HomeMy WebLinkAboutENERGY CONSERVATION CHECK LISTFlorltla Btailding.Code, Fifth Edition (2014) 2Energy'.,Conservatlon,
EnergyGauge Summit® FIa/Com-2015,: Effective -,Date June 30, 2015 �«
IECC 2012 Total;Butlding;Performance Compliance Option s
Check List
SCANNED
Qf By
Applications for compliance with the Florida Building Code, EneJyLQoiLflsWation shall
include: sty
❑ This Checklist
❑ An Input report generated from the software just after completing compliance
calculations without any further changes
❑ The full compliance report generated by the software that contains the project
summary, complaince summary, certifications and detailed component compliance
reports
❑ Boxes appropriately checked in the Miscellanous report generated by the software at
the end of the compliance report
Qoa®asc�ceeeo
S1/pBOs�s
Po ye
s V • � e
s� � 1 T •�e'
I. T •..P e
�� S+ . R i \Vp
�o
ONAL
EnergyGauge Summit® Fla/Com-2014. TAM 2014-1.0 Compliant Software. Effective Date: June 30, 2015
6/16/2017 Page 1 of 13•
PROJECT SUMMARY
Short Desc: Geriatric Solutions Description: Geriatric Solutions
Owner: Geriatric Solutions
Addressl: 5804 Indian Pines Blvd. City: Fort Pierce
Address2: State: FL
Zip: 34951
Type: Healthcare -Clinic Class: Renovation to existing
Jurisdictjon: FORT PIERCE, ST LUCIE COUNTY, FL (661100)
Conditioned' Area: 1400 SF Conditioned & UnConditioned Area: 1400 SF
No of Stories:;-] Area entered from Plans 0 SF
Permit No: 0 Max Tonnage 5
If different, write in:
Component Design Criteria Result
Gross Energy Cost (in $) 1,026.0 1,151.0 PASSED
LIGHTING CONTROLS
EXTERNAL LIGHTING
HVAC SYSTEM
PLANT
WATER HEATING SYSTEMS
PIPING SYSTEMS
Met all required compliance from Check List?
PASSES
PASSES
PASSES
No Entry
PASSES
No Entry
Yes/No/NA
IMPORTANT MESSAGE
Info 5009 -- -- -- An' input report of this design building must be submitted along with this
Compliance Report
EnergyGauge Summit® Fla/Com-2014. TAM 2014-1.0 Compliant Software. Effective Date: -'June 30, 2015
6/16/2017 Page 2 of 13
1. S
CERTIFICATIONS
I hereby certify that the plans and specifications covered by this calculation are in compliance with the
Florida Energy Code
Prepared By: Eric J.Svoboda,�PfE Building Official:
Date: 6 11 r / �— Date:
I certify that this building is in compliance with the FLorida Energy Efficiency Code
Owner Agent: Date:
If Required by Florida law, I hereby certify (*).that the system design is in compliance with the Florida
Energy Efficiency Code
Architect: Reg No:
Electrical Designer: Reg No:
Lighting Designer: Reg No:
Mechanical Designer: Reg No:
Plumbing Designer: Reg No:
(*) Signature is required where Florida Law requires design to be performed by registered design
professionals. Typed names and registration numbers may be used where all relevant information is
contained on signed/sealed plans.
EnergyGauge Summit® Fla/Com-2014. TAM 20144.0 Compliant Software. Effective DateAune 30, 2015
;, 6/16/2017 Page 3 of 13
Project: Geriatric Solutions
Title: Geriatric Solutions
Type: Healthcare -Clinic
Total
1) Proposed 2) Baseline
65.90 86.80
$1,026 $1,354
ELECTRICITY(MBtulkWhl$)
65.90
86.80
19280
25404
$1,026
$1,354
AREA LIGHTS
16.50
24.90
4820
7288
$256
$388
MISC EQUIPMT
21.00
21.00
6153
6153
$327
$328
PUMPS & MISC
0.00
0.10
8
23
$0
$1
SPACE COOL
18.00
17.80
5266
5215
$280
$278
SPACE HEAT
0.30
1.10
83
320
$4
$17
VENT FANS
10.10
21.90
2950
6405
$157
$341
Credits Applied: None
PASSES
Passing Criteria =1151
Design (including any credits) =1026
Passing requires Proposed Building cost to be at most 85% of
Baseline cost. This Proposed Building is at 75.8%
`EnergyGauge'SummM Fla/Com-2014.'TAM 2014-1.0 Compliant Software. Effective Date: June 30, 2015
6/16/2017 Page 4 of 13
Project: Geriatric Solutions
Title: Geriatric Solutions
Type: Healthcare -Clinic
(WWEA File: DAYTONABEACH.TMY)
External Lighting Compliance
Description Category Tradable? Allowance Area or Length ELPA CLP
(W/Unit) or No. of Units (W) (W)
(Sgft or ft)
Ext Light 1 Main entries Yes 30.00 3.0 90 60
Ext Light 2 Other (doors) than main entries Yes 20.00 3.0 60 60
Ext Light 3 Building facades (by linear foot) No 5.00 152.0 760 480
Tradable Surfaces: 120 (W) Allowance for Tradable: 900 (W) PASSES
All External Lighting: 600 (W)
Complicance check includes a excess/Base allowance of 750.00(W)
Project: Geriatric Solutions
Title: Geriatric Solutions
Type: Healthcare -Clinic
(WEA File: DAYTONABEACH.TMY)
Lighting Controls Compliance
Acronym Ashrae Description Area Design Min Compli-
ID (sq.ft) CP CP ance
PrOZo1Sp1 10,004 Exam/Treatment (Hospital) 1,400 1 1 PASSES
PASSES
EnergyGauge Summit® Fla/Com-2014: TAM 20141.0 Compliant Software. Effective Date:,June 30, 2015
:, 6/16/2017 ..Page 5 of 13
Project: Geriatric Solutions
Title: Geriatric Solutions
Type: Healthcare -Clinic
(WEAFile: DAYTONABEACH.TMY)
System Report Compliance
PrOSyl System 1
Constant Volume
Air Cooled No. of Units
Split System < 65000 Btu/hr 1
Component Category
Capacity
Design Eff
Design IPLV Comp-
Eff Criteria
IPLV Criteria ►iance
Cooling System Air Conditioners Air Cooled
60000
15.50 12.23
8.00 PASSES
Split System < 65000 Btu/h
Cooling Capacity
Heating System Electric Furnace
31000
1.00 1.00
PASSES
Air Handling Air Handler (Supply) -
1800
0.40 0.82
PASSES
System -Supply Constant Volume
Air Distribution ADS System (Sup)
6.00 3.50
PASSES
System (Sup)
Air Distribution ADS System (Ret)
6.00
PASSES
System (Ret)
PASSES
Plant Compliance
Description Installed Size Design Min Design
No Eff Eff IPLV
Min Category Comp
IPLV liance
None
EnergyGauge Summit® Fla/Com-2014. TAM 2014-1'.0 Compliant Software. Effective Date: June 30, 2015
6/16/2017 Page 6 of 13
Project: Geriatric Solutions
Title: Geriatric Solutions
Type: Healthcare -Clinic
(WEAFile: DAYTONABEACH.TMY)
Water Heater Compliance
Description Type
Category Design Min
Eff Eff
Design Max Comp
Loss Loss liance
Water Heater 1 Electric water heater <= 12 [kW] 0.95 0.93
PASSES
PASSES
Piping System Compliance
Category
Pipe Dia Is Operating Ins Cond Ins Req Ins Compliance
[inches] Runout? Temp [Btu-in/hr Thick [in] Thick [in]
[F] SF.F]
None
EnergyGauge Summit@.Fla/Com-2014. TAM 2014-1.0 Compliant.Software. Effective Date: June 30, 2015
6/16/20.17 Page 7,of 13
HVAC C403.2.8.1 Mechanical
Piping Insulation exposed to weather is protected
.._
from damage (due to sun, moisture, wind, etc.).
HVAC C403.2.7 Mechanical
HVAC ducts and plenums insulated. Where ducts
0❑
or plenums are installed in or under a slab,
verification may need to occur during Foundation
Inspection.
HVAC C403.2.8 ' Mechanical
Thermally ineffective panel surfaces of sensible
❑
heating panels have Insulation >= R-3.5.
HVAC C403.2.7 Mechanical
Ducts and plenums sealed based on static
❑
❑
pressure and location.
HVAC C408.2.2.1 Mechanical
Air outlets and zone terminal devices have means
❑
13
❑
for air balancing.
HVAC C403.2.6 Mechanical
Exhaust air energy recovery on systems meeting
0❑
Table C403.2.6
HVAC C403.2.11 Mechanical
Unenclosed spaces that are heated use only
radiant heat.
HVAC C403.2.4.1 Mechanical
Heating and cooling to each zone is controlled by
❑
❑
a thermostat control.
HVAC C403.2.4.2 Mechanical
Thermostatic controls have a 5 °F deadband.
❑
HVAC C403.2.4.2 Mechanical
Temperature controls have setpoint overlap
13
❑
❑
restrictions.
HVAC C403.2.4.3 Mechanical
Each zone equipped with setback controls using
automatic time clock or programmable control
system.
HVAC C403.2.4.3 Mechanical
Automatic Controls: Setback to 55°F (heat) and
13
13
❑
85°F (cool); 7-day clock, 2-hour occupant
override, 10-hour backup
SYSTEM_SPECIFIC C404.3 Mechanical
Temperature controls installed on service water
13
❑
13
heating systems (110 OF for dwelling units and
lavatories in public restrooms and 90 OF for other
occupancies.)
SYSTEM_SPECIFIC C404.4 Mechanical
Automatic time switches installed to automatically
13
❑
switch off the recirculating hot-water system or
heat trace.
SYSTEM_SPECIFIC C404.2 Mechanical
Heat traps installed on non -circulating storage
13
❑
❑
water tanks.
SYSTEM_SPECIFIC C403.2.3 Mechanical
PTAC and PTHP with sleeves 16 in. by 42 in.
labeled for replacement only as per Footnote b to
Table C403.2.3(3).
SYSTEM SPECIFIC C403.4.2 Mechanical
VAV fan >= 7.5 hp are driven by mechanical or
El
❑
electrical variable speed drive, or.driven by
vane -axial with variable speed blades,.or operate
with motor demand <=30% design kW at 50%
design flow - calculations required
SYSTEM_SPECIFIC C403.2.8 Mechanical
HVAC piping insulation thickness. Where piping is
installed in or under a slab, verification may need
to occur during Foundation Inspection.
SYSTEM_SPECIFIC C403.2.7.1.3 Mechanical
Ductwork operating >3 in. water column requires
air leakage testing.
SYSTEM SPECIFIC C403.3.1,C403.3.1.1 Mechanical
Air economizers provided where required, meet
the requirements for design capacity, control
signal, ventilation controls, high -limit shut-off,
integrated economizer control, and provide a
means to relieve excess outside air during
operation.
SYSTEM_SPECIFIC C403.3.1,C403.4.1 Mechanical
Water economizers provided where required,
11130
meet the requirements for design capacity,
maximum pressure drop and integrated
economizer control.
SYSTEM SPECIFIC C403.4.1.4 Mechanical
Economizer operation will not increase heating
13110
energy use during normal operation.
SYSTEM SPECIFIC C403.4.5 Mechanical
Zone controls can limit simultaneous heating and
❑
cooling and sequence heating and cooling to each
zone.
SYSTEM_SPECIFIC C403.4.3.1 Mechanical
Three -pipe hydronic systems using a common
return for hot and chilled water are not used.
EnergyGauge Summil® Fla/Com-2014. TAM 2014-1.0 Compliant Software: Effective Date: June 30, 2015
6/16/2017 Page 10 of 13
0
SYSTEM —SPECIFIC C403.4.3.2
Mechanical Two -pipe hydronic systems using a common
distribution system have controls to allow a
deadband >=15 OF, allow operation in one mode
for at least 4 him before changeover, and have
rest controls to limit heating and cooling supply
temperature to <=30 OF.
SYSTEM —SPECIFIC C403.4.3.3.1
Mechanical Hydronic heat pump systems connected to a
❑
common water loop meet heat rejection and heat
addition requirements.
SYSTEM —SPECIFIC C408.2.2.2
Mechanical HVAC hydronic heating and cooling coils have
❑
E3
❑
means to balance and have pressure test
connections.
SYSTEM SPECIFIC C403.2.10.1
Mechanical HVAC fan systems at design conditions do not
exceed allowable fan system motor nameplate hp
or fan system bhp.
SYSTEM SPECIFIC C403.2.10.2
Mechanical HVAC fan motors not larger than allowable limits.
❑
SYSTEM SPECIFIC C403.4.2
Mechanical VAV fan motors >=7.5 hp to be driven by variable
speed drive, have a vane -axial fan with variable
pitch blades, or have controls to limit fan motor
demand.
SYSTEM —SPECIFIC C403.4.2.1
Mechanical VAV fans have static pressure sensors positioned
❑
13
so setpoint <=1/3 total design pressure.
SYSTEM —SPECIFIC C403.4.2.2
Mechanical Reset static pressure setpoint for CDC controlled
❑
0
El
VAV boxes reporting to central controller based on
the zones requiring the most pressure.
SYSTEM_SPECIFIC C403.4.5.4
Mechanical Multiple zone HVAC systems have supply air
0
0❑
temperature reset controls.
SYSTEM C403.4.3.4
Mechanical Hydronic systems greater than 300,000 Bluth
—SPECIFIC
designed for variable fluid flow.
SYSTEM SPECIFIC C403.4.3.5
Mechanical Reduce flow in pumping systems >10 hp to
El
El
❑
multiple chillers or boilers when others are shut
down.
SYSTEM —SPECIFIC C403.4.3.4
Mechanical Temperature reset by representative building
❑
El
El
loads in pumping systems for chiller and boiler
systems >300,000 Btu/h.
SYSTEM SPECIFIC C403.4.3.3.3
Mechanical Two -position automatic valve interlocked to shut
❑
off water flow when hydronic heat pump with
pumping system >10 hp is off.
SYSTEM SPECIFIC C403.4.4
Mechanical Fan systems with motors >=7.5 hp associated
with heat rejection equipment to have capability to
operate at 2/3 of full -speed and auto speed
controls to control the leaving fluid temperature or
condensing temp/pressure of heat rejection
device.
SYSTEM —SPECIFIC C403.4.6
Mechanical Condenser heat recovery system that can heat
D
U❑
water to 85 OF or provide 60% of peak heat
rejection is installed for preheating of service hot
water in 24/7 facility, water cooled systems reject
>6 MMBtu, SHW load >=1 MMBtu.
SYSTEM —SPECIFIC C403.4.7
Mechanical Hot gas bypass limited to:
❑
❑
❑
<=240 kBtu/h — 50%
>240 kBtu/h —25%
SYSTEM —SPECIFIC C404.2
Mechanical Service water heating equipment meets efficiency
❑
'
requirements.
SYSTEM SPECIFIC C403.2.4.2
Mechanical Heating and cooling to each zone is controlled by
13
❑
IJ
a thermostat control. Minimum one humidity
control device per installed
humidification/dehumidification system.
SYSTEM —SPECIFIC
C403.2.4.3.3
Mechanical
Systems include optimum start controls.
.
SYSTEM
C403.2.4.1.1
Mechanical
Heat pump controls prevent supplemental electric
—SPECIFIC
resistance heat from coming on when not needed.
SYSTEM -SPECIFIC
C404.3 -- "-Mechanical---=Public
lavatory -faucet water -temperature <=110°F.
SYSTEM SPECIFIC
C404.5
Mechanical
All piping in circulating system insulated
SYSTEM_SPECIFIC
C404.5
Mechanical
First 8 it of outlet piping is insulated '
1311
.EnergyGauge Summit® Fla/Com-2014. TAM 2014-1.0 Compliant Software. Effective Date.,June 30, 2015
. 6/16/2017 Page I of 13
Project Name: Geriatric Solutions
Project Title: Geriatric Solutions
Address: 5804 Indian Pines Blvd.
State: FL
Zip: 34951
Owner: Geriatric Solutions
EnergyGauge Summit® v5.10
Proiect Information
Orientation: North
Biding TYpe: Healthcare -Clinic
Building Classification: Renovation to existing building
No.of Stories: 1
GrossArea: 1400 SF
Zones
No Acronym Description- Type
Area
[sf]
Multiplier
Total Area
[sf]
1 PrOZol Zone 1 CONDITIONED
1400.0
1
1400.0 ❑
Spaces
No Acronym Description Type Depth
IN
Width Height Multi
[ft] [ft] plier
Total Area
[st]
Total Volume
[cf]
6/16/2017
EnergyGauge Summit® v5.10
1
jffne,PrOZoI
40.00 9.00
1 1400.0
12600.0
PrOZa1Sp1 Zo0Sp1
Exam/Treatment(Hospital)
35.00
{
Lighting
No Type
Category
No. of
Watts per Power
Control Type
No.of
Luminaires
Luminaire [W]
Ctrl pts
In Zone: PrOZol
In Space: Pr0Zo1Sp1
I Compact
Fluorescent General Lighting
1
1574 1574
Occupancy sensor without 1
❑
Daylighting
Walls
No Descript ion
Type Width H (Elfec) Multi
Area DirectionConductance Heat
Dens. R-Value
[it]
[ft] plier
[sf] [Btu/hr. sf. F] Capacity
[lb/cf] [h.sf.FBtu]
[Btu/sf.F]
In Zone: J PrOZol
I PrOZolWal
5/8" stucco 40.00
10.00 1
400.0 NorthEast
0.2067 5.731
34.65 4.8
❑
/8"CMU/3/4"ISO
BTWN24"oc/.5"
Gyp
2 PrOZo1 va?
518" stucco 39.00
10.00 1
390.0 SouthEast
0.2067 5.731
34.65 4.8
❑
/8"CMU/3/4"ISO
BTWN24"oe/.5"
Gyp
3 PrOZolWa3
5/8" stucco 40.00
10.00 1
400.0 SouthWes
0.2067 5.731
34.65 4.8
❑
/8"CMU/3/4"ISO
t
BTWN24"oc/.5"
Gyp
4 PrOZolWa4
5/8" stucco 39.00
10.00 1
390.0 NorthWes
0.2067 5.731
34.65 4.8
❑
/8"CMU/3/4"ISO
t
BTWN24"oc/.5"
Gyp
6/16/2017 EnergyGauge•Summitg v5.10
Windows
No Description Type
Shaded
U SHGC
Vis.Tra
W H(Effec) Multi
Total Area
[Btu/hrsfF]
IN [ft]
plier
[s1]
In Zone: PrOZol
In Wall: South East
1 PrOZolWa2Wil UserDefined
No
1.2500 0.82
0.76
2.00 6.00
2
24.0
In Wall: South West
1 PrOZolWa3Wil UserDefined
No
1.2500 0.82
0.76
2.00 6.00
3
36.0
2 PrOZolWa3Wi2 User Defined
No
1.2500 0.82
0.76
6.00 6.00
2
72.0
Doors
No Description Type
Shaded? Width H (Effec) Multi
Area Cond.
Dens. Heat Cap. R-Value
[ft] [ft]
plier
[sf] [Btu/hr. sf. F] [lb/ci] [Btu/sf. F] [h.sf.F/Btu]
In Zone: PrOZol
Iu Wall: North East
I PrOZol Wa1Drl Solid core flush
No
3.00 7.00
1
21.0 0.3504
0.00
0.00 2.85
❑
(2.25)
In Wall: South West
1 PrOZol Wa3Drl Solid core flush
No
3.00 7.00
1
21.0 0.3504
0.00
0.00 2.85
❑
(2.25)
Roofs
No Description Type
Width
H (Effec) Multi
Area
Tilt Cond.
Heat Cap
Dens. R-Value
[ft]
[ft] plier
[sf]
[deg] [Btu/hr. SE F]
[Btu/sE F]
[lb/cf] [h.sEFBtu]
In Zone: Pr1Zol
I PrOZolRfl Mtl Bldg Roof/R-19
40.00
35.00 1
1400.0
0.00 0.0492
1.34
9.49 20.3
❑
Batt
'
6/16/2017 EnergyGauge Summit® v5,10
Skylights
No Description Type
U SHGC Vis.Trans W H(Effec) Multiplier
[Bm/hr sf F] [ft] [ft]
Area TotalArea
[Sf] [S11
In Zone:
In Roof:
Floors
No Description Type
Width H(Effec) Multi Area Cond. Heat Cap. Dens.
[ft] [ft] plier [st] [Btu/hr. sf. F] [Btu/sf. F] [lb/ct]
R-Value
[h.st.F/Btu]
I
In Zone: PrOZol
1 Pi0Zo1F11 1 ft. soil, concrete
floor, carpet and
rubber pad
40.00 35.00 1 1400.0 0.2681 -34.00 113.33
3.73
❑
Systems
PrOSyl System 1
Constant Volume Air Cooled Split No. Of Units 1
System < 65000 Btu/hr
Component Category
Capacity Efficiency H'LV
I Cooling System
2 Heating System
3 Air Handling System -Supply
4 Air Distribution System (Sup)
5 Air Distribution System (Ret)
60000.00 15.50 8.00
31000.00 1.00
1800.00 0.40
6.00
6.00
❑
❑
❑
❑
❑
Plant
Equipment Category
i
Size Inst.No Eff.
1PLV
6/16/2017 EnergyGauge Summit® v5.10
71
Water Heaters
W-Heater Description Capacit3Cap.Unit I/P Rt. Efficiency Loss
1 Electric water heater 30 [Gal] 5 [M] 0.9500 [Ef] [Btu/h] ❑
Ext-Lighting
Description
Category No. of Watts per Area/Len/No. of units Control Type
Wattage
Luminaires Luminaire
[sf/ft/No]
[W]
1 Ext Light I
Main entries 1 60
3.00 Photo Sensor control
60.00
❑
2 ExtLight2
Other(doors)than main 1 60
3.00 Photo Sensor control
60.00
❑
entries
3 Ext Light 3
Building facades (by linear 4 120
152.00 Photo Sensor control
480.00
❑
foot)
Piping
Operating Insulation
Nomonal pipe Insulation
Is Runout?
No Type
Temperature Conductivity
Diameter Thickness
[F] [ Btu-in/h.sf.F]
[in] [in]
Fenestration Used
Name Glass Type No. of Glass SHGC VLT
Panes Conductance
(Btu/h.sLF]
ASHULSg1C1rAl User Defined I 1.2500 0.8200 0.7600 ❑
1Frm
6/16/2017 EnergyGauge Summit® v5.10 5
s
Materials Used
Only R-Value
RValue Thickness
Conductivity
Density
SpecificHeat
Mat No
Acronym
Description
Used
[h.sEFBtu]
[ft]
[Btu/h.ft.F]
[Ib/cI]
[Btu/Ib.F]
187
at
o
BOARD,1/21N
178
Mat1178
CARPET W/RUBBER PAD
Yes
1.2300
❑
265
Mat1265
Soil, 1 ft
No
2.0000
1.0000
0.5000
100.00
0.2000
❑
48
Matl48
6 in. Heavyweight concrete
No
0.5000
0.5000
1.0000
140.00
0.2000
❑
268
Mat1268
0.625" stucco
No
0.1302
0.0521
0.4000
16.00
0.2000
❑
42
Matl42
8 in. Lightweight concrete
No
2.0212
0.6670
0.3300
38.00
0.2000
❑
block
269
Mat1269
.75" ISO BTWN24" oc
No
2.2321
0.0625
0.0280
4.19
0.3000
❑
23
Ma63
6 in. Insulation
No
20.0000
0.5000
0.0250
5.70
0.2000
❑
94
Matl l4
BUILT-UP ROOFING,
No
0.3366
0.0313
0.0930
70.00
0.3500
❑
3/81N
Constructs Used
Simple
Massless Conductance 'Heat Capacity
Density
RValue
No
Name
Construct
Construct [Btu/h.sEF]
[Btu/SEF]
[lb/cI]
[h.sEFBtu]
1011
5/8" stucco /8"CMU/3/4"ISO
No
No
0.21
5.73
34.65
4.8
❑
BTWN24"oc/.5"
Gyp
Layer
Material Material
Thickness
Framing
No.
[ft]
Factor
1
268 0.625" stucco
0.0521
0.000
❑
i 2
42 8 in. Lightweight
concrete block
0.6670
0.000
❑
3
269 .75" ISO BTWN24" oc
0.0625
0.000
❑
4
187 GYPORPLASBOARD,1/2IN
0.0417
0.000
❑
6/16/2017 1 EnergyGauge-Summit® v5.10
No
Name
Simple
Massless Conductance Heat Capacity
Density
RValue
Construct
Construct [Btu/h.sf.F]
[Btu/sf.F]
[Ib/cf]
[h.sf.FBtu]
1056
Mtl Bldg Roof/R-19 Batt
No
No 0.05
1.34
9.49
20.3
❑
Layer
Material
Material
Thickness
Framing
No.
IN
Factor
1
94
BUILT-UP ROOFING, 3/81N
0.0313
0.000
❑
2
23
6 in. Insulation
0.5000
0.000
❑
Simple
Massless Conductance Heat Capacity
Density
RValue
No
Name
Construct
Construct [Btu/h.sf.F1
[Btu/sf.F]
[Ib/cf]
[h.sf.F/Btu1
1057
1 ft. soil, concrete floor, carpet and rubber No
No 0.27
34.00
113.33
3.7
❑
pad
Layer
Material
Material
Thickness
Framing
No.
[ft]
Factor
1
265
Soil, 1 ft
1.0000
0.000
❑
2
48
6 in. Heavyweight concrete
0.5000
0.000
❑
3
178
CARPET W/RUBBER PAD
0.000
❑
No
Name
Simple
Massless Conductance Heat Capacity
Density
RValue
Construct
Construct [Btu/h.sf.F]
[Btu/sf.F1
[Ib/cf]
[h.sf.F/Btu]
1058
Solid core flush (2.25)
No
Yes 0.35
2.9
❑
Layer
Material
Material
Thickness
Framing
No.
[ft]
Factor
1-
279
Solid core flush (2.25")
0.000
❑
6/16/2017
EnergyGauge Summit® v5:10
7