HomeMy WebLinkAboutMISC EMAILChief Building Official
St Lucie County Building Department
2300 Virginia Avenue
Ft Pierce, FL 34982
Reference: Hibiscus by the Sea Condo
3880 N. Highway AIA
Ft. Pierce, FL 34949
Subject: New Roof Material — Gazebo Building
August 15, 2017
SCANNED
BY
St. -Lucie County
The roofer may install Advanced Aluminum Permatile Panel Aluminum 0.030 roof
panels on the existing one story (5/12 pitch) pool bldg. per the attached FL- 1763-R2 Florida
Test Report. #9-15 X 2-1/2" Woodbinder HSS 304 SS (w/with sealing washers) fasteners are to
be installed in a 7", 7", 7", 7" pattern @ 12" spacing per Table "A" in all zones.
The required applied uplifts in their appropriate zones for a mean roof height of < 15 feet,
in exposure "D" during a 170 mph.1,,132 mph �d wind event are as follows:
Zone #1 (45 psf)
Zone #2 (-75 psf)
Zone #3 (-113 psf)
The product, installed per the aforementioned pattern / spacing, has been tested to
provide a maximum total uplift design pressure of 153.5 psf, clearly exceeding the requirements
for all three zones.
If you have any questions, please call me at your convenience.
Thank you.
Dr. Ernest A. Kuonen, PE 022920
President, The Erning Corporation CA-8327
228 Moccasin Trail West
Jupiter, FL 33458