HomeMy WebLinkAboutPROJECT INFORMATIONTECTA AMERICA
South Florida, Inc.
RECEi' a SEP ? 0 7.017
To:
Planning and Development Services
Building and Code Regulation Division
SCANNED
BY
St. Lucie County
Project: Indiro Crossings Roof Replacement.
1. Building Permit Application Roof B, E, F.
2. Building Permit Application Roof H.
3. Building Permit Application Roof I.
4. Building Permit Application Roof J.
�C CD
e� 4)
Tecta America South Florida Inc. 11431 SW 30th Avenue, Deerrield Beach, FL 33442 1 T: 954.419.9339 F: 954.419.9337 1 tectaamedca.com.
1
R 02017 FLORIDA TEC
PROVIDING SOLU770i TO THE ROOFING INDIITRr
DATE.' August 18, 2017
COMPANYNAME: Tecta America
PR(7✓ECT ADDRESs: 4822 - 4898 N Kings Hwy, Fort Pierce
ASCE 7-10
Lab ReportNo. 127553B
C.A. # 30448
Lab Certificate # 17-0703.01
Input Parameters: Directional
Procedure All
Heights Building (Ch 27
Part 1)
Basic Wind Speed(V) =
170.00 mph
Structural Category =
II
Exposure Category
C
Natural Frequency =
N/A
Flexible Structure
No
Importance Factor =
1.00
Ed Directional Factor
= 0.85
Alpha =
9.50
Zg
- 900.00
ft
At =
0.11
et
1.00
Am =
0.15
Hn
= 0.65
Cc =
0.20
1
500.00
ft
Epsilon =
0.20
Zmin
= 15.00
ft
Pitch of Roof =
0 : 12
Slope of Roof(Theta)
_ .00
Deg
h: Mean Roof Ht
15.00 ft
Type of Roof
- FLAT
RHt: Ridge Ht =
15.00 ft
Eht: Save Height
= 15.00
ft
OH: Roof Overhang at Eave=
.00 ft
Overhead Type
= No Overhang
Bldg Length Along Ridge =
182.00 ft
Bldg Width Across Ridge= 111.00
ft
Wind Pressure on Components and Cladding (Ch 30 Part 1)
All pressures shown are based upon ASD Design, with a Load Factor of .6
Width of Pressure Coefficient Zone "a" =
-
6.00 ft
Description Width Span Area Zone Max
Min
Max P
Min P
ft ft £t"2 GCp
GCP
pef
Psf
Field 2.00 5.00 10.0 1 0.30 -1.00 15.37 -37.60
Perimeter 2.00 5.00 10.0 2 0.30 -1.80 15.37 -63.42
Corner 2.00 5.00 10.0 3 0.30 -2-80 15.37 -95.45
FASTENER SPACING CALCULATION
NOA: FL16730-R12
Fastener SDacineCalculatedlnAccordance With RAS-137 SvstemTvoe:LWC-41
`"""--Ma�.be`signPre'ssure "
"'-"R %Fastener
1?V`'--
IkckType""�"
60
4.75
285
Metal
DevatedPressure Zone
Fasteners Spacing
(inch)
Sheet Width.
(inch)
Field:-
37.80 -
6
114
Perimeter.
63.42
6
71
- Comer:. _ .
95.45
6
71
Perimeter
Width (inch)
72.0
10735 SW 2161' St. Unit 416 Page 1 1 Tel: 305-256-4550
Miami FL33170 www.FloridaT Fax: 305-256-6833
EC.net
Lab Report No. 127553E
qqp g FLORIDA EC
RL(,,:I'.'ED SEP 20 201&oWDINGSOLUTIONSTOFNE ROOFING INDUSTRY
DATE: August 18, 2017
COMPANYNAME: TectaAmerica
PROJECT ADDRFm.- 4822 - 4898 N Kings Hwy, Fort Pierce
ASCE 7-10
C.A.# 30448
Lab Certificate # 17-0703.01
Input Parameters: Directional
Procedure All
Heights Building (Ch 27
Part 1)
Basic Wind Speed(V)
170.00 mph
Structural Category =
II
Exposure Category
= C
Natural Frequency =
N/A
Flexible Structure
- No
Importance Factor =
1.00
Ed Directional Factor
= 0.85
Alpha =
9.50
Zg
- 900.00
ft
At =
0.11
Bt
= 1.00
Am =
0.15
Hal
0.65
Cc =
0.20
1
= 500.00
ft
Epsilon =
0.20
Zmin
15.00
ft
Pitch of Roof =
0 : 12
Slope of Roof(Theta)
_ .00
Deg
h: Mean Roof Ht =
15.00 ft
Type of Roof
= FLAT
RHt: Ridge at =
15.00 ft
Eht: Have Height
= 15.00
ft
OR: Roof Overhang at Eave=
.00 ft
Overhead Type
= No Overhang
Bldg Length Along Ridge =
182.00 ft
Bldg Width Across Ridge- 111.00
ft
Wind Pressure on Components and Cladding (Ch 30 Part 1)
All pressures shown are based upon ASD Design, with a Load Factor of .6
Width of Pressure Coefficient Zone "a" =
=
6.00 ft
Description Width Span Area Zone
Max
Min Max P
Min P
ft ft ft-2
GCp
GCp psf
paf
Field 2.00 5.00 10.0 1 0.30 -1.00
15.37 -37.80
Perimeter 2.00 5.00 10.0 2 0.30 -1.80
15.37 -63.42
Corner 2.00 5.00 10.0 3 0.30 -2.80
15.37 -95.45
FASTENER SPACING CALCULATION
NOA: F1,16730-1112
Fastener Spacing Calculated In Accordance WithRAS-137
SvstemTvne:LWC41
ftmDesign Pressure _
ft /Fastener
FV
�' Deck Type
60
4.75
285
Metal
DevatedPressure Zone
Fasteners Spacing;
SheetWid[h:
Field:-,.
37.80.-
6
114
Perimeter.
1 63,42
6
71
- _< _Corner.;..-..:
95.45
6
91
P.E.
10735 SW 216`^ St. Unit 416 page 1 of 1 Tel: 305-256-4550
Miami FL 33170 www.FloridaTEC.net Fax: 305-256-6833
Lab Report No. 127553A
FLORIDATEC
PROVIDING SOLUTIONS TO THE ROOFING INDUSTRY
RECEIV=DSEP? 0 2017 Lab Certificate al7-070301
FIELD WITHDRAWAL RESISTANCE TEST RESULTS TAS-105
TEST DATE: August 17, 2017
COMPANYNAME: Tecta America
PROJECTADDRESS: 4822 - 4898 N Kings Hwy, Fort Pierce
Note: The undersigned representative agrees that all testing has been conducted and results have been reported in
compliance with Miami Dade County Protocol TAS 105 or TAS 105A.
FIELD TECHNICIAN: Angelo Blanco
EQUIPMENT INFORMATION:
Test Apparatus:
Com-Ten FGC 2000 / SPl-1KD-RS
Deck Type: I Metal
Min Characteristic 275 or above
Resistance Force: -
See following pages for more details.
DISCLAIMER
by Florida Tee, Inc. in order to perform the required number of tests will ONLY be sealed on a
Contractor and/or owner are responsible to perform permanent repairs to avoid any roofleaks.
10735 SW 216" St. Unit 416 Page 1 of 13 Tel: 305-256-4550
Miami FL 33170 Fax: 305-256-6833
www.FloridaTEC.net
PROVIDING SOLUTIONS TO THE ROOFING INDUSTRY
FIELD WITHDRAWAL RESISTANCE TEST RECORDING SHEET
Roof
Area:
BUILDING/ROOF SYSTEM INFORMATION
Roof Area Dimensions: Height:
15FT
Length:
112 FT
Second Largest Dimension:
SOFT
Total Roof Area:
8176FT2
Squares:
81
DECKTYPE
FASTENER INSTALLATION INFORMATION
Fastener Type:
Is the fastener a self -driller?
TEST INFORMATION
Number of tests conducted:
Component to be secured:
Pre -drilled?
Metal
#15XHD Fasteners
YES
YES
Test
,,;Number'
Plan k,
.Identifier„
� wli iaf F'ai ure
.a.a .•-.,
r:'Loadl Ib
, �' '" -FlePerimeter�orCornerA,__
r ur,.-�.;,;:
-
1
A
522
Comer
2
395
Perimeter
3
485
Comer
4
501
Field
5
476
Perimeter
6
412
Perimeter
7
362
Field
8
473
Field
9
398
Perimeter
30
1
F
420
Comer
STATISTICAL ANALYSIS:
Mean Failure Load:
Sample Standard Deviation:
Min. Charasteristic Resistance Force:
F= 444.40
Sr— 53.46
F= 406.20
10735 SW 216"' St. Unit 416 Page 2 of 13 Tel: 305-256-4550
Miami FL 33170 Fax: 305-256-6833
www.FloridaTEC.net
ROOF SKETCH:
•
1
FLORIDA TEC
PROVIDING SOLUTIONS TO THE ROOFING INDUSTRY
Roof An
Groun
•
3
19 /\1N
112' DECK A
° ° o
8 •
5 9
•
7
6 10
® O
99'
10735 SW 21611 St. Unit 416 page 3 of 13 Tel: 305-256-4550
Miami FL 33170 Fax: 305-256-6833
www.FloridaTEC.net
1 � F R T
EC
PROVIDING SOLUTIONS TO THE ROOFING INDUSTRY
FIELD WITHDRAWAL RESISTANCE TEST RECORDING SHEET
Roof I_I
Area:
::
BUILDING/ROOF SYSTEM INFORMA71ON
Roof Area Dimensions: Height:
15FT
Length:
110FT
Second Largest Dimension:
60FT
Total Roof Area:
6600Fr
Squares:
66
DECKTYPE
FASTENER INSTALLATION INFORMATION
Fastener Type:
Is the fastener a self -driller?
TEST INFORMATION
N umber of tests conducted:
Componentto be secured:
Pre -drilled?
Metal
#15XHD Fasteners
YES
10
AnchororBaseSheet
YES
T`est'�
..Number
Plan
.1Wentifler.
- InmalIFiilure
Load, l
Field
Perl after or Corner
Area
1
B
377
Comer
2
456
Perimeter
3
391
Field
4
512
Perimeter
5
520
Field
6
519
Field
7
386
Field
8
415
Comer
9
466
Perimeter
30
IF
470
Comer
STATISTICAL ANALYSIS:
Mean FaHun: Load:
Sample Standard Deviation:
Min. Charasteristic Resistance Force:
F= 451.20
Sr— 66.09
F= 411.11
10735 SW 216" St. Unit 416 Page 4 of 13 Tel: 305-256-4550
Miami FL 33170 www.FloridaTEC.net Fax: 305-256-6833
FLORIDA TEC
PROVIDING SOLUTIONSTO THE ROOFING INDUSTRY
Root Arc
Groun
ROOF SKETCH:
1
2
3
4
110,
6 5
7
10 9 8
609
10735 SW 2161' St. Unit 416 page 5 of 13 Tel: 305-256-4550
Miami FL 33170 Www.FloridaTEC.net Fax: 305-256-6833
� TE i
PROVIDING SOLUTIONS TO THE ROOFING INDUSTRY
FIELD WITHDRAWAL RESISTANCE TEST RECORDING SHEET
Roof
Area:
BUILDING/ROOF SYSTEM INFORMATION
Roof Area Dimensions: Height: 15FT
Length: 61 FT
Second Largest Dimension: 41 FT
Total Roof Area: 2501 FY2
Squares: 25
DECKTYPE
FASTENER INSTALLATION INFORMATION
Fastener Type:
Is the fastenera self -driller?
Number of tests conducted:
Component to be secured:
Pre -drilled?
Metal
#15XHD Fasteners
YES
10
Anchoror Base Sheet
YES
Test
Number �
Plan
' Wentifier
, IndialFailure
= Field Pi.kirreter.or6rner.Area=-'.:-
1
C
467
Comer
2
522
Perimeter
3
375
Comer
4
30
Field
5
410
Field
6
421.
Perimeter
7
412
Field
8
473
Perimeter
9
530
Perimeter
10
4:W
Comer
STATISTICAL ANALYSIS
Mean Failure Load:
Sample Standard Deviation:
Min. Charasteristic Resistance Force:
F= 440.60
Sr— 49.44
F= 405.27
10735 SW 2161' St. Unit 416 Page 6 of 13 Tel: 305-256-4550
Miami FL33170 WWw.FloridaTEC.net Fax:305-256-6833
FLORIDA TEE
PROVIDING SOLUTIONS TOTNE ROOFING INDUSTRY
Roof Are
Groun
ROOF SKETCH:
1
2
3
5 4
611
6
7
8
10
9
•
•
id— 411
10735 SW 210 St. Unit 416 page 7 of 13 Tel: 305-256-4550
Miami FL 33170 www.FloridaTEC.net Fax: 305-256-6833
FLORIDA TEC
PROVIDING SOLUTIONSTO THE ROOFING INDUSTRY
FIELD WITHDRAWAL RESISTANCE TEST RECORDING SHEET
Roof
Area
BUILDING/ROOF SYSTEM INFORMATION
Roof Area Dimensions: Height:
15FT
Length:
SOFT
Second Largest Dimension:
38FF
Total Roof Area:
2840FT2
Squares:
18
DECKTYPE
FASTENER INSTALLATION INFORMATION
FastenerType:
Is the fastener a self-driI Ier?
TEST INFORMATION
N umber of tests conducted:
Component to be secured:
Pre -drilled?
Metal
MISXHD Fasteners
YES
10
AnchororBaseSheet
YES
' tes7 - e-
Number.,
IPl5
.Identifier;
" initial Failure
< Load. Ib Ia
Fleld Perm eter�,or CornerrAre'w�
1
D
392
Comer
2
38S
Perimeter
3
376
Comer
4
417
Field
S
470
Perimeter
6
426
Field
7
421
Perimeter
8
410
Field
9
401
Comer
30
395
Comer
STATISTICAL ANALYSIS
Mean Failure Load:
Sample Standard Deviation:
Min. Charasteristic Resistance Force:
F"— 409.30
Sr— 26_73
F= 390.19
10735 SW 216th St. Unit 416 Page 8 of 13 Tel: 305-256-4550
Miami Fl-33170 www.FloridaTEC.net Fax: 305-256-6833
FLORIDA 'SEC
PROVIDING SOLUTIONS TOTNE ROOFING INDUSTRY
Roof Ar(
ROOF SKETCH:
•
2
•
1
Groun
•
3
•
7
10735 SW 216th St. Unit 416 Page 9 of 13 Tel: 305-256-4550
Miami FL 33170 www.FloridaTEC.net Fax: 305-256-6833
J A
FL 4f l 9I ®A d E
PROVIDING SOLUTIONS TO THE ROOFING INDUSTRY
FIELD WITHDRAWAL RESISTANCE TEST
Roof
Area El'
BUILDING/ROOF SYSTEM INFORMATION
Roof Area Dimensions: Height:
15FT
Length:
182 FT
Second Largest Dimension:
111 FT
Total Roof Area:
12489Fr
Squares:
124
DECKTYPE
FASTENER INSTALLATION INFORMATION
FastenerType:
Is the fastener a self-dril ler?
Number of tests conducted:
Componentto be secured:
Pre -drilled?
Metal
#15XND Fasteners
YES
13
AnchororBaseSheet
YFS
SHEET
.Number.,eIdentifler>:�?rs
"S�PIan`a a
u, InitialFaliure ➢
`� s
Fleld
e,a4_W_a_ ' r• `�i?`
Perimeter orXafner Areaaae::.=A-: x
1
E
510
Comer
2
1
521
Perimeter
3
460
Comer
4
478
Perimeter
5
528
Field
6
573
Field
7
475
Field
8
518
Perimeter
9
499
Field
10
581
Perimeter
11
476
Field
12
512
Field
13
489
Comer
STATISTICAL ANALYSIS:
Mean Failure Load: 1~ 509.23
Sample Standard Deviation: Sr— 36_49
Min. Charasteristic Resistance Force: F= 487.17
10735 SW 216d' St. Unit 416 Page 10 of 13 Tel: 305-256-4550
Miami FL 33170 www.FloridaTEC.net Fax: 305-256-6833
FLORIDA TEC
PROVIDING SOLUTIONS TO THE ROOFING INDUSTRY
Roof Are
Grouni
ROOF SKETCH:
10735 SW 216t' St. Unit 416 page it of 13 Tel: 305-256-4550
Miami FL 33170 www.FloridaTEC.net Fax: 305-256-6833
FLO4i?
A TEC `
PROVIDING SOLUTIOHE ROOFING INDUSTRY
FIELD WITHDRAWAL RESISTANCE TEST RECORDING SHEET
Roof
Area:
BUILDING/ROOF SYSTEM INFORMATION
Roof Area Dimensions: Height:
15FT
Length:
92 FT
Second Largest Dimension:
7FT
Total Roof Area:
644 FT=
Squares:
6
DECKTYPE
FASTENER INSTAUATION INFORMATION
Fastener Type:
Is the fastener self -driller?
TEST INFORMATION
Number of tests conducted:
Component to be secured:
Pre -drilled?
Metal
#15XHD Fasteners
YES
10
AnchororBoseSheet
YES
Test ,
bMuurn er
-'; Plan
Wentifler
Initial Failure
-,-,., . 1�
-- --� " ,, ,; � .
,; I erimete or Car, ner a + ..?
1
F
466
Comer
2
475
Comer
3
495
Field
4
573
Perimeter
5
529
Field
6
512
Field
7
517
Field
8
478
Perimeter
9
566
Perimeter
10
F
520
Comer
STATISTICAL ANALYSIS:
Mean Failure Load:
Sample Standard Deviation:
Min. Chamsteristic Resistance Force:
1L 613.10
Sr— 36.41
F= 487.08
10735 SW 216t1 St. Unit 416 Page 12 of 13 Tel: 305-256-4550
Miami FL 33170 www.FloridaTEC.net Fax: 305-256-6833
FLORIDA iEC
PROWDING.SOLUMi TO THE ROOFING INDUSTRY
Roof Are
Gmum
ROOF SKETCH:
9T
•1 �9 10
0s 07
a2 •3 ®4 �6 08
7'
10735 SW 216th St. Unit 416 page 13 of 13 Tel: 305-256-4550
Miami FL33170 www.FloridaTEC.net Fax:305-256-6833