REVIEW COMMENTS St. Lucie Countv
Owner(s);
Betty M Hall (Tr)
Jurisdiction: SAINT LUCIE COUNTY
Lot#: 16 Block: 3
1
APPLICATION INFORMATION
Permit Number: 1709-0343 Stories: Automatic Sprinkler System? No
i
Permit Type: COMMERCIAL RENOVATION
CONTRACTOR INFORMATION
Contractor Name: Daniel Marin Fax Number: 866-778-6356
Business Name: Alpha Design Contractor Llc
Business Addr: 1492 Se Belcrest St
Email: Nicomaquin@Hotmail.Com
City / State / Zip: Port St Lucie, FI 34952
REVIEWS AND COMMENTS
Review Type Status Reviewed By Date Started Date Completed Date Released
DOCUMENTS MISSING PENDING Angela Huff 9/2112017
9/22/2017 Comment: PLEASE PROVIDE ELECTIC SUBCONTRACTOR AGREEMENT
I 11/8/2017
Comment: SUBMIT A ROOF SUB SHEET
FIRE DEPARTMENT REVIEW PENDING Tony Jerger
Comment:
FRONT COUNTER REVIEW COMPLETE Angela Huff 9/21/2017 9/2212017 912212017
Comment:
PE REVIEW COMMENTS (2) COMPLETE Joe Cicio 1111/2018 112912018 1/2912018
Comment:
PE REVIEW COMMENTS (3) INCOMPLETE Joe Cicio 1129/2018
— — _ Comment: THE OCCUPANT LOAD HAS BEEN CALCULATED INCORRECTLY • THE" WAITING AREA" REFERRED TO IS
1/11/2018 T _ -A - ` - FOR AIRPORT TERMINALS* USE THE GROUP B"BUSINESS AREA "AS STATED IN TABLE 1004.1.2 FOR THE
COMPLETE TENANT SPACE*** SECOND REVIEW*** THIRD REVIEW— SEE FBC TABLE 1004.1.2 FOR
BUSINESS SPACES "THERE IS A CALCULATION FOR GROUP B
1/11/2018 Comment: ENGINEER TO ROUND UP THE OCCUPANTS TO THE NEAREST WHOLE NUMBER / CANNOT HAVE
PORTIONS OF OCCUPANTS
1/29/2018 Comment: ENGINEER TO MODIFY THE MECHANICAL DUCT LAYOUT ON SHEET 2 TO CONFORM WITH THE FLOOR
PLAN ON SHEET 1
1/2912018 Comment: COMMENTS E-MAILED AS OF THIS DATE
Planning & Development Services
Building 8 Code Regulation Division
2300 Virginia Avenue
Fort Pierce, FL 34982
Phone:(772)462.2172 Fax:(772)462.6443
REVIEW COMMENTS
2
Comment: PLEASE NOTE: (1) ALL REVIEW COMMENTS WHEN ANSWERED WILL REQUIRE A COVER LETTER
ADDRESSING WHERE THE CHANGES WERE MADE, (2) ALL CHANGES WILL BE REQUIRED TO BE CLOUDED
ON THE PLANS AND (3) THE CONTRACTOR WHEN RESUBMITTING WILL BE REQUIRED TO INSERT THE
NEW UPDATED PAGES INTO THE PLANS OR IF THE CONTRACTOR PREFERS, A REVISED COMPLETE SET
OF PLANS CAN BE SUBMITTED
1/29/2018 PLEASE NOTE THAT A SUBMITTAL CHECKLIST WILL BE REQUIRED STATING THE TYPE AND QUANTITY OF
DOCUMENTS SUBMITTED FOR RE -REVIEW SIGNED AND DATED BY THE CONTRACTOR
PLEASE NOTE ANY COMMENT NOT ADDRESED MAY BE SUBJECT TO AN ADDITIONAL REVIEW FEE PER ST.
LUCIE COUNTY RESOLUTION #13-196
COMMENTS SENT
1/29/2018 Comment: CONTRECTOR TO PAY THE REVIEW FEES UPON RE -SUBMITTAL
PLANS EXAMINER ELECTRIC COMPLETE Walter Pride 11/2012017 11/2012017 11/2012017
Comment:
PLANS EXAMINER MECHANICAL INCOMPLETE Carl Peterson 11/22/2017
11/22/2017 Comment: PLEASE FURNISH THE MANUFACTURES CUT SHEETS FOR THE MINI SPLIT 107.2.11E THE FLORIDA
PLANS EXAMINER PLUMBING
Comment:
11/9/2017
11/9/2017
Comment:
11/9/2017
Comment:
11/9/2017 Comment
BUILDING CODE.
INCOMPLETE Greg Smyth
THIS OCCUPANCY CLASSIFICATION REQUIRES SEPARATE SEX RESTROOMS THAT MEET ADA
REQUIREMENTS PER SECTION 403.2 FPC 2014.
AND SECTION 604 OF THE FLORIDA ACCESSABILITY CODE 2014
OCCUPANT COUNT IS WRONG FOR THE SQUARE FOOTAGE PER TABLE 1004.1.2 FBC 2014 (ASSEMBLY).
PLEASE SHOW LOCATION OF HI LO DRINKING FOUNTAINS PER TABLE 403.1 FPC 2014 AND 2014 FLORIDA
ACCESSABILITY CODE SECTION 211.
PLEASE SHOW LOCATION OF SERVICE SINK PER TABLE 403.1 FPC 2014.
11/9/2017 Comment: ALL SINKS WILL REQUIRE HOT WATER PER SECTION 607.1 FPC 2014
PLANS EXAMINER REVIEW COMPLETE Joe Cicio 11/8/2017 1/11I2018
Comment:
1111/2018
PROPERTY INFORMATION
Address: 8757 S U S 1
City / State / Zip: Port St Lucie, FI 34952
Parcel#: 3414-501-1916-35017
Zoning: CG
APPLICATION INFORMATION
Permit Number: 1709-0343
Permit Type: COMMERCIAL RENOVATION
REVIEW COMMENTS
Page 1
Owner(s):
Betty M Hall (Tr)
Jurisdiction: SAINT LUCIE COUNTY
Lot#: 16 Block: 3
Stories: Automatic Sprinkler System? No
Contractor Name: Daniel Marin Fax Number: 866-778-6356
Business Name: Alpha Design Contractor Llc
Email: Nicomaquin@Hotmail.Com
Business Addr: 1492 Se Belcrest St
City / State I Zip: Port St
Lucie, FI 34952
REVIEWS AND COMMENTS
Review Tvpe
Status Reviewed By Date Started Date Completed Date Released
DOCUMENTS MISSING
PENDING Angela Huff 9/21/2017
9/22I2017 Comment:
PLEASE PROVIDE ELECTIC SUBCONTRACTOR AGREEMENT
11/8/2017 Comment:
SUBMIT A ROOF SUB SHEET
FIRE DEPARTMENT REVIEW
PENDING Tony Jerger
Comment:
FRONT COUNTER REVIEW
COMPLETE Angela Huff 912112017 912212017 9/22/2017
Comment:
PE REVIEW COMMENTS (2)
COMPLETE Joe Cicio 1/11/2018 1129/2018 1/29/2018
Comment:
PE REVIEW COMMENTS (3)
INCOMPLETE Joe Cicio 112912018
Comment:
THE OCCUPANT LOAD HAS BEEN CALCULATED INCORRECTLYTHE " WAITING AREA REFERRED TO IS
111112018
FOR AIRPORT TERMINALS' USE THE GROUP B " BUSINESS AREA " AS STATED IN TABLE 1004.1.2 FOR THE
COMPLETE TENANT SPACE "' SECOND REVIEW "' THIRD REVIEW "' SEE FBC TABLE 1004.1.2 FOR
BUSINESS SPACES "THERE IS A CALCULATION FOR GROUP B
1/11/2018 Comment:
ENGINEER TO ROUND UP THE OCCUPANTS TO THE NEAREST WHOLE NUMBER / CANNOT HAVE
PORTIONS OF OCCUPANTS
1/29/2018 Comment:
ENGINEER TO MODIFY THE MECHANICAL DUCT LAYOUT ON SHEET 2 TO CONFORM WITH THE FLOOR
11
PLAN ON SHEET 1
1/29/2018 Comment:
COMMENTS E-MAILED AS OF THIS DATE
REVIEW COMMENTS
Page 2
Comment: PLEASE NOTE: (1) ALL REVIEW COMMENTS WHEN ANSWERED WILL REQUIRE A COVER LETTER
ADDRESSING WHERE THE CHANGES WERE MADE, (2) ALL CHANGES WILL BE REQUIRED TO BE CLOUDED
ON THE PLANS AND (3) THE CONTRACTOR WHEN RESUBMITTING WILL BE REQUIRED TO INSERT THE
NEW UPDATED PAGES INTO THE PLANS OR IF THE CONTRACTOR PREFERS, A REVISED COMPLETE SET
OF PLANS CAN BE SUBMITTED
1/2912018 PLEASE NOTE THAT A SUBMITTAL CHECKLIST WILL BE REQUIRED STATING THE TYPE AND QUANTITY OF
DOCUMENTS SUBMITTED FOR RE -REVIEW SIGNED AND DATED BY THE CONTRACTOR
PLEASE NOTE ANY COMMENT NOT ADDRESED MAY BE SUBJECT TO AN ADDITIONAL REVIEW FEE PER ST.
LUCIE COUNTY RESOLUTION #13-196
COMMENTS SENT
1/2912018 Comment: CONTRECTOR TO PAY THE REVIEW FEES UPON RE -SUBMITTAL
PLANS EXAMINER ELECTRIC COMPLETE Walter Pride 11120/2017
Comment:
PLANS EXAMINER MECHANICAL INCOMPLETE Carl Peterson 1112212017
11/2012017 11/20/2017
11122/2017 Comment: PLEASE FURNISH THE MANUFACTURES CUT SHEETS FOR THE MINI SPLIT 107.2.1IF THE FLORIDA
BUILDING CODE.
PLANS EXAMINER PLUMBING INCOMPLETE Greg Smyth
Comment:
THIS OCCUPANCY CLASSIFICATION REQUIRES SEPARATE SEX RESTROOMS THAT MEET ADA
11/9/2017
REQUIREMENTS PER SECTION 403.2 FPC 2014.
AND SECTION 604 OF THE FLORIDA ACCESSABILITY CODE 2014
11/g/2017
Comment:
OCCUPANT COUNT IS WRONG FOR THE SQUARE FOOTAGE PER TABLE 1004.1.2 FBC 2014 (ASSEMBLY).
11/9/2017
Comment:
PLEASE SHOW LOCATION OF HI LO DRINKING FOUNTAINS PER TABLE 403.1 FPC 2014 AND 2014 FLORIDA
ACCESSABILITY CODE SECTION 211.
11/9/2017
Comment:
PLEASE SHOW LOCATION OF SERVICE SINK PER TABLE 403.1 FPC 2014.
11/912017
Comment:
ALL SINKS WILL REQUIRE HOT WATER PER SECTION 607.1 FPC 2014
PLANS EXAMINER REVIEW
COMPLETE Joe Cicio 11/8/2017 IM112018 1/11/2018
Comment:
��arrxa �ioccst�
Planning:& Development Services
Building & Code Regulation Division
2300 Virginla Avenue
Fort Pierce, FL. 34982
Phone:(772)462.2172 Faz:(772)462-6443
REVIEW COMMENTS
SCANNED
BY
St. Lucie Countv
1
Address: 8757 S U S 1 Owner(s):
Betty M Hall (Tr)
City / State / Zip: Port St Lucie, FI 34952
Parcel #: 3414-501-1916-350/7 Jurisdiction: SAINT LUCIE COUNTY
Zoning: CG Lot#: 16 Block: 3
APPLICATION INFORMATION
Permit Number: 1709-0343 Stories: Automatic Sprinkler System? No
i,Permit Type: COMMERCIAL RENOVATION
i
CONTRACTOR INFORMATION
Contractor Name: Daniel Marin G W\ Fax Number: 866-778-6356
Business Name: Alpha Design Contractor Llc
Business Addr: 1492 Se Belcrest St J Email: Nicomaquin@Hotmail.Com
City / State / Zip: Port St Lucie, FI 34952
REVIEWS AND COMMENTS (r-
Review Type
DOCUMENTS MISSING
912212017 Comment:
11/8/2017 Comment:
�. FIRE DEPARTMENT REVIEW
Comment:
.'FRONT COUNTER REVIEW
Comment:
Status Reviewed By Date Started Date Completed Date Released
PENDING Angela Huff 9121/2017
PLEASE PROVIDE ELECTIC SUBCONTRACTOR AGREEMENT
SUBMIT A ROOF SUB SHEET
PENDING
COMPLETE
Tony Jerger
Angela Huff 9/2112017 912212017 9122/2017
PE REVIEW COMMENTS (2) INCOMPLETE Joe Cicio 1111/2018
Comment: SHOW THE ACCESSIBLE RESTROOM DETAILS ON PLANS INCLUDING TURNING RADIUS, CLEAR FLOOR
SPACES AT FIXTURES, DISPENSOR DETAILS, GRAB BARS ETC. SHOW THE MANUEVERING CLEARANCES
AT THE KITCHEN DOOR AND THE WAITING DOOR' SHOW THE PATH AND LOCATION OF THE ACCESSIBLE
11/20/2017 PARKING SPACE THROUGH THE FRONT DOOR •• RESTROOM DOOR IS NOT ACCESSIBLE •• SECOND
REVIEW- FEE DUE*** SINK IN RESTROOM CANNOT EXTEND INTO THE REQUIRED MANUEVERING
-- —CLEARANCE OF THE RESTROOM DOOR* SHOW CORRECT FLOOR SPACE PER FBC ACCESS TABLE
404.2.4.1 • DID NOT SHOW THE REQUIRED ACCESSIBLE PATH FROM THE FACILITY TO THE ACCESSIBLE
PARKING AREA
Comment: SHOW THE REQUIRED APPLIANCE PROTECTION ON PLANS FOR THE REAR MECHANICAL UNIT AND THE
11120/2017 WATER HEATER PER FBCM 303.4 • MUST COMPLY WITH VEHICLE BARRIER LOADS PER FBC 1607.8.3 ••
SHOW THE REQUIRED BARRIERS FOR THE EXTERIOR SERVICE SINK...
Comment: ENGINEER TO DESIGN THE PLANS PER FBC 456.3.2 • RESTROOM ACCESS CANNOT BE THROUGH THE
1/11/2018 FOOR PREP, WARE -WASHING OR ANY STORAGE AREAS' SEE 466.3.2.2 FOR PUBLIC BATHROOM
REQUIREMENTS
Comment: SEE FBC 456.3.2.2 FOR THE DOORS TO THE PUBLIC RESTROOM • A RESTROOM DOOR WITH THE
1/11/2018 REQUIRED CLOSER MUST COMPLY WITH 12" CLEARANCE IN THE MANUEVERING SPACE PER FBC
ACCESS 404.2.4.1
.mow. ,i-uriiz r�iOunZ`
Planning & Development Services
Building & Code Regulation Division
2300 Virginia Avenue
Fort Pierce, FL 34982
Phone:(772)462.2172 Faz:(772)462.6443
REVIEW COMMENTS
Comment:
THE OCCUPANT LOAD HAS BEEN CALCULATED INCORRECTLY' THE " WAITING AREA" REFERRED TO IS
1/11/2018
FOR AIRPORT TERMINALS "USE THE GROUP B"BUSINESS AREA" AS STATED IN TABLE 1004.1.2 FOR THE
COMPLETE TENANT SPACE
1/1112018
Comment:
ENGINEER TO ROUND UP THE OCCUPANTS TO THE NEAREST WHOLE NUMBER / CANNOT HAVE
PORTIONS OF OCCUPANTS
1/11/2018
Comment:
ENGINEER TO SHOW THE INTERIOR FRAMING DETAILS ON PLANS PER FBC 2211 REFERENCE
STANDARDS` FBC 2211
1/1112018
Comment:
ENGINEER TO SHOW THE GYP INSTALLATION ON PLANS PER FBC 2506.2 AND REFERENCE STANDARDS
1/11/2018
Comment:
COMMENTS E-MAILED AS OF THIS DATE
1/1112018
Comment:
ENGINEER TO RESUBMIT [ 3 ] SETS OF ORIGINAL PLANS
Comment: PLEASE NOTE: (1) ALL REVIEW COMMENTS WHEN ANSWERED WILL REQUIRE A COVER LETTER
ADDRESSING WHERE THE CHANGES WERE MADE, (2) ALL CHANGES WILL BE REQUIRED TO BE CLOUDED
ON THE PLANS AND (3) THE CONTRACTOR WHEN RESUBMITTING WILL BE REQUIRED TO INSERT THE
NEW UPDATED PAGES INTO THE PLANS OR IF THE CONTRACTOR PREFERS, A REVISED COMPLETE SET
OF PLANS CAN BE SUBMITTED
1/11/2018 PLEASE NOTE THAT A SUBMITTAL CHECKLIST WILL BE REQUIRED STATING THE TYPE AND QUANTITY OF
DOCUMENTS SUBMITTED FOR RE -REVIEW SIGNED AND DATED BY THE CONTRACTOR
PLEASE NOTE ANY COMMENT NOT ADDRESED MAY BE SUBJECT TO AN ADDITIONAL REVIEW FEE PER ST.
LUCIE COUNTY RESOLUTION #13-196
COMMENTS SENT
PLANS EXAMINER ELECTRIC
Comment:
COMPLETE Walter Pride
PLANS EXAMINER MECHANICAL INCOMPLETE Carl Peterson
11 /2012017 11/2012017 1112012017
11/22/2017
11/22/2017 Comment: PLEASE FURNISH THE MANUFACTURES CUT SHEETS FOR THE MINI SPLIT 107.2.1IF THE FLORIDA
BUILDING CODE.
PLANS EXAMINER PLUMBING
INCOMPLETE Greg Smyth
Comment:
HIS OCCUPANCY CLASSIFICATION REQUIRES SEPARATE SEX RESTROOMS THAT MEET ADA
11/9/2017
REQUIREMENTS PER SECTION 403.2 FPC 2014.
AND SECTION 604 OF THE FLORIDA ACCESSABILITY CODE 2014
11I9/2017
Comment:
OCCUPANT COUNT IS WRONG FOR THE SQUARE FOOTAGE PER TABLE 1004.1.2 FBC 2014 (ASSEMBLY).
11/9/2017
Comment:
PLEASE SHOW LOCATION OF HI LO DRINKING FOUNTAINS PER TABLE 403.1 FPC 2014 AND 2014 FLORIDA
ACCESSABILITY CODE SECTION 211.
11/9/2017
Comment:
PLEASE SHOW LOCATION OF SERVICE SINK PER TABLE 403.1 FPC 2014.
11/9/2017
Comment:
ALL SINKS WILL REQUIRE HOT WATER PER SECTION 607.1 FPC 2014
I PLANS EXAMINER REVIEW
Comment:
COMPLETE Joe Cicio 1118/2017 111112018 1/11/2018
A .4"" do `
Planning S Development Services
Building & Code Regulation Division
2300 Virginia Avenue.
Fort Pierce, FL. 34982
Phone:V72)462.2172 Fax:(772)462=6443
PROPERTY INFORMATION
Address:
8757 S U S 1
City / State / Zip:
Port St Lucie, FI 34952
Parcel#:
3414-501-1916-350/7
Zoning:
CG
APPLICATION INFORMATION
Permit Number: 1709-0343
Permit Type: COMMERCIAL RENOVATION
CONTRACTOR INFORMATION
Contractor Name:
Daniel Marin
Business Name:
Alpha Design Contractor Llc
Business Addr:
1492 Se Belcrest St
City I State I Zip:
Port St Lucie, FI 34952
REVIEW COMMENTS
1
Ownei(s):
Betty M Hall jr)
Jurisdiction: SAINT LUCIE COUNTY
Lot#: 16 Block: 3
Stories: Automatic Sprinkler System? No
Fax Number: 866-778-6356
Email: Nicomaquin@Hotmail.Com
REVIEWS AND COMMENTS
Review Tyne
Status Reviewed By Date Started Date Completed Date Released
DOCUMENTS MISSING
PENDING Angela Huff 912112017
912212017 Comment:
PLEASE PROVIDE ELECTIC SUBCONTRACTOR AGREEMENT
11/812017 Comment:
SUBMIT ROOF SUB SHEET
. FIRE DEPARTMENT REVIEW
PENDING Tony Jerger
Comment:
'FRONT COUNTER REVIEW
COMPLETE Angela Huff 9121/2017 912212017 9122/2017
Comment:
PLANS EXAMINER ELECTRIC
COMPLETE Walter Pride 11/2012017 1112012017 11/2012017
Comment:
PLANS EXAMINER MECHANICAL
INCOMPLETE Carl Peterson 1112212017
— — - - 11/22/2017_ Comment:
PLEASE FURNISH THE MANUFACTURES CUT SHEETS FOR THE MINI SPLIT 107.2.1IF THE FLORIDA
BUILDING CODE.
PLANS EXAMINER PLUMBING
INCOMPLETE Greg Smyth
Comment:
THIS OCCUPANCY CLASSIFICATION REQUIRES SEPARATE SEX RESTROOMS THAT MEET ADA
111912017
REQUIREMENTS PER SECTION 403.2 FPC 2014.
AND SECTION 604 OF THE FLORIDA ACCESSABILITY CODE 2014
11/9/2017 Comment:
OCCUPANT COUNT IS WRONG FOR THE SQUARE FOOTAGE PER TABLE 1004.1.2 FBC 2014 (ASSEMBLY).
11/9/2017 Comment:
PLEASE SHOW LOCATION OF HI LO DRINKING FOUNTAINS PER TABLE 403.1 FPC 2014 AND 2014 FLORIDA
ACCESSABILITY CODE SECTION 211.
11/9/2017 Comment:
PLEASE SHOW LOCATION OF SERVICE SINK PER TABLE 403.1 FPC 2014.
Planning & Development Services
Building & Code Regulation Division
2300 Virginia Avenue
Fort Pierce, FL. 34982
Phone:(772)462.2172 Fax:(772)462-6443
REVIEW COMMENTS
11/9/2017 Comment: ALL SINKS WILL REQUIRE HOT WATER PER SECTION 607.1 FPC 2014
PLANS EXAMINER REVIEW
INCOMPLETE Joe Cicio 1118/2017
111812017 Comment:
SUBMIT LIFE SAFETY PLANS IN TRIPLICATE WI TRAVEL DISTANCES AND EGRESS DOOR CAPACITIES
Comment:
THIS WOULD FALL UNDER A SMALL TENANT SPACE AS A GROUP B OCCUPANCY' SEE FBC 303.1.1 FOR
11/8/2017
DETAILS' CHANGE PLANS
11/812017 Comment:
THE PARTIAL KITCHEN PLAN ON SHEET 2 DOES NOT MIRROR THE SHEET 1 PLANS
Comment:
FBC 107.1 REQUIRES ALL CONSTRUCTION DOCUMENTS TO BE PREPARED BY A FLORIDA REGISTERED
11/2012017
DESIGN PROFESSIONAL' PLEASE REMOVE THE DESIGN BY: RICHARD A. JEMISON CRITERIA FROM THE
PLANS AS BENCHMARK ENGINEERING IS THE DESIGN PROFESSIONAL
Comment:
THIS IS A CHANGE OF OCCUPANCY WITH NO CHANGE OF OCCUPANCY CLASSIFICATION' SEE 2014
11/20/2017
EXISTING BUILDING CODE CHAPTER 10 / SPECIFICALLY 1012.8
Comment:
SHOW THE ACCESSIBLE RESTROOM DETAILS ON PLANS INCLUDING TURNING RADIUS, CLEAR FLOOR
SPACES AT FIXTURES, DISPENSOR DETAILS, GRAB BARS ETC. SHOW THE MANUEVERING CLEARANCES
1112012017
AT THE KITCHEN DOOR AND THE WAITING DOOR' SHOW THE PATH AND LOCATION OF THE ACCESSIBLE
PARKING SPACE THROUGH THE FRONT DOOR'• RESTROOM DOOR IS NOT ACCESSIBLE
Comment:
SHOW THE REQUIRED FORWARD APPROACH OR PARALLEL APPROACH ON PLANS PER FBC ACCESS.
11/20/2017
904.4.1 OR 904.4.2 FOR THE SERVICE / SALES COUNTER 904.4 •' SHOW COMPLIANT CABINET DETAILS "
11/20/2017 Comment:
SHOW THE REQUIRED MALTEASE CROSS ON A PLAN FRONT ELEVATION PER FA.C. 69A-60
11/20/2017 Comment:
SHOW THE RESTROOM DETAILS ON PLANS PER FBC 1210
Comment:
SHOW THE REQUIRED APPLIANCE PROTECTION ON PLANS FOR THE REAR MECHANICAL UNIT AND THE
11/20/2017
WATER HEATER PER FBCM 303.4' MUST COMPLY WITH VEHICLE BARRIER LOADS PER FBC 1607.8.3
Comment:
PLEASE NOTE: (1) ALL REVIEW COMMENTS WHEN ANSWERED WILL REQUIRE A COVER LETTER
ADDRESSING WHERE THE CHANGES WERE MADE, (2) ALL CHANGES WILL BE REQUIRED TO BE CLOUDED
ON THE PLANS AND (3) THE CONTRACTOR WHEN RESUBMITTING WILL BE REQUIRED TO INSERT THE
NEW UPDATED PAGES INTO THE PLANS OR IF THE CONTRACTOR PREFERS, A REVISED COMPLETE SET
OF PLANS CAN BE SUBMITTED
11/20/2017
PLEASE NOTE THAT A SUBMITTAL CHECKLIST WILL BE REQUIRED STATING THE TYPE AND QUANTITY OF
DOCUMENTS SUBMITTED FOR RE -REVIEW SIGNED AND DATED BY THE CONTRACTOR
PLEASE NOTE ANY COMMENT NOT ADDRESED MAY BE SUBJECT TO AN ADDITIONAL REVIEW FEE PER ST.
LUCIE COUNTY RESOLUTION #13-196
COMMENTS SENT
11/20/2017 Comment:
COMMENTS E-MAILED AS OF THIS DATE