THRESHOLD INSPECTION REPORT
OCEAN HARBOR NORTH BUILDING E
5167 NORTH HWY AIA, FT. PIERCE, FLORIDA 34949
SLC BUILDING PERMIT NUMBER: 1708-0101
PROJECT NAME:
Ocean Harbor North —Bldg E
DATE:
December 29, 2017
CLIENT:
Elliott Merrill Community Management
LOCATION:
Vero Beach, Florida
CONTRACTOR:
Structure Con
PROJECT MGR:
Khris McConnell
INSPECTED BY:
Michael Lue
WEATHER:
Overcast Cool
WORK INSPECTED:
Unit 501
OBSERVATIONS:
Demolition is completed.
There are (13) PT cables within the area being repaired at the southwest corner which have been locked off and spliced
with new anchors. One of the thirteen cables were found to be dead, meaning the cable was broken prior to the start of
the repairs.
Further investigation will be required to investigate and locate the break in the cable. The extent of the repairs will have
to be determined based on the location of the break.
All reinforcing is in place and coated with corrosion inhibitor.
RECOMMENDATIONS:
1. Provide pvc chairs under the bars to provide the required concrete clearances.
2. The PT specialist to locate the break in the one broken cable.
3. Provide a 44 bar at the outer edges of the balconies at the 45 degree comers.
4. Pour the first sequence of concrete around the locks so that the cables may be stressed in sequence and the locks can
be later removed
5. Provide #4 hairpin with 12" legs around curved cable at the southwest comer of the balcony
,6puu14.4
�` N'CHONy '•..
,,'I FL 0�
--''�oFIssIOX4 <
Page 1 of 2
M L Engineering IL..
Consulting Engineers
Threshold Inspector
2030 3711 Avenue
Vero Beach, Florida 32960
Phone: (772)569-1257
Fax: (772) 569-4041
w .mleneineerineinc.com
Project No. 17-io'iY
Building Official:
Contractor:
Project Manager:
File
Report No. 1
Joe Cicio, SLC Plans Examiner
Khris McConnell — Structure -Con
Gene Ross, Elliott Merrill
Pic 1
Unit 501 Balcony
South east corner
Provide ff4 bar along edge at comer
Seal open end of alum screen enclosure column from
below to avoid being filled with concrete
Broken cable found
Page 2 of 2
M L Engineering Inc.
Consulting Engineers
Threshold Inspector
2030 37'h Avenue
Vero Beach, Florida 32960
Phone: (772) 569-1257
Fax: (772) 569-4041
w .mleneineerineinc.com
PROJECT NAME:
CLIENT:
CONTRACTOR:
Project No. 17-1au
Building Official:
Contractor:
Project Manager:
File
Report No. 2
Joe Cicio, SLC Plans Examiner
Khris McConnell— Structure -Con
Gene Ross, Elliott Merrill
THRESHOLD INSPECTION REPORT
OCEAN HARBOR NORTH BUILDING E
5167 NORTH HWY Al A, FT. PIERCE, FLORIDA 34949
SLC BUILDING PERMIT NUMBER: 1708-0101
Ocean Harbor North — Bldg E
Elliott Merrill Community Management
Structure Con
DATE:
February 2, 2018
LOCATION:
Vero Beach, Florida
PROJECT MGR:
Khris McConnell
INSPECTED BY: Michael Lue WEATHER: Overcast Cool
Units 101 Bc 501 All structural repairs are completed
WORK INSPECTED
Unit 308
OBSERVATIONS:
Demolition is completed at edge repairs. Most of the reinforcing and PT anchors have been cleaned and coated with rust
inhibitive primer. Reinforcing bar was added along the comer where the edge cracks occurred.
The existing PT cable ends were left too long and are too close to the slab edge.
No PT cables had to be locked off or spliced at this time.
RECOMMENDATIONS:
1. Cut all PT cable ends back closer to the anchors. Provide a greased protector cap and grout PT pockets with a high
strength non -shrink grout.
2. Adjust the added reinforcing edge bar along the corner to maintain a minimum of 1-1/2" concrete cover.
3. Coat all existing concrete surfaces with bonding agent prior to repouring concrete at repaired areas.
4. Re -pour are repaired areas with the recommended high strength repair mortar.
n�LC�L�II�%h��i
L!
LAPB 1 6 HD
i
Page 1 of 2
M L Engineering Inc.
Consulting Engineers
Threshold Inspector
2030 3Th Avenue
Vero Beach, Florida 32960
Phone: (772)569-1257
Fax: (772)569-4041
www.mlengineeringine.com
Project No. 17-ilm
Building Official:
Contractor:
Project Manager:
File
Pic 1
Unit 308
North west comer
Pic 3
Unit 308
Report No. 2
Joe Cicio, SLC Plans Examiner
Khris McConnell — Structure -Con
Gene Ross, Elliott Merrill
All reinforcing at repaired areas coated with corrosion
inhibitor
Page 2 of 2
M L Engineering Inc.
Consulting Engineers
Threshold Inspector
2030 37' Avenue
Vero Beach, Florida 32960
Phone: (772) 569-1257
Fax: (772) 569-4041
www. mlensineerinainc. com
Project No. 17-iau
Building Official:
Contractor:
Project Manager:
File
Report No. 1
Joe Cicio, SLC Plans Examiner
Khris McConnell — Structure -Con
Gene Ross, Elliott Merrill
THRESHOLD INSPECTION REPORT
OCEAN HARBOR NORTH BUILDING E
5167 NORTH HWY AIA, FT. PIERCE, FLORIDA 34949
SLC BUILDING PERMIT NUMBER: 1708-0101
PROJECT NAME: Ocean Harbor North —Bldg E DATE: December 29, 2017
CLIENT: Elliott Merrill Community Management LOCATION: Vero Beach, Florida
CONTRACTOR: Structure Con PROJECT MGR: Khris McConnell
INSPECTED BY: Michael Lue WEATHER: Overcast Cool
WORK INSPECTED:
Unit 501
OBSERVATIONS:
Demolition is completed.
There are (13) PT cables within the area being repaired at the southwest comer which have been locked off and spliced
with new anchors. One of the thirteen cables were found to be dead, meaning the cable was broken prior to the start of
the repairs.
Further investigation will be required to investigate and locate the break in the cable. The extent of the repairs will have
to be determined based on the location of the break.
All reinforcing is in place and coated with corrosion inhibitor.
RECOMMENDATIONS:
I. Provide pvc chairs under the bars to provide the required concrete clearances.
2. The PT specialist to locate the break in the one broken cable.
3. Provide a #4 bar at the outer edges of the balconies at the 45 degree corners.
4. Pour the first sequence of concrete around the locks so that the cables may be stressed in sequence and the locks can
be later removed
5. Provide #4 hairpin with 12" legs around curved cable at the southwest comer of the balcony
Page 1 of 2
M L Engineering Inc.
Consulting Engineers
Threshold Inspector
2030 37'h Avenue
Vero Beach, Florida 32960
Phone: (772)569-1257
Fax: (772) 569-4041
www.mlengineeringinc.com
Project No. 17-iau
Building Official:
Contractor:
Project Manager:
File
O1 Balcony
east comer
Report No. 1
Joe Cicio, SLC Plans Examiner
Khris McConnell — Structure -Con
Gene Ross, Elliott Merrill
#4 bar along edge at comer
t end of alum screen enclosure column from
avoid being filled with concrete
cable found
APR 1 6 RECD
Page 2 of 2
M
M L Engineering Inc.
Consulting Engineers
Threshold Inspector
2030 3711 Avenue
Vero Beach, Florida 32960
Phone: (772)569-1257
Fax: (772)569-4041
www.mlentrinecringinc.com
do
Project No. 17-180
Building Official:
Contractor:
Project Manager:
File
Report No. 2
Joe Cicio, SLC Plans Examiner
Khris McConnell — Structure -Con
Gene Ross, Elliott Merrill
THRESHOLD INSPECTION REPORT
OCEAN HARBOR NORTH BUILDING E
5167 NORTH HWY AIA, FT. PIERCE, FLORIDA 34949
SLC BUILDING PERMIT NUMBER: 1708-0101
PROJECT NAME: Ocean Harbor North — Bldg E DATE: February 2, 2018
CLIENT: Elliott Merrill Community Management LOCATION: Vero Beach, Florida
CONTRACTOR: Structure Con PROJECT MGR: Khris McConnell
INSPECTED BY: Michael Lue WEATHER: Overcast Cool
Units 101 & 501 All structural repairs are completed
WORK INSPECTED
Unit 308
OBSERVATIONS:
Demolition is completed at edge repairs. Most of the reinforcing and PT anchors have been cleaned and coated with rust
inhibitive primer. Reinforcing bar was added along the corner where the edge cracks occurred.
The existing PT cable ends were left too long and are too close to the slab edge.
No PT cables had to be locked off or spliced at this time.
RECOMMENDATIONS:
1. Cut all PT cable ends back closer to the anchors. Provide a greased protector cap and grout PT pockets with a high
strength non -shrink grout.
2. Adjust the added reinforcing edge bar along the comer to maintain a minimum of 1-1/2" concrete cover.
3. Coat all existing concrete surfaces with bonding agent prior to repouring concrete at repaired areas.
4. Re -pour are repaired areas with the recommended high strength repair mortar.
Page 1 of 2
4
M L Engineering Inc.
Consulting Engineers
Threshold Inspector
2030 3Th Avenue
Vero Beach, Florida 32960
Phone: (772) 569-1257
Fax: (772)569-4041
www.mlenaineeringine.com
Project No. 17-180
Building Official:
Contractor:
Project Manager:
File
Pic 1
Unit 308
North west comer
Pic 3
Unit 308
Report No. 2
Joe Cicio, SLC Plans Examiner
Khris McConnell — Structure -Con
Gene Ross, Elliott Merrill
All reinforcing at repaired areas coated with corrosion
inhibitor
Page 2 of 2