years for a totol of 5 years max) CLAP Alarm panel on transfer to emergency w/silence button & light DS Inhibits transfer in either direction when in inhibit. Allows automatic operation when in Auto (Standard on 800A and above) HT Heater and Thermostat LCM LonWorks Communication Module MCM Modbus RTU Communication Module M90 Series Power Measurement Meters (Not available in NEMA 4 enclosure) M90 EPM2000 True RMS Digital Meter with display (Amps, Volts, Power, Energy, Power Factory and Frequency). 3 Line LED Display.50/60 Hz Universal Operation. 1 or 3 phase. Standard Modbus RTU RS485 C_ communications capability. 40 -1200 Amps. M90A Adds Pre -Wiring for Enervista Viewpoint Monitoring of M90 Accessory & ATS Status using Modbus RS485 Serial Communications M90B Adds Pre -Wiring for Enervista Viewpoint Monitoring of M90 Accessory & ATS Status using Ethernet TCP/IP Communications M91 EPM6000 True RMS Digital Meter with display (Amps, Volts, Power, Energy, Power Factory and Frequency, THD). Certified energy and demand metering. Meets ANSI C12.20 and IEC 687 Accuracy Classes. Front IrDA Part Laptop Connection. Standard Modbus RTU RS485 or DNP 3.0 communications capability. M91A Adds Pre -Wiring for Enervista Viewpoint Monitoring of M91 Accessory & ATS Status using Modbus RS485 Serial Communications M91B Adds Pre -Wiring for Enervista Viewpoint Monitoring of M91 Accessory & ATS Status using Ethernet TCP/IP Communications OCVR-1SG Lockable see -through microprocessor cover for NEMA 3R or 12 OCVR-1SS Lockable see -through microprocessor and meters cover for NEMA 311 or 12 — T3/W3; T Elevator _Pre Signal Auxiliary Contacts Open 0-60 seconds.prior to iransfer`t_oeitherdirectiori re closesaftertrarisfer �Unwersal Motor Load Disconnectiircmt Auxiligry Contact opens, 0 5 minutes priorto transfer in either dir6di n, re closes after transfer' ;Can be configured by end user forPre transfer, Pos[ transfer or both. VI Voltage Imbalance Monitor (Three Phase) NOTE: For additional options or other configurations, contact the GE factory. Page 5 • PB-1201 Reference Charts Testing Standards JL and CSA listed UL 1008, CSA 22.2 No.178 Ringing wave Immunity IEEE 472 (ANSI C37.90A) Conducted and radiated emissions EN55022 Class B (CISPR 22) (Exceeds EN55011 & MILSTD 461 Class 3) ESD immunity test EN61000-4-2 Class B (Level 4) Radiated RF, electromagnetic field immunity test EN61000-4-3 (ENV50140)10v/m Electrical fast, transient/burst immunity test EN61000-4-4 Surge Immunity test EN61000-4-5 IEEE C62.41 1.2 X 50Ns, 0.5 to 4 kV Conducted immunity test EN61000-4-6 (ENV50141) Voltage dips and interruption immunity EN61000-4-11 18-1201 • POge 6 Dimensional and Weight Specifications .. Tg. Am•Model Application RaHelght Width Depth Ref. Open NEMA1Notes (A) (a) (C) Figure Type'W0_ 14_(6j� ,691311i ;1.00, 1$Oi i2416_ll! 18:1461'4 111281 20T9)!_. '75J34)' v_ _ _ _ _ _59 (27)69131)/ 225, r -- — - 'A -- 4 70(321,., - 751341 , - 591271t — 4114 (52)' t260' �23 -46 (1171 24(61) 14(36) --- 2 3' _ '71132)__..: 224 (102),' ZTGi '�600� 4 ; '66 (1681 ,- 24 (61) 19S (50)� _ _ _ .. '-_2141971' toa1901861_�.;. 460_I209)i 4, _ 210;1951"._ 490 (2221, —'741188) ' 4011021, 19.5 —_ _. ,10_00 1200' 3 ----" ' - - ..' '- _ ...._ 190.(815... :47512161P ' -- - - -- - - _- 210(951..a 560:1254)1 34511561- 103014671! 147 7. 450 (204) 1180 (535P ;90(229) "35.5190) �481122) C. 3- - -- , - - - . 46512111- _ 11501522i I260Q 3000 _ _ _ _. _ .c.. _ •._.; .- _ ... -_- -, .. _ _ _6701304)_ 1_ (635)! C 40.80 2.3 18(8) 1271581 100,150 200,225 1- 6 4 4611171 241611 14(36) A 241111 133 (601 260,400 2.3 651291 176180) 4 76 f34) 188 (851 1 5 • ZTGD 600 2.3 66(168) 24(61) 19.5 (50) 77(35) 2211100) 4 8 87 (391 230 (104) 1-5,7 800.1000,1200 43 74 (188) 40(1.021 19.5 (50) 210 (951 475 (2151 230 (104) 560 (254) 1600, 2000 4 365 (166) 1030 (467) 901229) 35.5(90) 48 (122) C 470(213) 11801535) 2600, 3000 4 4851220/ 11501522) 1- 5, 7-8 69013131 14001635) L Metric dimensions Icm) and weights (kg) shown in Parentheses adjacent to English measurements. Reference Figures 2. Includes 1.25" door projection beyond base depth Mavaminimum of3chies. orwldepth far etc. coon of handle, lights, swatches, pushbuttons, etc. I I M 3. Alldimensionsandweghtsareapproximato and J, subject to change without notice.❑4. Pocking materials must be added to weights shownAllow IS% additional weight for cartons, skids, A AA crates, etc5. Special enclosure (NEMA 3R, 4,4x, 12, etcJ GE i ensions factoryford tails.5may ddfer. Consuitthe GEfactory for details. 6. AZTG(D)40-225A,when ordered with the fallowing FgureA Figure6 G options, will require a larger enclosure:A62M. Figure C Digital Meter, HT, OCVR-1SG, OCVR-1SS. Contact the GE factory for dimensions. 7. Add 3' in height for removable firing eyes. 8. Ventilation lowers on side and rear of enclosure at 1600-3000 amps. One set of lowers must be clear for airflow With standard cable connections. Page 7 • PS-1201 View full-size in new tab Rheem RH1P3617STANDA - 3 Ton Air Handier,17" Wide, PSC Motor, Single -Stage Airflow, Aluminum Evaporator Coil, 480/3/60 Item: RH1P3617STANDA MFR: RH1P3617STANDA What's the price? Sign in or register for pricing. Quantity ` 1 Add to Cart Your Order Templates Save products for later, or create lists to quickly re -buy items for routine jobs. Add to Order Template Inventory At Nearby Branches Florida 0 Boynton Beach #106 0 Hollywood #111 0 Kendall #116 0 Miami #113' 0 Naples #165 28 Pompano Beach #109 0 Port St Lucie #103 0 Tamarac #108 0 West Palm Beach #105 All Branches Skip To Section Description Specifications Parts List Description Features include: • Versatile 4-way convertible design for upflow, downflow, horizontal left and horizontal right applications. • Factory -installed indoor coil. • Sturdy cabinet construction with 1.0 inch [25A mm] of foil faced insulation for excellent sound and insulating characteristics. • Field -installed auxiliary electric heater kits provide exact heat for indoor comfort. Kits include circuit breakers which meet U.L. and cUL requirements for service disconnect. • 11/2 ton [5.3 kW] through 5 ton [17.6 kW] models are between 421/2 to 551/2 inches [1080 to 1410 mm] tall and 22 inches [559 mm] deep. • All models meet or exceed 330 to 400 CFM [156 to 189 Us] per ton at .3 inches [.7 kPa] of external static pressure. • Enhanced airflow up to .7" external static pressure. • Evaporator is constructed of aluminum fins bonded to internally grooved aluminum tubing. Specifications 32 Suction Line Fitting Sweat Suction Line Size 3/4" Motor Type PSC Liquid Line Fitting Sweat Liquid Line Size 318" Certifications AHRI, ISO 9001:2008 Color Gray Warranty Offered 10 Year Conditional Parts with Registration Energy Star Rated No LEED Certified No UL Listed Yes UL Recognized No Product Family RH1P Tonnage 3 Tier Standard Efficiency GEM - Case Quantity Parts List Online Only via Direct Ship PROTECH 42-19736-02 - Relay - SPDT (24VAC coil) MFR: 4249736-02 Inventory Details 270 Online Only via Direct Ship What's the price? Sign in or register for pricing. Add to Cart On Sale: 10% Off In Cart PROTECH 43-25136-08 - Capacitor-15/370 Single Round MFR: 43-25136-08 Inventory Details 0 Pompano Beach #109 83 All Branches Name Rheem RH1P3617STANDA - 3 Ton Air Handler, 17"Wide, PSC Motor, Single -Stage Airflow, Aluminum Evaporator Coil, 480/3/60 (Brand Rheem Gemaire Item Number RH1P3617STANDA Manufacturer Product Number RH1P3617STANDA SKU - PIM Number 1399041970764 ERP Number 350864 UPC 662021359460 Unit of Measure EA Weight 97.0 LB Length 21.7IN Width 17.5 IN Height 42.5IN Hazardous Material No EPA Cert Required No Country of Origin MEX Equipment Type Heat Pump Stage Single SEER 15 Refrigerant R-410a CFM 1054-1148 Cooling Capacity 18000-24000 Air Flow Convertible Voltage 460 VAC Phase Three Cycle/Hertz 60 Minimum Circuit Amps 2 Maximum Fuse Size 15 Blower Motor HP 1/3 HP Blower Motor RPM 1075 Filter Size 16" x 20" RPM 1075 Drain Connection Size 3/4" An-D3� _ kck J-5 ciJ� View full-size in new tab Rheem RA1336AD1NB - Classic 3 Ton 13 SEER, Condenser With High/Low Pressure, 460 Volt, 3 Phase, 60 Hz Item: RA1336ADlNB MFR: RA1336ADlNB What's the price? Sign in or register for pricing. Quantity' 1 Add to Cart Your Order Templates Save products for later, or create lists to quickly re -buy items for routine jobs. Add to Order Template J • Diagnostic service window with two -fastener opening - provides access to the high and low pressure. • External gauge port access - allows easy connection of "low -loss" gauge ports • Single -row condenser coil - makes unit lighter and allows thorough coil cleaning to maintain "out of the box" performance • 35% fewer cabinet fasteners and fastener -free base - allow for faster access to internal components and hassle -free panel removal • Service trays - hold fasteners or caps during service calls • OR code - provides technical information on demand for faster service calls • Fan motor harness with extra long wires allows unit top to be removed without disconnecting fan wire. • General Terms Of Limited WarrantyCompressor: Five (5) Years • Parts: One (1) Year • Rheem will furnish a replacement for any part of this product which fails in normal use and service within the applicable period stated, in accordance with the terms of the limited warranty. Specifications Name Rheem RA1336ADlNB - Classic 3 Ton 13 SEER, Condenser With High/Low Pressure, 460 Volt, 3 Phase, 60 Hz Brand Rheem Gemaire Item Number RA1336ADlNB Manufacturer Product Number RA1336ADlNB SKU - PIM Number 1405358021531 ERP Number ( 348811 UPC N/A . Unit of Measure EA Weight 1143.0 LB i Length 29.8 IN Width 29.81N Height 27.0IN Hazardous Material No - EPA Cert Required No Country of Origin MEX . Tier Classic Equipment Type Straight Cool Stage Single SEER 13-15.1 EER 11 Refrigerant R410a .CFM 2900 Cooling Capacity 36000 Voltage 460 VAC Full Load Amps 1.3 Phase Three Cycle/Hertz 60 Minimum Circuit Amps 23 Maximum Fuse Size 15 Condenser Motor HP 1/4 HP Condenser Motor Speeds Variable Rated Load Amps 16.7 Locked Rotor Amps 83.9 Suction Line Fitting Sweat Suction Line Size 3/4" Liquid Line Fitting Sweat Liquid Line Size 3/8" Certifications AHRI Color Gray Compressor (1) Scroll Inverter No Number of Fan Blades 1 ' Sound Level (dBA) 77.5 Warranty Offered Rheem will furnish a replacement for any part of this product which fails in normal use and service within the applicable period stated, in accordance with the terms of the limited warranty. Conditional Parts (Registration required) Ten Years Energy Star Rated Yes UL Listed Yes UL Recognized No Fins per Inch 22 Product Family I RA13 Tonnage I3 ' GEM -Case Quantity Documentation Use & Care Instructions Specification Sheet ,t Installation Instructions Warranty Document J}� Consumer Literature 3 Parts List PROTECH 42-10266444 - Contactor - 30A 3-Pole (24V coil) w/Auxiliary Contacts MFR: 42-10266444 Inventory Details 0 Pompano Beach #109 6 All Branches What's the price? Sign in or register for pricing. Add to Cart Capacitor - 5/370 Single Round MFR: 43-25136-03 Copeland 45-100834-80 - Molded Plug MFR: 45-100834-80 Inventory Details 9 Pompano Beach #109 1223 All Branches What's the price? Sign in or register for pricing. —Add-to—Cart— Snap-in Bushing - Conductor Protection MFR: 45403252-02