HomeMy WebLinkAboutSUBMITTALTAWN, Submittal
Prepared For.
Silverline Plastics
Sold To:
Date: June 26, 2017
Customer P.O. Number.
Customer Project Number.
Job Number.
Job Name:
Silverfine Plastics Repl Chiller
Trans U.S. Inc. is pleased to provide the enclosed submittal for your review and approval.
Product Summary
Qty Product
1 Air-cooled Sintesis (TM)
Chris Cowling
Trane
6965 Vista Parkway North, Suite 11
West Palm Beach, FL 33411
Phone: (561) 653-1521
Cell: (561) 683-1521
Fax: (561) 697-8714
Please Note:
6CANNEo
3t. Luc�y
le county
The attached information describes the equipment we propose
furnish for: this pmject, and is submitted foryour approval.
Productperformance and submittal data is vaildfora period of 6 months
from the date ol'submittalgenetation. IF six months ormore has elapsed
between submittal generation and equipment release, the product
performance and submittal data will need to be verified. Itisthe
customer's responsibility to obtain such verification.
0 Please review submittal for accuracy before ordering.
J:IJOBS14614190317ISubmittal - RTAF200 Chiller - Silverfine Plastics 6-26-17. doc
Table Of Contents
Product Summary
Air-cooled Sintesis (TIVI) (item Al) .................................................................................................
3
TagData ............. : .......... .........................................................................................................................
3
ProductData ............................................................................................................................................
3
PerformanceData ................................................ j .......................................
........................................... 4
Product Data Report-RTAF200 ................................................................................................................
5
MechanicalSpecifications ........................................................................................................................
7
UnitDimensions .....................................................................................................................................
10
Weight, Clearance & Rigging Diagram ...................................................................................................
15
Accessory............................................. ................................................................................................
17
FieldWiring .................................................................................... .......................................................
21
0
litem
ITag(s)
I Qtv
I Description
jA1
I RTAF200
11
jAir-cooled Sintesis (T RTAF
Product Data - Air-cooled Sintesis (TM)
Item: Al Qty: 1 Tag(s): RTAF200
RTAF air-cooled screw chiller
200 nominal tons
460V/60Hz/3 phase
High efficiency
Standard noise
UL listed to US and Canadian safety std
A§ME pressure vessel code
Refrigerant charge R-1 34a
AHRI certified, ASHRAE 90.1 compliant
Standard cooling
2 pass evaporator
Grooved pipe
Factory installed flow switch water- 35 cm/s
Factory insulation -all cold parts 0.75 inch
Wide ambient
Microchannel coil w1profiessionally applied condenser coil coating
Variable speed fans
Oil cooler
Variable speed compressors
Single point unit power connection
Circuit breaker with high fault rated control panel
High amp 'short circuit rating
15A - 11 5V convenience outlet
Architectural louvered panels
Elastomeric isolators (Fid)
Factory Start-up and I" year Parts & Labor warranty
Year 2-5 parts, labor & refrigerant warranty — whole unit
FLD = Furnished by Trane U.S. Inc. I Installed by Equipment Submittal Page 3 of 22
others
SlIverfine Plastics Addl Chiller June 20, 2017
Performance Data - Air-cooled Sintesis (TM)
Tags
RTAF200
Capacity (tons)
191.55
Unit power (kW)
215.95
Compressor power (kW)
197.28
Efficiency (EER)
10.644
IPLV(EER)
17.782
Evap le2ving temp (F)
44.DO
Evap enterinq temp (F)
54.00
Evap flow rate (gpm)
457.76
Evap pressure drop (ft H20)
15.24
Evap fouling factor (hr-sq ft-deg F/ Btu)
0.000100
Evap fluid freeze point (F)
32.00
Saturated evap temp - ckt I (F)
40.16
Saturated evap temp - ckt 2 (F)
41.98
Ambient air ternp (F)
95.00
Saturated cond temp - ckt 1 (F)
125.28
Saturated cond temp - ckt 2 (F)
122.35
Elevation (ft)
0.00
Compressor IA - RLA/AFD input (A)
164.00
Compressor 2A - RLA/AFD input (A)
136.00
Number of condenser fans ( )
14
RLA - condenser fans (each) (A)
2.80
Fan motor power (kW)
17.86
Single point power MCA (A)
383.00
Single point power MOP (A)
500.00
Short circuit current rating (A)
65000.00
Refrigerant charge - ckt I (lb)
134.3
Refrigerant charge - ckt 2 (lb)
129.4
Oil charge - ckt 1 (gal)
1.96
Oil charge - ckt 2 (gal)
1�96
Shipping weight (lb)
11378.1
Operating weight (lb)
11561.0
Length (in)
318.244
Width (in)
89.059
Height (in)
98.194
Rated capacity (AHRI) (tons)
191.55
Rated efficiency (AHRI) (EER)
10.644
AHRI certified selection
AHRI
certified
selection
FLD = Furnished by Trane U.S. Inc. linstalled by Equipment Submittal Page 4 of 22
Othem
Silverline Plasti cs Addl Chiller June 20, 2017
Job Information
Air-cooled Sintesis (rm)
MIME,
Tao RTAF200 Unit nominal tonnaae 200 nominal tons
Model number RTAF 200
Quantitv I TOPSS version 201
General Data
CaDacitv
Efficiencv
Information
191.55 tons
IPLV
17.782 EER
Evaoorator @DDlicabon
Standard coolinq
Evaoorator conflouration
2 Dass evaDorator
EvaD foulina factor
0.000100 hr-sa ft-deo F/ Btu
Flow switch
Factory installed 35 cm/s
EvaD leavino temD
44.00 F
Saturated evao temD - ckt 1
40.16 F
EvaD enterino temD
54.00 F
Saturated evaD terro, - ckl: 2
41.98 F
EvaD flow rate
457.76 aDrn
EvaD Dressure droD
15.24 ft H20
Evaoorator fluid tvoe
Fluid tVDe - water
Evat) fluid concentration
—
EvaD fluid freeze noint
32.00 F
Condenser
AmbientalrtemD
95.00 F
Fan motor Dower
17.86 kW
Elevation
0.00 ft
Unit aDDlication
Wide ambient
Condenser fin ODtiOnS
Microchannel coil
Saturated cond teMD - Ckt 1
125.28 F
Number of condenser fans
14.00 Each
Saturated cond terrD - ckt 2
122.35 F
Electi-Iral Information
Incornino Dower line connection
Sinale Doint unit Dower
Short circuit current ratina
Hiah arnD ratino
Unit voltaae
460.OV/60.DHz(3 Dhase
Power line connection tvoe
Circuft breaker-hiah fault
Unit Dower
215.95 kW
ComDressor Dower
197.28 kW
ComDressDr 1A - RLAJAFD inDUt
164.00 A
Compressor 2A - RLAIAFD inout
136.00 A
Sinale Doint Dower MCA
3a3.00 A
Sinale DOint Dower MOP
500.00 A
Physical Information
Length
318.244 in
Refrigerant charge - ckt 1
134.3 lb
Width
89.059 in
Refrigerant charge - ckt 2
129.4 lb
Height
98.194 in
Oil charge - ckt 1
1.96 gal
Operating weight
11561.0 lb
Oil charge - ckt 2
1.96 gal
Shipping weight
11378.1 lb
6/20/2017 TOPSS version 201
Data generarlDn date Page 1 of 2
FLD = Furnished by Trane U.S. Inc. linstalled by Equipment Submittal Page 5of22
Others
Plastics Addl Chiller
C
June 20. 2017
Job Information
Air-cooled Sintesis (TM)
Teo RTAF200 Unit nominal tonnaae 200 nominal tons
Model number RTAF 200
Quantitv I TOPSS version 201
Acoustical Performance
Unit sound oackaae Standard noise
A-weiahted sound nower 103 dBA
A -weighted 75% sound power 96 dBA
A -weighted 50% sound power 94 dBA
A -weighted 25% sound power 91 dBA
A -weighted sound pressure * 74 dBA
A -weighted 75% sound pressure 68 dBA
A -weighted 50% sound pressure 66 dBA
A -weighted 25% sound pressure 63 dBA
Note: * At 30 feet in free field.
This unit complies with the efficiency requirements of all versions of ASHRAE Standard 90.1 and
CANSPCSA C743.
Certified in accordance with the AHRI Air -Cooled Water -Chilling Packages Certification Program, which is
based on AHRI Standard 55015901( -Pond AHRI Standard 551/59 1 �()Certified units may be found in the
AHRI Directory at www.ahridirectory.org.
Information for LEED
ASHRAE 90.1/CSA connDliance ASHRAE90.1-allversionsUDtO IPLV 17.782 EER
Refriaerant charae - ckt 1 134.3 lb Rated caDacitv (AHRI) 191.55 tons
Refriaerant charae - ckt 2 129.4 lb Rated efficlencv (AHRI) 10.644 EER
This product meets the minimum efficiency requirements of ASHRAE Standard 90.1 and CANSICSA C74.3 version 2007
�hich are based on AHRI standard rating conditionsond, therefore, also meets the LEED "Minimum Energy Performance"
prerequisite in the Enerqv and Atmosphere. section.
The LEED Green Building Rating SystenT�, developed by the U.S. Green Building Council, proVides independent, third -party verification that a building
Project meets green building and performance measures.
6120/2017 TOPSS version 201
Data generation date Page 2 of 2
FLD = Furnished by Trans U.S. Inc. linstalled by Equipment Submittal Page 6
Others
Silverline Plastics Addl Chiller June 20, 2017
Mechanical Specifications - Air-cooled Sintesis (TM)
Item: Al Qty: I Tag(s): RTAF200
General
Units are leak and pressure tested at 390 psig (2689 kPa) high side, 250 psig (1724 kPa) low side, then evacuated and
charged. All Air-cooled Sintesis (TM) chillers are factory tested to confirm operation prior to shipment.
Unit panels, structural elements and control boxes are constructed of galvanized steel and mounted on a bolted
galvanized steel base. Unit panels, control boxes and the structural base are finished with a baked on powder paint.
Anytime water only is present in the evaporator, the Trane UC800 controller must have flow control of the chilled water
system. Flow control can be done either directly or through an input to a building automation system to conduct an
action resulting in minimum flow through the chiller evaporator barrel to avoid potentially catastrophic damage to the
evaporator due to freezing. If the system has sufficient glycol to protect down to the lowest expected ambient, flow
control is optional.
A control power transformer shall be factory -installed and factory -wired to provide unit control power.
Chiller is built and certified to UL2014 US and Canadian safety standard.
Power Requirements
Unit is provided with single -point electrical unit power connection. Standard power connection includes main three
phase power to the compressors, condenser fans and control pow6r transformer.
Note: A separate field supplied low voltage power source is required to power the evaporator freeze protection.
Note: An additional separate field supplied low voltage power source is required to power the Convenience Outlet.
Factory Refrigerant Charge (R-134a)
Packaged units ship with a fulloperating charge of oil and HFC-134a refrigerant.
Evaporator
The evaporator is a tube -in -shell heat exchanger design with internally and externally finned copper tubes roller
expanded into the tube sheets. All tubes can be individually replaced. The evaporator is designed, tested and stamped
in accordance with ASME Pressure Vessel Code Section Vill for a refrigerant side working pressure of 200 psig (1379
kPa). The evaporator is designed for a water side working pressure of 150 psig (1034 kPa). Each shell includes a vent,
a drain, and fittings for temperature control sensors.
Evaporator water connections are grooved pipe.
Heaters, with thermostat, are provided to help protect the evaporator from freezing at ambient temperatures down to -20
F (-29 C), depending on application.
Note: A separate field supplied low voltage power source is required to power the evaporator freeze protection.
Evaporator is insulated with UV resistant 0.75 inch Armaflex 11 or equal insulation (K=0.28). Insulation also covers the
liquid and suction line and evaporator heads.
Evaporator will be configured with a 2 pass arrangement.
Operating Temperature
Unit is designed for operation in standard leaving evaporator temperature (equal to or greater than 40.0 F).
Pressure Vessel Code
Chiller complies with ASME Pressure Vessel bode Section Vill. ASME nameplates are attached to applicable pressure
vessels, including oil separators.
Condenser and Fans
Air-cooled microchannel condenser coils use all aluminum brazed fin construction. The condenser coil will have an
integral subcooling circuit. The maximum allowable working pressure of the condenser is 350 psig. Condensers are
factory proof and leak tested at 525 psig. Coils can be cleaned with high pressure water.
Direct -drive vertical -discharge condenser fans are dynamically balanced.The condenser fan motors are permanent
magnet motors with integrated drive to provide variable speed fan control for all fans. Units are equipped with EC
FLD = Furnished by Trane U.S. Inc. linstalled by Equipment Submittal Page 7 of 22
othem
Addl Chiller C C June 20. 2017
condenser fan motors with permanently lubricated ball bearings and external overload and overcurrent protection. The
fan impeller is a 5 bladed -shrouded fan. Fans are insulation class F, IP54.
Wide Ambient Operation
Wide ambient units will start and operate between 4OF to 130OF (-200C to 54.50C) ambient.
Oil Cooler
Unit has an oil cooler incorporated into the chiller oil circuit to provide reliable operation with wide ambient unit
application.
Standard Noise Sound Package
Unit will be built with low noise condenser fans.
Compressor and Lube Oil System
The rotary screw compressor is semi -hermetic, direct drive with capacity control via an adaptive frequency drive, rolling
element bearings, differential refrigerant pressure oil pump and oil heater. The motor is a suction gas cooled,
hermetically sealed two pole squirrel cage induction motor.
Oil separation is provided to separate from the compressor. Oil filtration is provided internal to the compressor. Check
valves in the compressor discharge and lube oil system are also provided.
Refrigeration Circuits
Each unit has two refrigerant circuits, with one or two rotary screw compressors per circuit. Each refrigerant circuit
includes a compressor suction and discharge service valve, liquid line shutoff valve, removable core filter, liquid line
sight glass with moisture indicator, charging port and an electronic expansion valve. Fully modulating compressors and
electronic expansion valves provide variable capacity modulation over the entire operating range.,
Adaptive Frequency Drive Compressor Starter
Trane's Adaptive Frequency Drive (AFD) technology is specifically designed for Trane air-cooled chillers. AFD
incorporates the Trane communication protocol enabling seamless integration with the, unit controller. The AFD data
such as drive Status, temperature modes, and diagnostic information are accessible to the unit controller and through
the Tracer TU service tool.
The AFD contains technology that enables the drive to last the life time of the chiller and to operate with less down time.
The technology enables operation on various power systems including alternative energy sources. AFD will protect
itself and the compressor motor from over current, low or high line voltage, phase loss, incoming phase imbalance, and
over temperature due to loss of panel ventilation.
The AFD incorporates improved serviceability and troubleshooting tools. All AFD control circuits are powered with class
2 low voltage.
Drive Cooling
the drive is air-cooled with a ventilation fan in the panel.
Unit Controls
All unit controls are housed in an outdoor rated weather tight enclosure per UL2014 with removable plates to allow for
customer connection of power wiring and remote interlocks. All controls, including sensors, are factory mounted and
tested prior to shipment.
Microcomputer controls provide all control functions including startup and shut down, leaving chilled water temperature
control, evaporator flow proving, compressor staging and speed control, electronic expansion valve modulation,
condenser fan sequencing and speed control, anti -recycle logic, automatic lead/lag compressor starting, load limiting
and chilled water pump control.
The UC-800 unit control module with Rapid Restart (TM), ufilizing Adaptive Control (TM) microprocessor, autornatically
takes action to avoid unit shutdown due to abnormal operating conditions associated with low refrigerant pressure, high
condensing pressure and motor current overload. Should the abnormal operating condition continue until a protective
limit is violated, the unitl will be shut down.
Unit protective functions of the UC-600 include: low evaporator refrigerant pressure, high condenser refrigerant
pressure, low oil flow, critical sensor or detection circuit faults, current overload, high compressor discharge
temperature, communications lost between modules, electrical distribution faults, phase loss, phase imbalance, phase
reversal, external and emergency stop, momentary power loss, under/over voltage, and loss of evaporator water flow.
FLD = Furnished by Tirane U.S. Inc. linstalled by Equipment Submittal Page 8 of 22
others
Qih1i__ 01.; AaAr �hill C I.— �n �n17
Unit Display
A full color TD-7 AdaptiView touch screen display indicates all important unit and circuit parameters, in logical groupings
on various screens. The parameters,including chilled water set point, leaving chilled water temperature, demand limit
set point, evaporator and condenser refrigerant temperatures and pressures, compressor and fan speeds, and all
pertinent electrical information. The display also provides on screen trending graphs of predefined parameters as well
as custornizable trend graphs based on user defined parameters from a list of all available parameters. The display also
provides indication of the chiller and circuits top level operating modes with detailed sub -mode reports available with a
single key press, as well as diagnostics annunciation and date and time stamped diagnostic history. The standard color
display is fully outdoor rated, and can be viewed in full daylight without opening any control panel doors.
The display is outdoor capable including an UV resistant touchscreen with an operating range between 40.00F to
158.20F operating temperature.
Chilled Water Reset I
This provides the control logic and factory installed sensors to reset leaving chilled water temperature. The set point can
be reset based on ambient temperature or return evaporator water temperature.
Factory Mounted Flow Proving
The factory. jnstalled evaporator water flow switch is provided with the control logic and relays to turn the chilled water
flow on and off as the chiller requires for operation and protection. The flow switch installed on this chiller is designed for
use with glycol in the evaporator with a set point of 35 cm/s.
High Fault Circuit Breaker
A molded case high interrupting capacity circuit breaker (UL approved) is available. The circuit breaker can also be
used to disconnect the chiller from main power with a t4ough the door handle and comes wired from the factory with
terminal block power connections. The external operator handle is lockable.
Short Circuit Current Rating (SCCR)
A short circuit current rating offers a measure of safety for what the starter panel enclosure is able to withstand in the
event of an explosion caused by a short circuit.
Convenience Outlet
Provides a 15 amp, 115 volt (60 Hz) convenience outlet on the unit.
Note: An additional field supplied power connection must be provided to power the convenience outlet.
Elastorneric Isolators
Isolators provide isolation between chiller and structure to help eliminate vibration transmission. Elastomeric isolators
are more effective and recommended over spring isolators.
FLD = Furnished by Trane U.S. Inc. I Installed by Equipment Submittal Page 9 of 22
Others
Silverline Plastics Addl Chiller C June 20, 2017
Unit Dimensions - Air-cooled Sintesis (TM)
Item: Al Qty: I Tag(s): RTAF200
'9
E
E
E
z
0
z
0
z
z
A
on
0
<
0
z
z
, t
I
z
0
R
0
FLD = Furnished by Tirane U.S. Inc. linstalled by Equipment Submittal Page 10 of 22
Others
Sliverline Plastim Add[ Chiller C C June 20, 2017
Unit Dimensions - Air-cooled Sintesis (TM)
Item; Al Qty: 1 Tag(s): RTAF200
z
0
P�:
0
z
Lu
FLD = Fumished by Tmne U.S. Inc. linstalled by Equipment Submittal Page 11 of 22
Othem
Chiller
)imensions - Air-cooled Sintesis (TM)
Al Qty: 1 Tag(s): RTAF200
W
w
Uj
LU
0
z
FLD = Furnished by Trane U.S. Inc. /Installed by Equipment Submittal Page 12 of 22
others
Silverline Plastics Addl Chiller June 20, 2017
Unit Dimensions - Air-cooled Sintesis (TIVI)
Item: Al Qty: I Tag(s): RTAF200
0
n4=0
0 -U
ru I
L)
Q�
0
Uj
0
n
Lu
LU
LLI
U)
n Z
0 w
Cl
z
0
L)
FLD = Fumishedby Trane U.S. Inc. linstalledby Equipment Submittal Page 13 of 22
Others
Silverline Plastlos Add[ Chiller C June 20, 2017
Unit Dimensions - Air-cooled Sintesis (TM)
Item: Al City: 1 Tag(s): RTAF200
w
W,
0
�z
.0
�z
�z
DO
ou
z
z
z 0
OHU111051
IO
I
11 wp !
- - , 01,111, 11 i M101, I
S
z
LU
LU
z
0
> z
C, 0
Z ()
LU Z
0
FLD = Fumishedby Trane U.S. Inc. linstalled by Equipment Submittal Page 14 of 22
Othe�
LIFTING
WEIGHT 1
LIFTING
WEIGHT 2
LIFTING
WEIGHT3
LIFTING
WEIGHT4
TOTALSHIPPING
MIGHT
3053.4 to
3042.4 Is
246,1B lb
2453.7 lb
1 1.1 Its
WARNING
LIFTING AND MOMG INSTRUCTIONS
Use the spreader bar as sh� In the diagram. Refer
to installation instructions located Inside =hot
panel for further rigging Information.
Other lifflng arrangements could result in death,
sedous Injury or equipment damage.
NOTES:
1. LIF I CHAINSICABLES WI LL NOT BE THE SAME LENGTH.
ADJUST TO KEEP UNIT LEVELWHILE UFITNG.
2. DO NOT FORK UFT UNIT.
3. LIFTING DIAGRAM IS A GENERIC
REPRESENTATION FOR ALL UNITS, IT MAY
NOT REPRESENT SIZE OF UNIT SELECTED.
4. TOTAL SHIPPING WEIGHT INCLUDES ARCHITECTURAL
NDIVIDUAL WEIGHTS DO NOT ADD UP TO TOTAL.
S. DO NOIT ALLOW LIFTING STRAPS TO CONTACT UNIT T HE
UNIT DURING LIFTING.
'O'T" 4Ei4-s I 13i'l3F" 6� I i)
IG LOCATION 3
qG LOCATION 4
R SIDE OF UNIT)
X
M
JD
n
CENTER OF GRAVITY
CG
RIGHTSIDE
NOTE' UNIT PICTURED IS A REPRESENTATION OF
THE ENTIRE PRODUCT AND MAY NOT SHOW
ACTUAL UNIT SIZEOR OPTIONS SELECTED, HOWEVER.
CENTER OF GRAVITY DIMENSIONS DO
REPRESENT UNIT AND OPTIONS SELECTED.
CONTROLPANEL
ENOVIEW
CD m
0
CD
0
(D
U3
> U3
n
�co
3
0
a
m
m
U)
In
w
INCOMING CUSTOMER
LOWVOLTWIRING
LOCATIONS
LOW VOLT KNOCKOUTS
ARE Z' UP FROM
PREVIOUS KNOCKOUT.
0
-0
RACER TD7
CUSTOMER WIRE SELECTION TABLE
Power Wire Connection to High Fault Circuit Breaker
CIR 1 & CIR 2 SIngle Point Power
Lug Wire Size Rbnge (Per Phase)
(2) 500 k=11 - 210
Short Circuit Rating 65000.00 A
H
471
L13 111161— —30 WIG, ------------------- —25
2 511'". 1
7
116,
p; >
(D C,
0
0
0
0
am jr
ul CL
0)
> (D
UNIT CLEARANCE
NO OBSTRUCTIONS ABOVE UNIT
NOTES:
1. AREA ABOVE UNIT REQUIRED FOR OPERATION,
MAINTENANCE, ACCESS PANEL AND AIRFLOW.
NO OBSTRUCTIONS ABOVE UNIT:
2. FOR OBSTRUCTIONS OR MULTIPLE UNITS,
REFER TO THE CLOSE SPACING BULLETIN.
3. CLEARANCE OF 78!'ON THE SIDE OF THE UNIT
IS REQUIRED FOR COIL REPLACEMENT. IF SUFFICIENT SIDE
CLEARANCE IS NOT POSSIBLE, COIL MUST BE REPLACED
FROM TOP OF UNIT.
TE 3
>
c
—f w
1, 0
(13 6
CL
cl)
>
In
0
0
MOUNTING LOCATIONS AND POINT LOAD WEIGHTS
POINT
1
POINT
2
POINT
3
POINT
4
POINT
5
POINT
6
POINT
7
POINT
LOAD
2189.0 lb
2146.0 lb
V34�0 lb
17M.O:b
923.0 lb
907.0 lb
711.0 (b
699.0 lb
RDP-4
RDP�
ROP-4
RDP�
RDP-4 RED
RDP-4 RED
RDP-4 BROWN
ROP4 CROWN
ISOLATOR SELECION
CHARCOAL
CHARCOAL
CHARCOAL
CHARCOAL
2250.0 lb
2250.0 lb
1500.0 lb
1500 0 lb
MAXILOAD
4000.0 lb
4000.0 lb
4000D Ib
4000.0 lb
TOTAL OPERATING WEIGHT 11561.0 lb
TOTAL OPERATING WEIGHT INCLUDES ARCHITECTURAL
PANELS. INDIVIDUAL WEIGHTS DO NOT ADD UP TO TOTAL
WEIGHT.
MOUNTING HOLE DIAMETER 9fl6"
DIAGRAM IS A GENERIC REPRESENTATION
FOR ALL UNITS, IT MAY NOT REPRESENT SIZE
OF UNIT SELECTED.
U-1
z
0-
0
la�
F-
z
0
0
5
2
(D m
0 0
U rl
0
F o
(A CL
;a m
f g
> w
n
I
c
Silverline Plasfi� Add[ Chiller C June 20, 2017
Accessory - Air-cooled Sintesis (TM)
Item: Al Qty: I Tag(s): RTAF200
CO
z
0
U)
z
LU
0
0
U)
LU
z
Uj
0-1
CL
0
LLI
z
FLD = Fumishedby Trane U.S. Inc. linstalledby Equipment Submittal Page 20 of 22
Othem
POWER SECTION
I
lQl
CIRCUIT BREAKER
OR
TERMINAL BLOCK
ONN�ENI312
,I,WARNING
AAVERTISSEMENT
POWERHOOD
A
A
N
m-
;;: -1
m
U3 C
a
c
;u
>
n
Fl
CD
a
Item: Al Qty: I Tag(s): RTAF200
GENERN-NOTIES
THE UNIT UNTIL CHECK OUT AND STARTUP PROCEDURES HAVE BEEN COMPLETED.
Z AU- MOTORS ME PROTECTED MOM PRIMARY SINGLE PHASE FAILURES.
3. PUMP CONTROL MUST BE USED TO PROME PUMP CONTROL EVAPORATOR CHIT I ED WATER PUMP MUST
BECONTROITSSBYTHECRILLEROUTPUT. FAILURE TO COMPLY WITH THIS REQUIREMENT MAY RESULT IN DAMAGE TO THE UNIT.
G] SINGLE SOURCE POWER IS PROVIDED AS STANDARD ON THESE PRODUCTS, FIELD CONNECTIONS ME MADE TO lQt
WRING REQUIREMENTS
6, RECOMMENDED FIELD WIRING CONNECTIONS ME SHOWN BY DOT7ED LINES
<T POWER FOR THE EVAPORATOR HEATER ANDOR OFTIONAL CONVENIENCE OUTUET IS SUPPLIED BY A CUSTOMER PROVIDED POWER SUPPLY.
MAX FUSE SIZE IS 20 AMPS FOR EVAPORATOR HEATERS MD20 AMPS FOR OPTIONAL CONVENIENCE OUTLET. WHENPOWERED.
THEHEATERSWII-LUSE24MOVA.
7. 00 NOT RUN LOW VOLTAGE CONTROL WRING (30 VOLTS OR LESS) IN CONDUIT WITH I IS VOLT OR HIGHER WRING DONOTEXCEEDTHE
FOU-OWNG MA)UMUK RUN LENGTHS FOR A GIVEN SIZE: 14 AWO 61100 FT: 15 AING, 2000 FT: 18 AW0. 1000".
SHIP DEB TWISTED PAIR LEADS ARE REQUIRED FOR CONNECTIONS TO THE COMMUNICATIONS INTERFACE MODULE (IN, AND 1xS)
THE SHIELD SHOULD BE GROUNDED AT THE RTAF CONTROL PANEL END.
<-91 CUSTOMER SUPPUED POWER 1155011PH OR 23MOPH TO POWER RELAYS, MAK RUSE SIZE IS 2D AMP& GROUND ALL CUSTOMER
SUPPLIED POWER SUPPLIES AS REQUIRED BY APPLICABLE CODES. GREEN GROUND 56RMS ME PROVIDED IN UNIT CONTROL PANEL
<jo WREDTO N� UNIT. 22 AWNS SHIELDED COMMUNICATION WIRE EQUIVALENT TO HEUX I.F22P0614216 RECOMMENDED.THE SUM TOTAL OFAU-
IWERCONNECTMC��SEGM�TSNOTTO�C�450DFEET CONNECTION TOPOLOGY SHOULD BE DASY CHAIN. REPER TO BUILDING AUTOMATION
SYSTEM (BAS) COMMUNICATION INSTALLATION LITERATURE FOR END OF LINE TERMINATION RESISTOR REQUIREMENTS.
<all AU- UNIT POWER WIRING MUST BE SIR VOLT COPPER CONDUCTORS ONLY AND HAVEA MINIMUM TEMPERATURE NSUI-ATION RATING OF 93 DEGREES C.
REFERTO UNU NAMEPLATE FOR MINIMUM CRCUITAMPACITYMD MA)UMUMOVSRCURRENT PROTECTION DEVICE PROVIDEA� EQUIPMENT GROUND IN
ACCORDANCEWTH AMUCABLE El ECTRIC WOES. RUM TOWIRERANGE TABLE FOR UUG SIZES.
1Z ALL FIELD WIRING MUST BE IN ACCORDANCE WITH NATIONAL ELECTRIC CODE AND LOCAL REQUIREMENTS.
CONTACT RATINGS AND REQUIREMENTS
<E WIRED TO CUSTOMER COMPRESSOR%%% RI-AOUTPUff 2-10VVC.
16. ALL CUSTOMER CONTROL CIRCUIT WRING MUST BE COPPER CONDUCTORS ONLY AND HAVEA MINIMUM INSULATION RATING OF 300VOLTS. EXCEPT
AS NOTED. A-1-CUSTOMER WRING CONNECTIONS ME MUNDETO CIRCUIT BOARD MOUNTED BOX LUGSWTPH AWIRE RANGE OF 1A TO 16 AWG OR DN FAIL
MOUNTED SPRING FORCE TERMINALS.
<E UNIT PROVIDED DRY CONTACTS FOR THE CONDENSERCH]ILLED WATER PUMP CONTROL REI.AYS ARE RATED FOR 7.2 AMPS RESISTIVE� SIR AMPS PILOT
DUTY. OR 13 HP. 7.2FIA AT 120 VOLTS 60 HZ, CONTACTS ARE RATED FOR 5 AMPS GENERAL PURPOSE DUTY NOVOLTS.
CUSTOMER SUPPLIED CONTACTS FOR ALL LOW VOLTAGECONNECTIONS MUST BE COMPATABLEWITH DRY CIRCUIT 24 VOLTS DO FOR A 12111ARESITIVE
UDAX)� SILVER OR GOLD PLATED CONTACTS RECOMMENDED.
<a�] THE CONTACTS FOR AUTO STOP AND EMERGENCY STOP SWITCHES ME JUMPERED AT THE FACTORY BY JUMPERS IWI 9 TW2 TO ENABLE UNIT OPERATION. IF
REMOTE CONTROL IS SEEMED. REMOVED THE JUMPERS AND CONNECT TO THE DESIRED COWROLCIRCOU.
20. SOLID O�%LS REPRESENT MAXNUMBER OF CONDUITS ANMR CABLE GI.ANOS USED.
<2] FIE1DWIRING REQUIRED ONLY WITH FIELD INSTALLED PUMP OPTION.
<� 4M. 50� UNITS WILL BE FACTORY WIRED TO WILUBE 230V ACROSS THE EVAP HEATERS.
FLD a Furnished by Trane U.S. Inc. linstalled by Equipment Submittal Page 22 of 22
Others